Revised 05-03
Digital Tach/Hourmeter with Overspeed Trip Point Replaces SHD-96113N
Section 20
(00-02-0288)
Installation Instructions for SHD30 and SHD30-45 Models
Please read the following information before installing. A visual inspection for any damage which may have occurred during shipping is
recommended. It is your responsibility to have a qualified person install the unit, and make sure it conforms with NEC and local codes.
GENERAL INFORMATION
WARNING
C US
BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT Approved for Class I, Division 2,
✔ Disconnect all electrical power to the machine. Groups C & D Hazardous Areas
✔ Make sure the machine cannot operate during installation. When installed per Murphy
✔ Follow all safety warnings of the machine manufacturer. Drawing 20-08-0258
✔ Read and follow all installation instructions.
Vac, 10kHz
Mounting
MUST BE INSTALLED PER MURPHY DWG. 20-08-0258
Vdc
A@ 5Va
The SHD30 is designed for installation in panels from 0.032 to 0.125 in. (1 to
A @ 90Vd
Vdc, 125Vd
Vac,5kHz; 2mA
YP: 325uA
YP:150uA
AY = 0.5A, 30Vd
Vac-120Vac TYP
A @ 5Va
15mw MAX
Vdc TYP:
3 mm) thick. A round hole, 3-1/8 in. (79 mm) in diameter is needed for
1mA
CD IGN 90-300Vd
ELAY
OUTPUT REL
PU 5Va
MPU
WARNING: PERFORM THE WIRING INSTALLATION WITH THE POWER SOURCE OFF.
NEVER ROUTE THE SHD30 MODELS OVERSPEED OUTPUT LEADS WITH PRIMARY IGNITION WIRING.
Connecting the Overspeed Output SHD30 models normally open SCR output connected to a Murphy
A 7-connector terminal strip, on the back of the SHD30 models, is pro- MARK III digital fault annunciator. Figure 7 displays a typical wiring of
vided for connection of the overspeed output. Terminals C., and N.C. are the SHD30 models normally open SCR output to a Murphy MARK IV
used for connecting the output as a normally closed relay contact. annunciator. Figure 8 displays a typical wiring of the SHD30 models nor-
Terminals (+) and (–) are used for connecting the output as a normally mally closed relay output to a Murphy LCDT-NC annunciator. Figure 9
open SCR. Shown in Figure 5 is a typical wiring installation of the displays a typical wiring of the SHD30 models normally open SCR output
SHD30 models normally closed relay output connected to a Murphy to a Murphy LCDT-NO annunciator.
MARK III digital annunciator. Figure 6 shows a typical wiring of the
Figure 5: SHD30 models Normally Closed Relay output to MARK III Figure 6: SHD30 models Normally Open SCR output to MARK III
Back of MARK III Back of MARK III
16 16
Remove Leave Jumper
Jumper 17 in place
17
TB2
1 NO 32 32
2C TB2
TB1 3 NC 1 NO
1 MPU + 5-120Vrms 4 +Overspeed SCR 2C
2 MPU – 5 –Overspeed SCR TB1 3 NC
3 NEG 90-300vdc 6 Reset Hourmeter 1 MPU + 5-120Vrms 4 +Overspeed SCR
4 POS 90-300vdc 7 2 MPU – 5 –Overspeed SCR
N O C NC + – SHD30 To be 3 NEG 90-300vdc
4 POS 90-300vdc
6 Reset Hourmeter
7
TB2 1 2 3 4 5 6 7
installed in accor- NO C NC + –
+ dance with NEC
CD Ignition TB2 1 2 3 4 5 6 7
TB1 1 2 3 4 IGN 90-350VDC code for Class I, +
— Div. 2 Grps. C & TB1 1 2 3 4 CD Ignition
IGN 90-350VDC
D hazardous —
locations.
WARNING: Overspeed relay contact for use with FWMurphy non- SHD30 models To be installed in accordance with NEC code for Class I,
incendive or intrinsically safe products only. Div. 2 Grps. C & D hazardous locations.
SHD3-97051N 2 of 4
OVERSPEED OUTPUT WIRING continued
WARNING: PERFORM THE WIRING INSTALLATION WITH THE POWER SOURCE OFF.
NEVER ROUTE THE SHD30 MODELS OVERSPEED OUTPUT LEADS WITH PRIMARY IGNITION WIRING.
Figure 8: SHD30 models Normally Closed Relay output to LCDT-NC Back of MARK IV
TB2
LCDT 1 NO
Terminal Block 2C
TB1 3 NC 46
1 MPU + 5-120Vrms 4 +Overspeed SCR
2 MPU – 5 –Overspeed SCR
44 44 3 NEG 90-300vdc 6 Reset Hourmeter
4 POS 90-300vdc 7
45 45
NO C NC + –
46 46
SHD30 TB2 1 2 3 4 5 6 7
TB2 47 47
1 NO
2C 48 48
TB1 1 2 3 4 +
TB1 3 NC CD Ignition
1 MPU + 5-120Vrms IGN 90-350VDC
4 +Overspeed SCR 49 49
2 MPU – 5 –Overspeed SCR —
3 NEG 90-300vdc 6 Reset Hourmeter 50 50
4 POS 90-300vdc 7
+ – SHD30 models to be installed in accordance with NEC code for
N.O. C NC
Cl. I, Div. 2 Grps. C & D hazardous locations.
TB2 1 2 3 4 5 6 7
TB1 1 2 3 4
Figure 9: SHD30 models Normally Open S.C.R. output to LCDT-NO
LCDT
– Terminal Block
+ SHD30 to be installed in RESET
Figure 10: SHD30 models with Normally Open S.C.R. output typical Figure 11: SHD30 models with Normally Open S.C.R. output typical
wiring for negative ground ignition systems. wiring for positive ground ignition systems.
SWICHGAGE® 307PHCD SWICHGAGE® 307PHCD
TATTLETALE® TATTLETALE®
+ +
SHD30
Emergency SHD30 – Emergency
TB2 – SW Stop Switch SW Stop Switch
1 NO TB2
2C ALT 2 1 NO ALT 2
TB1 3 NC 2C
1 MPU + 5-120Vrms 4 +Overspeed SCR
ALT 1 TB1 3 NC ALT 1
2 MPU – 5 –Overspeed SCR GRD 1 MPU + 5-120Vrms 4 +Overspeed SCR
2 MPU – GRD
3 NEG 90-300vdc 6 Reset Hourmeter 5 –Overspeed SCR
4 POS 90-300vdc 7 Frame Ground 3 NEG 90-300vdc 6 Reset Hourmeter Frame Ground
65-02-0155 4 POS 90-300vdc 7 65-02-0127
NO C NC + – Adapter Adapter
Connect to NO C NC + –
TB2 1 2 3 4 5 6 7 Package Package Connect to
Good Engine TB2 1 2 3 4 5 6 7 Good Engine
1 2 3 4 5 6
TB1 1 2 3 4 Ground 1 2 3 4 5 6
Ground
TB1 1 2 3 4
+ – CD Ignition – + CD Ignition
90-350 VDC 90-350 VDC
SHD30 models to be installed in accordance with NEC code SHD30 models to be installed in accordance with NEC code
for Class I, Div. 2 Grps. C & D hazardous locations. for Class I, Div. 2 Grps. C & D hazardous locations.
SHD3-97051N 3 of 4
CALIBRATING AND OPERATING THE SHD30
CONTROL SYSTEMS & SERVICES DIVISION FRANK W. MURPHY, LTD. MACQUARRIE CORPORATION
P.O. Box 1819; Rosenberg, Texas 77471; USA Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K. 1620 Hume Highway
+1 281 633 4500 fax +1 281 633 4588 +44 1722 410055 fax +44 1722 410088 Campbellfield, Vic 3061; Australia
e-mail sales@fwmurphy.com e-mail sales@fwmurphy.co.uk +61 3 9358 5555 fax +61 3 9358 5558
FW Murphy
MURPHY DE MEXICO, S.A. DE C.V. www.fwmurphy.co.uk e-mail murphy@macquarrie.com.au
P.O. Box 470248
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje MURPHY SWITCH OF CALIFORNIA
Tulsa, Oklahoma 74147 USA
San Luis Potosí, S.L.P.; México 78384 41343 12th Street West
+1 918 317 4100 +52 444 8206264 fax +52 444 8206336 Palmdale, California 93551-1442; USA
D
RE
Villahermosa Office +52 993 3162117 +1 661 272 4700 fax +1 661 947 7570
STER