Functional description, SRS

Unicon Biograte (30 t/h)


KPA Unicon Oy
Myllykatu 12
FI-76100 Pieksämäki
Tel. +358 207 749 200
KPA Unicon Oy Functional description, SRS 2. (20)

SISÄLLYSLUETTELO

1. GENERAL ........................................................................................ 3
2. BOILER EMERGENCY STOP CIRCUIT ....................................................... 4
3. FUEL HANDLING EMERGENCY STOP CIRCUIT ........................................... 5
4. TSH1022 BACK FIRE THERMOSTAT 1 ..................................................... 6
5. TSH1023 BACK FIRE THERMOSTAT 2 ..................................................... 7
6. LI506 STEAM DRUM LEVEL 1 ................................................................ 8
7. LI507 STEAM DRUM LEVEL 2 ................................................................ 9
8. LI513 STEAM DRUM LEVEL 3 .............................................................. 10
9. PIA502 STEAM DRUM PRESSURE 1 ...................................................... 11
10. PIA504 STEAM DRUM PRESSURE 2 ...................................................... 12
11. PIA505 STEAM DRUM PRESSURE 3 ...................................................... 13
12. PIA701B FURNACE PRESSURE MEASUREMENT ........................................ 14
13. PSH701A FURNACE PRESSURE SWITCH ................................................ 15
14. QIA707 FLUE GAS OXYGEN ................................................................ 16
15. SS702 FLUE GAS FAN RUNNING .......................................................... 17
16. SS703 FLUE GAS FAN ROTATION GUARD ............................................... 18
17. DEVICES STOPPED BY BOILER EMERGENCY STOP .................................... 19
18. DEVICES STOPPED BY FUEL HANDLING EMERGENCY STOP ........................ 19
19. DEVICES STOPPED BY BOILER PROTECTION INTERLOCKING ...................... 20

9845 CARVIA
KPA Unicon Oy Functional description, SRS 3. (20)

1. GENERAL

The boiler plant is equipped with Siemens S7-300 Fail-safe automation system (DCS),
but is normally operated from the power plant automation system with the help of the
process diagram displays.

In this description safety related locking is indicated as ”noom” locking, where:


n = number of signals required to be ”not OK” for locking to be executed
m = number of all signals in the circuit

For example with 3 signals (measurements) locking is executed with 2oo3. So if two
measurements are “not OK” locking is executed.

With 1oo2 locking only one of two signals need to be “not OK” for locking to be executed.

In all tripled measurements (e.g. drum level measurements) following is applied:


• Median of measurements is used as the control value in
controllers
• It is enabled for the operator to choose the measurements to be
used in control functions.

As a basic function in all analog measurements L LL and H HH alarm limits are


changeable by operator. Locking limits are not changeable by operator.

History

• Revision:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 4. (20)

2. BOILER EMERGENCY STOP CIRCUIT

Function:

• Boiler plant emergency stop circuit OK signal stop boiler plant


• Connected in safety related system as 1oo1 locking

Alarms:

• Boiler emergency stop button pressed

Interlocks:

• Devices, which are connected to boiler emergency stop circuit, are stopped

Connecting circuits:

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 5. (20)

3. FUEL HANDLING EMERGENCY STOP CIRCUIT

Function:

• Boiler plant emergency stop circuit OK signal stop boiler plant


• Connected in safety related system as 1oo1 locking

Alarms:

• Fuel handling emergency stop button pressed

Interlocks:

• Devices, which are connected to fuel handling emergency stop circuit, are
stopped

Connecting circuits:

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 6. (20)

4. TSH1022 BACK FIRE THERMOSTAT 1

Function:

• Circuit controls back fire of stokers.


• Thermostat is in safety related system as 1oo2 locking

Alarms:

• TSH1022 BACK FIRE THERMOSTAT 1

Interlocks:

• Water valve opens when thermostat is not in good condition

Connecting circuits:

• HS-1009-3/4 Back fire valve

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 7. (20)

5. TSH1023 BACK FIRE THERMOSTAT 2

Function:

• Circuit controls back fire of stokers.


• Thermostat is in safety related system as 1oo2 locking

Alarms:

• TSH1023 BACK FIRE THERMOSTAT 2

Interlocks:

• Water valve open when thermostat is not in good condition

Connecting circuits:

• HS-1009-3/4 Back fire valve

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 8. (20)

6. LI506 STEAM DRUM LEVEL 1

Function:

• Circuit measures boiler drum level


• Measurement range 0…800 mm. On the display (0 - 800 mm  0…100 %)
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 650 mm
o L =< 400 mm
o HH => 750 mm
o LL =< 200 mm

Interlocks:

• Boiler protection when two measurements < 200 mm


• Boiler protection / wet boiling guard if two measurements > 750 mm

Connecting circuits:

• LICA-508 Boiler drum level control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 9. (20)

7. LI507 STEAM DRUM LEVEL 2

Function:

• Circuit measures boiler drum level


• Measurement range 0…800 mm. On the display (0 - 800 mm  0…100 %)
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 650 mm
o L =< 400 mm
o HH => 750 mm
o LL =< 200 mm

Interlocks:

• Boiler protection when two measurements < 200 mm


• Boiler protection / wet boiling guard if two measurements > 750 mm

Connecting circuits:

• LICA-508 Boiler drum level control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 10. (20)

8. LI513 STEAM DRUM LEVEL 3

Function:

• Circuit measures boilers drum level


• Measurement range 0…800 mm. On the display (0 - 800 mm  0…100 %)
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 650 mm
o L =< 400 mm
o HH => 750 mm
o LL =< 200 mm

Interlocks:

• Boiler protection when two measurements < 200 mm


• Boiler protection / wet boiling guard if two measurements > 750 mm

Connecting circuits:

• LICA-508 Boiler drum level control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 11. (20)

9. PIA502 STEAM DRUM PRESSURE 1

Function:

• Circuit measures boiler drum pressure


• Measurement range 0…30 bar
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 21,5 bar
o HH => 22 bar

Interlocks:

• Boiler protection when two measurements > 22 bar

Connecting circuits:

• PICA-502 Boiler drum pressure control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 12. (20)

10. PIA504 STEAM DRUM PRESSURE 2

Function:

• Circuit measures boiler drum pressure


• Measurement range 0…30 bar
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 21,5 bar
o HH => 22 bar

Interlocks:

• Boiler protection when two measurements > 22 bar

Connecting circuits:

• PICA-502 Boiler drum pressure control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 13. (20)

11. PIA505 STEAM DRUM PRESSURE 3

Function:

• Circuit measures boiler drum pressure


• Measurement range 0…30 bar
• Measurement is in safety related system as 2oo3 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o H => 21,5 bar
o HH => 22 bar

Interlocks:

• Boiler protection when two measurements > 22 bar

Connecting circuits:

• PICA-502 Boiler drum pressure control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 14. (20)

12. PIA701B FURNACE PRESSURE MEASUREMENT

Function:

• Circuit measures boiler furnace pressure


• Measurement range -10…10 mbar
• Measurement is in safety related system as 1oo1 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o HH > - 0,1 mbar
o H > - 0,3 mbar
o L > - 3,0 mbar
o LL > - 5,0 mbar

Interlocks:

• Boiler protection when measurement > 1 mbar over 30 s


• Hysteresis – 0,1 mbar

Connecting circuits:

• PICA-702 Furnace pressure control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 15. (20)

13. PSH701A FURNACE PRESSURE SWITCH

Function:

• Circuit measures boiler combustion chamber pressure


• Pressure switch is in safety related system as 1oo1 locking

Alarms:

• Furnace pressure high

Interlocks:

• Boiler protection when measurement > 1 mbar, 30 seconds

Connecting circuits:

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 16. (20)

14. QIA707 FLUE GAS OXYGEN

Function:

• Circuit measures flue gas oxygen


• Measurement range 0…25 %
• Measurement is in safety related system as 1oo1 locking

Alarms:

• Measuring circuit fault


• Alarm limits:
o L<1%
o LL < 0,7 %

Interlocks:

• Boiler interlocking when measurement is < 0,5 %. Secondary air fan is kept
running.

Connecting circuits:

• QICA-707 Flue gas oxygen control

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 17. (20)

15. SS702 FLUE GAS FAN RUNNING

Function:

• Circuit controls flue gas fan running indication from frequency converter
• Measurement is in safety related system as 1oo1 locking

Alarms:

Interlocks:

• Boiler protection when flue gas fan not running

Connecting circuits:

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 18. (20)

16. SS703 FLUE GAS FAN ROTATION GUARD

Function:

• Circuit controls flue gas fan running with inductive rotation guard
• Measurement is in safety related system as 1oo1 locking

Alarms:

Interlocks:

• Boiler protection when flue gas fan rotation guard not active

Connecting circuits:

Revisions:

9845 CARVIA
KPA Unicon Oy Functional description, SRS 19. (20)

17. DEVICES STOPPED BY BOILER EMERGENCY STOP

TAG Device
171-71-1040 Boiler Silo Feeder 1
171-71-1041 Boiler Silo Feeder 2
171-71-1042 Stoker Screw 1
171-71-1043 Stoker Screw 2
171-71-1039 Grate 1
171-71-1038 Grate 3
171-71-1035 Grate 5
171-71-1036 Grate 7
171-71-1037 Grate 9
171-71-1046 Ash grate
171-71-1044 Ash Scraper
171-71-1201 Primary Air Fan
171-71-1202 Secondary Air Fan
171-71-702 Flue Gas Fan
171-71-704 Recirculation Gas Fan
171-36-710 Electrostatic Precipitator
171-71-708 Wet Ash Conveyor
171-71-709 Wet Ash Container Equalizer
171-71-707 Fly Ash Container Equalizer
171-71-1104 Exhaust Fan 1
171-71-1105 Exhaust Fan 2
171-71-1106 Exhaust Fan 3
171-71-1107 Exhaust Fan 4
171-71-1108 Air Damper 1
171-71-1109 Air Damper 2
171-71-1110 Air Damper 3
171-71-1111 Air Damper 4
171-71-802 Compressor
171-62-1101 Water Heater

18. DEVICES STOPPED BY FUEL HANDLING EMERGENCY


STOP

TAG Device
171-71-945 Push Feeder Hydraulic Pump 1
171-71-946 Push Feeder Hydraulic Pump 2
171-71-917 Levelling Roller
171-71-923 Fuel Conveyor 1
171-71-927 Belt Conveyor
171-71-926 Magnet
171-71-928 Disc Screen 1
171-71-929 Disc Screen 2
171-71-947 Crusher
171-71-930 Fuel Conveyor 2
171-71-1034 Hydraulic Unit for Fuel Silo
Slide Gate

9845 CARVIA
KPA Unicon Oy Functional description, SRS 20. (20)

19. DEVICES STOPPED BY BOILER PROTECTION


INTERLOCKING

TAG Device Boiler protection


171-71-1042 Stoker screw 1 X
171-71-1043 Stoker screw 2 X
171-71-1039 Grate 1 X
171-71-1038 Grate 3 X
171-71-1035 Grate 5 X
171-71-1036 Grate 7 X
171-71-1037 Grate 9 X
171-71-1046 Ash grate X
171-71-1044 Ash Scraper X
171-71-1201 Primary Air Fan X
171-71-1202 Secondary Air Fan X
171-71-704 Recirculation Gas Fan X

In case of flue gas oxygen boiler protection, the secondary air fan is kept running.