Professional Documents
Culture Documents
Paper
- Dry paper is an excellent insulator because of the hygroscopic properties.
- Hygroscopic means that it absorbs moisture from the air.
- Paper will lose its insulation properties if it becomes very wet.
- Because of this, paper insulated cables are sheathed with impervious materials, with
lead being the most common.
- Paper insulated lead covered (PILC) is traditionally used for heavy power work.
- The paper insulation is impregnated with oil or non-draining compound in order to
ensure its long term performance.
- PILC usually needs special jointing methods to ensure that the insulation remains sealed.
- PILC usually weights heavier than P.V.C or XLPE (thermosetting) cables. Therefore, P.V.C
or XLPE is usually chosen over PILC.
P.V.C
- P.V.C stands for polyvinyl Chloride.
- Usually used for low voltage cable insulation.
- P.V.C properties:
a) Clean to handle
b) Reasonably resistant to oil or other chemicals.
BASIC ELECTRICAL ENGINEERING ELE 290
c) Becomes hard and difficult to strip in cold condition (P.V.C should not be used in
temperatures below 5˚C)
d) Becomes soft at high temperatures. (must not be allowed to exceed 70˚C)
e) May be degraded by ultra-violet if exposed to sunlight
- If P.V.C is in contact with absorbent materials, the plasticiser may be leached out making
the P.V.C hard and brittle.
- However, there are special P.V.C that can be used in either below than 5˚C or greater
than 70˚C.
Thermosetting (XLPE)
- Cross-linked polyethylene (XLPE)
- Has better electrical properties than P.V.C
- Used for medium – high voltage application.
- Higher resistance to deformation at high temperature. (Can be used in temperature up to
90˚C)
- Higher resistance to temperature will increase the useful current rating, especially when
the ambient temperature is high.
- Also available with LSF properties.
Mineral
- An excellent insulator, such as magnesium oxide, provided that it is kept dry.
- Has the hygroscopic property, same as the paper insulation. Therefore, this type of
insulation is sealed within a copper sheath..
- Properties of mineral insulation:
i) Totally fire-proof (operate at temperatures up to 250˚C)
ii) Inorganic thus non-ageing
iii) Great mechanical strength
iv) Waterproof
v) Resistant to radiation and electrical pulses
vi) Pliable
vii) Corrosion resistant
- In cases where the copper sheath may corrode, the cable is used with an overall LSF
covering, which reduce the temperature at which the cables may be allowed to operate.
- Special seals are used to terminate the cables in order to prevent the ingress of moisture.
- There are also special mineral insulated cables with twisted cores to reduce the effects of
electromagnetic interference.
BASIC ELECTRICAL ENGINEERING ELE 290
8.1.2 Cables
1- PVC sheath
2- PVC insulation
3- Copper conductor (Solid/Stranded)
1- PVC oversheath
2- Melinex binder
3- PVC strings
4- Neutral conductor (black PVC covered wires)
5- Earth continuity conductor (bare copper wires)
6- PVC phase insulation
7- Copper conductors
Consac cables
Waveconal cables
Table below gives the maximum conductor operating temperature for the various types of cables.
The maximum operating temperature for PVC is set at 70˚C, even though the cables can operate at
higher temperature up to 90˚C, because the jointers used to connect the cable may be unable to
tolerate temperatures more than 90˚C. The minimum cross-sectional area for the cables are also
shown in the table below.
BASIC ELECTRICAL ENGINEERING ELE 290
Any of the cables listed in the previous subsection are permitted to be used as overhead
conductors provided that they are properly supported. Normally, the cables used will comply
with the British Standard referring particularly to special cables for use as overhead lines. Such
cable includes those with an internal or external catenary wire, which is usually of stell and is
intended to support the weight of the cable over the span concerned.
Since overhead cables are installed outdoors, they must be chosen and installed so as to offset
the problems of corrosion. Since such cables will usually be in tension, their supports must not
damage the cables or its insulations. Flexible low voltage cables have conductors of cross-
sectional area of 4mm2 or greater whilst flexible cords are sized at 4mm 2 or smaller. Generally,
electrician is nearly always concerned with flexible cords rather than flexible cables.
Braided circular
Unkinkable
Circular sheathed
1- Rubber/PVC sheath
2- Rubber/PVC insulation (60˚C resistant) for cores
3- Tinned copper for cores
1- PVC insulation
2- Plain copper core
Flexible cables should not normally be used for fixed wirings, but if they are used, they must be
visible throughout their entire length. The maximum mass which can be supported by each flexible
cord is listed in the table below.
XLPE cables
Power cables
As well as providing protection against electric shocks, electrical installation must be protected
from excess current (overcurrent) which may damage equipment or cause a fire. Overcurrent can
be divided into two(2) categories:-
i) Overload current
ii) Short circuit current
- equipment is overload
- installation is abused
- badly designed installation
- installation has been modified by an incompetent person
The danger in all such cases is that the temperature of the conductors will increase to such an extent
that the effectiveness of any insulating materials will be impaired.
The device used to detect such overload currents, and to break the circuit when they occur are the:
1. Fuse ( rewireable/replaceable )
2. Miniature Circuit Breaker (MCB)
In order to protect against overload current, the protective devices must be rated greater than or at
least equal to the design current; and the current carrying capacity of the cables must be greater
than or equal to the rating of the protective devices.
An overload current is perhaps no more than twice or three times of the normal circuit current
rating, but for a short-circuit current, it is likely to be several hundred, or even several thousand
times than the normal circuit current rating. In these circumstances, the circuit protection must
break the fault current rapidly, before danger is caused through overheating or mechanical stress.
The current likely to flow under short circuit conditions is called the prospective short -circuit
current (IP), the value of which can be measured using a special test instrument, (where the circuit
has been installed), or obtained from the supply authority.
Prospective short circuit current is the highest electric current which can exist in a particular
electrical system under short circuit conditions.If the device used for overload protection is also
capable of breaking a prospective short circuit current safely, it may be used for both overload and
short circuit protection.
BASIC ELECTRICAL ENGINEERING ELE 290
Overload protective device can provide both overload and short circuit protection if the device has a
breaking capacity not less than the value of I P and:-
1. Design current of the circuit is less than the nominal current setting of the device
2. The current carrying capacity of any circuit conductors is more than the nominal current
setting of the device.
BASIC ELECTRICAL ENGINEERING ELE 290
8.3 Fuses
Types of fuses:-
Semi-Enclosed/Rewireable Fuses
Semi enclosed/rewireable fuses must be fitted with fuse elements in accordance with the
manufacturers instruction. In the absence of such instructions, the fuse must be fitted with a single
element of plain or tinned copper wire of the appropriate diameter.
BASIC ELECTRICAL ENGINEERING ELE 290
Cartridge Fuses
HBC Fuses
The barreal of a high breaking capacity fuse is made from high grade ceramic to withstand the
mechanical forces of heavy current interruption. The plated caps of both sides of the fuses provides
good electrical contact.
An accurately machined element usually made of silver is shaped to give the HBC fuse a precise
characteristic.
This type of fuse may be fitted with an indicator bead which shows when it is blown.
- Consistent in operation
- Reliable
- Discriminates between overload currents of short duration(eg. Motor starting) and high
fault current.
- Expensive
HBC fuse consists of several parallel strips of pure silver with notches cut at predetermined positions.
A short length of pure tinfoil is wrapped round the centre notch of each strip.
The silver strips are spot-welded to silver plated copper end rings. This type of construction provides:
BASIC ELECTRICAL ENGINEERING ELE 290
All cartridges are filled with silica sand to ensure quick and efficient arc extinction in all conditions of
operations.
Types of MCB’s:
Advantages of MCB’s
Disadvantages of MCB’s
Thermal magnetic circuit breakers, which are the type found in most distribution boards, incorporate
both techniques with the electromagnet responding instantaneously to large surges in current (short
circuits) and the bimetallic strip responding to less extreme but longer-term over-current conditions.
Magnetic circuit breakers use a solenoid (electromagnet) whose pulling force increases with the
current. Certain designs utilize electromagnetic forces in addition to those of the solenoid. The circuit
breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the
rating of the circuit breaker, the solenoid's pull releases the latch which then allows the contacts to
open by spring action. Some types of magnetic breakers incorporate a hydraulic time delay feature
using a viscous fluid. The core is restrained by a spring until the current exceeds the breaker rating.
During an overload, the speed of the solenoid motion is restricted by the fluid. The delay permits
brief current surges beyond normal running current for motor starting, energizing equipm ent, etc.
Short circuit currents provide sufficient solenoid force to release the latch regardless of core position
thus bypassing the delay feature. Ambient temperature affects the time delay but does not affect the
current rating of a magnetic breaker.
Time delay characteristic is provided by a thermally operated bi metal element which may be either
directly or indirectly heated. Instantaneous tripping in short circuit conditions is achieved by
arranging for a powerful magnetic pull to deflect the bimetal.
With assisted bimetal tripping the MCB will display a normal time delay characteristic for small and
moderate overloads. This delay will be reduced to instantaneous operation in short circuit
conditions.
RCDs are designed to prevent electrocution by detecting the leakage current, which can be far
smaller (typically 5-30 milliamperes) than the currents needed to operate conventional circuit
breakers or fuses (several amperes). RCDs are intended to operate within 25-40 milliseconds, before
BASIC ELECTRICAL ENGINEERING ELE 290
electric shock can drive the heart into ventricular fibrillation, the most common cause of death
through electric shock.
A residual current device (RCD), similar to a residual current circuit breaker (RCCB), is an electrical
wiring device that disconnects a circuit whenever it detects that the electric current is not balanced
between the energized conductor and the return neutral conductor. Such an imbalance is sometimes
caused by current leakage through the body of a person who is grounded and accidentally touching
the energized part of the circuit. A lethal shock can result from these conditions. RCDs are designed
to disconnect quickly enough to mitigate the harm caused by such shocks although they are not
intended to provide protection against overload or short-circuit conditions.
Current taken by the load is fed through two equal and opposing coils in the differential current
transformer. When phase and neutral current are balanced, they produces equal fluxes in the
transformer.
BASIC ELECTRICAL ENGINEERING ELE 290
If more current flows in the phase side than in the neutral side, an out of balanced flux will be
produced, and this will be detected by the detector coil. (Fault condition)
The fault detector coil opens the contactors by energizing the trip coil. This will isolate the circuit
from faults.
Functional testing of RCD operation should be carried out by operating the test button at regular
intervals. Initial and periodic inspection and testing procedures additionally require the RCD to be
tested using the appropriate instrument.
BASIC ELECTRICAL ENGINEERING ELE 290
The earth can be considered to be a large conductor which is at zero potential. The purpose of
earthing is as follows:-
TN – S system
This is likely to be the type of system used where the supply arrangement of installation
is fed from underground cables with metal sheaths and armour. The TN – S provides a
continuous path back to the star point of the supply transformer, which is effectively
connected to earth.
TT system
This is likely to be used where the supply arrangement to the installation is fed from
overhead cables, where no earth terminal is supplied. With such systems, the earth
electrode for connecting the circuit protective conductors to earth has to be provided by
the consumer. Effective earth connection is sometimes difficult and insuch cases a
residual current device should be installed.
BASIC ELECTRICAL ENGINEERING ELE 290
TN – C –S system
Where the installation supply
arrangement uses a combined
protective earth (PE) and neutral
(N) producing (PEN) conductor,
which is at some point split up
into separate PE and N lines.
BASIC ELECTRICAL ENGINEERING ELE 290
In electricity supply, a ring or radial circuit is an electrical wiring technique that provides two
independent conductors for live, neutral and protective earth within a building for each connected
load or socket.
This design enables the use of smaller diameter wire than would be used in a radial circuit equivalent
total current. Ideally, the ring acts like two radial circuit proceeding in opposite direction around the
ring, the dividing point between them dependent on distribution of load in the ring.
Ring circuits are a way of installing a circuit using a cable size smaller than an equivalent radial circuit
could safely manage as the loadings on the cables are reduced by 50%. These are common in the UK,
and a small number of other countries
Ring circuits continue to operate without the user being aware of any problem if there
are fault conditions or installation errors that make the circuit unsafe
Ring spur installations encourage using three connectors in one terminal, which can
cause one to become loose and overheat.
Testing ring circuits may take 5–6 times longer than testing radial circuits.
Ring circuits can generate strong unwanted magnetic field
Ring circuits may not always be adequately protected against over currents
Radials with a broken connection will not function (if L or N broken), or function with no
safety earth connection (if E broken).