Professional Documents
Culture Documents
Hasil Simulasi Off Grid Fix Di Jurnal
Hasil Simulasi Off Grid Fix Di Jurnal
PVsyst TRIAL
Simulation variant :
Simulation parameters
Collector Plane Orientation
kapasitas yg efisien 2 no shading
Simulation date
System type
Tilt
10/01/19 18h55
PV Array Characteristics
PV module Si-poly Model REC 350TP2S 72 XV
PVsyst TRIAL
Original PVsyst database Manufacturer REC
Number of PV modules In series 10 modules In parallel 15 strings
Total number of PV modules Nb. modules 150 Unit Nom. Power 350 Wp
Array global power Nominal (STC) 52.5 kWp At operating cond. 47.8 kWp (50°C)
Array operating characteristics (50°C) U mpp 345 V I mpp 139 A
Total area Module area 301 m² Cell area 265 m²
PVsyst TRIAL
Temperature Fixed (20°C)
Controller Model Conext_MPPT_80_600 - 48V
Manufacturer Schneider Electric Nb. units 15
Technology MPPT converter Temp coeff. -5.0 mV/°C/elem.
Converter Maxi and EURO efficiencies 96.0 / 93.6 %
Battery Management control Threshold commands as Battery voltage
Charging 54.9 / 50.2 V Corresp. SOC 0.91 / 0.75
Discharging 45.5 / 48.9 V Corresp. SOC 0.13 / 0.45
PVsyst TRIAL
Wiring Ohmic Loss Global array res. 42 mOhm Loss Fraction 1.5 % at STC
Serie Diode Loss Voltage Drop 0.7 V Loss Fraction 0.2 % at STC
LID - Light Induced Degradation Loss Fraction 1.5 %
Module Quality Loss Loss Fraction -0.4 %
Module Mismatch Losses Loss Fraction 1.0 % at MPP
Strings Mismatch loss Loss Fraction 0.10 %
Incidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Param. 0.05
PVsyst TRIAL
Battery Pack Nb. of units 144 Voltage / Capacity 48 V / 7200 Ah
User's needs Daily household consumers Constant over the year Global 84.5 MWh/year
Daily household consumers, Constant over the year, average = 232 kWh/day
Annual values
20000
enegy
15000
daily
10000
of
5000
Fraction
0
0 3 6 9 12 15 18 21 24
PVsyst TRIAL
PVsyst TRIAL
PVsyst Evaluation mode
PVSYST V6.77 10/01/19 Page 3/5
PVsyst TRIAL
Battery Pack Nb. of units 144 Voltage / Capacity 48 V / 7200 Ah
User's needs Daily household consumers Constant over the year Global 84.5 MWh/year
PVsyst TRIAL
Normalized productions (per installed kWp):
10
8
Lu : Unused energy (battery full)
Lc : Collection Loss (PV-array losses)
Ls : System losses and battery charging
Nominal power 52.5 kWp
1.21 kWh/kWp/day
1.43 kWh/kWp/day
0.57 kWh/kWp/day
1.2
1.1
1.0
Performance Ratio PR and Solar Fraction SF
0.8
6 0.7
Energy
0.6
4 0.5
Normalized
0.4
0.3
2
0.2
PVsyst TRIAL
0.1
0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
PVsyst TRIAL
August 217.7 224.6 9539 1842 0.000 7180 7180 1.000
September 231.0 230.0 9679 2234 0.000 6948 6948 1.000
October 251.3 240.7 10089 2375 0.000 7180 7180 1.000
November 245.7 227.5 9547 2100 0.000 6948 6948 1.000
December 253.1 230.2 9668 1977 0.000 7180 7180 1.000
Year 2746.8 2700.8 113757 23221 0.000 84534 84534 1.000
PVsyst TRIAL
Battery Pack Nb. of units 144 Voltage / Capacity 48 V / 7200 Ah
User's needs Daily household consumers Constant over the year Global 84.5 MWh/year
+0.4%
-1.5%
-0.5%
Array nominal energy (at STC effic.)
PV loss due to irradiance level
PVsyst TRIAL
Direct use
Missing
3.6%
90536 kWh
Stored
96.4%
-5.1%
0.0%
0.0%
0.0%
Converter Loss during operation (efficiency)
Converter Loss due to power threshold
Converter Loss over nominal conv. voltage
Converter Loss due to voltage threshold
Converter losses (effic, overload)
Battery Storage
energy -0.1% Battery Stored Energy balance
0.0% -5.7% Battery efficiency loss
0.0 kWh
-2.8% Charge/Disch. Current Efficiency Loss
-0.1% Gassing Current (electrolyte dissociation)
-0.1% Battery Self-discharge Current
84534 kWh Energy supplied to the user
PVsyst TRIAL
84534 kWh Energy need of the user (Load)
PVsyst TRIAL
Battery Pack Nb. of units 144 Voltage / Capacity 48 V / 7200 Ah
User's needs Daily household consumers Constant over the year Global 84.5 MWh/year
Investment
PV modules (Pnom = 350 Wp) 150 units 2000000 IDR / unit 300000000 IDR
Supports / Integration 0 IDR / module 0 IDR
Batteries ( 2 V / 1200 Ah) 144 units 8500000 IDR / unit 1224000000 IDR
controller 330000000 IDR
Settings, wiring, ... 45000000 IDR
Substitution underworth 0 IDR
Gross investment (without taxes) 1899000000 IDR
PVsyst TRIAL
Financing
Gross investment (without taxes)
Taxes on investment (VAT)
Gross investment (including VAT)
Subsidies
Net investment (all taxes included)
Rate 10.0 %
1899000000
189900000
2088900000
0
2088900000
IDR
IDR
IDR
IDR
IDR
Annuities ( Loan 5.0 % over 25 years) 148212588 IDR/year
Maintenance 0 IDR/year
insurance, annual taxes 0 IDR/year
Provision for battery replacement (lifetime 5.5 years) 0 IDR/year
Total yearly cost 148212588 IDR/year
PVsyst TRIAL
Energy cost
Used solar energy 84.5 MWh / year
Excess energy (battery full) 23.2 MWh / year
Used energy cost 1753 IDR / kWh
PVsyst TRIAL
PVsyst Evaluation mode