A GEOGRAPHIC A
NORTH
11
5°
IMPZ.SS.06
ROAD 21.50M
TRUE
NORTH
B 60000 B
3030
SECURITY TOILET
3000
3000
ROOM
3730
INTERLOCK
3955
3600
DRIVE WAY
CABLE 1. ALL DIMENSIONS ARE IN MM AND ALL LEVELS ARE IN M UNLESS OTHERWISE SPECIFIED.
5940
C 1000 STAIRCASE-4
PULLING PIT
C
HOLDING TANK 2. HEIGHT OF THE BUILDING SHALL BE GOVERNED BY THE REQUIREMENT OF THE EQUIPMENT TO BE HOUSED
1420
3. THE WALLS AROUND THE TRANSFORMER/REACTOR SHALL BE FIRE PROOF.
5100
2940 2855 4355
6590
4. THE GROUND WATER TANK & TRANSFER PUMPS WILL BE INDICATED TENTATIVELY SUBJECT TO
1200
CHANGE IN DETAILED DESIGN.
3000
7375 IDT DELUGE
2690
5. THE CAPACITY OF FIRE WATER TANK WILL BE INDICATED AFTER THE FINALIZATION OF HYDRAULIC CALCULATIONS.
STAIRCASE-1 132kV CABLE
2900
TRENCH 6. FOR CIVIL DEATILS, PLEASE REFER RELEVANT CIVIL ARCHITECTURAL DRAWINGS.
IDT-2 ROOM OWMH-1 DIESEL 7. GROUND WATER TANK WILL BE LOCATED ON ROOF OF SECURITY ROOM.
1930
35/50MVA-132/12kV 1500x1500
TANK
6600 6600 8. THE TRANSFORMER ROOF SHALL BE OF STEEL STRUCTURE. PROCEDURE FOR ERECTION AND DISMANTLING
1W 1V 1U
FOR 11kV OUTGOING CABLES
4000
OFF LOADING OF ROOF TRUSSES, SHEETING AND LOUVERS FOR TRANSFORMER TO BE SUBMITTED FOR APPROVAL
2x10Nos.150Ø uPVC DUCTS
2000
2000
10000
3000
PLATFORM
3200
9. ALL BLOCK WALLS AND THERMAL INSULATED EXTERNAL WALLS ARE SHOWN WITH
INCLUDING PLASTERING THICKNESS
2745
D 1540 2060 3000 INTERLOCK D
3000 1710 1890 4500 10. NO OF CABLE DUCTS LOCATION FOR THE INTERNAL CABLING OF THE SUB STATION SHALL BE
CABLE
2W DRIVE WAY AS PER REQUIREMENTS AND DEWA APPROVAL
AIR LOCK
5218
CL PULLING PIT
11000
ROLLING SHUTTER 2V
835 800 800 800 800 800 800 800 800 800 800 1000 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000 800 800 800 800 800 800 800 800 800 800 800 1035
11kV CABLE
2000
ROOM
835 800 800 800 800 800 800 800 800 800 800 1000 800 800 800 800 800 800 800 800 800 800 800 1000 1000 800 800 800 800 800 800 800 800 800 800 835
TRENCH
2U 11. OPEN AREA INSIDE THE COMPOUND SHALL BE PAVED WITH 800mm THICK INTERLOCK PAVING.
1500
2000
CABLE FIRE PUMP ROOM 12. FIRE BARRIERS SHALL BE DESIGNED / INSTALLED GIVING DUE CONSIDERATION FOR
RISER -1 (FIRE WATER TANK ABOVE) EASY OPERATION AND MAINTENANCE OF EQUIPMENTS
2745
CRANE MAINTENANCE PLATFORM AND
4000
MOTOR MAINTENANCE PLATFORM
900x530 WALL OPENING
CL 14. SCMS PANELS, DMZ PANELS, OPERATOR CONTROL DESKS, SCMS PRINTER & SCMS CUPBOARD
1927
11kV BUSDUCT
ACCESS LADDER
SHALL BE PROVIDED WITH RAISED FLOOR.
200 800 2000 7586 2664 SYMBOL DESCRIPTION
1222 9028 1000
THERMAL
2920
LV CABLE TRENCH
4737
1930
FIRE ESCAPE 35/50MVA-132/12kV
HATCH WITH GRATING
1W 1V 1U
LADDER
2580
IDT-1
E03 GRATING
CABLE
800
2W PULLING PIT ET DELUGE
5218
CL
2V
11kV CABLE
DUNE SAND WITH ROOF TILES
TRENCH
2U
IDT-2
E04
1485
CAST IN SITU SLAB
RYDA
UTILITY CORRIDOR
HATCH WITH
F LADDER F
4900
REMOVABLE PRECAST COVER
11000
17000
CL
1927
UTILITY CORRIDOR
26360
1515
EARTHING
LV CABLE TRENCH
TRANSFORMER 290mm THK.
THERMO BLOCK WALL
50000
29470
36000
132kV CABLE
E07
SPCB
1485
1500x1500 SOLID BLOCK WALL
1930
35/50MVA-132/12kV
IDT-3
4900
1V 1U
11kV SWITCHGEAR ROOM-1
1W
E08 HOLLOW BLOCK WALL
SPARE
E09
11kV SWITCHGEAR ROOM-2
1515
2W PULLING PIT EARTHING CAVITY WITH APPROVED INSULATION +100 THK
5218
CL TRANSFORMER SOLID BLOCK WALL + 20 THK PLASTER )
2V
11kV CABLE
TRENCH
2U
COLUMN STOPPING AT GROUND FLOOR LEVEL
1485
FIRE ESCAPE 914mmx914mm FIRE ESCAPE
HATCH WITH
REFERENCE DRAWINGS
HATCH WITH LADDER
LADDER
CABLE
ET ROOM-3
13250 CL
PULLING PIT
CAGE LADDER
4900
1927
8380
1515
EARTHING
FOR 11kV OUTGOING CABLES
5360
TPD / 132kV / FAY ROAD / SLD / 01 132kV SINGLE LINE DIAGRAM (TENDER DRAWING)
H 7750 ABBREVIATIONS: H
IDT INTER DISTRIBUTION TRANSFORMER R0 TPD / 11kV / FAY ROAD / SLD / 01 11kV SINGLE LINE DIAGRAM (TENDER DRAWING) --
2650
ET EARTHING TRANSFORMER
O/W OIL WATER COLLECTION AREA R0 DEWA/132kV-SS/FAYROAD/001/2017 AL FAY ROAD 132/11kV SUBSTATION (TENDER DRAWING) --
STAIRCASE-2 300mm COBBLE STONE
ABOVE GRATING REV DRAWING NUMBER DRAWING TITLE STATUS
CABLE CABLE RCC REINFORCED CEMENT CONCRETE No.
PULLING PIT PULLING PIT
FT FLOOR TRAP
4950 4950 4950 CL CENTER LINE
1300
1300
1300
REVISIONS
INTERLOCK
4700
4700
4700
FOR 11kV OUTGOING CABLES
CAPACITOR ROOM-2
CAPACITOR ROOM-3
2x10Nos.150Ø uPVC DUCTS
1100
1100
14800
1890 1710 3000 4950 4950 4950 DETAILS
1300
1300
1300
CONCRETE
PLATFORM 2000 12715 CLIENT
CABLE 7540
4700
4700
4700
2900
1855 1500 1800 1855 1500 1855 1500 GOVERNMENT OF DUBAI Dubai Electricity & Water Authority
STAIRCASE-3 1800 Transmission power Division
2940
1100
1100
1100
2500
------------------------------------
DRAWING TITLE
OVERALL EQUIPMENT LAYOUT
GROUND FLOOR PLAN L
L
SUB CONTRACTOR REF. CAD REF. REV SHEET LAST SHEET QTY OF SHEET
------------------------------------ XXXXXX
0 1 -- 2