You are on page 1of 8

HORIZONTAL SPLIT CASE PUMP VERTICAL SPLIT CASE PUMP

FAIRBANKS NIJHUIS™ 900 SERIES


SPLIT CASE FIRE PUMPS
Built Per NFPA 20

LISTED

www.FairbanksNijhuis.com
SPLIT CASE FIRE PUMPS

FAIRBANKS NIJHUIS™ 900 SERIES


Split Case Fire Pumps

Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:

• Easy access to all working parts;

• Rugged construction;

• Liberal water passages; and

• Efficient operation.

Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
In addition to horizontal split case pumps, Fairbanks Nijhuis
Fairbanks Nijhuis split case fire pumps are built per the also offers split case performance in a vertical format. Vertical
rigid standards of NFPA 20 and are listed by Underwriters fire pumps provide distinct advantages over horizontal pump
Laboratories (UL) and approved by Factory Mutual (FM). constructions.

• Less floor space is required.


Available in a broad range of operating pressures and flows
from a minimum of 250 GPM, Fairbanks Nijhuis split case • In-line piping arrangement allows piping in any direction
pumps can be driven by either an electric motor or diesel in most cases.
engine. Fairbanks Nijhuis’ UL-Listed, FM-Approved fire pump
• Elevated motor protects against potential flooding if the
packages also include the system controller, with a full range
pump station is in a low area.
of options and accessories available to complete the NFPA-
compliant fire pump package. • Components are register-fitted to prevent misalignment.

2
SPLIT CASE FIRE PUMPS

1
Pump Features
7
2
8 15 16
14
17
3 9 13

10
5 11 12
6 18
VERTICAL HORIZONTAL
SPLIT CASE SPLIT CASE

1. Computer Machined 8. Internal Water Seal Passages 14. Split Case Design
major components with 360 degree registered between volute and stuffing box cannot simplifies disassembly. The suction and
fits to assure concentricity of parts. be damaged. discharge piping and shaft alignment are
not disturbed.
2. Integral Bearing Arms 9. Interwoven, Graphite
eliminate bearing misalignment and Impregnated T.F.E. 15. O-Ring Sealed Shaft Sleeves
simplify maintenance. prevent corrosion of the shaft. This eliminates
diagonally cut packing rings seal
the need for stainless steel shafts.
the pump shaft.
3. Enclosed Impeller Design
provides high efficiency and performance. 10. Stuffing Boxes 16. Case Wearing Rings
and throttle bushings protect the
are extra deep for proper sealing. Split packing
4. Dynamically Balanced Impeller glands simplify packing maintenance.
casing from wear and are easily and
inexpensively replaced.
is keyed to the shaft and secured by adjustable
shaft sleeves. 11. Double Row Thrust 17. Bronze Shaft Sleeve
ball bearing.
5. Double Suction Impeller prevents shaft wear, is slip fit over the shaft,
keylocked, and extends the entire length
balances hydraulic thrust loads. 12. Grease Seals of the seal box.
and nonsparking neoprene rotating slingers
6. Cast Iron Drip Rim Base protect both bearings during pump operation
18. Certified Performance Test
directs condensation and any stuffing box and washdown.
leakage to drain. with Positive Suction Pressure
13. Bearings is provided for each fire pump for customer
7. Short Bearing Span selected for 50,000 hour minimum life
approval. Pumps are also hydrostatically tested
per NFPA 20 at no less than 250 psi.
holds shaft deflection to .002" at face of at maximum load. Average bearing life
stuffing box at maximum load. 5 x minimum.

www.FairbanksNijhuis.com 3
Fire Pump Feature Selector
Standard Optional
• Bronze fitted pump construction • Ductile iron casings (available in selected 1800 and 1900 models)

• Bronze shaft sleeves • Some models available in 316 SST, duplex and super duplex

• Bronze case wearing rings • Right- or left-hand rotation

• Dynamically balanced impellers • Impeller wearing rings

• Stainless steel impeller key • Stainless steel shafts

• Carbon steel shaft • Double row ball bearings on inboard side

• Corrosion-resistant lantern rings* • External bypass line from casing to stuffing boxes
(optional on Model 1800s and 1900s, standard on Model 2800s and 5800s)
• Bronze stuffing box bushings
• Formed steel drip-rim base (horizontal electric driven units only)
• Bronze or stainless steel glands
• 15' Suction lift test to verify performance at 150% of rated flow
• Interwoven graphite-impregnated T.F.E. packing rings
• Available accessories include valves, headers, main relief valves, increasers and
• Cast integral bearing arms (most models) reducers, waste cones, and more.
• Regreaseable ball bearings

• Double row thrust bearing (outboard side)

• Upper casing lifting lugs

• Water slingers and grease seals

• Hydrostatic and Certified Performance test**

• Coupling guard
VERTICAL PUMPS PROVIDE
SUCTION IN-LINE PIPING IN ANY DIRECTION SUCTION
• Suction and discharge gauges with shutoff cocks STANDARD
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
OPTIONAL
RIGHT-HAND ROTATION LEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP) (TOP VIEW HORIZONTAL PUMP)

• Automatic air release valve


* Standard on Model 2800s and 5800s; furnished when suction pressure is below 40 psi on Model 1800s and 1900s.
• Casing relief valve (electric driven units only) ** Test is performed with positive suction pressure.
LIC
IN
AU

ST
IT
DR

UT
HY

19 17

www.FairbanksNijhuis.com

800 AIRPORT ROAD, NORTH AURORA, ILLINOIS 60542 USA


PARALLELWEG 4, 7102 DE, WINTERSWIJK, THE NETHERLANDS
NO. 10 JIA YE ROAD BIN HU DISTRICT, WUXI CITY, JIANG SU PROVINCE, CHINA 214124

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
FMF-02-1048 09/30/17 © 2017 Pentair plc All Rights Reserved.
Customer : INNOPHOS Customer Technical Offer
Project name : REEMPLAZO BOMBA Encompass 2.0 - 19.1.5
CONTRA INCENDIOS

Item number 001 Size / Stages /


Quote number LOC-310-JUN-19-BFBN Pump speed

Pump HORIZONTAL ELECTRIC FIRE PUMP


Qty Description
1 Fairbanks Nijhuis - Horizontal Splitcase 4"-1823DF
COS
Conditions of service
Flow: 750 USgpm (170 m3/h)
Pressure rated: 130 psi
Speed: 3560 rpm
Suction pressure: 10 psi
Impeller diameter: 8.75
Shutoff head: 147 psi
Elevation: 300 ft
Temperature: 95° F
Country of origin: United States
Fire pump configuration
Pump
Materials of construction: Bronze fitted with Cast Iron casing
Pump rotation: Right handed
Flange rating (Suction/Discharge): (Suction 5 / Discharge 4) 125/125 LB
Pump base: Steel bent form base
Pump shaft material: Carbon Steel AISI C1045
Casing relief valve: UL listed & FM approved, Cla-Val

Driver
Qty Description
1 Driver
Driver type
Motor: USEM - 100HP 405TS TEFC 3600 RPM 60 Hz 230/460 V, Across-The-Line

Fire Pump Controller


Qty Description
1 Fire pump controller
Fire pump controller
Fire pump controller: Tornatech GPA, Across-The-Line, 460V, 60Hz, 100 HP
Transfer Switch: No
Fire pump controller - alarm and indicators
Standard digital text indications for fire pump controller
Phase loss
Phase unbalance
Incoming over voltage
Incoming under voltage
Motor over current
Motor under current
Motor run
Fail to start
Standard high luminous LED's
Power available
Phase reversal
Customer : INNOPHOS Customer Technical Offer
Project name : REEMPLAZO BOMBA Encompass 2.0 - 19.1.5
CONTRA INCENDIOS
Fire Pump Controller LOC-310-JUN-19-BFBN
Qty Description
Pump on demand
Weekly test
Fire pump controller - additional option selections
Enclosure for Standard Controller: NEMA 2
Pressure transducer: Pressure transducer and run test solenoid valve for fresh water, 0-500 PSI
Redundant pressure transducer: Not required
Suction pressure transducer: Not required
Controller Rated Temperature: Controller rated for 40°C ambient temperature
Anti condensation heater: None
Withstand rating for controller: Standard Withstand Rating, 100,000 Amps
Pump control function: None
Label language: Spanish
Modbus: Modbus TCP/IP provision
Export packing: No

Remote Alarm Panel


Qty Description
1 Remote Alarm Panel
Remote Alarm Panel
Remote Alarm Panel: None

Engineering Tests
Qty Description
1 Testing
Engineering Tests
Driver to be used for engineering tests: Calibrated test lab motor

Weight, Freight, Boxing


Qty Description
1 Skid weight: 65 lb (29.48 kg)
Approximate total weight for Qty shown
Fire pump weight: 574 lb (260.36 kg)
Driver weight: 650 lb (294.84 kg)
Fire pump controller weight: 235 lb (106.59 kg)
Jockey pump controller weight: 0 lb (0 kg)
Skid weight: 65 lb (29.48 kg)
Total weight: 1524 lb (691.28 kg)
Inland freight: Laredo, TX
Export boxing: Skeleton crating

Skid
Qty Description
Pump and drive skid
1 Pallet, 38" W x 72" L, Floor area per skid 19 sq.ft (1.77 sq.m)
Controller skid
Pallet 26 '' W x 34 '' L, Floor area per skid 6.14 sq.ft (0.57 sq.m)
Shipping comments
Pentair does not recommend stacking skids. Please use the estimated dimensions to calculate shipping container requirements, as floor load
only.
Total floor area 25.14 sq.ft ( 2.34 sq.m)
Customer : INNOPHOS Pump Performance Curve
Project name : REEMPLAZO BOMBA Encompass 2.0 - 19.1.5
CONTRA INCENDIOS

120

90 Power
Power - hp

60

30

0
HORIZONTAL ELECTRIC FIRE PUMP PERFORMANCE CURVE
250
Preferred operating region

225

10.38 in
200 53 65
73

175 80
81 78

150 8.72 in 80
Head - psi

125
78

100
73
7.06 in
75
65

50
53

25

0
0 100 200 300 400 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400

Flow - USgpm

Item number : 001 Size : 4"-1823DF


Service : HORIZONTAL ELECTRIC FIRE PUMP Stages :1
Quantity :1 Driver type : Motor
Quote number : LOC-310-JUN-19-BFBN Frequency : 60 Hz
Date last saved : 06 Jun 2019 11:51 AM Speed, rated : 3560 rpm
Flow, rated : 750.0 USgpm Based on curve number : 184-4X5X11D-3560
Differential head / : 130.0 psi Efficiency : 73.97 %
pressure, rated Max working pressure, allowable : 175.0 psi.g
Flange rating (suction / : 125/125 Max Shutoff Head (Calculated) : 147.0 psi
discharge)
Max suction pressure, allowable : 28.00 psi.g
Suction pressure, max (user : 10.00 psi.g
specified)
Pump shutoff w/ suction pressure : 157.0 psi.g
Power driver, minimum : 100 hp
Encompass 2.0 - 19.1.5

General Arrangement
Pump Data
Electric Driven Fire Pump Series Horizontal Splitcase
Model Pentair Fairbanks Nijhuis 4"-1823DF
Preliminary Drawing Size 4x5x11D
Flow 750.0 USgpm
Rated Pressure 130.0 psi.g
RPM 3560 rpm
Rotation Right handed
Liquid Type Water
Discharge Size 4.00 in
Suction Size 5.00 in
Impeller Diameter 8.75 in
Connection Type 125/125
Base Type Steel bent form base
- -
Pump Materials of Construction
Pump Bronze fitted with Cast Iron casing
Shaft Carbon Steel AISI C1045
Motor Data
Power 100 hp
Phase 3
Frequency 60 Hz
Volts 230/460 V
RPM 3600
Frame 405TS
Service Factor 1.15
Enclosure TEFC
Manufacturer USEM
Site Information
Elevation 300.0 ft
Temperature 95.00 deg F
Estimated Weights
CP W X YY D Z S HY ZZ
Pump 574.0 lb
26.00 14.50 12.00 12.75 10.00 5.00 5.00 6.00 1.25
Driver 650.0 lb
C HA HB HE HF HG HH HP
28.00 18.00 54.00 15.00 52.00 4.00 0.63 1.00

NOTES: Quote Information


Not for construction, installation, or application purposes unless certified. Customer INNOPHOS
All dimensions are in inches Customer Quote LOC-310-JUN-19-BFBN
Dimensions may vary ± 1/2" (13mm) due to normal manufacturing tolerances. Job Name REEMPLAZO BOMBA CONTRA INCENDIOS
Bases are designed to be completely filled with grout. Market INDUSTRIAL FIRE
Coupling gap may vary 1/8" (3mm) through 2 1/16" (52mm) Quote Item 001
See configuration for estimated total weight. Quote Date 06 Jun 2019