Professional Documents
Culture Documents
in
HVAC
Prof. B A Shah,
Assistant Professor,
Mechanical Engineering Department
Institute of Technology,
Nirma University
Courtesy GIFT city and GEDA
Outline of Presentation
• ICAP (India Cooling Action Plan)
• Strategies to reduce energy consumption in HVAC
• Inverter AC Technology
• GIFT City District Cooling System (DCS)
• Other Strategies
Introduction- EC in HVAC
• The main power consumers in most buildings are lighting and the
heating, ventilation and air-conditioning (HVAC) systems.
• Substantial savings can be achieved by optimising the heating,
ventilation and air-conditioning (HVAC) system and by upgrading
plant with energy efficient technology.
• Poor maintenance, lack of knowledge on how to use them efficiently,
overuse, and the large number of old and inefficient systems at work
in the sector make HVACs a significant contributor to the country’s
demand for energy.
Strategies to reduce energy consumption
• Reduce Cooling Load
• Use energy efficient HVAC system
• Use of BMS(Building Management System)
• Use VSD(Variable Speed Drive) and inverter technology
• Use Renewable Energy
HVAC System Components
Non-inverter air-conditioner
What are the benefits of Inverter Air-Conditioners?
India’s 1st IFSC
Operational Greenfield Smart City
Air Conditioning System at GIFT
• District Cooling System (DCS) is going to be used in India’s first smart
city – GIFT City.
• Overall 35% energy saving have been claimed by using DCS in GIFT
City.
• No Split ACs or separate Building based chillers will be used, All
buildings including commercial and residential will be provided air
conditioning through DCS only.
WHAT IS DISTRICT COOLING SYSTEM
The Central DCS Plant will include Chiller, Primary Pump, Secondary
Pump, Condenser Pump, Cooling Tower, Thermal Energy Storage and
Distribution network of CHW.
The consumer system would usually comprise of energy transfer
station, tertiary Pumps & chilled water piping and air handling units in
the building.
…District Cooling
What is District Cooling ?
• A DCS consists of three primary components:
• The Central Plant
• The Distribution Network
• The Consumer System
DISTRICT COOLING SYSTEM IN GIFT
Heat load in TR
150000 TR/ 135 MW
Availability of
Chillers Availability of Chillers
Can be use for Can be use for TES Charging
TES Charging
250 MW
135 MW
WATER DEMAND
Building based Chiller system DCS System
25 MLD
20 MLD
22
•Counter series Chillers
•Effective CHW Distribution
•Thermal Energy Storage Tank
23
Counter Series Chillers
35⁰C
10 ⁰C 35 ⁰C 10 ⁰C
38 ⁰C 6 ⁰C
14⁰ C 32 ⁰C
24
Thermal Energy Storage
25
…District Cooling
• District Cooling Advantages
• Less operating costs for System owners
• Easy to operate from centralized Control Room
• Improved supply reliability
• Building owner ends up with more space available for other purposes. A heat exchanger is
needed at the building site instead of a complete cooling system.
• System flexibility makes it possible to adjust cooling capacity to varying demands
• Eliminates the need for building owner to buy, service or maintain cooling equipment
• Environmentally friendly refrigerants are kept contained in one central system
• Optimum number of standby equipment requirements
• Lower operating manpower for centralized maintenance facility
27
CHW Distribution through tunnel 28
Operating Cost comparison in Gift City
System Operating cost per TR Remarks
DCS Rs. 8 Break even reached @ 3500 TR
(0.8 KW/TR) which is 2% of total city demand
Building based water cooled chiller Rs. 11 Space for chiller & Cooling tower
(1.1 KW/TR) required
Diversity Not applicable
Air cooled chillers Rs. 12 Space for heat rejection not
(1.2 KW/TR) possible in high rise towers
• There are two types of compressor drive: Fixed speed and variable
speed. The fixed speed chiller operates at a constant speed and is
designed to deliver a constant quantity of compressed gas
irrespective of the load. Variations in load are accommodated by
several methods:
• Cycling operation (on-off): When the required conditions have been
met, the compressor switches off or goes into idle or bypass mode.
• Using a variable speed drive allows matching the compressor
operation with the load in an efficient and energy saving manner. This
is especially relevant at low loads.
Comparison of fixed and variable speed drives
• In the falling film evaporator, the surface of the tubes in the upper portion
of the evaporator is covered with a thin film of refrigerant, giving a very
effective heat transfer mechanism. In the mixed falling film type evaporator
(see Fig. 5), a thin film of refrigerant is sprayed over the top tubes. Some of
this evaporates and the gas passes on to the compressor. The remaining
refrigerant covers the bottom tubes and evaporates as well. The FF-type
offers higher heat transfer efficiency and requires a lower charge of
refrigerant than the flooded type evaporator In the full falling film
evaporator (see Fig. 5), the film covers all the tube and the remaining
refrigerant collects in the bottom of the evaporator. Only the evaporator
bottom has a small amount of liquid refrigerant so that refrigerant charge
is less, complying with environment protection.
• The mixed falling film is claimed to use 15% less refrigerant than the
flooded type. The full falling film type is claimed to use 40%
refrigerant less than the full flooded type. Less refrigerant implies less
energy usage in compressing and pumping the refrigerant around the
cooling circuit.
Condensers
• Energy saving on fans is much greater than on other equipment. On fan loads, the
power requirement varies as the cube of the speed, so the slower the fan speed,
the less energy required. A fan running at 80% speed will consume 50% of the
energy at 100% speed. Modern fan controls consist of much more than just speed
controls and variable speed drives.
• Key to identifying the energy savings opportunities of VSDs in HVAC systems is an
understanding of the operating cycle of the system versus the heating and cooling
needs actually required. Most HVAC systems are designed to keep the building
cool on the hottest days and warm on the coldest days. Therefore, the HVAC
system only needs to work at full capacity on those days.
• For the rest of the year, the HVAC system can operate at reduced capacity. This is
where a variable air volume system with variable speed drives (also-called
variable frequency drives, or VFDs) can be used to match air flow to actual
heating and cooling demands. The VSD can reduce the motor speed when full
flow is not required, thereby reducing the power and the electrical energy used.
VAPOUR ABSOBPTION SYSTEM
PAGE 8.8
LARGER HEAT EXCHANGER
◼ Larger heat exchanger, condenser and
evaporators allow higher evaporator
temperature and lower condenser
temperature
◼ Regularly clean all heat exchanger
◼ Provide proper water treatment
◼ Performance can drop by 50% in absence of
cleaning and water treatment
NEW TECHNOLOGY
◼ Thermal storage to take advantage of
cheap power at night
◼ Tariff as well as temperature favourable
◼ Heat recovery systems
◼ Heat pipes, heat wheels variable speed
drives heat pumps
References
[1] http://www.ee.co.za/article/energy-saving-in-hvac-systems.html
[2] J Eldridge: “Variable speed compressor technology and
applications”, Daikin.
[3] SEW Eurodrive: “LTP-B Eco HVAC pump control”, www.sew-
eurodrive.co.za
[4] A Lynegar: “Smarter VSDs improve centrifugal pump
operation”, Flow control, March 2017.
[5] York: “York Variable Speed Drives”, www.johnsoncontrols.com
Thank You