Professional Documents
Culture Documents
Job Information
Job01
TIG
Unit Information
Capacity 216.00 tons Efficiency 0.675 kW/ton
NPLV 0.430 kW/ton Refrigerant charge (HFC-134a) 222 kg
Full Load Sound Pressure-AHRI Condition 80 dBA
Pressure vessel code ASME pressure vessel code
Refrigeration isolation valves
Oil cooler Without oil cooler
Evaporator Information
Evap leaving temp 6.7 C Evap flow rate 118.6 m3/hr 522.40 gpm
Evap entering temp 12.2 C Evap pressure drop 12.60 ft H2O
Minimum evap flow rate 53.14 234.00 gpm Evap fouling factor 0.00010 hr-sq ft-deg F/Btu
Number of evaporator passes 3 pass Evap fluid freeze point 0.0 C
Evap fluid type Water Evap fluid concentration 0.00
Condenser Information
Cond entering temp 32.2 C Cond flow rate 803.10 gpm
Cond leaving temp 36.4 C Cond pressure drop 19.50 ft H2O
Number of cond passes 2 pass condenser Cond fouling factor 0.00025 hr-sq ft-deg F/Btu
Cond fluid type Water Cond fluid concentration 0.00
Condenser tube type Enhanced fin - copper
Electrical Information
Unit voltage 415 Volt 3 phase Unit hertz 50 Hertz
Unit power 145.90 kW Starter type AdaptiR
Minimum circuit ampacity 290.40 A Maximum overcurrent protection 522.80 A
Starter expected inrush 260.00 A Motor locked rotor amps 1536.00 A
Run load amps 232.40 A
This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Certified in accordance with the AHRI Water-Cooled Water-Chilling Packages using the
Vapor Compression Cycle Certification Program which is based on AHRI Standard 550/590
(I-P). Certified units may be found in the AHRI directory at www.ahridirectory.org.