Professional Documents
Culture Documents
LISTED
www.FairbanksNijhuis.com
SPLIT CASE FIRE PUMPS
Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:
• Rugged construction;
• Efficient operation.
Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
In addition to horizontal split case pumps, Fairbanks Nijhuis
Fairbanks Nijhuis split case fire pumps are built per the also offers split case performance in a vertical format. Vertical
rigid standards of NFPA 20 and are listed by Underwriters fire pumps provide distinct advantages over horizontal pump
Laboratories (UL) and approved by Factory Mutual (FM). constructions.
2
SPLIT CASE FIRE PUMPS
1
Pump Features
7
2
8 15 16
14
17
3 9 13
10
5 11 12
6 18
VERTICAL HORIZONTAL
SPLIT CASE SPLIT CASE
1. Computer Machined 8. Internal Water Seal Passages 14. Split Case Design
major components with 360 degree registered between volute and stuffing box cannot simplifies disassembly. The suction and
fits to assure concentricity of parts. be damaged. discharge piping and shaft alignment are
not disturbed.
2. Integral Bearing Arms 9. Interwoven, Graphite
eliminate bearing misalignment and Impregnated T.F.E. 15. O-Ring Sealed Shaft Sleeves
simplify maintenance. prevent corrosion of the shaft. This eliminates
diagonally cut packing rings seal
the need for stainless steel shafts.
the pump shaft.
3. Enclosed Impeller Design
provides high efficiency and performance. 10. Stuffing Boxes 16. Case Wearing Rings
and throttle bushings protect the
are extra deep for proper sealing. Split packing
4. Dynamically Balanced Impeller glands simplify packing maintenance.
casing from wear and are easily and
inexpensively replaced.
is keyed to the shaft and secured by adjustable
shaft sleeves. 11. Double Row Thrust 17. Bronze Shaft Sleeve
ball bearing.
5. Double Suction Impeller prevents shaft wear, is slip fit over the shaft,
keylocked, and extends the entire length
balances hydraulic thrust loads. 12. Grease Seals of the seal box.
and nonsparking neoprene rotating slingers
6. Cast Iron Drip Rim Base protect both bearings during pump operation
18. Certified Performance Test
directs condensation and any stuffing box and washdown.
leakage to drain. with Positive Suction Pressure
13. Bearings is provided for each fire pump for customer
7. Short Bearing Span selected for 50,000 hour minimum life
approval. Pumps are also hydrostatically tested
per NFPA 20 at no less than 250 psi.
holds shaft deflection to .002" at face of at maximum load. Average bearing life
stuffing box at maximum load. 5 x minimum.
www.FairbanksNijhuis.com 3
Fire Pump Feature Selector
Standard Optional
• Bronze fitted pump construction • Ductile iron casings (available in selected 1800 and 1900 models)
• Bronze shaft sleeves • Some models available in 316 SST, duplex and super duplex
• Corrosion-resistant lantern rings* • External bypass line from casing to stuffing boxes
(optional on Model 1800s and 1900s, standard on Model 2800s and 5800s)
• Bronze stuffing box bushings
• Formed steel drip-rim base (horizontal electric driven units only)
• Bronze or stainless steel glands
• 15' Suction lift test to verify performance at 150% of rated flow
• Interwoven graphite-impregnated T.F.E. packing rings
• Available accessories include valves, headers, main relief valves, increasers and
• Cast integral bearing arms (most models) reducers, waste cones, and more.
• Regreaseable ball bearings
• Coupling guard
VERTICAL PUMPS PROVIDE
SUCTION IN-LINE PIPING IN ANY DIRECTION SUCTION
• Suction and discharge gauges with shutoff cocks STANDARD
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
OPTIONAL
RIGHT-HAND ROTATION LEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP) (TOP VIEW HORIZONTAL PUMP)
ST
IT
DR
UT
HY
19 17
www.FairbanksNijhuis.com
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
FMF-02-1048 09/30/17 © 2017 Pentair plc All Rights Reserved.
Customer : INNOPHOS Customer Technical Offer
Project name : REEMPLAZO BOMBA Encompass 2.0 - 19.1.5
CONTRA INCENDIOS
Driver
Qty Description
1 Driver
Driver type
Motor: USEM - 100HP 405TS TEFC 3600 RPM 60 Hz 230/460 V, Across-The-Line
Engineering Tests
Qty Description
1 Testing
Engineering Tests
Driver to be used for engineering tests: Calibrated test lab motor
Skid
Qty Description
Pump and drive skid
1 Pallet, 38" W x 72" L, Floor area per skid 19 sq.ft (1.77 sq.m)
Controller skid
Pallet 26 '' W x 34 '' L, Floor area per skid 6.14 sq.ft (0.57 sq.m)
Shipping comments
Pentair does not recommend stacking skids. Please use the estimated dimensions to calculate shipping container requirements, as floor load
only.
Total floor area 25.14 sq.ft ( 2.34 sq.m)
Customer : INNOPHOS Pump Performance Curve
Project name : REEMPLAZO BOMBA Encompass 2.0 - 19.1.5
CONTRA INCENDIOS
120
90 Power
Power - hp
60
30
0
HORIZONTAL ELECTRIC FIRE PUMP PERFORMANCE CURVE
250
Preferred operating region
225
10.38 in
200 53 65
73
175 80
81 78
150 8.72 in 80
Head - psi
125
78
100
73
7.06 in
75
65
50
53
25
0
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400
Flow - USgpm
General Arrangement
Pump Data
Electric Driven Fire Pump Series Horizontal Splitcase
Model Pentair Fairbanks Nijhuis 4"-1823DF
Preliminary Drawing Size 4x5x11D
Flow 750.0 USgpm
Rated Pressure 130.0 psi.g
RPM 3560 rpm
Rotation Right handed
Liquid Type Water
Discharge Size 4.00 in
Suction Size 5.00 in
Impeller Diameter 8.75 in
Connection Type 125/125
Base Type Steel bent form base
- -
Pump Materials of Construction
Pump Bronze fitted with Cast Iron casing
Shaft Carbon Steel AISI C1045
Motor Data
Power 100 hp
Phase 3
Frequency 60 Hz
Volts 230/460 V
RPM 3600
Frame 405TS
Service Factor 1.15
Enclosure TEFC
Manufacturer USEM
Site Information
Elevation 300.0 ft
Temperature 95.00 deg F
Estimated Weights
CP W X YY D Z S HY ZZ
Pump 574.0 lb
26.00 14.50 12.00 12.75 10.00 5.00 5.00 6.00 1.25
Driver 650.0 lb
C HA HB HE HF HG HH HP
28.00 18.00 54.00 15.00 52.00 4.00 0.63 1.00