You are on page 1of 7

17th Mediterranean Conference on Control & Automation

Makedonia Palace, Thessaloniki, Greece


June 24 - 26, 2009

A DCS Supervisory Control of a Centrifugal


Compessor for Oxygen Consumption Optimization
Silvia Maria Zanoli
Luca Barboni
D.I.I.G.A
affidabilità automazioni- I&C
Università Politecnica delle Marche
api raffineria di Ancona
Via Brecce Bianche, Ancona, Italy
Falconara , Ancona, Italy
s.zanoli@univpm.it
L.Barboni@apioil.com

Abstract—In this paper, a supervisory control system for syngas.


flue
gases steam
oxygen consumption optimization on a Syngas GT HRSG ST
Manufacturing Process Plant is proposed. A grey-box Heat Recovery Steam Turbine
Gas Turbine
Steam Generator
multivariable parametric identification of the oxygen fuel-oil
compressor system is first performed. Consequently, by
means of dynamic simulations the structure of an optimal electric electric
power power
control system has been determined, also reflecting the
implementation constraints linked with the use of a DCS. syngas
Finally, operating results of the system implemented on the ASG
fuel-gas Steam to
real process are shown which confirmed the expected results Auxiliary Steam
plants
obtained by simulations. Generator
diesel-oil
Keywords- Supervisory control, parametric identification, Figure 1. Schematic representation of a combined cycle power plant
relative gain array (RGA), antisurge control system, DCS.

I. INTRODUCTION This Unit is located in the Syngas Manufacturing


Process Plant (SMPP) of the IGCC plant and it is designed
The IGCC plant (Integrated Gasification Combined to produce a total of about 1800 tons per day of oxygen at
Cycle) located in the industrial area of api Refinery of 95% mol of purity, upon the project conditions.
Ancona (ITALY) is devoted to the production of electric Furthermore the ASU produces high pressure nitrogen for
power by using the heavy residues (TAR) coming from the syngas dilution to the Gas Turbine (GT), low pressure
low pressure plants of the oil refinery. The combined cycle nitrogen for utility uses, instrument air, and service air.
plants, like the IGCC, enable for the thermal energy
recovery by re-using it for other industrial processes, such In this paper, a supervisory control system for the
as the steam production. In order to enhance the efficiency oxygen consumption optimization is presented. The
level and the profitability of oil refineries as well as the proposed scheme aims at achieving economic advantages
commitment to meet precise production standards, an especially preventing the continuous waste of oxygen
increasing level of system automation ([1], [2], [3], [4]) is actually sent in the atmosphere in considerable quantities,
required. Furthermore, the existence of rigorous as well as limiting continuous wear of the vent valve.
environmental standards together with the need to operate Furthermore by replacing manual operations on valves by
in high safety conditions contribute to the implementation automatic controllers the energy consumption is optimized.
of automatic systems of rising complexity.
II. ACTUAL PROCESS CONTROL SYSTEM
In the plant considered in the present study, depicted in In the following, the processes central to the
Fig. 1, the production of electric power (300 MW) functioning of the centrifugal compressor (Base Load
basically depends on the performances of a Gas Turbine Oxygen Compressor, BLOC CM-8903) are described
(GT), specifically planned for the combustion of a syngas, together with its actual control system (see Fig. 2). The
and of a Steam Turbine (ST). The input steam is generated gaseous oxygen coming out of the exchanger (E-8912) is
through a Heat Recovery Steam Generator (HRSG) by sent to the suction regulating valve PV-89607 of the
using the thermal energy contained in the GT flue gases. compressor through the pump P-8903A (acting on the
Part of the steam generated by HRSG unit is sent to the liquid phase). Under normal running conditions the suction
plants and, in order to face up additional steam requests, pressure control is automatically handled by the controller
the IGCC has also been provided with an Auxiliary Steam PC-89250, which acts on the valve LV-89250, located on
Generator (ASG). the cryogenic pump P-8903A discharge (therefore
In order to minimise the pollution’s emissions, the Gas operating on liquid oxygen).
Turbine, charge consists in a syngas generated by the The suction valve of the compressor PV-89607 has
heavy residues cracking process, called gasification been designed to protect the compressor from over-
(aprox. 60 t/h). The flow of high pressure oxygen (aprox pressures, and the controller PC-89607 has a set-point
72 bar gauge) is sent to the gasification plant by a which is normally higher than the working discharge
centrifugal compressor, which is fed by low pressure pressure of the compressor.
oxygen (aprox. 7.5 bar gauce) coming from an Air
Separation Unit (ASU).

978-1-4244-4685-8/09/$25.00 ©2009 IEEE 1196


.

Figure 2. Actual control system for the BLOC centrifugal compressor

The BLOC recirculation system aims at controlling the elimination of oxygen waste sent to the atmosphere)
compressor load in case of low capacity operation so as to together with the minimization of the recycle valve
avoid surge conditions [5]. The high-pass selector (in the UV_89610 opening (which will be kept as long as possible
local panel of BLOC control) selects the highest signal closed, but used to assure the compressor working point at
between the PC-89610 controller (in DCS) and the anti- a safe distance from its surge condition), with a consequent
surge controller (UC-89610). The set point of the BLOC energy saving.
discharge pressure (PC-89616) is normally equal to the
pressure required by the facilities (aprox. 72 bar gauge). In the realization of the controller special care should
The implementation of the control is given, as from the be given to some process constraints. In particular, low
design, to the vent valve PV-89616. differential pressure on the cryogenic pump P-8903 should
be avoided in order to prevent emergency shut down
The controller PDC-89316 for the differential pressure situations. In addition, as previously stated it should be
of cryogenic pumps, and the controller FC-89650 (flow of avoided to move the compressor working point in
gaseous oxygen from the “main condenser” of the ASU), proximity of its surge conditions. Finally, interaction
are used during the start-up, with the centrifugal between the PCA_89250 and PC_89610A controllers
compressor CM-8903 turned off) to gradually increase the should be limited so as to minimise disturbances on the
load of the ASU plant during the start-up operations. line between the exchanger E-8912 and the compressor
suction.
The oxygen compressed by BLOC is sent to two
gasification reactors which regulate the flow fed through A. Low differential pressure constraints analysis
the valves FV-80023 and FV-80123, according to a typical The limit conditions for the pump P-8903 according to
lead-lag logic for the control of combustion ratios (Cross the processed flow have been verified through a test. The
Linked Ratios, CLR). The value of heavy oil flow being target was therefore to verify the maximum opening for the
processed is set by the operator according to the valve LV_89250 and the maximum flow so as to enable
percentage of maximum flow (33 t/h per each reactor) the reduction of the suction to pumps P-8903.
through two manually operated stations (HC-80021, HC-
80121). The valve LV_89250 has been opened by way of the
manual mode controller with consecutive 1–2% increases
The control system of the discharge pressure CM-8903 until a maximum opening of 66.5% has been reached, in
through the vent PV_89616, even by guaranteeing good order to detect the pressure increase of gaseous oxygen
performances as for the set point tracking terms and of the according to the valve opening, under conditions of
decoupling action with the upstream plant, certainly constant flow (57.5 t/h).
presents substantial economic disadvantages, such as the
continuous wear of the vent valve (subject to differential Subsequently, under automatic pressure control (set-
pressures of 72 bar) and, primarily, the continuous waste point = 8.5 barg), the oxygen flow has been increased
of oxygen sent to the atmosphere. Furthermore, the manual beyond NOC flow of the plant (66.9 t/h). The differential
control of the valve UV_89610 to adjust the machine at pressure on the pump has not gone through substantial
every change of its working point does not satisfy the decreases (-0.2 bar) and the trip of P-8903 has not been
economic target to limit the compressor energy risked (differential pressure of trip = 4 bar).
consumptions. The test results thus gave positive response about the
III. THE NEW CONTROL SYSTEM DESIGN SETTINGS AND opportunity to use the valve LV_89250 as an actuator,
CONSTRAINTS
without running the risk of oxygen pump trip.
The new control logic has therefore to ensure a stable For safety reasons, within the monitoring control
control of the discharge pressure of the compressor CM- diagram a logic of self-deactivation has been considered in
8903. This should guarantee the possibility to keep the the event of low differential pressure on the pump together
vent PV_89616 closed (less wear of the valve and with correlated visual and audio alarm for the operator.

1197
B. Compressor surge B. Valve PV_890607 modelling
The set-point for the suction pressure of the The computed parametric identification previously
compressor CM-8903 is normally fixed so as to guarantee made was based on sampled process data which not
the energy optimisation of the machine. The constraint included the action of the valve PV_89607 the reason
which determines the lower allowed suction pressure that being that historical functioning data were not available
guaranties a correct machine performance is related to the for such an actuator (normally used only in the short start-
characteristic curves of the machine and to the antisurge up transients, which is not the subject of this study). To
control system. In practice such a control system for the include this action effects, we built the mathematical
protection of the compressor from surge starts to open the model of the valve based on the functioning equations of
recycle valve in order to guarantee the minimum such an actuator.
acceptable flow, as soon as the compression ratio
overcomes the given threshold. Such a threshold has been An interpolation of the valve characteristic curve,
chosen so as to have a minimum distance from the surge function of the valve opening variable x, has been obtained
under the most unfavourable temperature conditions. minimizing the square deviation between the points of the
characteristic curve and the following sigmoidal
C. Interaction and variables selection approximation function:
The attempts experienced in the past, aiming at K
 CˆV   
controlling the discharge pressure PT_89607, had
alternatively involved the compressor suction valve 1  e    x  x0 

PV_89607 (16’ butterfly valve) and the recycle Considering the definition of the flow coefficient CV of
UV_89610. Even though in the literature [5], [6], [7] the a valve the following equation can be written [6]:
compressor suction valve is typically used to control
discharge pressure, the results obtained through PV_89607  p  
had never been satisfactory. Furthermore, since it was not  CV  Q   0    
possible to achieve a suction oxygen storage on the line  p  0 
from E-8912 to the CM-8903 suction, the line pressure in which Q is the fluid flow measured in [U.S. gal/min],
regulation had to be carried out through the LV_89250 (4’ p0 and p are the reference and operative differential
globe) valve, acting on the liquid oxygen located upstream pressure in [lb/in2] and 0 and  are the reference and
the evaporator. operative fluid density expressed in [lb/ft3]. From (1) and
As often happens when different control loops are (2) it is possible to write the equation of the mass flow
within the same process, the question arises upon which such as
variable should be manipulated by each controller.
q m  k  CV  x    P , T   p t/h 
Therefore, as explained in the next section, proper   
techniques [7], [8], [9] have been adopted in order to select
manipulated variable /controlled variable pairs which where k is a coefficient which takes into consideration of
guaranties a more efficient control action. Then, before the measurement units and the constants introduced in the
proceeding with the tests on the real system, different previous formula.
control schemes have been simulated, by using from time As, for the considered application, in the typical
to time different pairings among the various actuators, i.e. functioning range of the valve (0.016 bar) and for flow
the manipulated variables, and the variables to be ranging from 55t/h to 70t/h, the differential pressure is
controlled. rather constant, it was possible to draw a square function
between the upstream pressure of the PV_89607 and flow,
IV. MODELS IDENTIFICATION depending in a non linear way also by the valve opening.
A. “Grey-box” parametric models  
Pupstream  f qm2 , x   
By starting from simplified physical laws, which are
known except for a certain number of parameters, it has From (4), new transfer functions of PV_89607 on the
been chosen to model the process by using a “grey-box” suction pressure and on the compressor discharge pressure
parametric identification technique [10], [11]. That is, the have been deduced, within the linear model previously
identification of the transfer functions has been carried out identified. As a matter of fact, by starting from the
without considering the physical system under knowledge of suction pressure variations and of the
examination as a pure “black box”, but all the known compressor flow, the contribution of the valve PV_89607
notions on the process physics under examination have on the discharge pressure was always assessable.
been utilised, limiting the identification procedure the C. Variables selection
unknown parameters.
The problem of variables selection consists in solving
The obtained results have confirmed the initial choice two important questions such as the choice of the
of a single pole and the dead time transfer functions, in manipulable variable which has greater influence on the
which the quoted parameters and the gain constituted the variable to be controlled and the minimization of
unknown variables to estimate. interaction phenomena. The target is therefore to select
By starting from the prior knowledge of the system, it manipulated variable /controlled variable (MV/CV) pairs
has been decided to use the MISO output error models, in which make the automatic control more efficient, by
order to focus the identification on the deterministic considering the interactions of each manipulated variable
transfer functions, by treating as white noise the part of with each controlled variable. Very often techniques of this
non-modelled dynamics that, in the present case, is kind are based on the knowledge of static gains matrix of
reasonably restricted [11], [12], [13]. the process model. Nevertheless, also with a correct

1198
selection of variables, it can be necessary to carry out a TABLE I. PERFORMACES OF MANUAL VS AUTOMATIC CONTROL FOR
THE COMPRESSOR DISCHARGE PRESSURE
subsequent calibration of control parameters and, if
necessary, to insert also decouplers within the control
system [7], [8], [14].
In the multivariable system being examined, in order to
find the best pairing between the control valves and the
pressure to be controlled (compressor suction and
discharge) the procedure known in literature as the
Relative Gain Array (RGA) has been adopted [7], [8], [9].
This procedure is based on the building of a matrix of the
relative gains Λ and its use to decide the pairings MV/CV. functional through parameters manipulation of the various
Here below the obtained Λ matrixes are reported: feedback and feedforward controllers, with non-linear least
squares and non-linear simplex types algorithms, so to
RGA1 LV-89250 LV-89610 avoid stopping on local minimums of the J functional
Psuction 0.35 0.65
during the training phase (“suboptimal solutions”).
Pdischarge 0.65 0.35
RGA2 LV-89250 PV-89607 In order to make the training of control logic more
Psuction 0.2445 0.7555 efficient, within the training epoch different simulated
Pdischarge 0.7555 0.2445 disturbances following typical load variations of the
downstream process (load percentage of gasifiers) and set-
From the analysis of the results, it can be deduced that point variations of controllers have been introduced.
the best pairing between MVs and CVs is the one that Obviously the goodness of the tuning of the control system
associates the valve LV-89250 with the discharge pressure. resulted to be connected with the predictive capacities of
From the control viewpoint then, the suction pressure the identified model, as well as by the quantity of
could be manipulated both through the recycle valve UV- information contained in the training signals.
89610 and through the PV-89607.
Here it is worth underlining that, although the problem
The conclusions reached with the RGA method are in of local minimums was present and the lack of
perfectly agreement with what is commonly known in information on all the possible cases of disturbances, the
literature [7]: compressor flow and the compressor method proved to be efficient from the operating
discharge pressure control normally take place with the viewpoint and enabled to realize the “tuning” of logics
valve having a higher differential pressure, that is to say having also dozen of different parameters.
the valve LV-89250 (design Δp = 0.30 bar, line size 4’’),
whereas the suction pressure control takes place with the V. SIMULATION RESULTS
valve having lower differential pressure, that is to say the
PV-89607 (design Δp = 0.02 bar, line size 16’’) or the Once the goodness of the model was assessed by using
recycle valve UV_89610. the classical cross-validation methods [10], [11],
simulations of the different control diagrams have been
Furthermore, the dynamic simulations being carried carried out in order to assess the performances in terms of
out and the later tests performed on the plant, as it will be control error and robustness, in face of the same
shown, have confirmed the conclusions drawn in this disturbances intentionally introduced on the system.
paragraph.
The final adopted scheme, shown in Fig. 4, entails the
D. Development of an “optimal” autotuning technique following pairing between manipulated variables and
Before implementing the control logic on DCS, controlled ones.
different control solutions have been simulated on the LV_89250 ↔ PT_89607 (discharge)
realized model, by trying to quantify the diversity of
PV_89607↔ PT_89607 (only protection for high
performances among the various possible MV/CV
discharge pressures, as from original
pairings. design)
In order to assess the goodness of the designed control UV_89610 ↔ PT_89603 (suction)
structures, independently of the parametrization of the
control diagram (consisting in the gains and in the time In table 1 the control results obtained in simulation for
constants of feedback PID controllers, of feedforward the compressor discharge pressure are reported,
lead/lag controllers and of decouplers), an “optimal” compared with the ones obtained in practice by an expert
tuning technique has been developed. operator through manual control. The sampling period
used TS = 1s; the term IAE stands for the integral of
The idea consists in finding the tuning parameters of absolute values of the error in the period being examined.
the entire control diagram minimizing a penalty function
similar to the one used for LQG optimal control. The Fig. 3 shows the simulated trends of the discharge
chosen functional J accounts for both the control error and pressure and of the suction pressure (blue) as opposed to
the control effort: i f the respective imposed set-points (green), and the
predicted positions for the valves LV_89250 and


  
min J  min  e T i   Q  e i   u T i   R  u i  

 PV_89607, considering the disturbances introduced
if i i0 through load variations of gasifiers.
 
 min q1  eP2m i  q2  eP2a i  r1  uP2m i  r2  uP2a i
It is worth pointing out that the introduced disturbances
ii0
Every control logic has been trained over numerous correspond to real load variations occurred in a time
epochs by trying to minimize the above-described window of about 8 hours. The tuning parameters of

1199
  .

Figure 3. Simulation results


the diagram have been obtained with the autotuning
technique previously described.
The adopted control scheme (see Fig. 4) is Figure 5. SP (violet) and PV (yellow) of the discharge pressure “Pm”,
characterized by the compressor suction pressure set-point SP (violet) and PV (yellow) of the suction pressure “Pa”,
manipulation through the combined action of two
contributions: a feedforward controller for the pressure to CM-8903, a partially decoupling [7] controller
compensation of disturbances introduced on the system by has been introduced on the set-point of PCA_89250 in
set point load variations of the two downstream gasifiers order to decrease the interaction effects between the two
and a feedback controller of PID type (PC_89608) or the control loops.
compensation of any other disturbance derived both by
inaccuracies in the identified model dynamics, (used for Assuming the remote set-point (RSP) of PCA_89250 (u1)
the calculation of the feedforward compensator) and by and the position of the recycle UV_89250 (u2) as inputs,
any other unmeasured disturbance acting on the system. and the PT_89603 (y2) and PT_89607 (y1) as outputs, the
process to be examined can be described by a 2x2 transfer
The feedforward control is largely applied in the field matrix P(s).
of chemical engineering, allowing substantial increases of
the control capacity, especially when facing, as in the case Since the adopted feedback control structure, in most
under examination, with a non-linear process with a slow of the industrial processes, uses conventional SISO
dynamics [7], [8], but known through a parametric controllers, the control matrix GC(s) results diagonal.
identification. Indicating with GC1(s) and GC2(s) the two elements in
The controller PC_89610 acts on the suction pressure the diagonal, the modes of the closed loop system will be
PT_89603, according to a (valve) position control scheme related to the solution of the following characteristic
[7], [8], applied in this case to the set-point of the suction equation:
pressure (PCA_89250 controlling PT_89603).
1  GC1 ( s )  P11 ( s )   1  GC 2 ( s )  P22 ( s )  
A. Decoupler  
  GC1 ( s )  P12 ( s )    GC 2 ( s )  P21 ( s )   0
Since both the recycle valve UV_89610 and the suction
pressure PT_89603 have an influence on the discharge

Figure 4. Proposed control system for the BLOC centrifugal compressor

1200
It is clear that the closed-loop poles of the whole .
system tend to overlap with the ones of the two SISO
loops, if the second term of the algebraical sum tends to
cancel out. The choice carried out through the RGA
analysis [7], [8] tries to minimize the undesired
consequence of closed-loop poles displacement as an
effect of the “mixed” terms. In order to cancel out
completely this pairing term, it has nevertheless been
considered the insertion of a partial decoupler with the
purpose of cancelling out one of the undesired factors of
the product in “mixed” terms, simply calculated as a single
feedforward on the variable which manipulates the slowest
and most critical control variable, that is to say on the
remote set-point of PCA_89250.
The calculation of the controller parameters has
followed standard forward control techniques, and usual
considerations concerning the physical feasibility hold. In
the case under examination:
P12 s  
GDECOUPLER s    
 P11 s 
Figure 6. Comparison between the measured and the predicted
As it can be seen in Fig. 5, on a load increase of +0.5% variables trends
for each gasification train, the logic immediately increases 3. the use of the valve PV_89607 to control the
the RSP of PCA_89250 (Fig. 5b, green line). The
discharge pressure CM-8903 has also introduced
PCA_89250 controller starts opening the valve LV_89250
dangerous transients on the upstream system
and the suction pressure tends to increase. At the same
time the PC_89610A controller on the recycle detects the pressure, controlled by LV_89250. In particular,
suction pressure increase (its PV), and, as a consequence, if the system operates at higher pressures of the
it starts to close the UV_89610 valve (Fig. 5d), by upstream system, there would be the risk, during
transferring the action of the suction pressure on the the transients, of reaching the maximum
recycle valve. The latest trend represents the rate of allowable pressure threshold with the subsequent
performance of the compression ratio of CM-8903 during activation of the protection systems.
this transient. A limitation for the control effort amplitude 4. in order to optimise the downstream system and
of PC_89608 acting on SP of the suction pressure has been
to keep the recycle as close as possible, a revision
foreseen, in order to minimize the “controlled”
of process operating parameters would be needed
disturbances introduced on the suction pressure; such
variations are anyway replaced by a new position of the (in particular, it would be necessary to increase
compressor recycle at steady state conditions. the upstream pressure), with a consequent higher
energy dissipation from the upstream system.
What has been explained can be well interpreted by
referring to the typical curves of flow/pressure of the From the above-mentioned motivations, the use of the
compressor considering the working point shift caused valve PV_89607 has not been regarded economically
by suction pressure variations and the recycle valve profitable(which would introduce further pressure drops)
position, in order to compensate a disturbance inducing for the control of the discharge pressure.
minor pressure drops on the downstream circuit Analogous attempts have been carried out by using the
(decreasing of flow fed to the two gasifiers and consequent recycle valve of the compressor UV_89610 for the control
closing of the valves FV_80023 and FV_80123). of the discharge pressure PT_89607. Also in this case the
B. Discussion problems pointed out have been the energy non-
optimisation and the interaction with the controllers of the
The tests carried out by using the valve LV_89250 to upstream system.
control the suction pressure and the valve PV_89607 to
control the discharge pressure, have confirmed the
VI. OPERATIONAL RESULTS
theoretical aspects previously quoted; after all, the
following conclusions have been highlighted: After the simulation phase tests, the controller has been
implemented at the DCS. Figure 6 shows the system
1. with the normal operating pressures of the plant, performances with the new supervisory control relating to
the valve PV_89607 has not shown an acceptable a running period of about 12 hours outlighting a good
discharge pressure CM-8903 regulating capacity. match between the real trends (red line) with the simulated
2. To bring the valve to work to lower openings (in ones (blue), referred to the same process conditions. The
order to bring higher differential pressures on the trends in Fig. 6a represent the rate of performance of the
discharge pressure (blue for simulation data, red for
valve, and therefore a higher regulating capacity),
measured data) according to the load variations on the two
an automatic control on the compressor recycle gasification trains (see Fig. 6e). Fig. 6b represent the
would be needed (unforeseen in the original diagram of the suction pressure reaching the compressor:
logic) to avoid, in case of excessive closings of in green the set-point used as a manipulated variable for
PV_89607, the operation of the antisurge system. the control of the discharge pressure, in blue the simulation
and in red the measured values. The trend values of valves

1201
LV_89250 and UV_89610 are shown in the following consequent economic improvements deriving from the
Fig.6c and 6d (green for simulation , red for measured following reasons:
values), finally Fig. 6f represents the trend of the a. possibility to keep the vent PV_89616 closed (less
compression ratio of the compressor. wear of the valve and elimination of oxygen waste sent to
Comparing the experimental results on the real system the atmosphere)
with the prediction of the two controlled variables based b. possibility to optimize recycle valve opening
on the proposed model, it can be stated that a good UV_89610 (which will stay as long as possible closed, but
matching level has been achieved and that the controller is without bringing the compressor to the surge state), with a
expected to fulfill the assigned targets. Besides, from the consequent energy saving
analysis of the results it can be stated that the opening of
the valve LV_89250 has been precisely predicted as well, c. possibility of a controlled operation at a lower
whereas there are problems in the estimation of the recycle suction pressure, with a consequent energy saving
valve conditions. This is fundamentally linked to the fact d. realization, together with the other supervisory
that the working point of the UV_89610 for the identified control systems of ASU, of an “avalanche effect” on the
model was far from the conditions of this validation. It energy optimization, since the oxygen consumption is
should be note d that the measured signal and the linked with the processed charge of the whole plant, which
simulated one roughly possess the same first derivative. in this case is exclusively linked to the consumptions
requested by the two gasifiers.
Prediction Real
IAE 6599 7080 e. probable lower wear of the refractory and of the
< err [%] > 0.2214 0.2375 feed injectors, thanks to a more stable pressure
err max [%] 0.9969 1.3194 f. its “robust” behaviour, both in terms of its
< err [bar] > 0.1594 0.1710
disturbances rejection capacity and in terms of “bad-
err max [bar] 0.7178 0.9500
samples 41400 41400
quality control”, it is useful for the DCS operator as with
other supervisory logics of the ASU.
Although the disturbances inserted in the system Besides, the controller meets the required process
during the final test have been higher in both frequency constraints avoiding the emergency shutdown of the
and intensity than in all the simulations tests, the control cryogenic pump due to a low differential pressure as well
system was always able to compensate by reaching at the as limiting the problems of interaction between the
latest 0.95 bar of error during transients, with a load PC_89250 and PC_89610A controllers therefore
variation of –5% for each gasifier. As a consequence of the minimizing disturbances on the line between the
above load decreases and in relation to the behavior of exchanger unit and the suction compressor. The activation
other supervisory controllers acting on the ASU, the load of the antisurge logic is also avoided in practice, thus
to the other compressors is also reduced (in particular to adding more efficiency to the whole system.
the BLOC centrifugal compressor), by allowing a “domino
effect” on the energy saving. REFERENCES
To safeguard the reliability of the productive process
various conditions of “bad quality” have been [1] M.J.Piovoso, Industrial Process Control, IEEE Control Systems
Magazine, June, 2000, pp. 22-24.
contemplated on which occurrences the plant is
[2] D.E Seborg., A perspective on Advanced Strategies for Process
automatically and in a “bumpless” way switched back to Control, Proc. European Control Conference, Karlsruhe, Germany.
the originally designed strategy control. The planned 1999
control system also contemplates different conditions of [3] S.M. Zanoli, L. Barboni, T. Leo, “Hybrid model of a gasification
“bad quality” to safeguard the reliability of the productive plant”, IFAC Praha, 2005
process, and considering these conditions the plant can [4] S.M. Zanoli, L. Barboni., T. Leo, “An application of hybrid
automatically and in a “bumpless” way return under the automata for the MIMO model identification of a gasification
strategy of design control. plant”, IEEE Conf. On System, Man and Cybernetics (SMC07), pp.
1427-1432, October 07-10, Montreal, Canada, 2007.
In particular, the present supervisory control system [5] R. Della Volpe, “Macchine” – Liguori Editore – 2002
stays active until: the pumps P-8903 run and are not at [6] P. Smith, R. W. Zappe, “Valve Selection Handbook” – Elsevier –
maximum load; the discharge pressure PT_89607 is under 2004
control (inhibition of supervisory control for high absolute [7] F. G. Shinskey, “Process Control Systems” – Mc Graw Hill – 1996
value of the derivative of the discharge pressure); the vent [8] W. L. Luyben, M. L. Luyben, “Essentials of Process Control” – Mc
valve PV_89616 in the compressor discharge is closed; the Graw Hill – 1997
butterfly valve PV_89607 is open at more than 85%; the [9] E. H. Bristol,, “On a New Measure of Interaction for Multivariable
gasification reactors run; the compressor CM-8903 runs; Process Control”, IEEE Trans. Autom. Control, Gen. 1966
the compressor CM-8903 is not under surge conditions. [10] S. Bittanti, “Identificazione dei Modelli e Controllo Adattativo” –
Whenever a single of these conditions is not satisfied, the Pitagora Editrice Bologna – 1997.
present supervisory control system is shutted down. [11] L. Ljung, “System Identification - Theory for the User” – Prentice-
Hall – 1987.
[12] Y. Zhu, T. Backx, “Identification of Multivariable Industrial
VII. CONCLUSIONS Processes for Simulation, Diagnosis and Control” – Springer -
If from the methodological point of view the Verlag – 1993.
importance of the modelling and simulation approach in [13] Y. Zhu, “Increase MPC Project Efficiency by using a Modern
the solution of complex control problems is reinstated, Identification Method” – ERTC Computing, Paris, France – 2001.
from the operating point of view the new supervisory [14] Z. X. Zhu, "Variable pairing selection based on individual and
overall interaction measure," Industrial Engineering Chemical
control logic was able to ensures a stable control of the Research, vol. 35, pp 4091-4099, 1997
discharge pressure to the compressor CM-8903, with

1202

You might also like