Fisika Bangunan
Fisika Bangunan
4/21/2018
Miftahurrahma Ridwan
16/394860/TK/44152
Table of contents
Ruangan K1 300 LUX
Ruangan K1 300 LUX
Philips Lighting - TBS463 2xTL5-54W HFP ND AC-MLO (2xTL5-54W/965)................................................................................................... 3
Site 1
Building 1
Storey 1
Room 1
Room summary....................................................................................................................................................................................... 6
Luminaire layout plan.............................................................................................................................................................................. 7
Luminaire parts list.................................................................................................................................................................................. 8
Views....................................................................................................................................................................................................... 9
Workplane 1 / Perpendicular illuminance (adaptive)............................................................................................................................. 11
Page 2
Ruangan K1 300 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS463 2xTL5-54W HFP ND AC-MLO 2xTL5-54W/965 / Philips Lighting - TBS463
2xTL5-54W HFP ND AC-MLO (2xTL5-54W/965)
90° 90°
75° 75°
100
60° 60°
150
250
300
cd/klm η = 61%
C0 - C180 C90 - C270
Page 3
Ruangan K1 300 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS463 2xTL5-54W HFP ND AC-MLO 2xTL5-54W/965 / Philips Lighting - TBS463
2xTL5-54W HFP ND AC-MLO (2xTL5-54W/965)
250
200
150
100
50
E(0°) 6490
1.1 E(C90) 46.5° 1067
0.50 1.1 E(C0) 46.6° 1058
E(0°) 1623
2.1 E(C90) 46.5° 267
1.0 2.1 E(C0) 46.6° 264
E(0°) 721
3.2 E(C90) 46.5° 119
1.5 3.2 E(C0) 46.6° 118
E(0°) 406
4.2 E(C90) 46.5° 67
2.0 4.2 E(C0) 46.6° 66
E(0°) 260
5.3 E(C90) 46.5° 43
2.5 5.3 E(C0) 46.6° 42
E(0°) 180
6.3 E(C90) 46.5° 30
3.0 6.3 E(C0) 46.6° 29
Distance [m] Cone diameter [m] Illuminance [lx]
C0 - C180 (Beam angle: 93.2°)
C90 - C270 (Beam angle: 93.0°)
Page 4
Ruangan K1 300 LUX 4/21/2018
Site 1 / Building 1 / Storey 1 / Philips Lighting TBS463 2xTL5-54W HFP ND AC-MLO 2xTL5-54W/965 / Philips Lighting - TBS463
2xTL5-54W HFP ND AC-MLO (2xTL5-54W/965)
C270 C90
600
C315 C0 C45
cd/m²
g = 65.0° g = 75.0° g = 85.0°
2H 2H 15.1 16.2 15.4 16.4 16.6 15.0 16.0 15.2 16.2 16.5
3H 15.4 16.3 15.7 16.6 16.8 15.3 16.2 15.6 16.5 16.7
4H 15.5 16.4 15.8 16.7 16.9 15.4 16.3 15.7 16.6 16.8
6H 15.6 16.4 16.0 16.7 17.0 15.5 16.4 15.9 16.6 16.9
8H 15.7 16.4 16.0 16.7 17.1 15.6 16.4 15.9 16.7 17.0
12H 15.7 16.4 16.0 16.7 17.1 15.6 16.4 16.0 16.7 17.0
4H 2H 15.2 16.1 15.6 16.4 16.7 15.1 16.0 15.4 16.2 16.5
3H 15.6 16.4 16.0 16.7 17.0 15.5 16.2 15.9 16.6 16.9
4H 15.8 16.5 16.2 16.8 17.2 15.7 16.4 16.1 16.7 17.1
6H 16.0 16.6 16.4 17.0 17.3 16.0 16.5 16.4 16.9 17.3
8H 16.1 16.6 16.5 17.0 17.4 16.1 16.6 16.5 17.0 17.4
12H 16.2 16.6 16.6 17.0 17.5 16.2 16.6 16.6 17.0 17.5
8H 4H 15.9 16.4 16.3 16.8 17.2 15.8 16.3 16.2 16.7 17.1
6H 16.2 16.6 16.6 17.0 17.5 16.1 16.6 16.6 17.0 17.4
8H 16.3 16.7 16.8 17.1 17.6 16.3 16.7 16.8 17.1 17.6
12H 16.5 16.8 16.9 17.2 17.7 16.5 16.8 17.0 17.3 17.8
12H 4H 15.9 16.3 16.3 16.7 17.2 15.8 16.2 16.2 16.7 17.1
6H 16.2 16.6 16.7 17.0 17.5 16.2 16.5 16.6 17.0 17.4
8H 16.4 16.7 16.9 17.2 17.7 16.4 16.7 16.9 17.1 17.6
Variation of the observer position for the luminaire distances S
S = 1.0H +0.8 / -1.2 +0.9 / -1.1
S = 1.5H +2.0 / -2.1 +1.6 / -2.0
S = 2.0H +3.5 / -2.8 +2.9 / -2.6
The UGR values are calculated in acc. with CIE Publ. 117. Spacing-
to-height ratio = 0.25
Page 5
Ruangan K1 300 LUX 4/21/2018
Room 1
Clearance height: 3.100 m to 3.500 m, Reflection factors: Ceiling 70.0%, Walls 42.8%, Floor 75.6%, Light loss factor: 0.80
Workplane
Surface Result Average (Target) Min Max Min/average Min/max
1 Workplane 1 Perpendicular illuminance (adaptive) [lx] 311 (≥ 300) 0.59 389 0.00 0.00
Height: 0.800 m, Wall zone: 0.000 m
Lighting power density: 11.38 W/m² = 3.66 W/m²/100 lx (Floor area of room 207.36 m²)
The energy consumption quantities refer to the lights planned for the room without taking into account light scenes and their dimming levels.
Consumption: 2850 - 4550 kWh/a of maximum 7300 kWh/a
Page 6
Ruangan K1 300 LUX 4/21/2018
Room 1
Page 7
Ruangan K1 300 LUX 4/21/2018
Room 1
# Luminaire Φ(Luminaire) [lm] Power [W] Luminous efficacy [lm/W]
Page 8
Ruangan K1 300 LUX 4/21/2018
Room 1
Storey 1 (26)
Storey 1 (27)
Page 9
Ruangan K1 300 LUX 4/21/2018
Storey 1 (28)
Storey 1 (29)
Page 10
Ruangan K1 300 LUX 4/21/2018
Page 11
Ruangan K1 300 LUX 4/21/2018
Isolines [lx]
Scale: 1 : 100
Page 12
Ruangan K1 300 LUX 4/21/2018
Scale: 1 : 100
Page 13
Ruangan K1 300 LUX 4/21/2018
Scale: 1 : 100
Page 14
Alasan Pemilihan Lampu :
Pemilihan lampu lighting dengan merk Philips Lighting TBS463 untuk digunakan pada ruangan K1
300 LUX adalah penyebaran cahaya yang merata dan dinamis yang cocok digunakan pada
ruangan kerja didalam ruangan serta arah pencahayaan tepi-ke-tepi yang stabil dan homogen
menimbulkan kesan kecerahan yang nyaman. Lampu dengan jenis ini juga didukung dengan
teknologi ActiLume dan Luxsense yang dapat menekan biaya secara keseluruhan dan mengurangi
konsumsi energi khususnya pada siang hari apabila lampu dibutuhkan untuk menyala pada siang
hari.