these two phasor representations can be time-stamped and sent A typical PMU device’s hardware architecture and
to the control room respectively from two different locations. functionality components are shown in Fig. 3. The analog
Therefore, though they may not arrive at the control room inputs from CT and PT will first go through a low-pass anti-
simultaneously due to different communication delays, they can aliasing filter. The basic anti-aliasing strategy is to use an
still be aligned and compared thanks to the same GPS time analog filter that has a cut-off frequency slightly higher than the
reference. Apparently, a comparison between ⃑⃑⃑𝑉1 and ⃑⃑⃑
𝑉2 won’t Nyquist criterion while another strategy is to use a much higher
sampling rate and then add a digital ‘decimation filter’ in
be meaningful without this time synchronization.
addition to the analog filter. In this case, the cut-off frequency
of the analog filter will be much higher than the Nyquist
criterion. It has been found out that a combination of analog and
digital filters makes the filtering performance more robust to
aging and temperature changes. In addition, the high sampling
rate can increase the phase calculation precision potentially and
even enable the PMUs to act as the digital fault recorders if
enough memory is available. The calculations of voltage and
current phasors, as well as frequency and rate of change of
frequency (ROCOF) estimation, are performed by the micro
controller unit and then all the measurement results are time-
stamped, packaged, and transferred to the control room via the
communication links.
Fig. 1 Synchronized phasor representations of sinusoid waveforms
III. FNET/GRIDEYE OVERVIEW
As a member of the phasor measurement family,
FNET/GridEye is developed as a pilot wide-area phasor
measurement system that can cover the national or continental
level power grid at a much lower cost before the universal PMU
installations can be achieved. In this section, the
FNET/GridEye system is briefly overviewed.
A. FNET/GridEye Sensor
In order to achieve the phasor measurement at as many
locations as possible, the FNET/GridEye sensor was designed
Fig. 2 PMU installation and connection diagram to be deployed at the low voltage distribution grid instead of
high voltage substations or power plants [16]. Therefore, the
PMUs are currently installed at the high-voltage substations high-priced PTs and CTs for typical PMUs can be waived and
or large power plants. Since there are three phases involved, the installation cost of a FNET/GridEye sensor can be reduced
each PMU will require three connections that measure all three to only tenth of a typical PMU. Nevertheless, there are some
phases for both current and voltage. A diagram of the typical extra technical challenges associated with the phasor
PMU installation on one phase at a substation is shown in Fig. measurement in the distribution grid. One example is that,
2. The current transformer (CT) and potential transformer (PT) different from the high voltage transmission systems with
scale down the current and voltage of the high voltage buses in relatively fewer harmonics, distribution grids have much worse
order to fit the input ranges of the A/D converters in the PMU. power quality due to the harmonics and distortions produced by
The burdens in Fig. 2 represent the VA rating of the electronic various electric appliances at the customer side. Therefore,
instruments connected to the PT/CT secondary circuits and the extra effects have been used to develop the advanced algorithms
attenuators are used for adjusting the output amplitudes further. that can achieve the accurate phasor measurement in the noisy
Due to the relatively high installation costs of PTs and CTs, environments [17]- [20].
PMUs are installed only at the most important nodes of the
power system right now.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
Three generations of FNET/GridEye sensors have been running on the real-time application agent to monitor power
developed since 2003 in order to improve measurement grid status by scanning the data streaming in. For example, on
accuracy and add more measurement functions. Fig. 4 shows this agent, the real-time disturbance detection module sends out
the Generation-II FNET/GridEye sensor which is the most alerts to system operators once it detects the occurrence of a
widely deployed so far. Its measurement accuracy reaches disturbance. Meanwhile, the data storage agent archives phasor
±0.0005 Hz in terms of frequency and ±0.0002 rad in terms of measurement data streams and outputs from the real-time
voltage angle. Furthermore, to mitigate the impact of GPS application agent for off-line applications. All the data are
signal loss on the accuracy and reliability of the sensors, chip archived in an efficient format to preserve data integrity while
scale atomic clock has been tested on the FNET/GridEye saving space. At the third layer, the non-real-time application
sensors [21]. agent runs offline applications to further exploit the archived
data. For example, the dynamic models of U.S. power grids
could be validated through comparing the actual system
frequency responses (stored in the archived phasor
measurements) with the model-produced simulation results.
The multi-layer structure of the FNET/GridEye data center
facilitates the concentrating, processing, and archiving of a
large volume of phasor measurements so as to successfully
meet the timeliness requirements of various applications.
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
(a) (b)
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
(c) (d)
(e) (f)
Fig. 13 Snapshots of the 2008 Florida blackout replay
2169-3536 (c) 2016 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/ACCESS.2017.2666541, IEEE Access
data analytics include the frequency extrema analysis [31], [15] Y. Liu et al., "Wide-Area-Measurement System Development at the
Distribution Level: An FNET/GridEye Example," IEEE Trans. Power
inertial frequency response analysis [32], and social event Delivery, vol. 31, no. 2, pp. 721-731, 2016.
impacts on power grid [33] etc. [16] L. Wang, J. Burgett, J. Zuo, C. Xu, B. J. Billian, R. W. Conners, and
Y. Liu, “Frequency disturbance recorder design and developments,” in
Proc. 2007 IEEE Power Eng. Soc. Gen. Meet., pp. 1–7.
VI. CONCLUSION
[17] Wei Wang, Liu Liu, Li He, Lingwei Zhan, Hairong Qi and Y. Liu, "Highly
In this paper, the FNET/GridEye was introduced as a pilot accurate frequency estimation for FNET," in Proc. 2013 IEEE Power &
Energy Society General Meeting, pp. 1-5, 2013.
electric power grid WAMS system. As shown by this paper,
[18] L. Zhan; Y. Liu; Y. Liu, "A Clarke Transformation-Based DFT Phasor
FNET/GridEye has accumulated rich operation experiences in and Frequency Algorithm for Wide Frequency Range," IEEE Trans Smart
the past decade which has benefited the phasor technology Grid, vol. PP, no. 99, pp.1-1, 2016.
development in the electric power industry. In order to further [19] W. Yao, L. Zhan, Y. Liu, M. Till, J. Zhao, L. Wu, Z. Teng, and Y. Liu, "A
Novel Method for Phasor Measurement Unit Sampling Time Error
explore the potential WAMS applications, FNET/GridEye will Compensation," IEEE Trans Smart Grid, vol. PP, no. 99, pp.1-1, 2016.
continue to increase its sensor accuracy and develop more data [20] L. Zhan and Y. Liu, "Improved WLS-TF algorithm for dynamic
analytics applications for power system status monitoring and synchronized angle and frequency estimation," in Proc. 2014 IEEE Power
Eng. Soc. Gen. Meet, pp. 1-5.
stability enhancement purposes. FNET/GridEye will [21] W. Yao; Y. Liu; D. Zhou; Z. Pan; J. Zhao; M. Till; L. Zhu; L. Zhan; Q.
significantly promote the field implementation of WAMS- Tang; Y. Liu, "Impact of GPS Signal Loss and Its Mitigation in Power
enabled applications in the electric power industry. System Synchronized Measurement Devices," IEEE Trans. Smart Grid,
vol. PP, no. 99, pp.1-1, 2016.
[22] D. Zhou et al., "Distributed Data Analytics Platform for Wide-Area
VII. REFERENCES Synchrophasor Measurement Systems," IEEE Trans. Smart Grid, vol. 7,
[1] A. G. Phadke, M. Ibrahim, and T. Hlibka, "Fundamental basis for distance no. 5, pp. 2397-2405, Sept. 2016.
relaying with symmetrical components," IEEE Transactions on Power [23] J. Chai et al., "Wide-area measurement data analytics using
Apparatus and Systems, vol. 96, pp. 635-646, 1977. FNET/GridEye: A review," in Proc. 2016 Power Systems Computation
[2] P. Bonanomi, “Phase angle measurements with synchronized clocks Conference (PSCC), pp. 1-6, 2016.
principle and applications,” IEEE Trans. Power App. Syst., vol. PAS-100, [24] R. M. Gardner, Z. Zhong, and Y. Liu, "Location determination of power
no. 12, pp. 5036–5043, Dec. 1981. system disturbances based on frequency responses of the system," U.S.
[3] A.G. Phadke, et al, "A new measurement technique for tracking voltage Patent 7765034, 2010.
phasors, local system frequency, and rate of change of frequency," IEEE [25] T. Xia et al., "Wide-area Frequency Based Event Location Estimation,"
Trans. Power App. Syst., vol. PAS-102, no.5, pp.1025-1038, May 1983. in Proc. 2007 IEEE Power Engineering Society General Meeting, pp. 1-
[4] J. De La Ree, V. Centeno, J. S. Thorp and A. G. Phadke, "Synchronized 7, 2007.
Phasor Measurement Applications in Power Systems," IEEE Trans. Smart [26] Y. Ye, R. M. Gardner and Y. Liu, "Oscillation analysis in Western
Grid, vol. 1, no. 1, pp. 20-27, June 2010. Interconnection using distribution-level phasor measurements," in Power
[5] Z. Lin, T. Xia, Y. Ye, Y. Zhang, L. Chen, Y. Liu, K. Tomsovic, T. Bilke, Eng. Soc. Gen. Meet., pp. 1-8, 2011.
and F. Wen, "Application of wide area measurement systems to islanding [27] J. Guo, H. Liu, D. Zhou, J. Chai, Y. Zhang and Y. Liu, "Real-time power
detection of bulk power systems," IEEE Trans. Power Syst., vol.28, no.2, system electromechanical mode estimation implementation and
pp.2006-2015, May 2013. visualization utilizing synchrophasor data," in Proc. 2016 IEEE/PES
[6] D. Zhou, Y. Liu and J. Dong, "Frequency-based real-time line trip Transmission and Distribution Conference and Exposition (T&D), pp. 1-
detection and alarm trigger development," in Proc. 2014 IEEE PES 5, 2016.
General Meeting, pp. 1-5, 2014. [28] J. Guo, "Data Analytics and Application Developments Based on
[7] G. Liu, J. Quintero and V. M. Venkatasubramanian, "Oscillation Synchrophasor Measurements." PhD diss., University of Tennessee, 2016.
monitoring system based on wide area synchrophasors in power systems," [29] G. Kou, P. Markham, S. Hadley, T. King and Y. Liu, "Impact of Governor
in Proc. of iREP Symposium - Bulk Power System Dynamics and Control Deadband on Frequency Response of the U.S. Eastern Interconnection,"
- VII. Revitalizing Operational Reliability, pp. 1-13, 2007. IEEE Trans. Smart Grid, vol. 7, no. 3, pp. 1368-1377, May 2016.
[8] A. G. Phadke, J. S. Thorp, R. F. Nuqui and M. Zhou, "Recent developments [30] L. Chen, P. N. Markham and Y. Liu, "Wide-area dynamic model
in state estimation with phasor measurements," in Proc. IEEE/PES Power validation using FNET measurements," in Proc. 2012 IEEE PES
Systems Conference and Exposition, pp. 1-7, 2009. Innovative Smart Grid Technologies (ISGT), pp. 1-7, 2012.
[9] I. Kamwa, J. Beland, G. Trudel, R. Grondin, C. Lafond and D. McNabb, [31] P. N. Markham, Y. Liu, T. Bilke and D. Bertagnolli, "Analysis of
"Wide-area monitoring and control at Hydro-Quebec: past, present and frequency extrema in the eastern and western interconnections," in Proc.
future," in Proc. IEEE Power Engineering Society General Meeting, 2011 IEEE Power and Energy Society General Meeting, pp. 1-8, 2011.
Montreal, Que., 2006, pp. 12. [32] L. Wu, Y. Liu, Dao Zhou, Jiahui Guo and Y. Liu, "Observation of inertial
[10] A. B. Leirbukt, J. O. Gjerde, P. Korba, K. Uhlen, L. K. Vormedal and L. frequency response of main power grids worldwide using
Warland, "Wide Area Monitoring Experiences in Norway," in Proc. IEEE FNET/GridEye," in Proc. 2016 IEEE Power and Energy Society General
PES Power Systems Conference and Exposition, Atlanta, GA, 2006, pp. Meeting, pp. 1-5, 2016.
353-360. [33] L. Chen, P. Markham, C. f. Chen and Y. Liu, "Analysis of societal event
[11] C. Lu, B. Shi, X. Wu and H. Sun, "Advancing China’s Smart Grid: Phasor impacts on the power system frequency using FNET measurements," in
Measurement Units in a Wide-Area Management System," IEEE Power Proc. 2011 IEEE Power and Energy Society General Meeting, pp. 1-8,
and Energy Magazine, vol. 13, no. 5, pp. 60-71, Sept.-Oct. 2015. 2011.
[12] P. M. Ashton, G. A. Taylor, A. M. Carter and H. Renner, "Opportunities to
exploit Phasor Measurement Units (PMUs) and synchrophasor
measurements on the GB Transmission Network," in Proc. 2011 46th
International Universities' Power Engineering Conference (UPEC), Soest,
Germany, 2011, pp. 1-6.
[13] Z. Zhong, C. Xu, B. J. Billian, L. Zhang, S.-J.S. Tsai, R. W. Conners, V.
A. Centeno, A. G. Phadke, and Y. Liu, “Power system frequency
monitoring network (FNET) implementation,” IEEE Trans. Power Syst.,
vol. 20, no. 4, pp. 1914–1921, Nov. 2005.
[14] J. Dong et al., "Wide-area measurements of three North America
interconnections at distribution level," in Proc. 2009 IEEE/PES Power
Systems Conference and Exposition, pp. 1-8, 2009.