You are on page 1of 2

VOLUME FLOW RATE REQUIREMENT:

𝐊 𝟏𝟒. 𝟎 𝐆𝐏𝐌/𝒑𝒔𝒊𝟏/𝟐
𝐐 = =
√𝑷 √𝟏𝟕𝟓 𝐩𝐬𝐢
𝐐 = 𝟏. 𝟎𝟓𝟖𝟑 𝐆𝐏𝐌

𝐐𝒕𝒐𝒕𝒂𝒍 = 𝐐 × 𝐧𝐨. 𝐨𝐟 𝐬𝐩𝐫𝐢𝐧𝐤𝐥𝐞𝐫𝐬


𝐐𝒕𝒐𝒕𝒂𝒍 = (𝟏. 𝟎𝟓𝟖𝟑 𝐆𝐏𝐌) × 𝟐𝟕𝟒 𝐬𝐩𝐫𝐢𝐧𝐤𝐥𝐞𝐫𝐬
𝐐𝒕𝒐𝒕𝒂𝒍 = 𝟐𝟖𝟗. 𝟗𝟕 𝐆𝐏𝐌
𝐐𝒕𝒐𝒕𝒂𝒍 ≅ 𝟐𝟗𝟎 𝐆𝐏𝐌 ≅ 𝟏𝟎𝟗𝟕. 𝟕𝟕 𝐋𝐏𝐌

FOR 10 HRS. CONTINUOUS OPERATION:


𝟔𝟎 𝒎𝒊𝒏
𝑻𝒂𝒏𝒌 𝑽𝒐𝒍𝒖𝒎𝒆 = (𝟏. 𝟎𝟗𝟕𝟕𝟕𝒎𝟑 /𝒎𝒊𝒏) × 𝟏𝟎 𝒉𝒓𝒔 ×
𝟏 𝒉𝒓
𝑻𝒂𝒏𝒌 𝑽𝒐𝒍𝒖𝒎𝒆 = 𝟔𝟓𝟖. 𝟔𝟔𝟐 𝒎𝟑

AREA OF DISCHARGE:
𝝅𝒅𝟐 𝝅(𝟎. 𝟏𝟐𝟓𝒎)𝟐
𝑨𝟏 = = = 𝟎. 𝟎𝟏𝟐𝟐𝟕𝒎𝟐
𝟒 𝟒
𝝅𝒅𝟐 𝝅(𝟎. 𝟏𝟎𝟎𝒎)𝟐
𝑨𝟐 = = = 𝟎. 𝟎𝟎𝟕𝟖𝟓𝒎𝟐
𝟒 𝟒
𝝅𝒅𝟐 𝝅(𝟎. 𝟎𝟕𝟓𝒎)𝟐
𝑨𝟑 = = = 𝟎. 𝟎𝟎𝟒𝟒𝟏𝒎𝟐
𝟒 𝟒
𝝅𝒅𝟐 𝝅(𝟎. 𝟎𝟓𝟎𝒎)𝟐
𝑨𝟒 = = = 𝟎. 𝟎𝟎𝟏𝟗𝟔𝒎𝟐
𝟒 𝟒
𝑨𝒕𝒐𝒕𝒂𝒍 = 𝑨𝟏 + 𝑨𝟐 + 𝑨𝟑 + 𝑨𝟒
𝑨𝒕𝒐𝒕𝒂𝒍 = 𝟎. 𝟎𝟏𝟐𝟕𝟕 + 𝟎. 𝟎𝟎𝟕𝟖𝟓 + 𝟎. 𝟎𝟎𝟒𝟒𝟏 + 𝟎. 𝟎𝟎𝟏𝟗𝟔
𝑨𝒕𝒐𝒕𝒂𝒍 = 𝟎. 𝟎𝟐𝟕 𝒎𝟐

VELOCITY:
𝒎𝟑 𝟏 𝒎𝒊𝒏
𝑸 𝟏. 𝟎𝟗𝟕𝟕 𝒎𝒊𝒏 × 𝟔𝟎 𝒔𝒆𝒄
𝑽= = = 𝟎. 𝟔𝟕𝟕𝟔 𝒎/𝒔
𝑨 𝟎. 𝟎𝟐𝟕𝒎𝟐

TOTAL HEAD:
Pressure Head:
𝟏𝟎𝟏. 𝟑𝟐𝟓 𝒌𝑷𝒂
𝑷 𝟏𝟕𝟓 𝒑𝒔𝒊 × 𝟏𝟒. 𝟕 𝒑𝒔𝒊
𝑯𝑷 = = = 𝟏𝟐𝟐. 𝟗𝟔 𝒎
𝜸 𝟗. 𝟖𝟏 𝒌𝑵/𝒎𝟑

Velocity Head:
𝑽𝟐 (𝟎. 𝟔𝟕𝟕𝟔𝒎/𝒔)
𝝂= = = 𝟎. 𝟎𝟑𝟒𝟓 𝒎
𝟐𝒈 𝟐 × 𝟗. 𝟖𝟏𝒎/𝒔

Elevation Head:
𝒛 = 𝟕𝒎

𝑯 = 𝑷𝒓𝒆𝒔𝒔𝒖𝒓𝒆 𝑯𝒆𝒂𝒅 + 𝑽𝒆𝒍𝒐𝒄𝒊𝒕𝒚 𝑯𝒆𝒂𝒅 + 𝑬𝒍𝒆𝒗𝒂𝒕𝒊𝒐𝒏 𝑯𝒆𝒂𝒅


𝑯 = 𝟏𝟐𝟐. 𝟗𝟔𝒎 + 𝟎. 𝟎𝟑𝟒𝟓𝒎 + 𝟕𝒎
𝑯 = 𝟏𝟐𝟗. 𝟗𝟗 𝒎
WATER PUMP POWER, HP:
𝑸𝜸𝑯
𝑯𝑷 =
𝟕𝟒𝟔
𝟏 𝒎𝒊𝒏
(𝟏. 𝟎𝟗𝟕𝟕𝟕𝒎𝟑 /𝒎𝒊𝒏) × ( 𝟑
𝑯𝑷 = 𝟔𝟎 𝒔𝒆𝒄) × (𝟗𝟖𝟏𝟎𝑵/𝒎 ) × (𝟏𝟐𝟗. 𝟗𝟗𝒎)
𝟕𝟒𝟔
𝑯𝑷 = 𝟑𝟏. 𝟐𝟕𝟓 𝑯𝑷

MOTOR POWER:
𝑾𝒂𝒕𝒆𝒓 𝑴𝒐𝒕𝒐𝒓 𝑷𝒐𝒘𝒆𝒓 𝟑𝟏. 𝟐𝟕𝟓 𝑯𝑷
𝑴𝒐𝒕𝒐𝒓 𝑷𝒐𝒘𝒆𝒓 = =
𝑷𝒖𝒎𝒑 𝑬𝒇𝒇𝒊𝒄𝒊𝒆𝒏𝒄𝒚 𝟎. 𝟕𝟎
𝑴𝒐𝒕𝒐𝒓 𝑷𝒐𝒘𝒆𝒓 = 44.68 HP

USE: 45 HP, 290 GPM, 3600 FIRE PUMP