You are on page 1of 1

IJD 950 Nominal Airflow: 3600 l/s

Cooling Capacity (kW) Total = Total Capacity (kW); Sens. = Sensible Capacity (kW)
Entering Air Temperature 23°C D.B., 17°C W.B. Note: Cooling capacities are based on the nominal airflow.

WATER PRESSURE ENTERING WATER TEMPERATURE °C


FLOW DROP 5 6 7 8 9
COIL (l/s) (kPa) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
2.50 7.7 61.5 46.3 57.2 44.5 52.2 42.5 47.8 40.7 42.8 38.7
4 ROWS 3.50 14.0 69.6 49.7 63.9 47.3 58.9 45.2 53.8 43.1 48.0 40.8
4.50 22.6 74.8 51.9 69.1 49.5 63.4 47.0 57.6 44.6 51.7 42.3
2.50 11.1 72.5 51.9 67.0 49.6 62.1 47.5 56.2 45.1 51.2 43.1
6 ROWS 3.50 20.6 81.6 55.9 75.5 53.3 69.4 50.6 63.1 48.0 56.8 45.4
4.50 31.9 87.1 58.4 80.8 55.6 74.7 52.9 67.8 49.9 61.5 47.3

Heating Capacity (kW)


Entering Air Temperature 21°C Note: Heating capacities are total - based on the nominal airflow. Electric Heating option: 27 kW
WATER PRESSURE ENTERING WATER TEMPERATURE °C
FLOW DROP
COIL (l/s) (kPa) 40 45 50 55 60 65 70 75 80
2.00 7.2 27.6 35.0 42.2 49.4 56.7 63.9 71.1 78.5 85.7
1 ROW 3.00 14.3 29.8 37.7 45.6 53.5 61.2 69.1 77.0 84.9 92.6
4.00 24.9 31.5 39.7 48.0 56.3 64.9 73.2 81.4 89.4 98.0

Air Handling Sound Levels


l/s - Pa - - - - l/s - W Test Conditions: JIS 8616. 1 m ducting with 25 mm insulation.
Sound Pressure Levels are at 1 m from source.
STD MOTOR SIZE 4 kW OCTAVE BAND FREQ. Hz
FAN
4k

1010 RPM MAX D.O.L. MOTOR 4 kW


SPEED SPL SWL 125 250 500 1k 2k 4k
W

500 MAX. FAN SPEED 1200 RPM


MO

930 RPM STD PULLEY RANGE RPM dB(A) dB(A) SOUND POWER LEVELS dB
TO

840–1035 RPM; SET AT 930 RPM


850 67 77 78 78 74 71 69 66
RL
AVAILABLE EXTERNAL PRESSURE (Pa)

400
IM

850 RPM 930 68 78 78 78 74 73 70 68


IT

1010 69 79 79 79 75 74 71 68
300

200

Note:
100 1. Air flows given are for a unit with no filter installed.
2. In a free blow application, beware of exceeding
0 indoor fan motor's full load amp limit.
2000 2500 3000 3500 4000 4500
AIR FLOW (l/s) 2.5 m/s Face Velocity

1500
Dimensions (mm) 55
WATER
CONNECTIONS
40 BSPM (1 1/2")
Not to Scale POINT LOADS (kg) *
ELECTRICAL
A B BOX
A B C D
95 103 64 54
1000 MINIMUM

ACCESS
* 4/1 row coil including water
CLEARANCE
1000 MINIMUM
CLEARANCE

PANEL HINGED
ACCESS
PANEL

D C
OPTIONAL
VERTICAL SUPPLY AIR OPTIONAL
520 475 SPIGOT VERTICAL SUPPLY AIR
60 245 SPIGOT
150

30
130
WATER
OUT 905
405
1005
OVERALL

WATER
IN

DRAIN DRAIN 50
28 OD
308 1060 MTG CTR 308 943 SPRING CTR (16Ø)
993 FIXING CTR (13Ø)
1675 OA 1200 OA

46 © temperzone limited 2002