In ACI 318-02, the same set of strength reduction factors are used for the design of beams
and columns. The factor is adjusted depending upon the type of failure.
Definitions
The following definitions are used in specifying factors. Recall that the extreme fiber
concrete compressive strain at ultimate is assumed to be .003 in all cases.
Tension-controlled section (ACI 10.3.4) - a cross-section in which the net tensile strain in
the extreme tensile steel at the ultimate stage is greater than or equal to .005.
Note that the definitions are based on the reinforcement strain in the extreme level of
reinforcement, and not at the centroid of the tensile reinforcement.
> 0.005
1
We can relate these definitions to the type of failure as follows:
ACI 318-02 requires that beams (members without a significant axial force) be designed
such that the net tensile strain in the extreme tensile steel at the ultimate stage is greater
than or equal to .004. This ensures that beams are designed to be sufficiently
underreinforced. Per ACI 318-02 definitions, beams must be either tension-controlled, or
in the transition zone between tension-controlled and compression-controlled designs.
Beams cannot be designed as compression-controlled.
Limiting c/dt or a/dt ratios corresponding to specific strain conditions are given below. In
each case, these ratios are taken from simple linear relationships of the strain at the
extreme concrete compressive fiber (0.003) and the strain in the extreme layer of tensile
reinforcement.
c .003 a
.375 AND .375 1
dt .003 .005 dt
Values of c/dt and a/dt corresponding to the minimum strain limit for beams:
c .003 a
.429 AND .429 1
dt .003 .004 dt
c .003 a
.600 AND .600 1
dt .003 .002 dt
The ACI Code requires a lower factor (higher factor of safety) for compression-
controlled members because they exhibit brittle failures. The factor for tension and
compression controlled sections are 0.90 and 0.70, respectively, for members with other
than spiral transverse reinforcement. Most beams fall into this category. A linear
transition is assumed between the tension- and compression-controlled limits as shown in
the figure below.
2
From: PCA, Notes on ACI 318-02 (Also ACI 318-02, pg. 100)
Recall that ACI 318-02 limits the design of beams such that the strain in the extreme
layer of tension reinforcement is at least 0.004. At a strain t = 0.004, the strength
reduction factor (for other than spiral reinforced members) is = 0.81. Thus, it can be
stated that the strength reduction factor for beams varies between = 0.81 and = 0.90,
depending on the strain in the extreme layer of tension reinforcement. It is generally
most economical to design beams such that the strain in the extreme layer of tension
reinforcement exceeds 0.005, with = 0.90.
For common cases, such as a rectangular cross-section with a single layer of tensile
reinforcement and no compression reinforcement, we can derive simple relationships
between the balanced reinforcement ratio and the tension- and compression-controlled
limits. The simple derivation is shown below:
Assume d d t
For an underreinf orced (or balanced) rectangula r beam with a only tension reinforcem ent,
As f y As f y d f y d
C T .85 f ' c ab As f y a a a
.85 f ' c b .85 f ' c bd .85 f ' c
a f y c f y c f y
d .85 f ' c d .851 f ' c dt .851 f ' c
3
c .003 .851 f 'c
t 0.002 .600 .600
d t .003 .002 fy
The table below summarizes several parameters corresponding to the different strain
conditions:
Previous versions of ACI 318 (ACI 318-99 and earlier) limited the reinforcement ratio
that could be used in design to /b < 0.75. In the table above, it can be seen that ACI
318-02 effectively limits this ratio to 0.715 for singly-reinforced rectangular sections with
one layer of reinforcement. ACI 318-02 is therefore only slightly more conservative.
However, in order to use the “standard” strength reduction factor of = 0.90, note that
ACI 318-02 limits designs to /b < 0.625.
ACI 318-02 requires a minimum amount of reinforcement in beams so that beams are
prevented from failing immediately after cracking. The minimum amount of
reinforcement is given as:
3 f 'c 200
As ,min bw d bw d
fy fy
Note that ACI 10.5.3 stipulates that the above limit need not be applied if the area of
tensile reinforcement provided is at least 33% greater than required by analysis.