Professional Documents
Culture Documents
2
~ ~~
'
1
1
1 Institutional. Occupants cannot readily leave without assistance. Examples
include (but are not limited to) hospitals, nursing homes and locked cells.
2 Public assembly. Occupants cannot quickly vacate due to their large
numbers. Examples include (but are not limited to) auditoriums, department
stores, ballrooms and passenger depots.
1 3 Residential. Occupants, because they are sleeping, may not be aware of a
hazard. Examples include (but are not limited to) hotels, dormitories and
apartments.
4 Commercial. Occupants transact business, receive services or trade goods.
Examples include office and professional buildings, restaurants and markets.
Other commercial occupancies are work and storage areas that do not qualify
as an industrial occupancy.
5 Industrial. Occupancy is restricted to only those personnel with authorized
access. Examples include (but are not limited to) manufacturing plants,
processing plants and storage facilities.
6 Mixed. Two or more classes of occupancies share the same building.
3
Figure 6 System Application Requirements Controls must be provided to increase the
ventilation rate from normal to purge.
Occupancy Classification Automatic control shall be accomplished by
Refrig System Public Assembly, linking the alarm output of a refrigerant (or
Group Probability Institutional Residential, Commercial Industrial oxygen deprivation) monitor into the
AI High 1 2 3 ventilation system. Additionally, a switch to
Low 4 4 4 initiate the purge ventilation rate should be
A2 High 5 5 36.8 located outside the main entrance to the
Low 7 7 7 mechanical equipment room
A3 High 9 9 3,6,8
Low 9 9 7 The location of the ventilation system inlets
B1 High 16 2,6 3.6 and discharges are referenced by Standard
Low 4 4 4 15 only with regard to their guarding,
82 High 56 5,6 368 avoidance of recirculation and their
Low 7: 7 7 exclusive dedication to ventilation of the
B3 High 9 9 3,6,8 equipment room. Figure 8 suggests a
Low 9 9 7 configuration that provides for the complete
RefrigerantQuantity Rules From ASHRAE Standard 15 purging of refrigerant from the equipment
1 The refrigerant amount is limited to 50% of that listed in Figure 3, except Rule 2 applies in room by "sweeping" air across all
kitchens, laboratories and mortuaries. If any portion of a refrigerant system containing refrigeration equipment.
more than one pound of refrigerant(except R-744) is in a room with a flame-sustaining
device, this device shall be provided with a hood to exhaust combustion products to the When exhaust fans are used to keep the
open air. Otherwise, Rules 5 and 6 shall be followed. equipment room cool, or remove smoke
2 The refrigerant amount is limited as listed in Figure 3. from combustion, inlets are often located
3 The refrigerant amount is unlimited when:
a) the machinery-containingarea is separated from the areas of the building not containing near the ceiling as both heat and smoke
machinery by tight construction with tight-fitting doors; tend to rise. If the same ventilation system
b) free escape from the area is unhampered; serves as the refrigerant exhauster,
c) the number of persons in a machinery-room-containing-spaceon any floor above the provisions must be made for inlets at both
first floor (ground level or deck level) is equal to or less than one person per 100 sq ft floor and ceiling levels, because refrigerants
(9.3m2)of floor area, or if the number exceeds one person per 100 sq ft (9.3m2),the are three to five times heavier than air.
machinery-containingspace shall be provided with the required number of doors
opening directly into approved building exits; Figure 9 shows a proper way to handle this
d) detectors are located in areas where refrigerantvapor from a leak is likely to dual-purpose requirement.
concentrate to provide an alarm at the following levels: Group A1 below 19.5% volume
oxygen; Groups A2 and A3 at levels listed in Figure 3; and Groups BI, 82 and 83 Refrigerant Pressure Relief Piping
(except ammonia)at no higher than their TLV (or toxicity measure consistent therewith).
Otherwise the rules for commercial occupancy apply. In general, all equipment specifications
4 When the quantity of refrigerantin the largest system exceeds Figure 3 amounts, all require pressure relief devices to protect
refrigerant-containingparts, except piping and those parts outside the building, shall be components and packages from rupture
installed in a machinery room per Section 11.13 of ASHRAE Standard 15-1992. due to high pressure fIom fire or other
5 Refrigerant amounts and types of systems are limited as shown in Figure 6. abnormal conditions. This requirement is
6 Applications involving air conditioning for human comfort are not allowed.
7 When the quantity of refrigerant in the largest system exceeds Figure 3 amounts, all
also spelled out in Standard 15. Once the
refrigerant-containingparts, except piping and those parts outside the building, shall be equipment is installed, each pressure relief
installed in a machinery room per Section 11.I4 of ASHRAE Standard 15-1992 with limitations device or fusible plug must be piped to a
on refrigerant quantities as follows: safe location outside the equipment room.
550 Ib (250kg)-Institutional The terminus of this piping needs to be at
No limit except Rule 8- Public Assembly least 15 feet above the adjoining ground
No limit except Rule 8- Residential
and at least 20 feet from any window,
No limit except Rule 8- Commercial
No limit except Rule 8- Industrial ventilation opening or exit in any building.
Otherwise, Rule 5 applies to the amount of Group A2, A3, B2 or 83 refrigerantin the system. PVC piping is not recommended since
8 When the quantity of refrigerant exceeds Figure 3 amounts, all refrigerant-containing parts many adhesives used in this type piping
except piping, low-side components, condensers and parts outside the building shall be construction have not been tested for
installed in a machinery room per Section 11.I3 of ASHRAE Standard 15-1992. In addition, refrigerant compatibility.
refrigerants of Groups A2, A3, B2 and B3 shall meet the following requirements:
a) The special machinery room requirements of Section 11.I4 of ASHRAE Standard 15-1992
shall apply.
b) Except for ammonia, amounts in excess of 1100 Ib (500 kg) shall be approved by the
authority having jurisdiction.
9 Use of these refrigerants is prohibited except in laboratories in commercial occupancies. Only
unit systems containing not more than 6.6 Ib (3kg)of Group A3 or B3 refrigerantshall be used
unless the laboratory is occupied.
5
Refrigerating System Figure 5: Refrigeration System Classification
Refrigerating system classification is the (from ASHRAE Standard 34)
third step. There are five designations, but
they are based on the method used to
extract or deliver heat. Figure 5 identifies Air Or Substance
these five system types schematically and System Cooling Or To Be Cooled Or
by name. Systems are either high Designation
probability or low probability systems.
System probability indicates the relative Direct
likelihood of refrigerant leaking from a
refrigerant system into an occupancy-
classified area. Direct and indirect open
spray systems are high probability
systems. The basic design or location of Indirect
components is such that refrigerant leakage Open Spray
from a failed connection, seal or
component could enter the area under Vent !i
consideration. Examples of these systems
are direct-expansion split systems, rooftop
air conditioners and open spray air
washers. All other systems, including most
chillers, are considered low probability.
Refrigerant Quantity
Figure 6 indicates that the application of Indirect
group A1 and B1 refrigerants in low Closed
probability systems in any occupancy
results in Rule 4. Rule 4 states that if the
refrigerant quantities exceed those shown
in Figure 3, as almost always occurs, a
mechanical equipment room is required.
Equipment Layout
Once the refrigerant quantities shown in
Figure 3 are exceeded and Rule 4 applies, it
points to Section 11.13 of ASHRAE
Standard 15. Virtually any enclosed plant
employing any chiller using any of the While the exact equipment layout is not or b) the air volume required to maintain a
common commercial refrigerants (R-11, specified, it is generally good practice to maximum temperature rise of 18 F.
R-12, R-22, R-500, R-123 or R-l34a) should situate chillers such that airflow patterns
be designed in accordance with Section around them do not result in areas of air The purge ventilation rate is found by the
11.13 which prescribes specific stagnation. Figure 7 shows two possible equation Q = 100 x where
requirements for: configurations for a multiple chiller plant. 0 = airflow (cu ft/min)
Positioning chillers as shown in G = mass of refrigerant (Ibs) in the largest
8
Arrangement A provides good air system, any part of which is located in
Minimum headroom movement, .while Arrangement B creates the machinery room.
8
stagnant air areas between the chillers.
Tight-fitting doors "Q' represents the minimum airflow that
8
Ventilation the ventilation system must be capable of
Oxygen or refrigerant sensor/detector (with Ventilation volume requirements for providing while the equipment room is
periodic testing) mechanical equipment rooms are covered purged of refrigerants. According to
8
by Standard 15. Most rooms require Standard 15, it is, not necessary to run the
Mechanical ventilation mechanical ventilation because they are ventilation system at this volume
8
fully enclosed and usually attached in some continuously, provided that the normal rate
Prohibited open flames way to the remainder of the building. is maintained during occupancy.
8
Standard 15 defines two distinct ventilation Thus two distinct ventilation rates are
...I
(...
I/
4
Figure 7 Multiple-Chiller Equipment Figure 9: Dual Purpose Mechanical
Room Layouts Equipment Room Ventilation System
Arrangement A
Exhaust
Fan
Air
Inlet
Air
Inlet Exhaust
Fan
-
Air
Inlet
-
Exhaust
Fan
Arrangement B
Exhaust
Fan
6
Figure 1 0 Suggested Refrigerant 1 losses can be large and can occur quickly,
Vent Piping Choose a purge unit with low refrigerant- compared to low pressure refrigerants.
to-noncondensable-gas discharge ratio and
one that can operate with the chiller off. Sensor location is imprecisely defined by
2 ASHRAE Standard 15 as " . . . locate the
1 -2 Routinely monitor the chiller for leaks by sensor where refrigerant is likely to
logging the operation of the purge system concentrate." Key points to remember are:
and the chiller operating hours. This data 0
provides an excellent indicator of Focus on areas of concentration, rather
refrigeration system integrity. than leakage.
3 e
Choose a purge unit that embodies a safety
Account for airflow patterns in the
system to prevent excessive purging due to
equipment room.
malfunction or a large leak. 0
7
e h
A Publication of
The Trane Company
Commercial Systems Group
La Crosse, WI 54601
The Systems
Manual
The Trane Systems Manual is a unique,
comprehensive resource that will give you
an added advantage whey facing your
clients. With the Systems Manual, you can
easily pull together a professional HVAC
presentation to effectively communicate
your system and equipment ideas. This
colorful manual consists of marketing
presentation brochures that discuss the
importance of comfort for six market
segments: offices, schools, healthcare,
stores, manufacturing and the lodging
industry.
Behind each market segment tab are single Finally, the manual provides the
sheets that describe most of the commonly presentation support for marketing the
used airside systems; single-zone, variable system designer's efforts in determining
air volume, fan-coilhnit ventilators and which system is best for an application.
water-source heat pumps. This section, called computer-aided
systems engineering, outlines the system
Next, on single sheets, are descriptions of design and analysis tools available from ,
popular system options and control The Trane Company. Overall, a
strategies such as heat recovery, thermal comprehensive systems presentation tool
storage, low temperature air, demand developed for use by HVAC practitioners.
limiting and optimum startlstop, to name a
few. For information on how to obtain the
Trane Systems Manual, or for information
To help communicate the myriad of
on Trane's broad line of products and
equipment alternatives, the manual also
services, contact your local Trane
includes a complete portfolio of Trane
commercial sales office.
equipment in a featurelbenefit format. At
this point, system schematic sheets assist
in pulling each of the components together
as a system.
For existing building projects, a section is
devoted to the unique requirements of
constant volume systems such as
multizone, induction, dual duct and terminal
reheat. This section provides an easy to
understand description of the system along
with energy saving retrofit ideas.