Professional Documents
Culture Documents
1 Z S E 2 75 0 -10 5 E N , R E V. 9
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents – in whole or in parts – is forbidden
without prior written consent of ABB.
—
Table of contents
Design 5
GOE features 6
GOE(2) features 6
Features and benefits 7
Shed profile 7
Testing 8
Test tap 8
Test tap adapter 8
Oil sampling valve 8
Dimensions and data 9
Type designation 9
Rating plate example 9
GOE 250-210 to GOE 950-650 10
GOE 1050-750 to GOE 1800-1360 12
GOE 2550 14
GOE 2600 15
GOE(2) 16
Current capacity 18
Short-time current 18
Overload capacity of bushings 18
Connection details 19
Draw rod system 19
Draw lead system, GOE 21
Draw lead system, GOE(2) 21
Fixed bottom contact 22
Outer terminal 22
End-shields 23
Ordering particulars 26
Packing 27
Additional GOE and GOE(2) bushings 28
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 5
—
Design
The GOE bushing is available in two designs: GOE and For GOE 250 to 900 the top housing is equipped with two oil
GOE(2). The bushing is built up around a centre tube on level gauges of prism type. For GOE 1050 and larger, the top
which the condenser core is wound. For bushings up to housing is equipped with a magnetic oil level indicator.
550 kV paper of full width is employed. Bushings for higher
voltages are wound from paper strips in a manner similar to The mounting flange is an aluminium alloy casting. The
that used for cables. The foils are located so that the best gasket surface is machined flat. On the flange there is a test
possible combination of external flashover and internal tap. This tap is automatically earthed by a protective cap
puncture strength is achieved. when the tap is not connected to external test or measuring
circuits. The mounting flange and the top housing are shot
The upper insulator, which is made in one piece without blasted to obtain a thoroughly smooth surface finish. The
gaskets, the lower insulator and the mounting flange are mounting flange can be equipped with extensions on the oil
held between the end plates by the centre tube and sealing side, providing space for current transformers.
is accomplished by oil-resistant rubber gaskets in grooves.
The upper insulator is made of high quality electrical
porcelain. Standard color is brown. Light grey porcelain is
available on request.
1
15
1 2 2
3 4
5
4
5 6
6 8
1. Top end nut
2. Sealing plug 7
3. Flexible connection
4. Top housing 8
5. Oil level gauge
6. Porcelain insulator,
air side 9 9
7. Pre-stressed tubes
8. Transformer oil
9. Condenser core
10. Clamping ring
11. Mounting flange
12. Extension for current 10
transformer
13. Porcelain insulator, 16
oil side
14. Bottom end nut 11
15. Set of springs
16. Cemented flange 12
11
13 12
13
14
14
— —
01 Transformer bushing type GOE. 02 Transformer bushing type GOE(2).
6 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
years.
• Our unique draw rod system facilitates easy field
installation and removal without lowering the oil level.
R7 R5.5
• The worlds most used 800 kV bushing. Never any failures
in the field.
R9
• 3D models makes it easy to incorporate the bushing in its
18°
context. 27
12°
• We use a sealing system proven since 40 years around the
R7 65
world. R9.5 R5.5
• Our test criteria and margins exceeding international 18°
12°
standards.
• Only extra long creepage shed profile.
—
03 Shed profile, GOE.
Shed profile
The shed profile for all GOE bushings is of the alternating
type, with alternating long and short sheds. 66
51
GOE
The shed profile is designed according to IEC 60815. For R10
each pair of sheds, the ratio between nominal creepage
distance and the axial length is 4.0. This shed profile is R8
developed and tested specially for heavy pollution.
R10
GOE(2) 18° 31
10°
The shed profile is designed according to IEC 60815. For 70
each pair of sheds, the ratio between nominal creepage R8
R4.5
distance and the axial length is 3.94. 18°
10°
R4.5
—
04 Shed profile, GOE(2)
Application: Transformers
Classification: Oil impregnated paper, capacitance graded, outdoor-immersed bushing
Ambient temperature: +40 to -40 °C, minimum value as per temperature class 2 of IEC 60137.
Altitude of site: < 1 000 m
Level of rain and humidity: 1-2 mm rain/min horizontally and vertically, as per IEC 60060-1
Pollution level: According to specified creepage distance and IEC 60815
Type of immersion medium: Transformer oil. Maximum daily mean oil temperature 90 °C. Maximum temporary oil temperature 115 °C
Oil level below bushing flange: Maximum 30 mm
Max. pressure of medium: 100 kPa overpressure
Markings: Conforming to IEC/ IEEE
8 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
—
Testing
During manufacture and on completion the bushing is Requirements for tan d are max. 0.55 % for Um ≤ 362 kV, max.
subjected to a number of routine tests, according to 0.5 % for Um between 362 and 550 kV and max. 0.4% for
IEC 60137 and IEEE bushing standards. However, ABB’s Um > 550 kV. These measurements are carried out at the
requirements for acceptance are generally higher than IEC same time, and at the same levels, as the tan d test.
and IEEE standards.
Bushings with Um ≥ 245 kV are routine tested with a dry
A tightness test is carried out on the assembled bushing lightning impulse voltage withstand test, in addition to what
after the final drying and impregnation. The test is made at has been described.
an oil overpressure of 180 kPa (1.8 bar) for 12 hours at
ambient temperature. No sign of leakage is allowed. Each Type tests have been carried out according to IEC 60137 and
bushing is subjected to a final electrical routine test. The IEEE. Type test reports are available on request.
test is made at room temperature with the lower end of the
bushing submerged in oil. Capacitance and tan d are Test tap
measured in steps up to the power frequency withstand All GOE bushings are equipped with a test tap connected to
voltage, which is maintained for one minute. The PD value the outer layer of the condenser core. The max. test voltage
must not exceed 30 pC at the withstand voltage. of the tap is 20 kV, 50 Hz for one minute. Max. service
Capacitance, tan d and internal partial discharge are also voltage is 6 kV.
measured with decreasing voltage at the same voltage
levels as before the one minute test. It is always In connection with an external capacitance the test tap can
demonstrated that the PD value is below 5 pC at rated be used as a voltage tap. The test tap has dimensions
voltage (=√3 times bushing service voltage). according to IEEE Potential tap type A.
—
05 Test tap.
— —
06 Test tap adapter. 07 Oil sampling valve.
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 9
—
Dimensions and data
Type designation
The type designation of GOE bushings is built up
as explained below.
GOE xxx-xxx-xxx-xxx
Type of bushing
2019
GOE250-210-3150-0,6
1ZSCT14006483/02 1ZSC902052-AAB
52/30 3150
570 0,44
492 0,13
Table 2. Data GOE 250 to 950.
10
-AAB GOE 380-300-3150-0.6 3150 72.5 42 380 300 175 170 594 5700 2800 2300 1700
Nominal voltages 52 kV to 170 kV
-ABA GOE 380-300-5000-0.3 5000 72.5 42 380 300 175 170 448 5700 2800 2300 1700
-ABB GOE 380-300-5000-0.6 5000 72.5 42 380 300 175 170 594 5700 2800 2300 1700
1ZSC902145-AAA GOE 650-500-3150-0.3 3150 145 84 650 500 325 315 392 5700 2800 2300 1700
-AAB GOE 650-500-3150-0.6 3150 145 84 650 500 325 315 498 5700 2800 2300 1700
-ABA GOE 650-500-5000-0.3 5000 145 84 650 500 325 315 392 5700 2800 2300 1700
-ABB GOE 650-500-5000-0.6 5000 145 84 650 500 325 315 498 5700 2800 2300 1700
1ZSC902170-AAA GOE 950-650-3150-0.3 3150 245 1) 141 950 650 395 395 377 5000 2500 2000 1500
-AAB GOE 950-650-3150-0.6 3150 245 1) 141 950 650 395 395 466 5000 2500 2000 1500
1) The bushing can be used for rated voltage 170 kV according to IEC 60137.
-ABA GOE 250-210-5000-0.3 0.3 2955 ±80 38 825 ±20 1331 ±25 305 375 685 270 224 350 386 350 300 60 60 20 (6x)
-ABB GOE 250-210-5000-0.6 0.6 2955 ±80 38 825 ±20 1331 ±25 605 670 985 290 224 350 386 350 300 60 60 20 (6x)
1ZSC902072-AAA GOE 380-300-3150-0.3 0.3 2955 ±80 48 825 ±20 1331 ±25 305 375 685 230 224 350 386 350 300 60 60 20 (6x)
-AAB GOE 380-300-3150-0.6 0.6 2955 ±80 48 825 ±20 1331 ±25 605 670 985 240 224 350 386 350 300 60 60 20 (6x)
-ABA GOE 380-300-5000-0.3 0.3 2955 ±80 38 825 ±20 1331 ±25 305 375 685 270 224 350 386 350 300 60 60 20 (6x)
-ABB GOE 380-300-5000-0.6 0.6 2955 ±80 38 825 ±20 1331 ±25 605 670 985 290 224 350 386 350 300 60 60 20 (6x)
1ZSC902145-AAA GOE 650-500-3150-0.3 0.3 4775 ±125 48 1300 ±27 1806 ±33 305 400 835 330 264 400 386 350 350 45 90 20 (8x)
-AAB GOE 650-500-3150-0.6 0.6 4775 ±125 48 1300 ±27 1806 ±33 605 700 1135 350 264 400 386 350 350 45 90 20 (8x)
-ABA GOE 650-500-5000-0.3 0.3 4775 ±125 38 1300 ±27 1806 ±33 305 400 835 390 264 400 386 350 350 45 90 20 (8x)
-ABB GOE 650-500-5000-0.6 0.6 4775 ±125 38 1300 ±27 1806 ±33 605 700 1135 410 264 400 386 350 350 45 90 20 (8x)
1ZSC902170-AAA GOE 950-650-3150-0.3 0.3 6820 ±175 48 1800 ±37 2306 ±42 305 315 835 405 264 400 386 350 350 45 90 20 (8x)
-AAB GOE 950-650-3150-0.6 0.6 6820 ±175 48 1800 ±37 2306 ±42 605 615 1135 420 264 400 386 350 350 45 90 20 (8x)
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 11
Position of
A1 test tap
Earthing hole
M12
A2
Mounting hole H1
Position of oil
sample valve
D6
130
D5
D4
L2 L1
25
115
L3 D2
L4
D3
L5
—
D1
08 Dimensions GOE 250 to 950.
Table 4. Data GOE 1050 to 1800.
12
1ZSC902420-AAA GOE 1300-1050-2500-0.3 2500 420 242 1300 1050 630 n.a. 1155 518 9000 4500 2500 -
Maximum current 2500 A to 5000 A
Lightning impulse 1050 kV to 1800 kV
-AAB GOE 1300-1050-2500-0.6 2500 420 242 1300 1050 630 n.a. 1155 540 9000 4500 2500 -
-BAA GOE 1425-1150-2500-0.3 2500 420 242 1425 1150 695 n.a. 1265 518 9000 4500 2500 -
-BAB GOE 1425-1150-2500-0.6 2500 420 242 1425 1150 695 n.a. 1265 540 9000 4500 2500 -
1ZSC902550-AAA GOE 1550-1175-2500-0.3 2500 550 318 1550 1175 750 n.a. 1300 464 13000 6500 4300 1500
-AAB GOE 1550-1175-2500-0.6 2500 550 318 1550 1175 750 n.a. 1300 458 13000 6500 4300 1500
-BAA GOE 1675-1300-2500-0.3 2500 550 318 1675 1300 750 n.a. 1430 464 13000 6500 4300 1500
-BAB GOE 1675-1300-2500-0.6 2500 550 318 1675 1300 750 n.a. 1430 458 13000 6500 4300 1500
-CAA GOE 1800-1360-2500-0.3 2500 550 318 1800 1360 870 n.a. 1500 464 13000 6500 4300 1500
-CAB GOE 1800-1360-2500-0.6 2500 550 318 1800 1360 870 n.a. 1500 458 13000 6500 4300 1500
1) The bushing can be used for rated voltage 245 kV according to IEC 60137.
1ZSC902362-AAA GOE 1175-850-2500-0.3 0.3 9120 ±240 48 2470 ±55 3311 ±60 305 335 1035 810 330 480 485 500 430 45 20 (8x)
-AAB GOE 1175-850-2500-0.6 0.6 9120 ±240 48 2470 ±55 3311 ±60 605 610 1335 830 330 480 485 500 430 45 20 (8x)
1ZSC902420-AAA GOE 1300-1050-2500-0.3 0.3 13745 ±355 48 3620 ±56 4461 ±60 305 320 1035 1070 330 480 485 500 430 45 20 (8x)
-AAB GOE 1300-1050-2500-0.6 0.6 13745 ±355 48 3620 ±56 4461 ±60 605 620 1335 1090 330 480 485 500 430 45 20 (8x)
-BAA GOE 1425-1150-2500-0.3 0.3 13745 ±355 48 3620 ±56 4461 ±60 305 320 1035 1070 330 480 485 500 430 45 20 (8x)
-BAB GOE 1425-1150-2500-0.6 0.6 13745 ±355 48 3620 ±56 4461 ±60 605 620 1335 1090 330 480 485 500 430 45 20 (8x)
1ZSC902550-AAA GOE 1550-1175-2500-0.3 0.3 18020 ±470 48 4710 ±55 5751 ±61 305 310 1285 1995 428 720 565 600 660 30 24 (12x)
-AAB GOE 1550-1175-2500-0.6 0.6 18020 ±470 48 4710 ±55 5751 ±61 605 610 1585 2030 428 720 565 600 660 30 24 (12x)
-BAA GOE 1675-1300-2500-0.3 0.3 18020 ±470 48 4710 ±55 5751 ±61 305 310 1285 1995 428 720 565 600 660 30 24 (12x)
-BAB GOE 1675-1300-2500-0.6 0.6 18020 ±470 48 4710 ±55 5751 ±61 605 610 1585 2030 428 720 565 600 660 30 24 (12x)
-CAA GOE 1800-1360-2500-0.3 0.3 18020 ±470 48 4710 ±55 5751 ±61 305 310 1285 1995 428 720 565 600 660 30 24 (12x)
-CAB GOE 1800-1360-2500-0.6 0.6 18020 ±470 48 4710 ±55 5751 ±61 605 610 1585 2030 428 720 565 600 660 30 24 (12x)
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 13
Position of
A1
test tap
Earthing
hole M12
90°
150
D5
D4
L2 L1
28
196
L4 L3
D2
L5
D3
—
09 Dimensions GOE 1050 to 1800. D1
Table 6. Data GOE 2550.
14
1ZSC902800-AAC GOE 2550-1600-0.3 2500 800 462 2550 1600 1075 1760 520 13000 6500 3700 1600
Maximum current 2500 A
Lightning impulse 2550 kV
-AAD GOE 2550-1600-0.6 2500 800 462 2550 1600 1075 1760 560 13000 6500 3700 1600
—
10 Dimensions GOE 2550.
L2
L5
L1
L4
M12
215
150
L3
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
sample valve
Position of oil
90°
Earthing hole
Earthed layer
30°
Ø711
Ø48
28
test tap
D1
D2
Position of
Ø616
Ø528
Ø780
holes Ø32
12 mounting
Table 8. Data GOE 2600.
—
11 Dimensions GOE 2600.
11536 ±80
2385 ±5
150
300
595 505
300
9585 ±75
35
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
holes Ø32
Earthed layer
Position of
20 mounting
sample valve
18°
Ø930
33°
Ø48
test tap
M12
Ø567
Ø600
Ø755
Position of
Ø690
Ø1000
Earthing hole
15
Table 10. Data GOE(2).
16
1ZSC903550-AAA GOE(2) 1550-1175-1600-0.3 1600 550 318 1550 1175 750 n.a. 1175 459 10000 5000 3900 -
-AAB GOE(2) 1550-1175-1600-0.6 1600 550 318 1550 1175 750 n.a. 1175 505 10000 5000 3900 -
-BAA GOE(2) 1675-1300-1600-0.3 1600 550 318 1675 1300 750 n.a. 1300 459 10000 5000 3900 -
Nominal voltage 362 kV to 550 kV
-BAB GOE(2) 1675-1300-1600-0.6 1600 550 318 1675 1300 750 n.a. 1300 504 10000 5000 3900 -
Lightning impulse 1175 kV to 1675 kV
30°
Position of
Position of 30° test tap Earthing
test tap Earthing hole M12
hole M12 120°
120°
ØD6
Position of oil 12 mounting
sample valve holes Ø23
Position of oil 12 mounting Ø450
sample valve D6 holes Ø23
158
158 Ø450
Ø382
Ø450
Ø382
L2 L1
5046 ±10 4160 ±4
Ø422
Ø462
310 310 25
25
L3
L4 Ø300
L4 L3 Ø300
Earthed layer
Earthed layer Ø500
L5 D3 L5
Ø50 Ø50
— —
12 Dimensions GOE(2) 1175-1425. 13 Dimensions GOE(2) 1675.
18 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
—
Current capacity
The rated currents specified in this catalogue are Overload capacity of bushings
based on thermal tests and are in accordance If the conductor for the bushing is selected with
with IEC 60137 and apply to the built-in 120 % of the rated current of the transformer, the
conductors of the bushings. The GOE bushings bushing is considered to be able to withstand
conform to the requirements of IEC 60137 and overload conditions according to IEC 60076-7
IEEE for currents given in Table 11. without further clarification or tests. This
recommendation complies with IEC 60137.
Short-time current
The rated thermal short-time current (Ith), as Table 12. Rated current, short-time current and
dynamic current as defined in IEC 60137, for
defined in IEC 60137 clause 5, is listed in Table 11 draw rod and fixed bottom end terminal.
for draw rod and fixed bottom end terminal. Dynamic
Rated Short-time current current
For draw lead of stranded copper with the area current Current Ith Ith Id
100 mm2 the short-time current (Ith) is 9.6 kA for IEC IEEE 1s 2s peak
A A kA kA kA
1 second and 6.8 kA for 2 seconds. For other areas
1600 1450 100 75 250
the short-time current is directly proportional to
2500 2100 100 100 250
the area. The rated dynamic current (Id) is
3150 2700 100 100 250
2.5 times the 1 second short-time current. 5000 4250 100 100 250
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 19
—
Connection details
The oil side connection can be made with either a draw-rod Bottom contacts with 4 or 6 threaded holes for cable lugs
system, a draw-lead system or a fixed bottom contact. For are available. The bottom contacts are made of copper and
the air side connection the same outer terminals are have rounded edges, so that they may be used without any
provided for both systems. When ordering, please specify shield for low insulation levels (BIL <450 kV).
the items stated below.
At the level of the flange the draw rod is split into two parts.
Draw rod system If required to meet the transport conditions, a joint at any
Fig. 14: The centre tube of the bushing is used as current desired level below the flange can be offered on request.
conductor. The lower part with contact end shield can then be secured
to the cover during transport and storage of the
Fig. 15: The transformer leads are fitted with cable lugs, transformer.
which are bolted to a bottom contact.
Table 13. Ordering particulars for draw rod system.
Fig. 16: This contact is drawn against the lower end of the GOE type GOE GOE(2)
Type of draw rod BIL Cat. No. Cat. No.
bushing tube by a thin steel draw rod.
Lower draw rod 1) 250-2600 LF 170 059 LF 170 098
Upper draw rod 2) 250-2600 LF 170 057 LF 170 097
Fig. 17: During installation on the transformer, the upper end 1) Lower draw rod includes bottom contact, guiding cone and draw rod up to
of this rod is bolted to a spring device beneath the outer bushing flange level.
terminal, which consists of two concentric tubes of different 2) Upper draw rod includes the complete draw rod above mounting flange level
and the temperature compensation device.
materials and is so designed that it gives the required
contact load at all temperatures.
— — — —
14 15 16 17
20 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
∅150 ∅125
D2 D2
H2 H2
Threaded hole M8
for pulling wire
Threaded hole M8
for pulling wire L2 L2
Mounting
flange
Mounting
M16
flange
25
M16
60 25
60
L5
— —
18 Draw rod system for GOE. For all currents up to rated current of the bushing. 19 Draw rod system for GOE(2). For all currents up to rated current of the bushing.
Selection as per Table 13. Selection as per Table 13.
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 21
∅150 ∅125
D2 D2
Outer
terminal Outer
terminal
Threaded hole M8
H2 for pulling wire
H2
Threaded hole M8
for pulling wire
53
L2
350 End of cable L2
D3
46
30 End of
cable
D9
D3
— —
20 Draw lead system, LF 170 056, and outer terminal for GOE. 21 Draw lead system, LF 170 091, and outer terminal for GOE(2).
Selection as per Tables 14 and 15. Selection as per Tables 14 and 15.
22 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
Fixed bottom contact The fixed bottom contact system uses the center
Fixed bottom contacts with two or four holes are tube as a current conductor. The bottom contact
available, see Fig. 22. They are made of tinned is fastened to the bushing bottom nut with six
copper. M10 bolts.
74,5
84,5
100
44,5
100
44,5
Cu/Sn 14 (4x)
14 (4x) T=30
44,5 Cu/Sn
T=30
—
22 Fixed bottom contacts.
—
End-shields
The maximum stresses in the oil at the surface of ABB can also provide assistance with field
the shield insulation and the parts surrounding calculations to confirm the compatibility between
the bushing must be limited to those values the transformer and our bushings.
normal for insulated conductors and other similar
components in the same transformer.
A
mm
1000
500
Shield -X
Shield -V
Shield -U
No shield
0
0 500 1000 (kV) U
0 500 1000 1500 2000 2500 (kV) LI
U = Power frequency
LI = Lightning impulse
—
23 Recommended minimum distance A for different shields and test voltages.
24 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
45°
Rmin 5
60°
Large bottom
contact N1= 6
R1 —
H6 25 Mounting alternatives, type GOE.
H4 R3
H5
D5 R2
D4
60°
ø102 20°
ø125
60°
13
18
—
24 Recommendations for positioning, type GOE.
Rmin 5 45°
60°
—
H6 27 Mounting alternatives, type GOE(2).
R1
H4
H5
R3
D5 R2
D4
60° 60°
ø13
ø110 ø87
ø18
20°
—
26 Recommendations for positioning, type GOE(2).
—
Ordering particulars
Example 1
Bushing: GOE 650-500-3150-0.3, 1ZSC902145-AAA
Outer terminal: LF 170 073-A or -B
Inner connections: Draw lead, LF 170 056-A
Insulated shield: Epoxy insulated, LF 170 046-U
Example 2
Bushing: GOE 1550-1175-2500-0.6, 1ZSC902550-AAB
Outer terminal: LF 170 073-A or -B
Draw rod, upper part LF 170 057, lower part
LF 170 059, small contact (On request the lower
part of the draw rod can be sent separately at an
Inner connections: earlier delivery date.)
Insulated shield: Pressboard coated, LF 170 046-VP
Example 3
Bushing: GOE 1300-1050-2500-0.3, 1ZSC902420-AAA
Outer terminal: Silver plated, D2=50, H2=100
Draw rod, upper part LF 170 057, lower part
LF 170 059, small contact
(On request the lower part of the draw rod can be
Inner connections: sent separately at an earlier delivery date.)
Insulated shield: Pressboard coated, LF 170 046-VP
Test voltage 690 kV
Other requirements: Tan d over C2<1.0 %
TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE 27
—
Packing
The bushings are delivered in wooden crates; the same crate Table 18. Packing crate dimensions.
used for all flange extensions. When end shields are ordered, Wooden crate
they will be delivered together with the bushings in the Bushing L (mm) B (mm) H (mm) Mass (kg)
same crates. All crates are heat-treated according to ISPM15. GOE 250-380 3140 540 640 125
GOE 650 3740 590 640 155
GOE 950 4250 590 640 172
GOE 1050 5240 670 750 244
GOE 1175 5490 670 750 253
GOE 1300-1425 6640 670 750 299
GOE 1550-1800 8350 930 1100 728
GOE 2550 11360 990 1200 1030
GOE 2600 14670 1490 1570 2605
GOE(2) 1175 5440 640 690 235
GOE(2) 1425 6350 690 720 289
GOE(2)1550-1675 7440 690 720 334
L B
—
28 Packing crate.
28 TR ANSFORMER BUSHINGS T YPE GOE AND GOE(2) TECHNIC AL GUIDE
—
Additional GOE and GOE(2) bushings
Available on request
The following types of bushings are available on request.
Keep in mind that lead times may be longer than for the
standard range. Bushings are also available according to
certain established customer specifications. For full details,
please contact ABB.
L5 L2
—
29 Dimensions.
www.abb.com/transformercomponents