You are on page 1of 4

IGLC100-2G

Gaseous Fuel
Ratings Range – 60 Hertz Operation Standby Power Features
✓ Heavy-duty industrial gaseous fuel engine that meets the
latest EPA emissions levels
Liquid Propane: kW 67 - 80
✓ Brushless synchronous alternators with dynamic
kVA 67 - 100 balancing and four pole construction
✓ Fully featured microprocessor based controller that’s
Natural Gas: kW 67 - 98 easy to use and field programmable for customized
kVA 67 - 122 installations
✓ Generator sets are prototype tested and production
tested to ensure easy startup
Baldor generators are available in a variety of power ratings
and installation styles to meet the energy needs of the ✓ Gen-set accepts rated load in one step
smallest businesses and the largest manufacturing facilities. ✓ Heavy duty construction that’s designed for use in
All generator sets are designed to meet the specifications standby applications
to ensure the fastest startup and dependable long-term ✓ Manufactured in a dedicated and secure ISO-9001
operation. Rely on Baldor generators to provide the clean, certified facility
quiet and environmentally friendly electrical power when ✓ Generator sets are backed by a world wide network of
you need it most. Emergency backup, standby, peak parts and service centers
shaving or for any of your day or night electrical power
✓ Optional agency approvals available including UL2200
needs, you can count on a dependable Baldor generator to and NFPA110
provide the peace of mind and security you desire.
✓ Optional environmental enclosures available including
weather resistant, sound attenuated, containerized, and
walk-in models
✓ Full range of genset accessories and factory installed
options available
Genset Ratings
150°C Rise Alternator 150°C Rise Alternator
Genset Voltage Standby Rating – LP Fuel Standby Rating – Natural Gas
Alternator Phase Hertz
Model Number L-L / L-N
kW / kVA Amps kW / kVA Amps
IGLC100-2G UCI274C-311 208 / 120 3 60 80 / 100 277 96 / 120 333
220 / 127 3 60 80 / 100 262 97 / 121 317
240 / 120 (1) 3 60 80 / 100 240 96 / 120 288
240 / 120 (1) 1 60 67 / 67 279 67 / 67 279
240 / 139 3 60 80 / 100 240 98 / 122 293
380 / 220 3 60 80 / 100 151 85 / 106 161
416 / 240 3 60 80 / 100 138 96 / 120 166
440 / 254 3 60 80 / 100 131 97 / 121 158
480 / 277 3 60 80 / 100 120 98 / 122 146
UCI274C-17 600 / 347 3 60 80 / 100 96 98 / 122 117
UCI274D-311 208 / 120 3 60 80 / 100 277 97 / 121 335
220 / 127 3 60 80 / 100 262 97 / 121 317
240 / 120 (1) 3 60 80 / 100 240 97 / 121 291
240 / 120 (1) 1 60 78 / 78 325 78 / 78 325
240 / 139 3 60 80 / 100 240 98 / 122 293
380 / 220 3 60 80 / 100 152 97 / 121 183
416 / 240 3 60 80 / 100 138 97 / 121 167
440 / 254 3 60 80 / 100 131 97 / 121 158
480 / 277 3 60 80 / 100 120 98 / 122 146
UCI274D-17 600 / 347 3 60 80 / 100 96 98 / 122 117
363CSL1617 240 / 120 (1) 1 60 80 / 80 333 95 / 95 395
NOTES: (1) Alternator connections have two circuits available for low voltage.
Available current in each low voltage circuit is equal to high voltage current listed in table.
For ratings and voltages not listed above refer to the Genset Selector.
Standby ratings do not have an overload capability but can be used for the duration of the utility failure per ISO-3046, DIN6271 and BS5514.
Baldor reserves the right to implement specifications or design changes without notice.
Engine Application Data
Engine Specifications Engine Electrical System
Manufacturer General Motors Charging Alternator Volts dc 12
Engine Model # 5.7L Charging Alternator Amps 70
Engine Type 4 Cycle, 8 Cylinder Grounding Polarity Negative
Induction System Turbocharged/ Starter Motor Volts dc 12
Charge Air Cooled Battery Recommendations
Displacement, L (in3) 5.7 (350) Battery Volts dc 12
EPA Emissions Certification 40 CFR Part Min Cold Cranking Amps 750
60 & 1048 Quantity Required 1
HP at Rated Speed BHP (kWm) NG 155.0 (115.4)
HP at Rated Speed BHP (kWm) Propane 145.0 (108.2) Ventilation Requirements
Rated RPM 1800 Cooling Airflow, scfm (cmm) 16,500 (467)
Bore and Stroke in (mm) 4.00 x 3.48 Combustion Airflow, cfm (cmm) 230.4 (0.381)
(86 x 105) Heat Rejected to Ambient
Compression Ratio 9.4:1 From Engine, Btu/min (kW) 2844 (50)
Air Filter Type Dry From Alternator, Btu/min (kW) 512 (9)
Governor Type / Model Electronic Recommended Free Area Intake
Governor Manufacturer EControls Louver Size, ft2 (m2) 34.0 (3.16)
Freq Reg NL to FL Isochronous
Freq Reg Steady State +/-0.5% Engine Fuel System
Recommended Fuel
Engine Lubrication System Natural Gas min HHV (Btu/ft3) 1015
Oil Pan Capacity gal (L) 1.5 (6.0) Propane Vapor min HHV (Btu/ft3) 2650
Oil Capacity w/Filter gal (L) 1.6 (6.4) Fuel Supply Pressure in-H2O (kPa) 7-11 (1.7-2.7)
Oil Filter Quantity 1 Fuel Line At Engine
Oil Filter Type Cartridge Supply Line, npt 1-1/4
Recommended Oil 15W-40
Oil Press psi (kPa) 43 (296) NG Fuel Consumption – Standby Rating
100% Load cfph (m3ph) 1211.8 (34.3)
Engine Cooling System 75% Load cfph (m3ph) 989.8 (28.0)
Genset Max Ambient Temp °F (°C) 122 (50) 50% Load cfph (m3ph) 685.4 (19.4)
Engine Coolant Cap qt (L) 9.12 (8.6) 25% Load cfph (m3ph) 425.4 (12.0)
Engine + Radiator System Cap qt (L) 36 (34.1)
Water Pump Type Centrifugal Propane Fuel Consumption – Standby Rating
Coolant Flow gpm (Lpm) 39 (148) 100% Load cfph (m3ph) 502.3 (14.2)
Charge Air Cooler Flow Cfm (CMM) 230.38 (0.381) 75% Load cfph (m3ph) 406.0 (11.5)
Heat Rejected to Charge Air Cooler 50% Load cfph (m3ph) 286.7 (8.1)
@ Rated kW; Btu/min (kW) 711 (13) 25% Load cfph (m3ph) 179.5 (5.1)
Heat Rejected to Radiator
@ Rated kW; Btu/min (kW) 6300 (111) Engine Output Deratings - Standby
Max Restriction of Cooling Air Rated Temp 77ºF
in H2O (kPa) 0.5 (0.124)
Rated Altitude 325 ft
Max Altitude 10,000 ft
Engine Exhaust System
Exhaust Manifold Type Dry Temperature Derate -1% / 8ºF
Exhaust Flow @ Rated kW cfm (cmm) 846 (24.0) Altitude Derate -3% / 1000 ft
Exhaust Temp (dry manifold) °F (°C) 1350 (732.2)
Min Back Pressure in H2O (kPa) 0 (0)
Max Back Pressure in H2O (kPa) 40 (10.2)
Exhaust Outlet Diameter in (mm) 3 (76.2)
Exhaust Outlet Type O.D. Tube
Exhaust Catalyst Included
Alternator Specifications
Alternator Type 4-Pole, Rotating Field Automatic Voltage Regulator
Exciter Type Brushless Wound Field SX460
Excitation System PMG MX341, MX321
Shunt Connection Standard Voltage Regulation No Load to Full Load
PMG Optional Std Regulator +/- 1.5%
Insulation per NEMA MG1 PMG Regulator +/- 1%, +/-0.5%
Material Class H Load Acceptance 100% of Rating, One Step
Standby Temp Rise 150˚C
Lead Connection 12 Lead, Reconnectable Subtransient Reactance
Stator Pitch 2/3 480V, Per Unit 13%, 12%
Amortisseur Winding Full TIF (1960 Weighting) <50
Bearing Single, Double Shielded Line Harmonics 5% Maximum
Drive Coupling Flexible Disk Motor Starting kVA 30% Max Voltage Dip
Unbalanced Load 20% of Standby Rating Alt @ 480V SkVA UCI274C-311 340 kVA
Alt @ 480V SkVA UCI274D-311 430 kVA

Genset Controller Specifications

Baldor InteliLite NT Features


Large back-lit graphical LCD Display
64x128 pixel resolution
6 LED Genset Status Indicators
Alarm Red LED
Not In Auto Red LED
Warning Yellow LED
Running Green LED
Ready / Auto Green LED
Supplying Load Green LED
Sealed Membrane Panel to IP65
Push Buttons for Simple Control
Start, Stop, Fault Reset, Horn Reset, Mode,
Page, and Enter Keys
Display Metering and Protection
Oil Pressure Warning / Shutdown
High / Low Coolant Temperature Warning
High Coolant Temperature Shutdown
Low Fuel Level Warning / Shutdown
Over Speed Protection
Battery Voltage Over / Under Warning
Running Hour Meter
Generator Under / Over Volts Warn / Shutdown
Generator Under / Over Freq Warn / Shutdown
Generator Over Current Shutdown
Generator Output Metering for V1-V3, I1-I3,
Hz, kW, kWh, kVAr, kVAh
Additional Standard Genset Features Available Accessories and Options
✓ Formed Steel Sub-Base Open Unit
✓ Integral Vibration Isolation ❒ Industrial Silencer ❒ Residential Silencer
✓ Sub-Base Lifting Eyes ❒ Critical Silencer ❒ Hospital Grade Silencer
✓ Unit Mounted Radiator ❒ Exhaust Flex Pipe ❒ Rain Cap
❒ Radiator Duct Flange
✓ Engine Mounted Fan
✓ Radiator Fan Guard Enclosed Units
❒ Weather Resistant Enclosure
✓ Battery Charging Alternator
❒ Sound Attenuated w/Internal Critical Silencer
✓ Battery Rack and Cables
❒ Walk-In Enclosure
✓ Unit Mounted Control Panel
Alternator Accessories
✓ Spin-On Oil Filter
❒ PMG Exciter and AVR Upgrade
✓ Enamel Finish
❒ Alternator Space Heater
✓ One Set - Operation / Maintenance Manual ❒ Exciter Field Circuit Breaker
✓ Factory Tested Prior to Shipment ❒ Alternator Drip Shield
✓ Limited Warranty Genset Accessories
❒ Voltage Adjust Potentiometer
❒ Starting Battery
Optional Agency Approvals
Battery Charger ❒ Auto/Float
❒ UL2200 (Review Option Availability) Auto/ Float Equalize Timer ❒ Manual ❒ Automatic
❒ NFPA110 (Request Remote Annunciator) ❒ Battery Heater
❒ Engine Coolant Heater
❒ Oil & Coolant Drain Valves (Engine/Radiator)
Weight and Dimensions (Open Unit) ❒ Oil & Coolant Drain Extended to Base
Weight – Wet lb(kg) 2564 (1163) Main Output Breaker
Overall Dimensions Length x Width x Height ❒ Wall Mount ❒ Unit Mount
inches 96 x 48 x 60 Transfer Switch
mm 2438 x 1219 x 1524 ❒ Manual ❒ Automatic
Note: Drawing is provided for reference only. Control Panel
Use engineering outline for installation planning. ❒ Remote Annunciator
❒ Remote Communications
❒ Remote E-Stop
Fuel System
❒ Fuel Strainer
❒ Dual Fuel Automatic Changeover
Vibration Isolators
❒ Elastomer Isolator
❒ Standard Spring
❒ Seismic Spring

Baldor Electric Company


P. O. Box 2400 • Fort Smith, AR 72902-2400 U.S.A.
Phone (479) 646-4711 • Fax (479) 648-5792 • International Fax (479) 648-5895
© Baldor Electric Company www.baldor.com Printed in U.S.A.
FM24123 11/11 TP 2000