Contents / Introduction

Contents Contents

Introduction 2 General 29
Data Sheets
Applications 3
Technical Data Open-Close Duty 30-31
Type Designation 4 Electrical Data Open-Close Duty 32-33
Multi-turn Actuators 5 Technical Data Regulating Duty 34
Electrical Data Regulating Duty 35
Design Principle 6-7
Dimension Sheet, Norm 36
Functions 8 Dimension Sheet, Compact 37
Open-Close Duty 8 Dimension Sheet, E-pac 38
Regulating Duty 8 Output Drives 39
Limit Switching 9 Linear Thrust Unit 40
Torque Switching 10 Terminal Plan (Norm) 41
Wiring Diagram (Integral Starter) 42
Control Equipment 11
Legend - Integral Starter 43
Micro Switches 11
Reduction Gear Unit 12
Position Indicators 12
Intermediate Switch 13
Manual Operation 13
Top Bevel Gear Set 13
Space Heater 13 Introduction
Motors 14-15
In the course of ever increasing demand for
Actuators for Regulating Duty 16-20 automation in all sectors of industries, electric
Actuator Types 21 actuators for process control and regulation
have become more and more important. For
Auma Norm Actuators 21 more than 30 years, Auma concentrates on
Auma Integral Starter Actuators 21 design, development and manufacturing of
Control Versions 22 electric actuators. During this period, Auma
has acquired a know-how in this field that can
Auma Compact 22
hardly be surpassed. Auma today is one of the
Auma e-pac 23 leading manufacturers of electric actuators in
the world.
Interface 24
Valve Attachment 24 Auma India (Ltd.,) is now a subsidiary of
Auma Werner Riester Gmbh & Co. KG,
Output Drives 24 Germany manufacturing electric actuators
Electrical Connection 25 under brand name . Auma (India) Ltd.,
Actuator Gearbox Combination 26 started its operations in the year 1985 with HQ
and sophisticated manufacturing base at
Service Conditions 27 Bangalore.
Enclosure Protection 27 Sales support and after sales service are
Ambient Temperature 27 provided by network consisting of regional
Explosion Proof 28 offices & service centers.

2
Applications

Auma multi-turn actuators of the type range SA


can be used wherever the automation of the
valve is required. The adoption to the
requirements of nearly every valve automation
task is possible. This is on account of :
An extermely wide torque range
Various combination possibilities with
Auma Valve Gear boxes. Thereby the torque
range can be further extended and / or the
multiturn actuator can be converted into
part turn, lever or linear actuator.
A large variety of versions, whether for open
or closed loop control, explosion proof
applications, a suitable version is available.

Energy
Power Plants
Air Pollution Control
District Heating
Pipelines

Water / Waste Water


Water Works
Water Pipelines
Sewage Treatment
Pump Stations
Locks / Dams

Chemical Industry
Petro-chemical
Chemical
Pharmaceutical

Others
Air Conditioning
Steel Mills
Ship Building
Cement Plants
Food Industry

3
Type Designation

Auma OPEN-CLOSE Duty Model : SA


Norm Regulating Duty Model : SAR

Auma OPEN-CLOSE Duty Model :SA Compact


Compact Regulating Duty Model : SAR Compact
Actuator Auma
Types Integral Starter
Auma OPEN-CLOSE Duty Model :SA e-pac
e-pac Regulating Duty Model : SAR e-pac

Expl. Proof OPEN-CLOSE Duty Model :SAEx


Norm Regulating Duty Model : SAREx
Auma
Flame Proof /
Explosion Proof
Expl. Proof OPEN-CLOSE Duty Model :SACEx
Compact Regulating Duty Model : SARCEx
Torque Ratings 3 m kg Output Drives A Stem nut
6 m kg B Plug Sleeve
12 m kg C Dog Coupling
15 m kg D Stub Shaft
25 m kg E Bore with Keyway
30 m kg
50 m kg
60 m kg
100 m kg

Output Speed 4 rpm


5.6 rpm
8 rpm
11 rpm
16 rpm
22 rpm
32 rpm
45 rpm
63 rpm
90 rpm
125 rpm
180 rpm

Type Designation : Example

SA 12 A 22

Model Output Speed in RPM


Torque Rating Output Drive

4
Multi-turn Actuators

Multi-turn Actuator SA3 - SA100


Torque range 3 m kg to 100 m kg
Output speed 4 rpm to 180 rpm

Multi-turn Actuator Multi-turn Actuator


Integral Starter - Compact Integral Starter - e pac

Multi-turn Actuator
Flame Proof / Explosion Proof

5
Design Principle

Manual Operation

Motor

Change Gears Terminal


Compartment

Reduction Gearing

Valve Attachment

Switch Compartment

6
Design Principle
Motor Terminal Compartment

Especially high starting torque is frequently All electrical connections are terminated inside
required to unseat valves from end positions. the terminal compartment. Screw type terminals
The motors developed by Auma fulfil this are provided for easy connections. Multi-pin
basic requirement. plug-socket connector can be provided for ease
of connections & maintenance.

Change Gears Valve Attachment

Auma actuators are driven by special The mounting flange is according to ISO 5210 /
combination of gears which are outside the DIN 3210. Various output drives are available
grease filled housing & require no lubrication. for adaption to various types of valves.
If required, output speed can be easily altered
by changing the gear pair and / or motor at
site.

Reduction Gearing Manual Operation

A well proved principle of worm gearing is For commissioning or in an emergency, actuator


used to reduce the motor speed to required can be operated with hand wheel. When starting
output speed of actuator. Self-locking feature the motor, the manual drive is automatically
is achieved by worm gearing upto 90 output disengaged.
rpm. Worm shaft and output shaft with worm
wheel run in ample sized bearings. The sliding
worm is positioned between two sets of
springs on worm shaft. The worm moves
axially in relation to thrust which is the
measure for torque. Via lever & gears the
torque is transmitted to control unit.

Switch Compartment

Depending upon type of valve, the actuator


must be switched off at end positions by limit
switch or torque switch. For this purpose,
independent limit switching or torque
switching devices are provided in the switch
compartment. The switching devices are easily
accessible for any setting at site.

7
Functions
Open Close Duty

The characteristic feature of this actuator is


open loop. The normal valve positions in
OPEN-CLOSE Duty are end positions OPEN
and CLOSED. After receiving command, the
actuator operates the valve to one of the end
positions or if necessary to a preset
intermediate position. The valves are operated
relatively seldom, the time intervals can span
between a few minutes to several months.

Auma multi-turn actuators type SA for open


close service are rated for short time duty
S2-15min.
Typical Characteristics of
OPEN-CLOSE DUTY

Regulating / Modulating Duty

The characteristic feature of this actuator is


closed loop in which input command signal to
actuator is directly influenced by the flow
through the valve. Regulating / Modulating
duty actuator SAR operates between two set
bands between open-close positions depending
upon actual valve position and feedback signal.
The motors of these actuators are rated for
intermittent duty S4-25%. The mechanical
components and motor are designed to withstand
a large number of operations required for
Typical Characteristics of
modulating applications.
Regulating / Modulating Duty

Pemissible number of starts-stops depends upon


actuator size & speed. The details are available
in Data Sheets.

Short Time and Intermittent Duty IS 12824

Short time Duty S2 Intermittent Duty S4


Operation at constant load during a given A sequence of identical duty cycles, each cycle
time, less than that required to reach thermal including a significant period of starting, a period
equilibrium, followed by a rest and de- of operation at constant load and a rest and de-
energized period of sufficient duration to re- energized period. These periods being too short
establish machine temperatures within 2oC. to attain thermal equilibrium during one duty
cycle.
The duration of short time is limited to 15, 30
or 60 min. The relative on time at S4-25% is limited to
25% of the cycle time.

8
Functions
Limit Switching

The limit switching enables to switch off the switching points operate the electrical limit
actuator when reaching defined valve switches by cams. The setting accuracy is 1/10 of
position, usually end positions. The valve a turn of actuator output shaft.
travel is measured by mechanical counter gear
mechanism which when reaching the set In limit switching, two train counter gear and
four train counter gear versions are available :

Two Train Counter Gear

For Two train counter gear, two limit switches,


one for each direction of travel having 1 NO
+ 1 NC or 2 NO + 2 NC contacts are provided.
The number of spindle turns can be set
between 1 and 480 or 1 and 4800.

Two Train Counter Gear

Four Train Counter Gear

If limit switching is required at two end The accuracy of setting is 1/10 of a turn of
positions only, two train counter gear is used. actuator output shaft. For four train counter
However, if two additional intermediate gear, 4 limit switches of 1 NO + 1 NC or 2 NO
switching positions are desired, Four Train + 2 NC contacts are provided.
Counter Gear is required. This limit switching
has 4 counter gears and 4 micro switches. Two
counter gears are used to switch off at end
positions as in Two Train Counter Gear. The
other two are available for setting any desired
intermediate positions between end positions.
After cam actuation, the switches remain
actuated till reaching end of valve travel.
Examples of such application are :

To stop at intermediate position


Sequence control, that is to start
another equipment like pump or bypass
valve actuator after certain travel
of valve.
Four Train Counter Gear

9
Functions
Torque Switching

The torque switching enables to switch off the


actuator when pre-determined torque is
reached instead of a defined position. The
torque switching works on principle of sliding
worm.

Axial displacement of worm proportional to


thrust is transmitted to torque switches.
Torque switches operate in closing & opening
directions. The required tripping torque can be
easily set on the graduated dial. If limit switch
cut off is selected prior to torque switch, then
torque switch serves as overload protection.

For tight seating of certain valves, the actuator Torque Switching


must be operated to end position CLOSED
with defined force. Such operation can be When torque seating is used at end position,
carried out by torque seating. Limit seating is limit switches can be used for signalization.
commonly used in the end position OPEN. Therefore actuator controls can differentiate
whether actuator was switched off by torque
switch or by limit switch. Micro switches of
torque switching are provided with 1 NO + 1 NC
or 2 NO + 2 NC contacts for both open & close
directions.

Running Indication

Blinker switch is provided in the actuator and


can be used as running indicator.

10
Control Equipment
Micro Switches

With the help of micro switches, mechanical Limit switches are tripped when an end position
parameters such as travel & torque are is reached and torque switches are tripped when
converted into electrical signals for actuator the set tripping torque is exceeded.
control. There are four switches in the basic
version : The micro switches are sealed to enclosure
One limit switch each for the end protection class IP66, as per IS 13947. The micro
positions OPEN and CLOSE switches have double break change over
One torque switch each for the potential free contacts. The circuit is interrupted
directions OPEN and CLOSE. simultaneously at two points. The basic versions
of the switch contacts are of silver. For low
current ratings, micro switches with gold plated
contacts are available.

Single and Tandem Micro Switches

Limit and Torque Switches are available in Switching another circuit also with
single or tandem versions. different voltage & current
Safety function, to operate with single
switch
Multiplying the available contacts,
example for signalization.

For such applications, a relay is recommended


Single Micro Switch since there may be small differences in tripping
points of tandem switches.

Limit or Torque Switches in tandem version


have additional switching contacts. These
contacts can be wired for following applications :

Tandem Micro Switch

Micro Switch Ratings


Type of Rating in Amp at Approx. Electrical
Type of Switch
Current 30 V 75 V 125 V 250 V contact rating
AC, cos O = 0.8 500,000 cycles at
8 7 6 5 250 V AC, 5A
Inductive
Limit and 50,000 cycles at
Torque DC inductive 5 1 0.2 0.1 250 V DC, 0.1A
50,000 cycles at
DC resistive 7 1 0.5 0.25
250 V DC, 0.25A
AC, cos O = 0.8
Blinker 4
Inductive

11
Control Equipment
Reduction Gear Unit

A reduction gear unit (RGU) in the actuator is at site, variable ratio RGU is available which
used for mechanical position indication, allows simple modification at site depending
remote position indication & for operation of upon number of turns of output shaft for full
intermediate switches. The output shaft of the stroke of valve.
actuator drives final output shaft of RGU
through a series of reduction gears and final
o
shaft turns by approximately 270 while
actuator output shaft performs full number of
turns as set on two train or four train counter
gear unit. The reduction gear ratio needed for
each particular case is fitted at works if the
ratio is known. For this purpose fixed RGU
is supplied. If the ratio needs to be altered
Reduction Gear Unit (RGU)
Position Indicators

Mechanical Position Indicator

The position of the valve is indicated


continuously by adjustable discs having
symbols for OPEN and CLOSE. The discs can
be seen through an indicator glass on switch
compartment cover. The open-close discs can
be set to coincide with limit switching. The
mechanical position indicator requires
reduction gear unit for operation.

Remote Position Indicator Mechanical Position Indicator

The position of the valve can be transmitted as read off continuously on position meter
a continuous signal for remote indication. A calibrated & mounted on control panel.
potentiometer mounted on RGU is used for
this purpose. A power supply unit provides Technical Data
necessary voltage to the potentiometer. The Std: 220 ohms, 3W, Linearity + 3%
o
potentiometer rotates through 270 for one full Optional : 100, 560, 1000 ohms,
stroke of valve & output signal from Potentiometer 3W, Linearity + 3%
potentiometer is proportional to valve travel. Precision : 200, 500, 1000 ohms,
Thus the actual position of the valve can be 1W, Linearity + 0.5%
Power PS01, input 220V, 50Hz, output
Supply Unit 24V DC
Position 0 - 100% in various sizes
Meter

Digital Remote Position Indicator

Actual position display can be provided by


digital remote position indicator, which
displays open position in percentage.
Remote Position Indicator

12
Control Equipment
Intermediate Switches

With this limit switching, additional switching


points can be set for each direction of rotation.
The switching can be set between 25 and 75%
of valve travel in each direction. The switch
sub assembly consisting of 2 or 4 cam switches
is mounted on output shaft of RGU. Each
micro switch has 1 NO + 1 NC contact.

Intermediate Switches
Manual Operation

For commissioning or in an emergency when


there is no power supply, actuator can be
operated by hand wheel. The manual drive is
engaged by means of a lever. When motor
starts running, the manual drive gets
disengaged immediately & hand wheel does
not rotate during power operation.

In manual operation, hammer blow can be


effected with hand wheel. The hammer blow
makes it possible to open a jammed or rarely
operated valve.

Top Bevel Gear Set

Manual effort on hand wheel can be further


reduced by using a side mounted hand wheel
instead of standard hand wheel. Reduction
ratios available are
SA3 / 6 / 12 / 15 2:1
SA25 / 30 / 50 / 60 3:1
SA 100 4:1
Instead of hand wheel, a chain pulley can be
provided for actuators mounted in inaccessible
zones.
Top Bevel Gear Set

Space Heater

Condensation in the actuator is possible due to Technical Data


wide fluctuation of the ambient temperature.
Volts, AC 230 230 110 110
The heater integrated in the control unit
prevents the water condensation. The heater is Resistance
5K 2.7K 1.2K 0.6K
rated for continuous duty. This may be ohms
continuously energized or when the actuator Rating
is not operating. 10 20 10 20
Watts

13
Control Equipment
Motors

As a standard, Auma multi turn actuators are Single Phase AC Motors


equipped with 3 phase induction motors.
Auma motors are class F insulated and Auma actuators can be supplied with single
withstand winding temperature upto 140o C. phase AC motor. The required capacitor is fitted
in the terminal compartment cover.
The motors are used for short time duty (S2-15
min or S4-25% as per IS 12824) and provide DC Motors
approximately three times rated torque for
short duration. The size of the motor is smaller Auma actuators are also available with DC
compared to continuous duty motor S1 of motors. These motors operate on 24 V, 110 V or
same output power. This results in reduced 220 V DC supply.
inertia of the rotor and therefore less
overshoot after switching off of motor. Auma AC Motors with Other Voltages and
motors are designed for enclosure protection Frequency
class IP 68 when mounted on the actuator. All
motor cables are brought to terminal Three phase induction motors are available in
compartment cover from inside of the actuator wide range of operating voltages from 220 V to
thus avoiding terminal box. 560 V and operating frequency of 50 or 60 Hz.

Technical Data

3 ph AC Motor 1 ph AC Motor DC Motor


50/60 Hz : 220 V, 380 V 50/60 Hz :
400 V, 415 V 220 V
220 V - 240 V
Voltages 440 V, 460 V 110 V
110 V - 220 V
480 V, 500 V 48 V
550 V 24 V
Permissible Variation + 10% + 10%
+ 10%
in Voltage
Mounting C Type Flange, B14, IS 2223

Enclosure Protection IP 67 or IP 68 after mounting

Type of Cooling Surface Cooled


o
Insulation Class F Class, IS 325 (max. temp. rise 140 C)

Starting Direct on line

Type of Duty S2-15 min. or S4-25 % IS 12824

Direction of Rotation Clockwise and anticlockwise

Motor Protection 3 thermo switches 2 thermo switches 4 thermo switches

14
Control Equipment
Motor Protection

Motor winding may get overheated if the


Technical Data
actuator is run beyond rated duty or if the
rotor is stalled for considerably longer time or
AC Voltage Switch Rating
if too high ambient temperature is
encountered. In order to protect the motor 250 V AC
against over heating, thermo switches are 2.5 A
Cos O = 1
embedded in the windings of three phase, 250 V AC
single phase AC motors and DC motors. When 1.6 A
Cos O = 0.6
integrated into the control circuits, they will
protect the motor against damage due to Tripping Temp 140o C
excessive winding temperature.
o
Reset Temp 90 - 110 C
The thermo switches interrupt the control
circuit as soon as winding temperature of
o Note : The motor protection device must be
140 C is exceeded. After cooling down to a integrated into the controls, otherwise warranty
o
temperature of approx. 110 C, the actuator can for motor is not valid.
be switched on once again. PTC thermistors
can also be provided for motor protection.

Output Speeds

With large range of available output speeds, exchanging the change wheels and or motor at
almost every required operating time can be site. The grease filled housing need not be
achieved with Auma actuators. opened for this purpose. The torque switch
setting & limit switch setting remains the same.
The actuator output speed is determined by For actuators with output drive A (Stem nut),
the motor speed, change gears and reduction max. permissible stem velocity must be
gear ratio of worm / worm wheel. observed:
- for gate valves max. 500 mm/min
The output speeds are available from 4 - 180 - for globe valves max. 250 mm/min
rpm in geometric progression of 1: 1.4.
For higher velocities it is recommended to use
During trial run, if found necessary, the
spring loaded stem nut type AF (special design).
output speed can be easily changed by

Self Locking

Auma multi turn actuators SA/SAR3 to Note on Self Locking :


SA/SAR100 are self locking (see note below)
with exception of output speeds 125 & 180 Self-locking gearing does not ensure safe
rpm. Actuators with 125 & 180 rpm are having stopping after an operation. If this is required,
double start worm drive. After torque switch is separate locking arrangement must be provided.
tripped, the sliding worm may move back to
initial position by the action of torque
measuring springs. This allows torque switch
to be released. If control system provides
continuous signal, this results in hunting of
motor. This can be avoided by the use of
auxiliary relay.

15
Actuators for Regulating Duty
Description of Regulating Duty

Auma actuators of type SAR are suitable for - Max. No. of starts
Regulating duty / Modulating duty. SAR 1200 cycles / hour with motor power upto
actuator operates between two set bands in 0.55 kW & 600 cycles / hour with motor
closed loop and the motor is started, stopped power above 0.55 kW.
& reversed at short intervals to correct the - Output speed of actuator max. 45 rpm.
deviation from the set value. SAR actuators - Torque for regulating duty should not exceed
differ from SA actuators in several respects : 50% of max. torque of actuator.
- Max. torque of actuator can be used for
- 4 pole motors are used to reduce overshoot seating & unseating of the valve.
- Worm with high quality finish on flanks for - For reversing service, duration of impulse
better efficiency should be minimum of 50 ms.
- Disc springs on worm shaft are pre - Electronic position transducer or precision
compressed to reduce dead band when potentiometer should be used for remote
reversing. position indication.
- The motor should be short time duty
While selecting Auma actuators for regulating class S4 - 25%.
duty applications, following points should be
The SAR actuator basically consists of
noted :
control units as explained in following
diagram.

Principle of Operation

SAR : Regulating duty actuator CU01 : Electronic positioner

MSAR : Sensor for actuator, i.e. V : Regulating valve


position transmitter at actuator
M : Sensor for regulating valve
(potentiometer or inductive
LVDT) MU : Signal converter for sensor

MUSAR : Signal converter for SAR i.e. SE : Setting nominal value


Electronic position transducer
(RWG 1001/RWG 2002) or W : Reference input
inductive position transmitter
XR : Input value at controller
(IWG 1002/ IWG 1003).
YR : Output value at electronic
positioner

16
Actuators for Regulating Duty
Description of Electronic Units

Sensor for Actuator Technical Data


A potentiometer is used as sensor for actuator. Resistance 4.7 k ohms + 0.5 %
Single turn wire wound potentiometer with Power rating 3 Watt at 40 C
o

4.7 k ohms with linearity of + 0.5 % is available


o o
for this purpose. It is available in single or Angle of rotation 275 + 5
tandem version.
Linearity + 0.5%
Electronic position transducer RWG 1001

This device is a signal converter for the


transformation of resistance value into
proportionate current signal. It can also be
placed in the actuator where the position
determined by the potentiometer is converted
into 4-20 mA current signal.

As position transmitter, preferably a


potentiometer of 4.7 k ohm should be used so RWG 1001
that the reference voltage source is not over
loaded. This device requires 24V DC power Technical Data - RWG 1001
supply regulated within + 15%. Auma power Configuration 3 Wire
supply unit PS01 is recommended for this 24V DC
Supply Voltage
purpose. RWG 1001 is a 3 wire system and is min. 18, max. 33V
having linearity of 0.05 %. 0-20 mA
Output Current
(4-20 mA)
Electronic position transducer RWG 2002 Input resistance 150 k ohms
Displacement of zero
+ 25%
This is basically same as RWG 1001, however position, max.
with 2 wire system. The linearity is less than 1%. Displacement of end
position, max. from 50 to 100%
Influence of supply Max. 0.2%
voltage variation
Temp. drift 0.2% 10o C
Linearity not considering
0.05%
potentiometer

Technical Data - RWG 2002


Configuration 2 Wire
24V DC
Supply Voltage
min. 18, max. 33V
Output Current 4-20 mA
Input resistance 150 k ohms
Displacement of zero + 25%
RWG 2002 position, max.
Displacement of end
position, max. from 60 to 100%
Influence of supply Max. 0.15%
voltage variation
Linearity not considering
< 1%
potentiometer
17
Actuators for Regulating Duty
Description of Electronic Units

Dual Output Position Transmitter RWG 2002 DG :

It is a signal converter device for the Technical Data - RWG 2002 DG


transformation of resistance value into
proportionate galvanically isolated two current 24V DC
Supply Voltage
outputs. This device requires 24 V DC power + 10% regulated
supply regulated within + 10%. Auma power Output 1 (Isolated) 0/4-20 mA
supply unit PS01 is recommended for Output 2 (Isolated) 0/4-20 mA
this purpose. Current Drawn 100 mA
Adjustability of Span + 50%
Adjustability of Zero + 25%
Change in Output due to
Input Supply Variation < 0.2%
Operating Temperature o o
Range - 20 C to + 80 C
Linearity Error for both
Outputs < 1%

Inductive Position Transmitter IWG 1002

When using Auma actuators for regulating duty


with demand of high accuracy, an inductive
position transmitter can be fitted to give precise
read out of position.

The output signal is used as feed back to


electronic positioner or for position indicator.
The system consists of two parts, a linear
variable differential transformer (LVDT) and
an electronic unit. The smallest change of
magnetic core in the measuring coil is
transformed into proportional signal. The IWG 1002
transmitter has no moving contacts. This device
requires 24 V DC power supply regulated
Technical Data - IWG 1002
within + 15%. Auma power supply
unit PS01 is recommended for this purpose. Configuration 2 Wire
The linearity of the unit is less than 0.3%. 24V DC
Supply Voltage
+ 15% regulated
Output Current 4-20 mA
Resistance max. 600 ohms
Displacement of zero + 25%
position, max.
Displacement of end
position, max. 60 to 100%

Temp. drift 0.4% / 10o C


Linearity (not
< 0.3%
considering LVDT)
18
Actuators for Regulating Duty
Description of Electronic Units

Inductive position transmitter IWG 1003

IWG 1003 is similar to IWG 1002 however with Technical Data - IWG 1003
3 wire system.
Configuration 3 Wire
24V DC
Supply Voltage
+ 15% regulated
Output Current 0 / 4-20 mA
Resistance max. 600 ohms
Displacement of zero
+ 25%
position, max.
Displacement of end
position, max. 60 to 100%
Temp. drift 0.4% / 10oC
Linearity (not
considering LVDT) < 0.3%
IWG 1003

Electronic Positioner CU01

The electronic positioner CU01 is designed as a closing) depends upon the plus or minus sign of
three level positioner for regulating of actuator. the deviation. Thus the regulating signal
By comparing two input signals (reference generated by potentiometer or LVDT changes &
signal W & regulating signal X), the positioner when the regulating signal & reference signal
determines the difference. In case this exceeds a become equal, the actuator stops as long as no
certain value, the actuator is switched on by new correction is required.
relays. The direction of rotation (opening or

Technical Data
Input WE1 0-20 mA (4-20 mA)
XE2 0-20 mA (4-20 mA)
or 0-Uref
Time delay 0.5-15 secs.
Adjustment of zero 0 - 20%
point
Adjustment of end
position 60 to 100%
Sensitivity (dead 1% - 2.5%
band)
Relay output (max. 230V, 10A
resistive load

CU 01

19
Actuators for Regulating Duty
Description of Electronic Units

Signal Isolator

Auma signal isolators are available in various Various output signals :


versions : 4-20 mA single or dual or 4-20 mA & 1-5V
Power supply conditions :
230V AC, 110V AC or 24V DC Isolation is provided between input and output
Various input signals : and between two outputs.
4-20 mA or 1-5 V
Technical Data
230V AC + 15%
Power Supply 110V AC + 15%
24V DC + 1V
Input 4-20 mA
1-5V
4-20 mA single
Output 4-20 mA dual
4-20 mA & 1-5 V
Accuracy + 0.1% of output span
Zero & span + 2% min. at zero
adjustment + 10% min. at span
Signal Isolator

Power supply unit PS01

This unit gives 24V DC power supply for Version II : For remote position indication with
regulating system (example : for CU01) & for potentiometer 220 ohms as position transmitter :
remote position indication (example : by a In this two additional potentiometers P1 and P2
voltmeter suitably calibrated). There are two are provided for positions zero and maximum.
versions available:
Version I : For regulating application with
CU01 :
The output voltage Uo & Uc require no trimming
potentiometer. The voltage Uc is diverted from
voltage Uo, thus Uc can serve as common
reference potential for whole regulating system.
This version is suitable for IWG 1003 or
RWG 1001.
Supply voltage to PS01 is 220V or 110V + Version II
15%, 50 Hz
The maximum output voltage is Technical Data - PS01
Uo = 24V + 1 V DC
Supply voltage and 220V or 115V (+ 15%)
Uc = 5.5V + 0.5V DC
frequency 50 Hz or 60 Hz
Power drawn 9 VA
Output voltage 24V +1V DC
max.
Mounting Snap on type for DIN
rail 46277
Version I
20
Actuator Types
Auma Norm Actuators

This actuator offers a complete actuator type SA


with electric motor, torque switch for open -
close direction, limit switches for both end
positions & blinker switch for running
indication. The required reversing contactor
should be installed separately & wired to the
motor. For signalization of the switching and to
trip the contactors over micro switches, control
wires are required from actuator terminal
compartment cover to reversing contactor
installed separately.
Auma Norm

Auma Integral Starter Actuators

The purpose of offering Integral motor controls - Several actuators can be connected to common
for the actuator is to enable the customer to save supply cable using isolating switch for each
high installation costs for external controls. actuator.
Actuators with integral controls include control - Actuator signals are processed in the controls,
& switching elements and are supplied only feed back to process control system is
ready for use. necessary.
- Integral starter housing can be easily
All electrical components such as limit, torque, exchanged due to multi pin plug connector
thermo switches, all monitoring elements & between actuator & integral starter unit.
position transmitter are integrated into modern - Actuator can be operated from Local or
controls.This results in following simplification.
Remote position by means of selector switch
- No extensive wiring in the external control on the integral starter unit.
cabinet

Auma Integral Starter

21
Actuator Types
Control Versions of Integral Starter Units

Auma Compact Auma compact is available as Norm or


Regulating duty actuator. Depending upon Norm
This is a simpler version of Integral Starter Unit or Regulating duty, following features /
with selector switch & push buttons. The optionals are available :
selector switch has 3 positions :
Reversing contactors
LOCAL : Selector switch
Push buttons & indicating lamps
The actuator can be operated locally i.e. at the
Thermal overload relay
actuator by push buttons OPEN-OFF-CLOSE.
Power supply unit PS01 for 24 V DC output
The running direction is indicated by LEDs.
Electronic positioner CU01
REMOTE : Electronic position transducer RWG / IWG
Phase discriminator
The actuator can be operated from remote Signal isolator
control station. The running direction is DC relay for remote operation
indicated by LEDs on the actuator. Remote annunciation relay for supply
indication
OFF :
Multi pin connector can be provided between
The actuator cannot be operated with local actuator and compact and between compact &
controls or from remote. terminals for customer connections.
The selector switch can be locked in any position
with pad lock. The compact unit is completely
wired with reversing contactors and no
additional control box is required.

Auma Compact