You are on page 1of 8

Refrigeration System

Equipment Room Design


The purpose of this newsletter is to provide ASHRAE Standards
interim guidance to designers of The American Society of Heating,
mechanical equipment rooms housing Refrigerating and Air Conditioning
chillers that employ refrigerants classified Engineers (ASHRAE) is an organization
by ASHRAE Standard 34-1992. The advent whose members come from all aspects of
of new and replacement non-CFC the HVAC industry. Together, the members
refrigerants has resulted in a great deal of draft "standards" and "guidelines" to assure
uncertainty in the design community. safe distribution and use of HVAC products.
ASHRAE has attempted to remedy a large These standards can be considered state-
share of this uncertainty by quickly of-the-art design practices; frequently they
rewriting Standards 15 and 34 to are adopted and enforced by local code
accommodate recently applied HCFC and authorities. Until this occurs, it is the
HFC refrigerants. Interim guidance may be owner's/designer'sprerogative to specify
helpful until both of these standards are design according to the standards.
approved and in full circulation. However, when design issues are raised in
court, the legal system often refers to the
The Fane Company intends to provide an state-of-the-artdesign practice at the time
application manual entitled "Refrigeration the building was designed.
System Equipment Room Design," based
on the newly approved ASHRAE Standard The Design Process
75-1992, Safety Code for Mechanical A system designer who faces the task of
Refrigeration. Publication of that manual will designing a mechanical equipment room
obsolete this newsletter. that houses refrigeration equipment needs
a "recipe." Based on our review of
The focus of this newsletter is on changes Standards 15 and 34, a nine-step process
to mechanical equipment room design seems well suited.
requirements brought on by a change from
CFC- 7 1 to the alternative HCFC-123 in 1
centrifugal chillers. Both are low-pressure Define safety group classification.
refrigerants that operate at subatmospheric 2
pressures in evaporators and slightly above Define occupancy group classification.
atmospheric pressure in condensers of 3
centrifugal water chillers.A smaller number Define refrigerating system classification.
-
of centrifugal chiller plants employ medium 4
or high-pressure refrigerants. It is important Determine which refrigerant quantity rules
to recognize that the ASHRAE safety code 5
(Standard 15) applies to equipment rooms Determine best equipment layout
with chillers using all refrigerants, except arrangement.
water. Thus, changes to this standard are 6
significant to designers of chiller systems, Design ventilation system.
regardless of the refrigerant used in the 7
chillers. Design refrigerant pressure-relief piping.
8
Select safety monitoring equipment.
9
Determine extent of automation desired.
Safety Group Figure 1
Two ASHRAE Standards deal with the use
and handling of refrigerant in an equipment Standard 34: Standard 15:
Number Designation and Safety Safety Code for Mechanical
room: Standard 15 and Standard 34.
Classification of Refrigerants Refrigeration
Purpose and scope of each is shown in
Figure 1. Standard 34 defines "Safety Purpose: ". . .to establish a simple Purpose: " . . .to promote the safe
Group Classifications of Refrigerants" means of referring to common design, construction, installation and
according to their toxicity and flammability. refrigerants instead of using the operation of refrigerating systems."
The measure of toxicity delineation chemical name, formula or trade
between Group A and Group B refrigerants name. It also establishes a uniform
is a "threshold limit value-time weighted system for assigning reference
average: (TLV-TWA) concentration of numbers and safety classifications
400 parts per million (ppm), as shown in to refrigerants."
Figure 2. Standard 34 defines TLV-TWA as Scope: " . . .provides an unambiguous Scope: ". . . establishes reasonable
". . .the time weighted average system for numbering refrigerants and safeguards of life, limb, health and
concentration for a normal 8-hour assigning composition-designating property; defines practices that are
workday and a 40-hour work week, to prefixes for refrigerants. Safety consistent with safety; and prescribes
which nearly all workers may be classifications based on toxicity and safety standards."
repeatedly exposed, day after day, flammability data are included.
without adverse effect" ". . . applies a) to mechanical
refrigerating systems and heat pumps
The primary application of this definition is used in the occupancies defined in
likely to be workers in facilities that produce Section 4 (occupancy classification) and
or store the chemical; although a case installed subsequent to adoption of this
could be made for those rare mechanical code and b) to parts replaced and
equipment rooms where workers are components added after adoption of
present on a continuous 40-hour week this code."
basis.
The letter designation for toxicity is
followed by a number used to designate
flammability. Refrigerants with no flame Figure 2: ASHFiAE Standard 34 Refrigerant Safety Classifications
propagation potential are given a "1 lower
,I'

flammability refrigerants receive a "2" and


refrigerants with a higher flammability are Safety Group
assigned a "3." Standard 34 defines the Higher (a) Group A3 Group B3 Class 1 indicates refrigerants that do
flame propagation and lower flammability Flammability not show flame propagationwhen tested in
limits (LFL) for each of these three air at 101 kPa (14.7 psia) and 18 C (65 F).
Lower (b) Group A2 Group 82
categories. Flammability Class 2 signifies refrigerantshaving a lower
No Flame Group A I Group B1 flammability limit (LFL)of more than 0.10
Specific values are shown in Figure 2. kg/m3(0.00625 Ib/ft3at 21 C and 101 kPa
Propagation
Designators for the most common (70 F and 14.7 psia) and a heat combustion
refrigerants are shown in Figure 3. Lower Higher of less than 19,000 kJ/kg (8,174 Btu/lb). The
ASHRAE Standard 15 uses these same Toxicity(c) Toxicity(c) heat of combustion shall be calculated
assuming that combustion products are in
designators to delineate the design criteria Notes: the gas phase and in their most stable state
for refrigeration equipment located in or Class A signifies refrigerantsfor which (e.g., C, N, S give C02, N, SO3, F and CI
near a building. toxicity has not been identified at give HF and HCI if there is enough H in the
concentrations less than or equal to 400 ppm, molecule, otherwise they give F2 and CI,;
Occupancy Group based on data used to determine threshold excess H is converted to H20.
Occupancy classifications are based on limit value-time weighted average (TLV-TWA)
the ability of people to respond in the event or consistent indices. Class 3 indicates refrigerantsthat are highly
flammable, as defined by an LFL of less than
of an emergency. ASHRAE has defined six Class B signifies refrigerantsfor which there or equal to 0.10 kg/m3(0.00625 Ib/ft3at 21
occupancy classifications that reflect how a is evidence of toxicity at concentrations C and 101 kPa (70 F and 14.7 psia) or a
building is used. All equipment, other than below 400 ppm, based on data used to heat of combustion greater than or
piping, located less than 20 feet from any determine TLV-TWA or consistent indices. equal to 19,000 kJ/kg (8,174 Btu/lb).
building opening is governed by one of The heat of combustion is calculated as
these six occupancy classifications, shown explained above in the definition of a
Class 2 category.
in Figure 4.

2
~ ~~

Figure 3: Refrigerant/Refrigerant Blend Data and Safety Classifications

Normal Quantity of Refrigerant


Boiling Point Per Occupied Space (d)
Refrig Chemical Ib/l 000 f? g/m3
No. Chemical Name Formula OC OF (C) VOl. % (C)
Methane Series:
11 trichlorofluormethane CC13F 24 75 1.6 0.4 250
12 dichlorodifluoromethane CC12FZ -30 -22 12.0 4.0 200
22 chlorodifluoromethane CHCIF2 -41 -41 9.4 4.2 150
Ethane Series:
113 1,I.2-trichlorotrifluoroethane CC12FCCIF2 48 118 1.9 0.4 300
123 2,2-dichloro- CHC12CF3 27 81 0.004 0.001 0.08
1,I,I-trifluoroethane
134a 1,I,1,2-tetrafluoroethane CH2FCF3 -26 -15 16.0 6.0 250
152a 1,I-difluoroethane CH3CHFz -25 -13 1.2 0.7 20
Quantity of
Refrig Normal Safety Refrigerant Blend
No. Composition (Weight YO) Boiling Point Group Per Room Volume (d)
Azeotropes (b):
500 R-I 2/152a (73.8/26.2) -33 -27 AI 16.0 4.7 250
502 R-22/115 (48.8/51.2) -45 -49 AI 19.0 6.5 300
Notes:
(a) Per ASHRAE Standard 34, this toxicity classification is based on recommendedexposure limits provided by chemical suppliers. These
ratings are provisional and will be reviewed when toxicological testing is completed.
(b)Per ASHRAE Standard 34, azeotropic refrigerants exhibit some segregation of components at conditions of temperature and pressure
other than those at which they were formulated. The extent of segregation depends on the particular azeotrope and hardware system
configuration.
(c) To correct for height, H(feet),above sea level, multiply these values by (1-2.42 x 10-6 H). To correct for height, h (km),above sea level,
multiply these values by (1-7.94 x 10-2 h).
(d) The basis of the table amounts is given as follows:
Group AI - 80% of the cardiac sensitization level for R-I 1, R-I2, R-22, R-I 13, R-I34a, R-500 and R-502. Others are limited by
levels where oxygen deprivation begins to occur.
Group A2. A3 - Approximately 20% of LFL.
Group B1 - 100% of the measure consistent with the TLV for R-I23.
Group 82, B3 - 100% of IDLH or 20% of LFL, whichever is lower.

'
1
1
1 Institutional. Occupants cannot readily leave without assistance. Examples
include (but are not limited to) hospitals, nursing homes and locked cells.
2 Public assembly. Occupants cannot quickly vacate due to their large
numbers. Examples include (but are not limited to) auditoriums, department
stores, ballrooms and passenger depots.
1 3 Residential. Occupants, because they are sleeping, may not be aware of a
hazard. Examples include (but are not limited to) hotels, dormitories and
apartments.
4 Commercial. Occupants transact business, receive services or trade goods.
Examples include office and professional buildings, restaurants and markets.
Other commercial occupancies are work and storage areas that do not qualify
as an industrial occupancy.
5 Industrial. Occupancy is restricted to only those personnel with authorized
access. Examples include (but are not limited to) manufacturing plants,
processing plants and storage facilities.
6 Mixed. Two or more classes of occupancies share the same building.

3
Figure 6 System Application Requirements Controls must be provided to increase the
ventilation rate from normal to purge.
Occupancy Classification Automatic control shall be accomplished by
Refrig System Public Assembly, linking the alarm output of a refrigerant (or
Group Probability Institutional Residential, Commercial Industrial oxygen deprivation) monitor into the
AI High 1 2 3 ventilation system. Additionally, a switch to
Low 4 4 4 initiate the purge ventilation rate should be
A2 High 5 5 36.8 located outside the main entrance to the
Low 7 7 7 mechanical equipment room
A3 High 9 9 3,6,8
Low 9 9 7 The location of the ventilation system inlets
B1 High 16 2,6 3.6 and discharges are referenced by Standard
Low 4 4 4 15 only with regard to their guarding,
82 High 56 5,6 368 avoidance of recirculation and their
Low 7: 7 7 exclusive dedication to ventilation of the
B3 High 9 9 3,6,8 equipment room. Figure 8 suggests a
Low 9 9 7 configuration that provides for the complete
RefrigerantQuantity Rules From ASHRAE Standard 15 purging of refrigerant from the equipment
1 The refrigerant amount is limited to 50% of that listed in Figure 3, except Rule 2 applies in room by "sweeping" air across all
kitchens, laboratories and mortuaries. If any portion of a refrigerant system containing refrigeration equipment.
more than one pound of refrigerant(except R-744) is in a room with a flame-sustaining
device, this device shall be provided with a hood to exhaust combustion products to the When exhaust fans are used to keep the
open air. Otherwise, Rules 5 and 6 shall be followed. equipment room cool, or remove smoke
2 The refrigerant amount is limited as listed in Figure 3. from combustion, inlets are often located
3 The refrigerant amount is unlimited when:
a) the machinery-containingarea is separated from the areas of the building not containing near the ceiling as both heat and smoke
machinery by tight construction with tight-fitting doors; tend to rise. If the same ventilation system
b) free escape from the area is unhampered; serves as the refrigerant exhauster,
c) the number of persons in a machinery-room-containing-spaceon any floor above the provisions must be made for inlets at both
first floor (ground level or deck level) is equal to or less than one person per 100 sq ft floor and ceiling levels, because refrigerants
(9.3m2)of floor area, or if the number exceeds one person per 100 sq ft (9.3m2),the are three to five times heavier than air.
machinery-containingspace shall be provided with the required number of doors
opening directly into approved building exits; Figure 9 shows a proper way to handle this
d) detectors are located in areas where refrigerantvapor from a leak is likely to dual-purpose requirement.
concentrate to provide an alarm at the following levels: Group A1 below 19.5% volume
oxygen; Groups A2 and A3 at levels listed in Figure 3; and Groups BI, 82 and 83 Refrigerant Pressure Relief Piping
(except ammonia)at no higher than their TLV (or toxicity measure consistent therewith).
Otherwise the rules for commercial occupancy apply. In general, all equipment specifications
4 When the quantity of refrigerantin the largest system exceeds Figure 3 amounts, all require pressure relief devices to protect
refrigerant-containingparts, except piping and those parts outside the building, shall be components and packages from rupture
installed in a machinery room per Section 11.13 of ASHRAE Standard 15-1992. due to high pressure fIom fire or other
5 Refrigerant amounts and types of systems are limited as shown in Figure 6. abnormal conditions. This requirement is
6 Applications involving air conditioning for human comfort are not allowed.
7 When the quantity of refrigerant in the largest system exceeds Figure 3 amounts, all
also spelled out in Standard 15. Once the
refrigerant-containingparts, except piping and those parts outside the building, shall be equipment is installed, each pressure relief
installed in a machinery room per Section 11.I4 of ASHRAE Standard 15-1992 with limitations device or fusible plug must be piped to a
on refrigerant quantities as follows: safe location outside the equipment room.
550 Ib (250kg)-Institutional The terminus of this piping needs to be at
No limit except Rule 8- Public Assembly least 15 feet above the adjoining ground
No limit except Rule 8- Residential
and at least 20 feet from any window,
No limit except Rule 8- Commercial
No limit except Rule 8- Industrial ventilation opening or exit in any building.
Otherwise, Rule 5 applies to the amount of Group A2, A3, B2 or 83 refrigerantin the system. PVC piping is not recommended since
8 When the quantity of refrigerant exceeds Figure 3 amounts, all refrigerant-containing parts many adhesives used in this type piping
except piping, low-side components, condensers and parts outside the building shall be construction have not been tested for
installed in a machinery room per Section 11.I3 of ASHRAE Standard 15-1992. In addition, refrigerant compatibility.
refrigerants of Groups A2, A3, B2 and B3 shall meet the following requirements:
a) The special machinery room requirements of Section 11.I4 of ASHRAE Standard 15-1992
shall apply.
b) Except for ammonia, amounts in excess of 1100 Ib (500 kg) shall be approved by the
authority having jurisdiction.
9 Use of these refrigerants is prohibited except in laboratories in commercial occupancies. Only
unit systems containing not more than 6.6 Ib (3kg)of Group A3 or B3 refrigerantshall be used
unless the laboratory is occupied.

5
Refrigerating System Figure 5: Refrigeration System Classification
Refrigerating system classification is the (from ASHRAE Standard 34)
third step. There are five designations, but
they are based on the method used to
extract or deliver heat. Figure 5 identifies Air Or Substance
these five system types schematically and System Cooling Or To Be Cooled Or
by name. Systems are either high Designation
probability or low probability systems.
System probability indicates the relative Direct
likelihood of refrigerant leaking from a
refrigerant system into an occupancy-
classified area. Direct and indirect open
spray systems are high probability
systems. The basic design or location of Indirect
components is such that refrigerant leakage Open Spray
from a failed connection, seal or
component could enter the area under Vent !i
consideration. Examples of these systems
are direct-expansion split systems, rooftop
air conditioners and open spray air
washers. All other systems, including most
chillers, are considered low probability.

Refrigerant Quantity
Figure 6 indicates that the application of Indirect
group A1 and B1 refrigerants in low Closed
probability systems in any occupancy
results in Rule 4. Rule 4 states that if the
refrigerant quantities exceed those shown
in Figure 3, as almost always occurs, a
mechanical equipment room is required.

Equipment Layout
Once the refrigerant quantities shown in
Figure 3 are exceeded and Rule 4 applies, it
points to Section 11.13 of ASHRAE
Standard 15. Virtually any enclosed plant
employing any chiller using any of the While the exact equipment layout is not or b) the air volume required to maintain a
common commercial refrigerants (R-11, specified, it is generally good practice to maximum temperature rise of 18 F.
R-12, R-22, R-500, R-123 or R-l34a) should situate chillers such that airflow patterns
be designed in accordance with Section around them do not result in areas of air The purge ventilation rate is found by the
11.13 which prescribes specific stagnation. Figure 7 shows two possible equation Q = 100 x where
requirements for: configurations for a multiple chiller plant. 0 = airflow (cu ft/min)
Positioning chillers as shown in G = mass of refrigerant (Ibs) in the largest
8
Arrangement A provides good air system, any part of which is located in
Minimum headroom movement, .while Arrangement B creates the machinery room.
8
stagnant air areas between the chillers.
Tight-fitting doors "Q' represents the minimum airflow that
8
Ventilation the ventilation system must be capable of
Oxygen or refrigerant sensor/detector (with Ventilation volume requirements for providing while the equipment room is
periodic testing) mechanical equipment rooms are covered purged of refrigerants. According to
8
by Standard 15. Most rooms require Standard 15, it is, not necessary to run the
Mechanical ventilation mechanical ventilation because they are ventilation system at this volume
8
fully enclosed and usually attached in some continuously, provided that the normal rate
Prohibited open flames way to the remainder of the building. is maintained during occupancy.
8
Standard 15 defines two distinct ventilation Thus two distinct ventilation rates are
...I
(...
I/

Restricted personnel. rates: one for normal ventilation and tjl ,,

defined for the mechanical equipment


another for purging. The normal ventilation room. Multiple fans, multispeed fans or
rate applies only to occupied periods and is other modulation devices may be used if a
the larger of: a) 0.5 cfm per square foot of two-tiered ventilation system is used.
equipment room area or 20 cfm per person

4
Figure 7 Multiple-Chiller Equipment Figure 9: Dual Purpose Mechanical
Room Layouts Equipment Room Ventilation System

Arrangement A

Exhaust
Fan

Air
Inlet

Air
Inlet Exhaust
Fan

-
Air
Inlet
-

Exhaust
Fan

Arrangement B
Exhaust
Fan

Figure 8: Suggested Exhaust Fan Location

I 1 Vent pipes should be equipped with a3rip


leg capable of holding up to one gallon of
liquid. Provide a standard capped
refrigerant service valve to facilitate liquid
removal. A procedure to assure periodic
(once every six months) removal of any
accumulation of liquid must be developed.
Of course, appropriate refrigerant handling
procedures must be used when draining
the vent piping. Figure 10 shows a
suggested arrangement.
I

6
Figure 1 0 Suggested Refrigerant 1 losses can be large and can occur quickly,
Vent Piping Choose a purge unit with low refrigerant- compared to low pressure refrigerants.
to-noncondensable-gas discharge ratio and
one that can operate with the chiller off. Sensor location is imprecisely defined by
2 ASHRAE Standard 15 as " . . . locate the
1 -2 Routinely monitor the chiller for leaks by sensor where refrigerant is likely to
logging the operation of the purge system concentrate." Key points to remember are:
and the chiller operating hours. This data 0
provides an excellent indicator of Focus on areas of concentration, rather
refrigeration system integrity. than leakage.
3 e
Choose a purge unit that embodies a safety
Account for airflow patterns in the
system to prevent excessive purging due to
equipment room.
malfunction or a large leak. 0

Focus on occupant safety as the main


Safety Monitoring Equipment objective.
According to Standard 15, all equipment 0

rooms containing refrigerants must be Recognize that occupants are likely


equipped with a long-term monitor that will exposed to refrigerant danger through
automatically signal an alarm and start the inhalation.
ventilation system. Long-term monitors
have the following characteristics: Taking these factors into account, the
4 recommended height for the sensor is 18
Permanently mounted. inches above the floor. Occasionally,
5 equipment rooms are oddly shaped and a
Continuously operated. single sensor may not fulfill all
6 requirements. Single monitors with
1. Roof. Stable over the range of temperatures, multipoint sensors are available for these
humidities and barometric pressures to applications. As a general guideline, a
2. Alternate piping arrangment.
3. Purge discharge vent line. which they will be exposed. refrigeration system should not be more
7 than 50 feet from a refrigerant sensor.
4. Outside wall.
5. Rupture disc assembly. Zero drift or auto-zeroing.
8 Automation
6. Flexible steel connection. This subject deserves more attention than
7. Drip leg (length as required for Outputs to trigger external alarm(s) and to
start auxiliary equipment. can be given in this newsletter. Suffice it to
easy access). say that chiller plant automation systems
8. %" FL x lh'' NPT drain valve. 9
Long service life. provide enabling technology to bring cost-
10 effective refrigerant monitoring to any plant.
Require little maintenance. Professional facilities managers recognize
Purge units are used on low pressure 11 the operating benefits associated with
chillers to remove water and Refrigerant-specific (to avoid nuisance automated monitoring, integrated' with the
noncondensable gas that have found their alarms). chiller plant automation system. Refrigerant
way into the refrigerant circuits. In the cost savings alone can quickly pay for the
course of separating and eliminating Monitors for group AI refrigerants must added equipment. Further, a permanent
noncondensable gas from the refrigerant, a use an oxygen deprivation sensor. All other refrigerant monitor record can hold valuable
certain amount of refrigerant is carried refrigerants must use a refrigerant sensor. data if the proper operation of a plant is
along with the purge unit discharge. This With an oxygen deprivation sensor, a ever challenged.
refrigerant must be piped to a place outside monitor is set to alarm at 19.5 percent
the equipment room, according to Standard volume, since there is insufficient odor ' 1990-1991Threshold Limit Values for Chemical
Substances and Physical Agents and Biological
15. It is convenient to use the same vent warning, and the greatest danger is Exposure Indices, American Conference of
piping required for the pressure relief, as asphyxiation. A refrigerant sensor type is Governmental Industrial Hygienists, Columbus,
shown in Figure IO. Additionally, it is set no higher than the refrigerants TLV': OH, 1990.
prudent to follow these three simple rules Trane IntegratedComfort""systems.
Refrigerant sensors can also be used with
for equipment Selection
Group 1 refrigerants, providing much faster
detection of refrigerant leaks and thus
minimizing loss of refrigerant. This attribute
can be valuable in connection with high
pressure refrigerants, where refrigerant

7
e h

A Publication of
The Trane Company
Commercial Systems Group
La Crosse, WI 54601

The Systems
Manual
The Trane Systems Manual is a unique,
comprehensive resource that will give you
an added advantage whey facing your
clients. With the Systems Manual, you can
easily pull together a professional HVAC
presentation to effectively communicate
your system and equipment ideas. This
colorful manual consists of marketing
presentation brochures that discuss the
importance of comfort for six market
segments: offices, schools, healthcare,
stores, manufacturing and the lodging
industry.
Behind each market segment tab are single Finally, the manual provides the
sheets that describe most of the commonly presentation support for marketing the
used airside systems; single-zone, variable system designer's efforts in determining
air volume, fan-coilhnit ventilators and which system is best for an application.
water-source heat pumps. This section, called computer-aided
systems engineering, outlines the system
Next, on single sheets, are descriptions of design and analysis tools available from ,
popular system options and control The Trane Company. Overall, a
strategies such as heat recovery, thermal comprehensive systems presentation tool
storage, low temperature air, demand developed for use by HVAC practitioners.
limiting and optimum startlstop, to name a
few. For information on how to obtain the
Trane Systems Manual, or for information
To help communicate the myriad of
on Trane's broad line of products and
equipment alternatives, the manual also
services, contact your local Trane
includes a complete portfolio of Trane
commercial sales office.
equipment in a featurelbenefit format. At
this point, system schematic sheets assist
in pulling each of the components together
as a system.
For existing building projects, a section is
devoted to the unique requirements of
constant volume systems such as
multizone, induction, dual duct and terminal
reheat. This section provides an easy to
understand description of the system along
with energy saving retrofit ideas.

@American Standard IN. 1992 a Printed on recycled paper as part of


48 The Trane Company's recycling program

You might also like