Professional Documents
Culture Documents
CS4000
Installation Manual
çConsilium
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Consilium
Marine assumes no legal responsibility for any error or damage resulting from
the usage of this document.
Consilium Marine AB
P.O. Box 8763
SE-402 76 GÖTEBORG
SWEDEN
Tel: +46-31-710 77 00, Fax: +46-31-710 78 00
E-mail: cmab.got@consilium.se
Internet: www.consilium.se
Contents
ABOUT THIS MANUAL ............................................................................................................. 1
APPENDIX B: ID LIST.............................................................................................................. 29
Chapter 2: Installation
The different parts of the CS4000 fire alarm system, the central unit, the
control units, repeaters and the loop units, should first be mechanically
installed. The different loop units are thereafter electrically installed and
set up according to the definition of the loops. The cables must be tested
separately before the loops are connected to the central unit. This
eliminates any problem with the cable and the electrical installation of
the loop units. The installation is completed with the electrical
installation of the central unit and the control unit(s).
Mechanical installation
Install the central unit, the control units, repeaters and the loop units
according to the drawings. The control unit can be delivered installed in
the central unit or as a separate unit. Separate drawings are delivered
with the system.
Central unit
The central and control unit, even the external control unit, are delivered
in cabinets (IP22) for wall or console mounting. Separate drawings are
delivered with the system. The central units shall be installed indoors in
areas with 0- 80% RH non-condensing and temperatures ranging from
0°C to 50°C.
Loop units
A loop unit is a unit that can be connected to a loop or a conventional
zone, i.e. detector, manual call point, address unit, timer etc.
The mechanical installation of the different types of loop and zone units
is described on the data sheets respectively.
Installation Manual Chapter 2: Installation 4
Salwico CS4000
Electrical installation
Cable requirements
The cables for the external system channel to control panels and
repeater units must fulfil the following requirements:
Detector loops
Loop lengths
The length of a loop or a sub-loop depends on the following three
parameters, type of cable, shielded cable or unshielded cable. A cable is
considered to be shielded if the shielded part of the cable is more than
10% of the total length. Never exceed the recommended cable lengths.
The loop units are divided into three types, depending on their
individual load on the loop.
Type 1
Type 2
• SID-38T
• RDJ-2T
• TDT-2 and TDT-2K, rate-of-rise 57°C and rate-of-rise 86°
• CSS3300 rectifier
• AE-2 and AE-2K, configured as a sprinkler (ID 107, 120, 121, 125
and 126), heat detector (127), door indication (117), manual call
point (116) and sub central (114)
• NS-AUV, NS-AOS-IS, NS-AIN1 ID2.
Installation Manual Chapter 2: Installation 5
Salwico CS4000
Type 3 includes all address units with a constant voltage output on the
sub-loop
• AE-2 and AE-2K, configured as smoke detector (ID 111 and 124),
flame detector, IR, (ID 123) and heat detector with constant output
on the sub-loop (ID 118).
• AE-2K/I, configured as flame detector, UV, (ID 119) and ISIF (ID
99).
Important notice:
Leave at least 10% in spare addresses for future extensions with new
loop units when calculating the number of loop units.
For example, when only type 1 loop units are used:
254 addresses x 0.9= max 228 loop units/loop.
Detector loops
A loop may contain different types and different numbers of loop units.
The connection to the loop depends on the type of loop unit and the
configuration of your system. Some of the loop units are connected
directly to the loop and some via address units. The figures on the next
pages are examples of an addressable detector loop and a conventional
detector zone. For more details about connection, see appendix D.
Important notice:
• Set the address switch on each loop unit before connecting them to
the loop. If an address unit is used, set its ID switch too. See Setting
the address of the loop units later in this chapter and also
Appendix A and B.
Installation Manual Chapter 2: Installation 6
Salwico CS4000
IN FIRE CENTRAL
LB LOOP BOARD
SIDE B
-
LOOP X
SHORT CIRCUIT
ISOLATOR
SIDE A
-
+
CONVENTIONAL ADDRESSABLE
DETECTOR IS UNITS
(DETECTORS/
CALL POINTS)
The measured value should be less then 100Ω for a cable with
a maximum length of 2 km.
All addressable loop units such as detectors, manual call points etc
connected to the loop board LB must be given an address between
1-254 to be operational. The loop units located on the same physical
loop must all have unique addresses.
The address is set by a 8 pole DIP switch located on each addressable
unit. See further address list in appendix A.
Address switches
The address is set by the 8 pole DIP switch. The DIP switch values
follows the binary system.
O
N
1 2 3 4 5 6 7 8
1 2 4 8 16 32 64 128
O
N
=47
1 2 3 4 5 6 7 8
The switches numbered 1,2,3,4 and 6 are set to ON position. The values
for these switches are 1+2+4+8+32=47.
Detectors
It is important to seal the address switch on the detectors with the
attached label after the address has been set.
Address units
In addition to the loop address, address units and I/O units are equipped
with an ID dipswitch. The ID decides the function of the unit.
See appendix B for an ID list.
Addressable Timers
The addressable timers are located on the detector loop in the same way
as any loop unit.
For UR-2/UR-2K type timers, three address DIP switches should be set:
1. The loop address for the timer itself.
2. The first address of the interval of detectors to be disconnected.
3. The last address of the interval of detectors to be disconnected.
For NS-TIMAC only the loop address has to be set.
Please note that timers do not affect the function of the manual call
points or heat detectors.
Terminal layout
Since most systems are customer designed there exists no standard for
how the different boards are to be connected in the system. However in
the figure below you will find one board of each type that can be
connected to the CS4000 system.
You do not need to keep track of A and B side when connecting loop
units to the loop, for instance start counting from the primary side.
Control unit
The control units are connected via two separate channels, A and B.
Each channel to be routed in a separate cable, see the block diagram in
chapter 1. Minimum requirement for the cable to control units is
2x2x0.5mm2 twisted pairs.
Installation Manual Chapter 2: Installation 14
Salwico CS4000
Chapter 3: Verification
The definition of the loops must be performed by a person with a good
knowledge of the CS4000 fire system. The operator must have the
authority to work in access level 4. The system is delivered either with a
complete system definition or a test definition.
The addressable detector loops can be tested before connection to the
central unit with a test device, SE3000, to verify the cable status and the
addresses of the loop units.
Loops
We assume that there are no communication problems in the system
since the cable has already been tested but each loop have to be verified.
The verification procedure is described below, step by step.
history list” found under: menu/7 History/1 Fire History List. This
list is cleared every time the system is restarted.
Testing
After installation of the fire alarm system the different parts of the system
shall be tested to assure correct function. The CS4000 has a special test
mode, which makes the testing of detector zones easier. When a zone is in
test mode it will not activate any external alarm devices or controls in
case of a fire. Each tested detector and manual call point will indicate
activation with a red LED. The units in alarm will also be automatically
reset when the heat or smoke concentration is under the alarm level or if
the manual call point is reset. Fire alarms from zones not in test mode will
not be inhibited. Detectors and manual call points in the zone will blink
during test mode. The tested zone will automatically return to normal
operation after two hours.
It is now safe to test each detector, manual call point etc in this fire zone
during two hours. Use suitable testing equipment.
All alarms will be listed under: menu/7 History/1 Fire History List
Trouble shooting
Polarity fault
One or more loop units are not correctly installed if the measured
voltage is much less then 30 VDC. Proceed as follows to locate the loop
units with polarity fault:
1. Divide the cable in two halves.
2. Locate the polarity fault on one of the halves.
3. Divide this half of the cable again into two halves. Continue to
divide the cable into halves until you have found the polarity
fault.
All the section units are correctly installed when the measured voltage is
around 30 VDC.
Cause Remedy
Less loop units found than Install the missing loop units.
configured.
More loop units found than Compare the found loop units
configured. with the configuration program.
Wrong address for the loop Set the correct address.
unit.
Two or more loop units with See Address error paragraph
the same address. below.
Loop unit is broken. Replace the loop unit.
Note! Restart the loop by pressing the reset button on the LB3 loop
board after each time you have changed an address. You have to wait
for some minutes after restart to give the loop time to re-boot.
Address error
Use menu/ 6 Service menu/5 Loops, choose the relevant loop and then
press 2=Loops Units to list all found units on the loop. Compare the
found loop units with the ones configured. However, there is a
possibility that one or more loop units with the same address will
answer, which is reported as bad communication, an abnormal
condition.
Installation Manual Chapter 3: Verification 18
Salwico CS4000
Cable break
No loop units are answering.
- The cable is broken before the first loop unit if no answer is received
on a single fed loop.
- The cable is broken before the first loop unit and after the last loop
unit if the loop is a double fed loop.
Earth fault
The system will inform about which loop that has an earth fault.
Examine the faulty loop to locate the earth fault. See “earth failure”
under “test the cable” in chapter 2 for more details.
If the earth fault still remains after these steps, examine the cables to all
other devices connected to the fire alarm system.
Short circuit
No loop units answers
Search for the short circuits between the central unit and the first short
circuit isolator.
The easiest way to find a short circuit is to divide the cable in two
halves, locate the short circuit on one of the halves. Divide this half of
the cable again into two halves. Continue to divide the cable into halves
until you have found the short circuit.
Installation Manual Chapter 3: Verification 19
Salwico CS4000
Mute faults
The internal buzzer is temporarily silenced when the door to the control
panel is opened.
The fault indication stops flashing and turns over to steady yellow. The
fault is put in a fault list under menu/ 1 Fault Alarms/ 1 Fault List.
Reset faults
The cause of the problem must disappear before a fault can be reset.
The faults are reset from the Fault list under menu/ 1 Fault Alarms/ 1
Fault List.
Loop Requirements
The list in part A (Loop configuration) includes all data you need when
configuring the loops. Part B (Loop status) is more like a checklist, use
it and follow it point by point. When you have completed this part you
should have filled in, signed and faxed the special document ”Address
list/test report” one for each loop in the system. Part C (Central status) is
also a checklist but it deals with the status of the central unit.
Summary
The following document must be filled in and faxed to Consilium
+46 - 31 710 78 00 and your local Consilium representative in your
country before commissioning of the system starts.
Smoke detectors
• Smoke detectors shall if possible be installed in the middle of the
space or where the smoke most probably rises.
• Keep smoke detectors away from possible causes of unwanted
alarms such as showers, saunas, ovens and toasters.
• The detector shall not be installed behind air ducts etc delaying
the smoke to reach the detector, or near ventilation inlets that
blows smoke away from the detector. Minimum distance from
ventilation inlet is 0.5 m.
• Minimum distance from wall or bulkhead is 0.5 m.
• Maximum distance from wall or bulkhead is 5.5 m, and
maximum distance between two detectors is 11 m.
• In engine spaces, smoke detectors shall have 2 m extra cable
slack to enable relocation of the detector.
• In cabins and in lockers the detectors shall be mounted with the
LED of the detector facing the door.
Heat detectors
• Heat detector shall be installed to the best place to protect the
area, mainly in the middle of the space and in a place where the
detector works reliably.
• Alarm temperature of the detector shall be at least 30ºC above
normal temperature.
• Avoid placing the detector near heat-generating devices, such as
ovens, saunas etc., which may cause unwanted alarms.
• Maximum distance from wall or bulkhead is 4.5 m and between
two detectors it is 9 m.
Installation Manual Chapter 5: Guidelines for fire alarm installations 24
Salwico CS4000
Flame detector
• Flame detector to be installed when flames can be expected in
the initial stage of a fire.
• The flame detector shall be mounted so it has a clear view to the
anticipated fire.
• The detector should be mounted in the best angle (elevation and
azimuth) to cover the protection area. See the data sheet for the
actual flame detector for more info about angle of protection etc.
Address units
• The address unit is used to interface conventional detectors (or
any dry closing contact) to the addressable fire detection loop.
• In addition to the loop address, the address unit has one ID
switch that has to be set, please see appendix B.
Timers
• The timer unit is used for temporarily disconnection of detectors
in areas where smoke or heat can occur under normal
circumstances.
• The timer should be mounted for easy access and operation and
well marked with the function.
• In addition to the loop address the address interval for the
disconnected detectors must be set on the two extra DIP
switches in the timer.
Bells
• Installation height normally 200 mm from ceiling and max 2200
mm from floor.
• After installation, make sure that the cables are free from the
gong, otherwise the sound output will be reduced.
Electrical siren
• Make sure to programme the siren to correct sound and
intermittence with the DIP switch inside the siren. More
information about how to set the DIP switch are found in the
data sheet for this unit
• Turn the volume control to max.
• If the siren does not have a text clarifying the category of the
alarm (for example FIRE ALARM), it is recommended to mark
it properly.
Appendix B: ID list
The ID switch must be set on the address units type AE and NS-AIN. The ID
defines the function of the unit and type of unit connected to the address unit.
Setting the ID
The ID is set by the 4-pole (NS-AIN type) or 5-pole (AE type) DIP switch
located on the address units. The DIP switch value follows the binary system.
O
N
1 2 3 4 5
1 2 4 8 16
The value of the ID is according to the switches set to “ON” position, for
example:
O
N
1 2 3 4 5
= ID5
The switches numbered 1 and 3 are set to ON position. The values for
these switches are 1+4=5
Fault list
Listed below are all fault codes, their causes and how an operator with some knowledge
of the system can solve the problem.
been detected.
142 CABLE BREAK A cable break on the Locate the cable break and mend it.
NEGATIVE negative conductor has
been detected.
143 COMMUNICATION Two units have the Check the loop unit addresses
ERROR same address.
The communication with a Loop unit faulty. Exchange the unit.
unit is deficient. Interference Locate interference and deal with it.
144 WRONG TYPE OF UNIT The type of unit Check the specification and change
specified is different definition or the unit.
from the type found or
configured.
145 UNKNOWN TYPE OF Unit faulty Exchange the unit
UNIT Wrong type of detector Install the correct type and restart the
The type of unit specified has been installed loop.
is unknown to the system.
146 TIMER STUCK The timer has been Check the unit.
activated too long.
148 DOUBLE ADDRESS Two units sharing the Change one of the addresses.
same address
149 CABLE SHORT Short circuit on cable. Locate the short circuit and fix it.
CIRCUIT
150 VALVE CLOSED The valve is closed. Open the valve
151 CONFIGURED NOT Unit is configured but Add the unit or change the system
PRESENT not present. configuration.
152 PRESENT NOT Unit is present but not Remove the unit or change the
CONFIGURED configured. system configuration.
153 HIGH CURRENT ON There is high current in Check if there is to many units
LOOP the loop cable. connected to the loop. Compare with
the loop limitations.
154 LOOP POWER LOSS The loop voltage is Exchange the loop board.
missing.
155 EARTH FAULT Too low impedance on Locate the earth fault and fix it.
POSITIVE positive conductor.
156 EARTH FAULT Too low impedance on Locate the earth fault and fix it.
NEGATIVE negative conductor.
157 FUSE FAULT A fuse is defective. Replace the fuse.
158 BATTERY FUSE FAULT A battery fuse has Replace fuse or mend the cable.
blown or a cable break.
159 CABLE BREAK A cable break has been Mend the cable.
detected.
160 CABLE OVERLOAD Too high current on an Check external loads.
output.
161 POWER FAULT The main power supply Check the main power supply.
is lost.
162 EMERGENCY POWER Emergency power is Check the emergency power supply.
FAULT lost.
163 BATTERY FAULT A bad battery is Charge the battery. If the fault
detected. remains then replace the battery.
164 CHARGING LOSS The battery charger is Replace the battery charger.
unable to charge the
battery.
165 EXTERNAL FAULT External equipment has Check the external equipment.
indicated fault.
166 EARTH DETECTION Unable to detect earth Replace the earth fault circuit.
FAULT fault.
167 CHECKSUM EEP Incorrect EPROM Contact our service department.
Installation Manual Appendix C: Fault codes & Fuses 33
Salwico CS4000
checksum.
168 RESTARTED Something has restarted. If it happens repeatedly, contact our
More info is given on service department.
the control panel.
169 TOO LONG BOOT Exceeded the maximal If it happens repeatedly, contact our
allowed boot time. service department.
170 EXTERNAL LOAD ON There is a too high Locate the load and deal with it.
LINE external load on a
conventional zone.
171 EXTERNAL SOURCE Feeding voltage Locate the source and remove it.
ON LINE detected on a
conventional zone.
172 LOW POWER SUPPLY Low voltage on the Check the power supply.
IN1 primary 24VDC power
supply to the internal
PCB’S.
173 LOW POWER SUPPLY Low voltage on the Check the power supply.
IN2 secondary 24VDC
power supply to the
internal PCB’S.
174 LOW POWER SUPPLY Too low voltage on the Contact our service department.
LOCAL 3.3V/5V feeding to the
internal circuit boards.
175 LOW POWER SUPPLY Too low incoming Check the power supply
24VDC supply to the
internal circuit boards.
176 SYSTEM CONF FAULT The configuration file is Check the configuration file and re-
corrupt. configure the system.
An error has occurred Re-configure the system. If the fault
during downloading of remains, contact our service dept.
the configuration file.
177 LOW PRESSURE External equipment Check the pressure on the supervised
indicates low pressure. unit.
178 ACTUATOR 1 Missing feedback from Check cables to actuator 1. If the
actuator 1 cables are OK, change the actuator.
179 ACTUATOR 2 Missing feedback from Check cables to actuator 2. If the
actuator 2. cables are OK, change the actuator.
209 WRONG TYPE OF UNIT The type of unit Change the unit or the system
DEFINED specified is different configuration.
from the type
configured.
210 ERROR IN Fault detected in the Check the configuration.
CAUSE&EFFECT configuration.
DEFINITIONS
255 ILLEGAL Internal system error. Contact our service department.
Installation Manual Appendix C: Fault codes & Fuses 34
Salwico CS4000
Fuses
If a fuse is defective in the system a fault will be displayed at the control units. Locate
and replace the fuse with the information below.
Fuse list
Location Fuse Fuse rating Fuse type
Base board F1: Alarm bell output 1AT 5x20 mm
Base board F2: Alarm bell output 1AT 5x20 mm
Base board F3: Alarm bell output 1AT 5x20 mm
Base board F4: Alarm bell output 1AT 5x20 mm
Rectifier board F3: To transformer 3.15AF 5x20 mm
Rectifier board F4: To transformer 3.15AF 5x20 mm
Rectifier board F5: To external 230VAC 3.15AF 5x20 mm
Rectifier board F6: To external 230VAC 3.15AF 5x20 mm
Rectifier board F8: Battery 4 AF 5x20 mm
Rectifier board F9: Battery 4 AF 5x20 mm
Rectifier board F10: From transformer 6 AF 5x20 mm
Rectifier board F11: From transformer 6 AF 5x20 mm