Capacitor Bank Details.

Sr. Description Unit


No.
1 General
Application 5th. And 11th. Harmonic Filter bank /PF Improvement
Capacitors.
Location Out Door
System Specifications
Voltage kV 11 +/- 10%
Frequency Hz. 50 +/- 3%
Ambient Temp.
Max/Min. Deg. C 50/5
2 Capacitor Bank
Harmonic Tuning 5th. Harmonic 11 Harmonic
Rated Voltage ( Installed L-L) kV 14.81 14.94
Output at rated Voltage kVAr 2564 2323.5
Rated Bank Current Amps. 99.95 89.8
Rated Voltage (Effective L-L) kV 11 11
Output at rated voltage kVAr 1414 1260
Type of Connection Double Star Double Star
No. of Units per bank Nos. 6 6
Fundamental Current Amps. 81.34 + 66.08 +
Bank RMS Current (based on H Amps. 83 77.15
Spectrum available)
3 Capacitor Unit
Rated Output kVAr 427 387.25
Rated Voltage kV 8.553 8.626
Rated Current Amps. 49.98 44.89
No. of Bushings Nos. 2 2
Unit Protection Internal fuse Internal Fuse
Losses Watts/kVAr
Di-electric type All Poly Yes Yes
Propylene
Power Frequency withstand kV rms 38 38
voltage
Impulse withstand voltage kV peak 95 95
Permissible Over Load
Voltage % 115 115
Current % 130 130
Discharge device to discharge
Capacitor to 50 Volts in time Volts 50 50
(after disconnection of Power )
Time 300 sec. 300 sec.
Directly connected Internal Required Required
Resistance

Page 1/2
Unit Container Material / CRCA/1.5 mm CRCA/1.5 mm
Thickness
Creepage Distance Mm/kV 31 31
Clearances from
Phase to Phase mm. As per IEC Standard As per IEC Standard
Phase to Ground mm.
No. of Units Nos. 6 6

Existing Reactor Design Details for Information

Reactor
Rated Fundamental Current Amps. 82.5 75.7
Harmonic Current thru Reactor Amps. # #
Inductance mH 12.876 2.724
Inductance Reactance Ohms 4.043 0.855
Max. Permissible Cont. Current % 130 % of Rated RMS 130% of rated RMS

Page 2/2