You are on page 1of 2

DATE : 18.12.

2006

PROJECT RELIANCE MALL, JAMNAGAR

CONSULTANT : ATKINS

AHU DETAILS

AHU NOS - 1 , 2 , 3 , 4 , 6 , 7 , 8 (BUILDING 1)

AIR QUANTITY : 15000 CFM

STATIC PRESSURE : 62 MM WG

TR : 38 TR

EXTERNAL STATIC PRESSURE : 30 MM

SR NO DESCRIPTION UNIT VALUE

1 ALTITUDE FEET 0

2 FIN TYPE : ALUMINIUM INCHES 0.006

3 TUBE WALL THICKNESS INCHES 0.02

4 ENTERING DRY BULB TEMPERATURE (AIR) F 74.78

5 ENTERING WET BULB TEMPERATURE (AIR) F 65

6 ENTERING WATER TEMPERATURE F 45

7 SUPPLY AIR QUANTITY CFM 15000

8 CHILLED WATER FLOW USGPM 91.2

9 FINS PER INCH NOS 12

10 COIL ROW DEEP NOS 6

11 TUBE HIGH NOS 42

12 FIN LENGTH INCHES 68

13 COIL FACE VELOCITY FPM 605


14 LEAVING AIR DRY BULB TEMPERATURE F 54.21

15 LEAVING AIR WET BULB TEMPERATURE F 53.94

16 LEAVING WATER TEMPERATURE F 55.96

17 WATER TEMPERATURE RISE ACROSS COIL F 10.96

18 AIR SIDE PRESSURE DROP INCHES 0.96

19 WATER SIDE PRESSURE DROP INCHES 3.7

20 TOTAL HEAT M BTU / HR 500.37

21 SENSIBLE HEAT M BTU / HR 337.36

22 CHILLED WATER VELOCITY FPS 2.4

23 AVAILABLE COIL CAPACITY TR 41.6975

You might also like