AL-DIYAR CONSULTANTS

Made by Date : :MAY-2011 Project MOI- 2110


Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 01 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 49.6 + 24.8
= 74.4 MT
Supply duct static losses = Total equ. length x D P/M
= 74.4 x 0.49
= 36.456 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 161.456 PA


Adding 10% factor of safety = 16.1456 PA
Total supply external static losses = 177.6016 PA

SAY 180 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 19.3 + 9.65
= 28.95 MT
Return duct static losses = Total equ. length x D P/M
28.95 x 0.49
14 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 114 PA


Adding 10% factor of safety = 11 PA

2111-JAZAN HAIE AL SWAES


Total return external static losses = 126 PA

SAY 130 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 02 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 49.4 + 24.7
= 74.1 MT
Supply duct static losses = Total equ. length x D P/M
= 74.1 x 0.571
= 42.3111 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 167.3111 PA


Adding 10% factor of safety = 16.73111 PA
Total supply external static losses = 184.0422 PA

SAY 185 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 14.4 + 7.2
= 21.6 MT
Return duct static losses = Total equ. length x D P/M
21.6 x 0.571
12 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

2111-JAZAN HAIE AL SWAES


Additional return duct static losses = 100 PA

Total external static losses = 112 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 124 PA

SAY 125 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 03 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 31.4 + 15.7
= 47.1 MT
Supply duct static losses = Total equ. length x D P/M
= 47.1 x 0.653
= 30.7563 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 155.7563 PA


Adding 10% factor of safety = 15.57563 PA
Total supply external static losses = 171.3319 PA

SAY 175 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 6 + 3
= 9 MT
Return duct static losses = Total equ. length x D P/M
9 x 0.653
6 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA

2111-JAZAN HAIE AL SWAES


2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 106 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 116 PA

SAY 120 PA

AL-DIYAR CONSULTANTS
Made by Date : :MAY-2011 Project MOI- 2110
Bldg. 2111
Checked by Date :MAY-2011 Contract : Sheet No.
Revised by : Date :MAY-2011 Section : HVAC Calc. No.
Checked by : Date :MAY-2011 Job No. File
Subject : EXTERNAL STATIC LOSSES SUMMARY

AHU- 04 EXTERNAL STATIC PRESSURE CALCULATION :

Total equivalent supply length = Actual Length + Fitting Equivalent Length


= 30.7 + 15.35
= 46.05 MT
Supply duct static losses = Total equ. length x D P/M
= 46.05 x 0.735
= 33.84675 PA

ADDITIONAL STATIC LOSSES ON SUPPLY AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA
3- VAV 25 PA
Total supply duct static losses = 125 PA

Total external static losses = 158.84675 PA


Adding 10% factor of safety = 15.88468 PA
Total supply external static losses = 174.7314 PA

SAY 175 PA

Total equivalent return length = Actual Length + Fitting Equivalent Length


= 6 + 3
= 9 MT
Return duct static losses = Total equ. length x D P/M
9 x 0.735

2111-JAZAN HAIE AL SWAES


7 PA

ADDITIONAL STATIC LOSSES ON RETURN AIR DUCT :


1- Sound attenuators 50 PA
2- Volume damper 25 PA
3- Ceiling diffuser 25 PA

Additional return duct static losses = 100 PA

Total external static losses = 107 PA


Adding 10% factor of safety = 11 PA
Total return external static losses = 117 PA

SAY 120 PA

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 01 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 02 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 03 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


L-DIYAR CONSULTANTS

: 04 OF 04

Fitting Equivalent Length

Fitting Equivalent Length

2111-JAZAN HAIE AL SWAES


2111-JAZAN HAIE AL SWAES