You are on page 1of 4

SWEES MODEL NO SHMd5000-9620 SHMd5000-9640

AC Input parameters
Nominal Voltage 220/230/240VAC
Acceptable Voltage Range 120 -280VAC
Frequency 40Hz - 60Hz
Low Voltage Transfer 120VAC ±2%
Low Voltage Return 130VAC ±2%
High Voltage Transfer 290VAC ±2%
High Voltage Return 280VAC ±2%
Output parameters
Power rating VA/Watt 5000VA/ 4000W
Voltage (Bat mode) 220/230/240VAC(Factory –settable)
Voltage regulation (Bat <3%RMS for entire battery voltage range
mode)
Frequency (Line mode) Same as AC input
Frequency (Bat mode) 50Hz +/- 0.1Hz
Power factor 0.8
Waveform Pure sine wave
Efficiency >85%
Battery parameters
Battery voltage 96VDC
Backup time Depends on connected battery and load
Battery capacity Maximum recommended 200AH
Charging current Up to 15A (Factory settable)
Built in Solar charge controller
PV input Vmp Minimum 125V 125V
PV input Voc Maximum 300V 300V
Max PV input power 2100W 4200W
Charging current 20A 40A
Charge controller type MPPT MPPT
SCC efficiency >95% >95%
MPP Tracking efficiency >99% >99%
Recommended panel configuration
235W-60 cells 5 Series + 2 Parallel 6 Series+3 Parallel
240W-60 cells 7 Series 5 Series+3 Parallel
250W-60 cells 7 Series 5 Series+3 Parallel
280W-72 cells 4 Ser+2 Parallel 5 Series+3 Parallel
300W-72 cells 6 Series 6 Series+2 Parallel
Display and protection features
Overload protection (Line >130%, then Mains ON LED blink continuously
mode)
Overload protection 110% -150% for 10sec; >150% for 200ms;then PCU
(Battery mode) Shuts Down
Short circuit protection Miniature circuit breaker
(line mode)
Short circuit protection Electronic shutdown
(battery mode)
Transfer time <10ms
Protection features Input Low/High/Phase reverse, Battery Low, Over load,
Over Temperature, Short circuit
Audible alarms Battery low, overload, High Temp, Battery voltage error,
SCC charging current error.
LED indication + 4 line System Ready, Mains ON, Home UPS ON/Battery Low,
LCD display with Energy Charging/Charged, Over load/Over Temp, SCC
generation charging modes and alarms, AC voltage, Battery
voltage, AC energy consumed, DC Energy generated,
Carbon savings, AC Power and DC Power.
Environmental and Mechanical specifications
Audible Noise Less than 55dBA ( at 1M)
Operating temperature 0-40°C,32 -104°F
Relative humidity 0-95% non-condensing
Enclosure type Floor Mountable
Physical Dimension 35 x 50 x 56 CM
(L x H x D)
Weight (kg) 50Kg
SWEES MODEL NO SHMd7500-12060
AC Input parameters
Nominal Voltage 220/230/240VAC
Acceptable Voltage Range 120 -280VAC
Frequency 40Hz - 60Hz
Low Voltage Transfer 120VAC ±2%
Low Voltage Return 130VAC ±2%
High Voltage Transfer 290VAC ±2%
High Voltage Return 280VAC ±2%
Output parameters
Power rating VA/Watt 7500VA/ 6000W
Voltage (Bat mode) 220/230/240VAC(Factory –settable)
Voltage regulation (Bat <3%RMS for entire battery voltage range
mode)
Frequency (Line mode) Same as AC input
Frequency (Bat mode) 50Hz +/- 0.1Hz
Power factor 0.8
Waveform Pure sine wave
Efficiency >85%
Battery parameters
Battery voltage 120VDC
Backup time Depends on connected battery and load
Battery capacity Maximum recommended 200AH
Charging current Up to 15A (Factory settable)
Built in Solar charge controller
PV input Vmp Minimum 150V
PV input Voc Maximum 300V
Max PV input power 8600W
Charging current 60A
Charge controller type MPPT
SCC efficiency >95%
MPP Tracking efficiency >99%
Recommended panel configuration
235W-60 cells 6 Series + 6 Parallel
240W-60 cells 6 Series + 6 Parallel
250W-60 cells 6 Series + 5 Parallel
280W-72 cells 6 Series + 5 Parallel
300W-72 cells 5 Series + 5 Parallel
Display and protection features
Overload protection (Line >130%, then Mains ON LED blink continuously
mode)
Overload protection 110% -150% for 10sec; >150% for 200ms;then PCU
(Battery mode) Shuts Down
Short circuit protection Miniature circuit breaker
(line mode)
Short circuit protection Electronic shutdown
(battery mode)
Transfer time <10ms
Protection features Input Low/High/Phase reverse, Battery Low, Over load,
Over Temperature, Short circuit
Audible alarms Battery low, overload, High Temp, Battery voltage error,
SCC charging current error.
LED indication + 2 line System Ready, Mains ON, Home UPS ON/Battery Low,
LCD display with Energy Charging/Charged, Over load/Over Temp, SCC
generation charging modes and alarms, PV voltage, PV current,
PV power, Battery voltage, Battery current, Today’s
energy and Total energy.
Environmental and Mechanical specifications
Audible Noise Less than 55dBA ( at 1M)
Operating temperature 0-40°C,32 -104°F
Relative humidity 0-95% non-condensing
Enclosure type Floor Mountable
Physical Dimension 50 x 80 x 86 CM
(L x H x D)
Weight (kg) 80Kg

Note: Few parameters like size, weight and audible noise can change