AIRCONDITIONING HEATLOAD ESTIMATE

CLIENT : Shubharambh Banquets


Location : Third Floor (Hall 1) HEAT LOAD CALCULATIONS
DATE 5/26/2017
TIME 13:20
ENGINEER Calvin Symss
DESIGN DATA
AREA: = 814
HT.OF THE AREA: = 11
EQUIPMENT LOAD (WATTS/SQFT) = 1.8
LIGHTING LOAD (WATTS/SQFT) = 3 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 5 GRAND TOTAL HEAT 6.2
Cfm VENTILATION = 746 DEHUMIDIFIED AIR Cfm 2503
Cfm/PERSON = 15
NO.OF PEOPLE = 70 TONS AS PER Cfm 6.3
Cfm VENTILATION = 1050
TONNAGE REQUIRED 6.3
Cfm VENTILATION IN CAL. = 1050
Ambient Design Conditions CFM PER SQFT 3.07
D.B. W.B. %RH GR/LB AREA PER TON 130
OUTSIDE 104 78 - 90
INSIDE 74 - 55 72.0
DIFF. 30 - - 18.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
1050 18 0.12 0.68 1542
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 70 205 14350
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 15892
N-E 72 12 0.56 484
N-W 0 138 0.56 0 SAFETY FACTOR=5% 795
S-E 0 12 0.56 0 ROOM LATENT HEAT 16687
S-W 0 85 0.56 0
SKY LIGHT 0 118 0.56 0 ROOM TOTAL HEAT 64259
SOLAR & TRANSMISSION GAIN
NORTH 0 25 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 39 0.34 0
EAST 0 25 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 39 0.34 0 SENS 1050 30 0.88 1.08
N-E 272 25 0.34 2312 LAT 1050 18 0.88 0.68
N-W 0 25 0.34 0
S-E 0 32 0.34 0 SUB TOTAL
S-W 0 46 0.34 0 TOTAL 64259
ROOF 0 49 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 1928

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 6.2 66187


ALL GLASS 0 30 1.13 0 0
PARTIONS 315 23 0.4 0 2898
CEILING 0 23 0.4 0 0 SENSIBLE HEAT FACTOR 0.74
FLOOR 0 23 0.3 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 17.6
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 2503
1050 30 0.12 1.08 4082 TONS AS PER Cfm 6.3

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 70 245 17150 GRAND TOTAL HEAT(BTU/HR/SQFT.) 81.31
EQUIPMENT 1465 3.4 4982 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 58.44
LIGHTS 2442 3.4 1.25 10379 SQFT/PERSON 11.63
TONS PER SQFT 0.01
SUB TOTAL 42286 CFM PER SQFT 3.07
TONS/PERSON 0.09
LEAK LOSS + SAFETY FACTOR=12.5% 5286 DEHUMIDIFIED CFM/TON 401.56
ROOM SENSIBLE HEAT 47572 AREA PER TON 130.60
AIRCONDITIONING HEATLOAD ESTIMATE
CLIENT : Shubharambh Banquets
Location : Third Floor (Hall 2) HEAT LOAD CALCULATIONS
DATE 5/26/2017
TIME 13:20
ENGINEER Calvin Symss
DESIGN DATA
AREA: = 2946
HT.OF THE AREA: = 11
EQUIPMENT LOAD (WATTS/SQFT) = 1.8
LIGHTING LOAD (WATTS/SQFT) = 3 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 5 GRAND TOTAL HEAT 21.9
Cfm VENTILATION = 2701 DEHUMIDIFIED AIR Cfm 8867
Cfm/PERSON = 15
NO.OF PEOPLE = 240 TONS AS PER Cfm 22.2
Cfm VENTILATION = 3600
TONNAGE REQUIRED 22.2
Cfm VENTILATION IN CAL. = 3600
Ambient Design Conditions CFM PER SQFT 3.01
D.B. W.B. %RH GR/LB AREA PER TON 133
OUTSIDE 104 78 - 90
INSIDE 74 - 55 72.0
DIFF. 30 - - 18.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
3600 18 0.12 0.68 5288
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 240 205 49200
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 54488
N-E 72 12 0.56 484
N-W 0 138 0.56 0 SAFETY FACTOR=5% 2724
S-E 144 12 0.56 968 ROOM LATENT HEAT 57212
S-W 72 85 0.56 3427
SKY LIGHT 0 118 0.56 0 ROOM TOTAL HEAT 225751
SOLAR & TRANSMISSION GAIN
NORTH 0 25 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 39 0.34 0
EAST 0 25 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 39 0.34 0 SENS 3600 30 0.88 1.08
N-E 243 25 0.34 2066 LAT 3600 18 0.88 0.68
N-W 0 25 0.34 0
S-E 689 32 0.34 7496 SUB TOTAL
S-W 243 46 0.34 3801 TOTAL 225751
ROOF 0 49 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 6773

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 21.9 232523


ALL GLASS 0 30 1.13 0 0
PARTIONS 346 23 0.4 0 3183
CEILING 0 23 0.4 0 0 SENSIBLE HEAT FACTOR 0.75
FLOOR 0 23 0.3 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 17.6
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 8867
3600 30 0.12 1.08 13997 TONS AS PER Cfm 22.2

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 240 245 58800 GRAND TOTAL HEAT(BTU/HR/SQFT.) 78.93
EQUIPMENT 5303 3.4 18030 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 57.21
LIGHTS 8838 3.4 1.25 37562 SQFT/PERSON 12.28
TONS PER SQFT 0.01
SUB TOTAL 149812 CFM PER SQFT 3.01
TONS/PERSON 0.09
LEAK LOSS + SAFETY FACTOR=12.5% 18727 DEHUMIDIFIED CFM/TON 404.95
ROOM SENSIBLE HEAT 168539 AREA PER TON 134.55
AIRCONDITIONING HEATLOAD ESTIMATE
CLIENT : Shubharambh Banquets
Location : Third Floor (Hall 3) HEAT LOAD CALCULATIONS
DATE 5/26/2017
TIME 13:20
ENGINEER Calvin Symss
DESIGN DATA
AREA: = 1615
HT.OF THE AREA: = 11
EQUIPMENT LOAD (WATTS/SQFT) = 1.8
LIGHTING LOAD (WATTS/SQFT) = 3 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 5 GRAND TOTAL HEAT 12.3
Cfm VENTILATION = 1480 DEHUMIDIFIED AIR Cfm 5148
Cfm/PERSON = 15
NO.OF PEOPLE = 120 TONS AS PER Cfm 12.9
Cfm VENTILATION = 1800
TONNAGE REQUIRED 12.9
Cfm VENTILATION IN CAL. = 1800
Ambient Design Conditions CFM PER SQFT 3.19
D.B. W.B. %RH GR/LB AREA PER TON 125
OUTSIDE 104 78 - 90
INSIDE 74 - 55 72.0
DIFF. 30 - - 18.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
1800 18 0.12 0.68 2644
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 120 205 24600
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 27244
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 1362
S-E 0 12 0.56 0 ROOM LATENT HEAT 28606
S-W 144 85 0.56 6854
SKY LIGHT 0 118 0.56 0 ROOM TOTAL HEAT 126454
SOLAR & TRANSMISSION GAIN
NORTH 0 25 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 39 0.34 0
EAST 0 25 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 39 0.34 0 SENS 1800 30 0.88 1.08
N-E 0 25 0.34 0 LAT 1800 18 0.88 0.68
N-W 0 25 0.34 0
S-E 0 32 0.34 0 SUB TOTAL
S-W 480 46 0.34 7507 TOTAL 126454
ROOF 0 49 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 3794

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 12.3 130247


ALL GLASS 0 30 1.13 0 0
PARTIONS 624 23 0.4 0 5741
CEILING 0 23 0.4 0 0 SENSIBLE HEAT FACTOR 0.77
FLOOR 0 23 0.3 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 17.6
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 5148
1800 30 0.12 1.08 6998 TONS AS PER Cfm 12.9

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 120 245 29400 GRAND TOTAL HEAT(BTU/HR/SQFT.) 80.65
EQUIPMENT 2907 3.4 9884 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 60.59
LIGHTS 4845 3.4 1.25 20591 SQFT/PERSON 13.46
TONS PER SQFT 0.01
SUB TOTAL 86976 CFM PER SQFT 3.19
TONS/PERSON 0.10
LEAK LOSS + SAFETY FACTOR=12.5% 10872 DEHUMIDIFIED CFM/TON 419.71
ROOM SENSIBLE HEAT 97848 AREA PER TON 131.68
AIRCONDITIONING HEATLOAD ESTIMATE
CLIENT : Shubharambh Banquets
Location : Fourth Floor (Hall 4) HEAT LOAD CALCULATIONS
DATE 5/26/2017
TIME 13:20
ENGINEER Calvin Symss
DESIGN DATA
AREA: = 804
HT.OF THE AREA: = 11
EQUIPMENT LOAD (WATTS/SQFT) = 1.8
LIGHTING LOAD (WATTS/SQFT) = 3 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 5 GRAND TOTAL HEAT 6.1
Cfm VENTILATION = 737 DEHUMIDIFIED AIR Cfm 2613
Cfm/PERSON = 15
NO.OF PEOPLE = 54 TONS AS PER Cfm 6.5
Cfm VENTILATION = 810
TONNAGE REQUIRED 6.5
Cfm VENTILATION IN CAL. = 810
Ambient Design Conditions CFM PER SQFT 3.25
D.B. W.B. %RH GR/LB AREA PER TON 123
OUTSIDE 104 78 - 90
INSIDE 74 - 55 72.0
DIFF. 30 - - 18.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
810 18 0.12 0.68 1190
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 54 205 11070
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 12260
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 613
S-E 0 12 0.56 0 ROOM LATENT HEAT 12873
S-W 72 85 0.56 3427
SKY LIGHT 0 118 0.56 0 ROOM TOTAL HEAT 62531
SOLAR & TRANSMISSION GAIN
NORTH 0 25 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 39 0.34 0
EAST 0 25 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 39 0.34 0 SENS 810 30 0.88 1.08
N-E 0 25 0.34 0 LAT 810 18 0.88 0.68
N-W 325 25 0.34 2763
S-E 0 32 0.34 0 SUB TOTAL
S-W 231 46 0.34 3613 TOTAL 62531
ROOF 0 49 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 1876

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 6.1 64407


ALL GLASS 0 30 1.13 0 0
PARTIONS 303 23 0.4 0 2788
CEILING 0 23 0.4 0 0 SENSIBLE HEAT FACTOR 0.79
FLOOR 0 23 0.3 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 17.6
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 2613
810 30 0.12 1.08 3149 TONS AS PER Cfm 6.5

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 54 245 13230 GRAND TOTAL HEAT(BTU/HR/SQFT.) 80.11
EQUIPMENT 1447 3.4 4920 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 61.76
LIGHTS 2412 3.4 1.25 10251 SQFT/PERSON 14.89
TONS PER SQFT 0.01
SUB TOTAL 44141 CFM PER SQFT 3.25
TONS/PERSON 0.11
LEAK LOSS + SAFETY FACTOR=12.5% 5518 DEHUMIDIFIED CFM/TON 430.75
ROOM SENSIBLE HEAT 49659 AREA PER TON 132.56
AIRCONDITIONING HEATLOAD ESTIMATE
CLIENT : Shubharambh Banquets
Location : Fourth Floor (Hall 5) HEAT LOAD CALCULATIONS
DATE 5/26/2017
TIME 13:20
ENGINEER Calvin Symss
DESIGN DATA
AREA: = 2499
HT.OF THE AREA: = 11
EQUIPMENT LOAD (WATTS/SQFT) = 1.8
LIGHTING LOAD (WATTS/SQFT) = 3 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 5 GRAND TOTAL HEAT 18.6
Cfm VENTILATION = 2291 DEHUMIDIFIED AIR Cfm 7574
Cfm/PERSON = 15
NO.OF PEOPLE = 200 TONS AS PER Cfm 18.9
Cfm VENTILATION = 3000
TONNAGE REQUIRED 18.9
Cfm VENTILATION IN CAL. = 3000
Ambient Design Conditions CFM PER SQFT 3.03
D.B. W.B. %RH GR/LB AREA PER TON 132
OUTSIDE 104 78 - 90
INSIDE 74 - 55 72.0
DIFF. 30 - - 18.0
SUN GAIN BYPASS O.A. LATENT LOAD
AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
3000 18 0.12 0.68 4406
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPLE 200 205 41000
EAST 0 12 0.56 0
WEST 0 163 0.56 0 SUB TOTAL 45406
N-E 72 12 0.56 484
N-W 0 138 0.56 0 SAFETY FACTOR=5% 2270
S-E 216 12 0.56 1452 ROOM LATENT HEAT 47677
S-W 72 85 0.56 3427
SKY LIGHT 0 118 0.56 0 ROOM TOTAL HEAT 191642
SOLAR & TRANSMISSION GAIN
NORTH 0 25 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 39 0.34 0
EAST 0 25 0.34 0 CFM G.DIFF 1-B.F. FACTOR
WEST 0 39 0.34 0 SENS 3000 30 0.88 1.08
N-E 253 25 0.34 2151 LAT 3000 18 0.88 0.68
N-W 0 25 0.34 0
S-E 276 32 0.34 3003 SUB TOTAL
S-W 253 46 0.34 3957 TOTAL 191642
ROOF 0 49 0.12 0
HEAT GAIN SAFETY FACTOR @ 3% 5749

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 18.6 197392


ALL GLASS 0 30 1.13 0 0
PARTIONS 617 23 0.4 0 5676
CEILING 0 23 0.4 0 0 SENSIBLE HEAT FACTOR 0.75
FLOOR 0 23 0.3 0 0 SELECTED A.D.P. 54
DEHUMIDIFIED RISE 17.6
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 7574
3000 30 0.12 1.08 11664 TONS AS PER Cfm 18.9

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 200 245 49000 GRAND TOTAL HEAT(BTU/HR/SQFT.) 78.99
EQUIPMENT 4498 3.4 15294 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 57.61
LIGHTS 7497 3.4 1.25 31862 SQFT/PERSON 12.50
TONS PER SQFT 0.01
SUB TOTAL 127969 CFM PER SQFT 3.03
TONS/PERSON 0.09
LEAK LOSS + SAFETY FACTOR=12.5% 15996 DEHUMIDIFIED CFM/TON 407.47
ROOM SENSIBLE HEAT 143966 AREA PER TON 134.44