Professional Documents
Culture Documents
( Third Revision )
ICS 697.94
© BIS 2018
FOREWORD
This Indian Standard ( Third Revision ) was adopted by the Bureau of Indian Standards, after the draft finalized by
the Refrigeration and Air Conditioning Sectional Committee had been approved by the Mechanical Engineering
Divisional Council.
This standard was first published in 1960 and revised in 1971,1992 and it was second reprinted in May 2002
incorporating the Amendment No 1.
In this revision amendment No 1, 2, 3 and 4 have been incorporated. The major changes in this revision are as
follows:
a) Maximum power consumption has been reduced for the recommended rated cooling capacity.
b) Scope has been modified.
c) Reference of IS 3615 has been added in terminology.
d) Refrigerant used shall be as per IS 16656 : 2017/ISO 817.
e) Air filters shall be tested as per IS 7613.
f) Tolerance for voltage has been changed to ±15 percent for the rating requirement of air conditioners.
g) Fan/Blower speed has been added for cooling test.
h) Variations allowed in the performance test reading for the various temperature has been modified.
This standard is published in two parts. The other part in the series is:
Part 1 Unitary Air Conditioners
The basic unit of measurement together with their symbols for the various quantities used in the text have been
listed in Annex A.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis, shall be rounded off in accordance with IS 2 : 1960
‘Rules for rounding off numerical values (revised)’. The number of significant places retained in the rounded off
value should be the same as that of the specified value in this standard.
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
Indian Standard
ROOM AIR CONDITIONERS — SPECIFICATIONS
PART 2 SPLIT AIR CONDITIONERS
( Third Revision )
1 SCOPE air handling system installed in two separate cabinets.
It is designed primarily to provide conditioned air to
1.1 This standard prescribes the constructional and
an enclosed space, room or zone (conditioned space.
performance requirements of non ducted spilt air
It includes a prime source of refrigeration for cooling
conditioners up to an including capacity of 10 500 W,
and dehumidification and means for the circulation and
up to an including rated voltage of 240 V for single
filtering of air.
phase and 415 V for three phase and rated frequency
of 50 Hz. 3.2 Standard Barometric Pressure — Barometric
pressure of 1.013 25 bar (760 mm Hg).
1.2 This standard also prescribes the test conditions
and the corresponding test procedures for determining 3.3 Room Discharge Air Flow — Rate of flow of air
various performance characteristics of split air from the outlet of the unit into the room side
conditioners which operate non frosting when cooling 3.4 Room Intake Air Flow — Rate of flow of air into
and dehumidifying at standard rating conditions. the unit from the conditioned space.
1.3 This standard specifies split air conditioners which 3.5 Total Cooling capacity —The amount of sensible
may also serve as heaters by heat pump/electric heater and latent heat that the unit can remove from the
application. conditioned space in the definite interval of time.
1.4 This standard is not applicable to the following: 3.6 Rated cooling capacity — Total cooling capacity
at rated conditions.
a) water-source heat pumps or water cooled air
3.7 Total Heating capacity — The amount of heat that
conditioners and
the equipment can add to the conditioned space (but
b) equipment using the absorption refrigeration not including supplementary heat) in the definite
cycle. interval of time.
2 REFERENCES 3.8 Room Calorimeter — It is a test facility consisting
The Indian Standards given in Annex B are necessary of two contiguous calorimeters with a common
adjuncts to this standard and contain provisions which partition. One is designated as the room side
through reference in this text, constitute provisions of compartment, and the other as the outdoor
the standards. At the time of publication, the editions compartment. Each side is equipped with instrumented
indicated were valid. All standards are subject to revision reconditioning equipment whose output may be
and parties to agreements based on this standard are measured and controlled to counterbalance the room
encouraged to investigate the possibility of applying the side humidifying and cooling effect and the outdoor
most recent editions of the Standards indicated. side humidifying and heating effect of the split air
conditioner under test.
3 TERMINOLOGY 3.9 Rated Voltage — Voltage shown on the nameplate
For the purpose of this standard, the definitions given of the unit.
in IS 3615 ‘Glossary of terms used in refrigeration and 3.10 Rated Frequency — Frequency shown on the
air conditioning’ shall apply, in addition to the nameplate of the unit.
following:
4 CLASSIFICATION
Definitions relating to air flow (3.3 to 3.4) are illustrated
in Fig. 1. Exhaust air or fresh air in room side may be According to function and rated cooling capacity, split
indicated in Fig.1, if provided. air conditioners shall be classified as follows:
3.1 Spilt Air Conditioner — It comprises of indoor unit 4.1 Classification by Function
and outdoor unit. The Indoor unit may be mounted on a) Cooling and Dehumidification
floor or wall or ceiling. The Indoor and outdoor units b) Cooling and Heating by Heat Pump
consist of compressor, heat exchangers, fan motors and c) Cooling and Heating by Electric Heater
1
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
4.2 Unit type or cause mould or odours and shall be resistant to attack
of vermin and destructive pests.
a) Single Split having Single indoor and outdoor
unit 5.2.4 Sealing and insulating materials shall not lose
b) Multi Split having Multiple Indoor and Single their essential properties such as adhesion, moisture
outdoor Unit and heat resistance.
4.3 Unit Mounting Arrangement 5.2.5 Internal and external finishes shall be capable of
being cleaned effectively without undue deterioration
a) Floor Type and shall be such as to afford protection against climatic
b) Ceiling Type action in all seasons under normal use. All metal parts
c) Wall Type which are exposed to moisture or ambient conditions
4.4 Recommended classification of the split air shall be corrosion resistant or adequately protected
conditioners of rated cooling capacities are as under (W) against corrosion.
2 500, 3 500, 5 200, 6 400, 7 000, 8 700 and 10 500. 5.3 Electrically Charged Parts
5 CONSTRUCTION 5.3.1 The electrically live parts shall be protected from
accidental contact of the user.
5.1 General
5.3.2 Electric conductors shall be of electrically, thermally
5.1.1 The air conditioner and its parts shall be and mechanically stable and shall be made up of anti-
constructed with the strength and rigidity adequate for corrosive materials such as copper and copper alloys.
normal conditions of handling, transport and usage.
5.3.3 Switches and the like shall work smoothly and
5.1.2 There shall be no sharp edges or corners liable keep good electrical contact.
to cause injury under normal conditions of use and all
5.3.4 Make and break operation or status of a manual
moving parts which constitute accident hazards shall
switch shall be marked on prominent place by letters,
be effectively guarded.
symbols or colours.
5.1.3 Parts which require periodic servicing shall be
5.3.5 Electrical cables used shall conform to IS 694
readily accessible
5.4 Refrigerant Circuit
5.2 Material
5.4.1 The refrigerant pipes and fittings shall be of
5.2.1 Materials used in the construction of cabinet,
approved quality and shall withstand normal working
front panel, etc. shall comply with the corresponding
pressures of air conditioners and should conform to
Indian Standards wherever applicable except where
IS 10773 : 1995 or equivalent national standard/
such requirements are modified by this standard.
international standard.
5.2.2 The material shall be free from defects which
5.4.2 The refrigerant used shall be as per IS 16656 :
are liable to cause undue deterioration of failure.
2017/ISO 817.
5.2.3 Under normal conditions of use and maintenance, NOTE — Regulation by appropriate authority for the use of
the materials used shall not shrink, deteriorate, warp refrigerant shall be as per guidelines issued by statuary authority.
2
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
q) Fresh air volume, if provided; and 8.1.4 Enclosure Sweat Test Conditions
r) Manufacturer’s instructions and requirements The enclosure sweat test shall be conducted under the
which may affect performance. conditions given below:
8 RATING AND TEST CONDITIONS
a) Room air temperature:
8.1 Cooling test 1) Dry bulb temp : 27°C
2) Wet bulb temp : 24°C
8.1.1 Cooling capacity test conditions
b) Outside air temperature:
The Split air conditioner shall have nameplate rating 1) Dry bulb temp : 27°C
determined by tests conducted at the standard rating
2) Wet bulb temp : Not applicable
conditions specified below:
c) Test Frequency — 50 Hz
a) Room air temperature: d) Test voltage — Rated Voltage
1) dry bulb temp : 27°C e) Fan/blower speed — Speed declared by
2) wet bulb temp : 19°C manufacturer.
b) Outside air temperature:
8.2 HEATING TEST
1) dry bulb temp : 35°C
2) wet bulb temp : 24°C 8.2.1 Heating capacity test conditions
c) Test Voltage — Rated voltage The heating capacity rating shall be conducted under
d) Test Frequency — Rated frequency the conditions given below:
e) Fan/blower speed — Speed declared by a) Room air temperature:
manufacturer.
1) dry bulb temp : 20°C
8.1.2 Maximum Operating Test Conditions 2) wet bulb temp : Not specified
The maximum operating tests shall be conducted under: b) Outside air temperature:
1) dry bulb temp : 7°C
a) Room air temperature:
2) wet bulb temp : 6°C
1) dry bulb temp : 35°C
c) Test Voltage — Rated voltage.
2) wet bulb temp : 24°C d) Test Frequency — Rated frequency
b) Outside air temperature:
1) dry bulb temp : 46°C 8.2.2 Heating by Heat Pump Overload Rating Test
2) wet bulb temp : Not applicable Conditions (maximum heating performance test)
c) Test Voltage — Rated Voltage. The maximum operating tests shall be conducted under
d) Test Frequency — Rated frequency the conditions specified below:
e) Fan/blower speed — Speed declared by Room air temperature:
manufacturer.
a) Dry bulb temp : 27°C
8.1.3 Freeze-Up Test Conditions b) Wet bulb temp : Not specified
Freeze up tests shall be conducted under the conditions Outside air temperature:
specified below:
c) Dry bulb temp : 24°C
a) Room air temperature: d) Wet bulb temp : 18°C
1) dry bulb temp : 21°C Test Frequency — Rated frequency
2) wet bulb temp : 15°C
Test voltage — 85 percent and 115 percent of rated voltage
b) Outside air temperature:
1) dry bulb temp : 21°C 9 PERFORMANCE REQUIREMENTS
2) wet bulb temp : Not Specified
9.1 Variations Allowed in Performance Test
c) Test Voltage — 85 percent and 115 percent of Readings
Rated Voltage.
d) Test Frequency — Rated frequency The conditions specified for the test shall be average
values within the following variations:
e) Fan/blower speed — Speed declared by
manufacturer. a) ±2 percent of the standard voltage and
frequency; and
4
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
b) ±0.3°C for the specified dry bulb 9.4.5.3 The motor overload protective device may trip
temperatures, ±0.2°C for the specified wet only during the first 5 min after the shut down period
bulb temperatures and ±0.5°C for the specified of 3 min. During the remainder of that 1 h test period,
temperatures for all other Test. no motor overload protective device should trip.
9.2 Safety 9.4.5.4 For those models so designed that resumption
Split air conditioners shall meet as far as applicable of operation does not occur after initial trip within the
the requirements of IS 659. first 5 minutes, the unit may remain out of operation
for not longer than 60 min. It should then operate
9.3 Power Factor Test continuously for 1 h.
When operating under normal load under the conditions 9.5 Freeze-Up Tests
specified in 8.1.1 with controls set for maximum
cooling and with ventilating air damper and exhaust 9.5.1 Purpose
damper, if any, closed, the split air conditioner shall The air blockage test and the drip test shall be conducted
have overall power factor, measured at 230 volts, 50 c/s, to determine the ability of the air conditioner to operate
of not less than 0.90. satisfactorily under conditions with the maximum
9.4 Maximum Operating Conditions Test tendency to frost or ice the evaporator.
Test voltages should be as specified in 8.1.2. These The test should be continuous, with the unit on the
voltages should be maintained at the specified cooling cycle for 4 h after establishment of the specified
percentages under running conditions. The electrical temperature conditions.
service supplied to the unit service connection should 9.5.3.2 Requirements
be such that the voltage will not rise more than 3 percent
when the unit is stopped. After the service has been At the end of 4 h of operation, any accumulation of ice
adjusted to accomplish this result, no subsequent or frost on the evaporator shall not cover more than 50
adjustment should be made during either test. percent of the indoor side face area of the evaporator
coil.
9.4.4 Procedure
9.5.4 Drip Test
The split air conditioner shall be operated continuously
for 2 h after the specified air temperatures and 9.5.4.1 Procedure
equilibrium condensate level have been established. All The unit should be operated for 6 h with the room side
power to the split air conditioner shall then be cut off air inlet covered to completely block the passage of air
for 3 min and this test no water should be sprinkled on so as to attempt to achieve complete blockage of the
to the condenser by external means other than what is evaporator coil by frost.
condensed in the evaporator.
9.5.4.2 After 6 h operating period, the unit should be
9.4.5 Requirements
stopped and the air inlet covering removed until the
9.4.5.1 During one entire test, the split air conditioner accumulation of ice or frost has melted by itself. The
should operate without visible or audible indication of unit should then be turned on again, with the fans
damage and without tripping. operating at the highest speed, for 5 min.
9.4.5.2 The split air conditioner fan/blower motor 9.5.4.3 Requirements
should operate continuously for the first 2 h of the test
During the test no ice shall drop from the unit, and no
without tripping of the motor overload protective
water shall drip or blow off the unit on the room side.
devices.
5
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
6
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
simultaneous methods for determining capacities shall 9.11 Heat Pump Heating Capacity Test
be used. One method shall determine capacity on the
After installation of the air conditioner in the calorimeter
room side and the other shall determine the capacity
specified in 12, the operation switches and others shall
on the outdoor side.
be put in operation under the condition of heating by
(These two simultaneous determinations shall agree heat pump shall be worked out with the measuring
within 4 percent of the value obtained on the room side method and calculating formula defined in 10. The
for the test to be valid). heating capacity shall include those of auxiliary electric
heater and humidifying heater, if these are provided.
9.9.4.1 Test conditions shall be maintained until
equilibrium has been reached, and maintained for not The measured heating capacity shall not be less than
less than 1 hour before recording data for the capacity 90 percent of the rated heat pump capacity.
test. The test shall then be run for 1 h recording data
every 10 min, giving 7 sets of readings. 10 CALCULATIONS
9.9.4.2 The data to be recorded for this test are given Cooling capacity /Heating capacity shall be calculated
in Annex D. This Annex shows general information in terms of watts (W)
required, but is not intended to limit the data to be
10.1 Capacity Rating
obtained
10.1.1 Total Cooling Effect on Room Side
9.9.5 Requirements
The total cooling effect on the room side, as tested in
The capacity of the production unit as determined on
either the calibrated or balanced ambient room type
the room side shall be not less than 95 percent of the
calorimeter (see Fig. 2A and 2B) is calculated as follows:
name plate rating.
qtr = ∑ Er+ (hw1– hw2) wr + qlp + qlr ....................(1)
9.10 Noise Test
where
For noise test, the air conditioner shall be installed in a
noise measuring room shown in Fig. 7. The split air qtr = total room cooling effect as determined on
conditioner shall be operated in the cooling condition room side compartment, in watts;
as given in 8.1.1. The noise level in the indoor side ∑ Er= sum of all power input to room side
shall be measured in accordance with the method compartment, in watts;
described in 15 and shall not exceed the value given in hw1 = specific enthalpy of water or steam supplied
Table 3 and the noise level in the outdoor side shall be to maintain humidity. If no water is
measured in accordance with IS 4758 and shall not introduced during the test, hw1, is taken at
exceed the value given in Table 3. the temperature of the water in the humidifier
tank of reconditioning equipment, in kJ/kg;
Table 3 Noise Level
hw2 = specific enthalpy of condensed moisture
Rating Cooling Maximum Noise Level in dBA leaving the room side compartment. Since
Capacity (kW) Indoor side Outdoor side transfer of condensed moisture from room
Up to 5.2 58 68 side to outdoor side compartment usually
More then 5.2 62 70 takes place within the air conditioner. Due
to the practical difficulty in measuring its
NOTE — During starting and stopping, there should not be any temperature, the temperature of the
touching or abnormal noise.
7
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
condensate may be assumed to be at the numerically equal to qlp used in equation (1)
measured or estimated wet bulb temperature (see 10.1.1) only if the area of separating
of the air leaving the air conditioner, in kJ/kg; partition exposed to outdoor side is equal to
wr = water vapour (rate) condensed by air the area exposed to the room side
conditioner. This is measured by compartment, in watts; and
reconditioning equipment as the amount of qlr = heat leakage out of outdoor side (but not
water evaporated into room side including the separating partition), as
compartment to maintain required humidity, determined from the calibrating test, in watts.
in g/sec; 10.1.3 Total Room Dehumidifying Effect
qlp = heat leakage rate into room side
The total dehumidifying effect is calculated as follows:
compartment through separating partition
between room side and outdoor side qd = K2 wr ...……………..……………… (3)
compartments, as determined from where
calibrating test (or may be based on
calculation in case of balanced ambient room qd = total room dehumidifying effect in watts;
type calorimeter), in watts; and K2 = 2 460 kJ/kg; and
qlr = heat leakage rate into room side wr = water vapour condensed by air conditioner
compartment through wall, floor and ceiling as defined in 10.1.1.
(but not including the separating partition) 10.1.4 Total Room Sensible Cooling Effect
as determined from calibrating test, in watts.
The total room sensible cooling effect is calculated as
10.1.2 Total Cooling Effect on Outdoor Side
follows:
The total room cooling effect on the outdoor side, as
qs = qtr – qd.………….……………………….(4)
tested in either the calibrated or balanced ambient room
type calorimeter (see Fig. 2A and 2B) is calculated as where
follows: qs = total room sensible cooling effect, in watts,
qto = qo– ∑ Eo– E + (hw3– hw2) wr+ qlp+ q1o ....(2) qtr = taken from equation (1), and
where qd = taken from equation (3).
qto = total room cooling effect as determined on 10.2.1 The Heating Capacity by Heat Pump on Room
outdoor side, in watts; Side
qo = heat removed by cooling coil in outdoor side The heating effect on the room side as tested in either
compartment, in watts; the calibrated or balanced ambient room type
∑Eo= sum of all power input to any equipment, calorimeter is calculated as follows:
such as reheaters,circulating fans, etc, in
qhr = q – ∑ Ehr+ qlp+ qlr ………………………(6)
outdoor side compartment, in watts;
where
E = total power input to air conditioner, in watts;
hw3 = specific enthalpy of condensate removed by qhr = total heating capacity calculated on room
air treating coil in outdoor side compartment side of the calorimeter, in watts;
reconditioning equipment taken at the 1 = heat quantity removed by the cooling coil of
temperature at which the condensate leaves the room side of the calorimeter, in watts;
the compartment, in kJ/kg ∑Ehr= total power input to room side of the
hw2 = specific enthalpy of condensed moisture calorimeter, in watts;
leaving the room side compartment, as
qlp = heat leakage through the partition between
defined in 11.1.1;
room side and outdoor side, in watts); and,
wr = water vapour condensed by air conditioner,
qlr = heat leakage through the floor, the wall
as defined in 11.1.1;
(exclusive of the partition) and the ceiling,
qlp = heat leakage rate into room side in watts.
compartment through separating partition
between room side and outdoor side 10.2.2 The Heating Capacity by Heat Pump on
compartments, as determined from Outdoor Side
calibrating test (or may be based on The heating capacity by heat pump on the outdoor side
calculation in case of balanced ambient room as tested in either the calibrated or balanced ambient
type calorimeter).This quantity will be room type calorimeter is calculated as follows
8
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
interchanged between inlet and outlet positions to either indicating type or integrating type of instruments.
improve accuracy.
11.3.2 Electrical measuring instruments shall have
11.1.7 Temperature of fluids within conduits should accuracy of ± 0.5 percent of the quantity measured.
be measured by inserting temperature instruments
directly within the fluid or within a well inserted into 11.4 Water Flow Measuring Instruments
the fluid. If a glass thermometer is to be inserted directly 11.4.1 Volume measurements shall be made with either
into the fluid, it shall be calibrated for the effect of of the following instruments having an accuracy of ±1.0
pressure. percent of the quantity measured:
11.1.8 Temperature measuring instruments should be a) Liquid quantity meter, measuring either mass
adequately shielded from radiation from any adjacent or volume; and
heat sources.
b) Liquid flow rate meter.
11.2 Pressure Measuring Instruments 11.4.2 Liquid quantity meter shall employ a tank having
11.2.1 Accuracy of pressure measuring instruments, sufficient capacity to accumulate the flow for at least
not including barometers should permit measurements 2 min.
within ± 1 N/m2 (0.01 m bar) (0.1 mm H2O).
11.5 Noise Measuring Instrument
11.2.2 In no case the smallest scale division of the
Noise measurement shall be made with a sound level
pressure measuring instrument shall exceed the specified
meter whose accuracy is ±1.0 percent of the quantity
accuracy.
measured. The instrument shall be able to measure a
11.2.3 Barometric pressure shall be measured by a weighted sound pressure level.
barometer having scale markings permitting readings
with an accuracy within ±0.1 percent. 11.6 Other Instruments
11.6.1 Time interval measurements should be made
11.3 Electrical Instruments
with instruments whose accuracy is ± 0.2 percent of
11.3.1 Electrical measurements shall be made with the quantity measured.
10
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
11.6.2 Mass measurements should be made with The equalizing device shall be adjusted during
apparatus whose accuracy is ± 1.0 percent of the calorimeter tests or air flow measurements, so that the
quantity measured. static pressure difference between the room side and
outdoor side compartments is not greater than 1.5 N/m2
12 CALORIMETERS
or 0.015 mbar or 0.153 mm H2O. The construction
12.1 Calorimeter Required for Testing split Air details and calculations are specified in 13.
Conditioners
Air conditioners shall be tested for cooling capacity in
a room calorimeter of either the calibrated or balanced
ambient type as described in 12.3 and 12.4.
12.2 Calorimeters — General
12.2.1 The calorimeter provides a method for
determining cooling capacity simultaneously on both
the room side and the outdoor side. The room side
capacity determination is made by balancing the cooling
and dehumidifying effects with measured heat and water
inputs. The outdoor side capacity provides a confirming
test of the cooling and dehumidifying effect by balancing
the heat and water rejection on the condenser side with
a measured amount of cooling medium.
12.2.2 The two calorimeters compartments, room side
and outdoor side, are separated by an insulated partition
FIG. 3 AIR FLOW MEASUREMENT NOZZLE
having an opening into which the room air conditioner
is mounted. The air conditioner shall be installed using
12.2.4 The size of the calorimeter shall be sufficient
supporting members and filler pieces in a manner similar
to avoid any restriction to intake or discharge openings
to a normal installation. No effort shall be made to seal
of the air conditioner perforated plates or other suitable
the internal construction of the air conditioner to prevent
grilles shall be provided at the discharge opening from
air leakage from the condenser side to the evaporator
the reconditioning equipment to avoid face velocities
side or vice versa. No connections or alterations shall
exceeding 0.5 m/s. Sufficient space shall be allowed in
be made to the air conditioner which might in any way
front of any inlet or discharge grilles of the air
alter its normal operation.
conditioner to avoid interference with air flow.
12.2.3 A pressure equalizing device shall be provided Minimum distance from the air conditioner to side walls
in the partition between the room side and the outdoor or ceiling of the compartments should be 1 m = except
side compartments to maintain a balanced pressure for the back of a consol type room air conditioner which
between these compartments and also to permit should be in normal relation to the wall. The suggested
measurement of leakage, exhaust and ventilation air. dimensions for the calorimeter are given below :
This device consists of one or more nozzles of the type
shown in Fig. 3, a discharge chamber equipped with an Sl. Maximum Suggested minimum inside
exhaust fan and manometers for measuring No. rated cooling dimensions of each room of
compartment and air flow pressures. A suggested capacity of calorimeter
arrangement of components is shown in Fig. 4. unit (kW)* Width Height Depth
Since the air flow from one compartment to the other (meter) (meter) (meter)
may be in either direction, two such devices mounted
(1) (2) (3) (4) (5)
in opposite direction, or a reversing device shall be used.
i) 3 2.4 2.1 1.8
The manometer pressure pick up tubes shall be so
located as to be affected by air discharged from the air ii) 6 2.4 2.1 2.4
conditioner on test or by the exhaust from the pressure iii) 9 2.7 2.4 3.0
equalizing device. The fan or blower which exhaust air iv) 10.5 3 2.4 3.7
from the discharge chamber shall permit variation of
its air flow by suitable means, such as a variable speed * Figures given are rounded off value.
drive, or a damper as shown in Fig. 4. The exhaust
from this fan or blower shall be such that it will not 12.2.5 Each compartment shall be provided with
affect the inlet air to the air conditioner on test. reconditioning equipment to maintain specified air flow
11
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
and prescribed conditions. Reconditioning equipment calorimeter walls for ease in reading the thermometers,
for the room side compartment shall consist of heaters but should be sealed and insulated to avoid air leakage
to supply sensible heat and a humidifier to supply and heat leakage. The sampling tube fans and fan motors
moisture. The energy supply may be electric, steam or shall be installed completely within the calorimeter
any other source that can be controlled and measured. compartments and their electrical input included in the
Reconditioning equipment for the outdoor side load measurement. The fan motor shall be located so
compartment shall provide cooling and that its heat will not cause stratification of the air passing
dehumidification. A cooling coil equipped with by pass into the air conditioner. The fan should draw the air
dampers to control the dry bulb temperature and over the thermometers and return the air to the same
supplied with a variable temperature water or variable compartment in a manner that will not affect air
water quantity to control the wet bulb temperature may temperature measurements or inlet or discharge air flow
be used. If desired, dehumidifying apparatus of reheating of the air conditioner.
apparatus or both may be used in combination with the
12.2.7 It is recognised that in both the room side and
cooling coil. Reconditioning equipment for both
outdoor side compartments, temperature gradients and
compartments shall be provided with fans of sufficient
air flow patterns result from the interaction of the
capacity to overcome the resistance of the
reconditioning equipment and the room air conditioner
reconditioning equipment and circulate not less than
being tested. Therefore, the resultant conditions are
two times the quantity of air discharged by the air
peculiar to and depend upon a given combination of
conditioner to the room side or to the outdoor side as
compartment size, arrangement and size of
the case may be. In no case shall the reconditioning
reconditioning equipment, and the air conditioners air
equipment discharge less than one compartment air
discharge characteristics.
change per minute.
Accordingly, no single location for the measurement of
12.2.6 Remote reading thermometers, instruments, or
dry bulb and wet bulb temperatures may be specified
air sampling tubes shall be used to measure the specified
which will be acceptable for all combinations of
wet bulb and dry bulb temperature in both calorimeter
calorimeter facilities and room air conditioners which
compartments. Air sampling shall comply with 11.1.5.
may be tested.
The air sampling tube may be brought outside of the
12
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
It is intended that the specified test temperatures that of the other walls, the heat leakage through
surrounding the unit being tested shall simulate as nearly the partition may be determined on a proportional
as possible a normal installation of such a unit operating area basis”.
at ambient conditions identical with these specified test
12.3.3 For calibrating the heat leakage through the
temperatures.
separating partition, the following procedure may be
The point of measurement of specified test used:
temperatures, both wet bulb and dry bulb, shall be such
“A test is carried out as described in 12.3.2. Then
that the following conditions are fulfilled:
the temperature of the adjoining area on the other
a) The measured temperatures shall be the side of the separating partition may be raised to
representative of the temperature surround-ing equal the temperature in the heated compartment
the unit, and simulate the conditions thus eliminating heat leakage through the
encountered in an actual application for both partition, while the 11°C differential is
room and outdoor sides as indicated above, maintained between the heated compartment and
and the ambient surrounding the other five enveloping
b) At the point of measurement, the temperature surfaces. The difference in heat between the first
of air shall not be affected by air discharged test and the second test will permit determination
from the test unit. This makes it mandatory of the leakage through the partition alone”.
that the temperatures are measured upstream 12.3.4 For the outdoor side compartment equipped
of any recirculation produced by the test unit. with means for cooling, an alternate means of
NOTES calibration may be used to cool the compartment to
1 If the conditions of air movement and air flow patterns in the temperature at least 11°C below the ambient
calorimeter compartment are favourable, the temperature may temperature (on six sides) and carry out a similar
be measured at the outlet of the reconditioning equipment. analysis.
2 It has been established that the unit being tested does not
produce any bypassed air from discharge to intake opening, the 12.4 Balanced Ambient Room Type Calorimeter
specified temperatures may be measured immediately upstream
of such intake opening. In this case, care shall be taken to ensure 12.4.1 The balanced ambient room type calorimeter
that the temperature measuring equipment does not help or similar to that shown in Fig. 2B is based on the principle
penalize the conditioner in any way.
of maintaining the dry bulb temperatures surrounding
12.2.8 Interior surfaces of the calorimeter
the particular compartment equal to the dry bulb
compartments shall be of non porous material with all
temperatures maintained within that compartment.
joints sealed against air and moisture leakage. Access
doors shall be tightly sealed against air and moisture If the ambient wet bulb temperature is also maintained
leakage by use of gaskets or other suitable means. equal to that within the compartment, the vapour
proofing provisions of 12.2.8 are not required.
12.3 Calibrated Room Type Calorimeter
12.4.2 The floor, ceiling and walls of the calorimeter
12.3.1 Calibrated room type calorimeter is shown in compartments shall be spaced a sufficient distance away
Fig. 2A. Each calorimeter, including the separating from the floor, ceiling and walls of the controlled areas
partition, shall be insulated to prevent heat leakage in which the compartments are located in order to
(including radiation) in excess of 5 percent of the air provide uniform air temperature in the intervening
conditioner capacity. It is recommended that an air space space. It is recommended that this distance be at least
permitting free circulation may be provided under the 300 mm. Means shall be provided to circulate the air
calorimeter floor. within the surrounding space to prevent stratification.
12.3.2 Heat leakage may be determined in either the 12.4.3 Heat leakage through the separating partition
room side or outdoor side compartments by the shall be introduced into the heat balance calculation
following method: and may be calibrated in accordance with 12.3 or may
be calculated.
“All openings shall be closed. Either
compartment may be heated by electric heaters 12.4.4 It is recommended that the floor, ceiling and
to a temperature of at least 11°C above the walls of the calorimeter compartments be insulated so
surrounding ambient temperature. The ambient as to limit heat leakage (including radiation) to not more
should be maintained at a constant temperature than 10 percent of the air conditioner capacity, with
± 1°C outside all six enveloping surfaces of the a 11°C temperature difference or 300 W (250 kcal/h)
compartment including the separating partition. for the same temperature difference, whichever is
If the construction of the partition is identical with greater, as tested using the procedure given in 12.3.2.
13
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
14
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
13.4 Room Discharge Air Flow Measurement K3 = 1.41 for international system (SI) units and
15950 for metric technical units
13.4.1 Room discharge air flow should be measured
with apparatus similar to that illustrated in Fig. 6. Cd = Nozzle coefficient(see 14.2)
A = Nozzle area (m2)
13.4.2 The outlet or outlets of the room air conditioner
should be connected to the receiving chamber by hp = Static pressure difference across nozzle or
adapter ducting of negligible air resistance. velocity pressure of nozzle throat, the
P°hp vυ′
a n
approach velocity being considered
13.4.3 The exhaust fan should be adjusted to give zero P 1+ k negligible
static pressure at the discharge of the split air
v’n = negligible Specific volume of humid air at
conditioner in the receiving chamber.
nozzle inlet
13.4.4 The following readings shall be taken: Po = Standard barometric pressure = 1.013 25 bar
a) Barometric pressure. (760 mm Hg)
b) Nozzle dry bulb and wet bulb temperatures, P = Barometric pressure at nozzle inlet
and k = Specific humidity at nozzle inlet
c) Nozzle velocity pressure. vn = Specific volume of humid air at dry bulb and
13.4.5 Air mass flow rate and air volume flow rate wet bulb temperature conditions existing at
through a single nozzle shall be determined as follow: nozzle inlet but at standard barometric
pressure
NOTE — Where the barometric pressure deviates from the
hp
standard barometric pressure by not more than 0.03 bar (22.5 mm
Qm = K3 Cd A υ′ ...(8)
n Hg), v’nmay, for simplicity, be considered equal to vn.
15
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
13.5.2 With the equalizing device adjusted for a 15.1 Classification of Tests
maximum static pressure differential between room side Test shall be classified into the following three groups:
and outdoor side compartment of 1 N/m2; 0.01m bar
(0.1 mm H2O) the following readings should be taken: a) Production routine tests,
b) Type tests, and
a) Barometric pressure,
c) Acceptance tests.
b) Nozzle dry bulb temperatures, and
c) Nozzle velocity pressure. 15.1.1 Production Routine Tests
13.5.3 Air flow values shall be calculated in accordance These shall consist of routine tests that would be
with 13.4.5. conducted on each and every unit after completion at
the manufacturer’s works (see 15.3).
14 NOISE TEST 15.1.2 Type Tests
14.1 Noise Measuring Room These tests shall consist of the tests that would be
The noise measuring room shall be anechoic room necessary to check up the performance and
complying with the following: characteristics of the units and components and shall
be carried out by a recognized testing authority who
a) Background noise should be less than the may be the manufacturer if approved by the purchaser.
measured value by at least 11 dBA; and Once a room air conditioner has undergone type tests,
b) Distance between the wall and microphone to any minor or essential alterations which the
be such that the effect of sound reflected from manufacturer intends to make shall be reported to the
the wall can be negligible. testing authority laid down in this standard (see 15.4).
The room air conditioner shall be mounted firmly and If the purchaser desired any of the production routine
the microphone shall be located indoor size at the tests to be repeated at the time of purchase, then where
position shown in Fig. 7. The sound level in A scale agreed to between the purchaser and the manufacturer,
shall be measured using sound level meter. the tests may be carried out at the manufacturer’s works;
alternatively, the test may be repeated at the place at
16
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
the place specified by the purchaser provide that all metal parts at normal room temperature.
the arrangements for tests are made by the purchaser at The test voltage shall be alternating approximately sine
the specified place. wave form and of any convenient frequency between
15.2 Samples for Tests 25 to 100 c/s.
15.2.1 Type Tests 15.3.5 Performance Test
Two room air conditioners of each size be sent along Measurements shall be made of the following under
with manufacturer’s detailed specifications to the the prevailing ambient conditions and the performance
recognised testing authority for the purpose of type figures from (a) to (e) shall be compared with the unit
tests. The samples shall be picked up at random from which has already passed the type test:
stock or routine factory production. a) Dry bulb temperature of return air,
15.2.2 Acceptance Tests b) Dry bulb temperature of the supply air,
The number of samples shall be agreed upon between c) Voltage,
the manufacturer and the purchaser. d) Current consumption, and
e) Total power consumption.
15.3 Production Routine Tests
15.3.5.1 Permissible variations from the type
15.3.1 General Running Test
tested unit
Each unit shall be given a run to ensure vibration free
Temperature ± 1°C
and thorough running of mechanical parts.
Electrical requirements ± 5 percent
15.3.2 Pressure Test or Leakage Test
NOTE
No part of the assembly under test shall show signs of
Instruments accuracy shall be as follows: —
refrigerant leakage under normal working pressure
Temperature ± 0.2°C
when tested with a leak detector. This shall be in
Electrical meters Class 1
addition to the manufacturer’s production test on each
unit at the appropriate pressure corresponding to the 15.3.6 Leakage Current Test
refrigerant used.
The leakage current shall not exceed 3.5 mA when
15.3.3 Insulation Resistance Test tested as per IS 302 (Part 1).
The insulation resistance between all electric circuits
15.3.7 Earthing Resistance Test
and the metal parts when measured at normal room
temperature with a voltage of not less than 500 V dc The Earthing Resistance of an air conditioner shall not
shall not be less than 1MΩ. exceed 0.1 ohms when tested as per IS 302 (Part 1).
15.3.4 High Voltage Test NOTE — The tests at 15.3.1 and 15.3.5 may be carried out
separately on each indoor and condensing units without inter-
The electrical insulation of all circuits shall be such as connecting. These tests on the inter-connected units may be
to withstand a test pressure of 1 000 Vrms applied for carried out as per sampling plan agreed between manufacturer
not less than 2 seconds between circuits and accessible and purchaser.
17
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
15.4.1 The type test report shall also contain the plate Each split air conditioner may also be marked with the
particulars of the split air conditioners for the purposes Standard Mark.
of identification. 17.2.1 The use of the Standard Mark is governed by
the provisions of Bureau of Indian Standards Act, 1986
16 MANUFACTURER’S GUARANTEE
and the Rules and Regulations made thereunder. The
The manufacturer shall give a guarantee for the details of conditions under which the license for the
soundness of construction and performance of the air use of Standard Mark may be granted to manufacturers
conditioner, and shall be responsible for putting right or producers may be obtained from the Bureau of Indian
any manufacturing defects free of charge for a period Standards.
of twelve months right from the date of sale to the
original purchaser or date of inspection of approval in 18 PRECAUTIONS
the case of Government or Semi Government 18.1 Precautions to install and to run the split air
Institutions. Such repairs or replacements of defective conditioner shall be written on the main body and/ or
parts shall be carried out at manufacturer’s works or in the Instruction Manual.
his authorised agent at site or at service shop.
18
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX A
(Foreword)
BASIC UNITS OF MEASUREMENT AND THEIR SYMBOLS
19
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX B
(Clause 2)
LIST OF REFERRED INDIAN STANDARDS
ANNEX C
(Clause 6.1.2.2)
RATING CONDITIONS FOR UNITS INTENDED FOR EXPORT
20
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX D
(Clauses 9.7.3, 9.8.3 and 9.9.4.2)
DATA TO BE RECORDED FOR COOLING/HEATING CAPACITY TESTS
The following data shall be recorded for cooling (calibrated room type) (see Fig. 2A);
capacity tests: 11. Total power input to room side and outdoor side
1. Date; compartment;
2. Observers; 12. Water quantity evaporated in humidifier;
3. Barometric pressure; 13. Temperature of humidifier water entering room
side compartment or in or in humidifier Tank
4. Applied voltage for each test unit motor;
14. Cooling water flow rate through outdoor side
5. Frequency of applied voltage for each test unit
compartment heat rejection coil;
motor,
15. Temperature of cooling water entering outdoor
6. Total power input to unit, except if more than one
side compartment for heat rejection coil;
external power connection is provided on unit,
record input to each connection separately; 16. Temperature of cooling water leaving outdoor side
compartment from heat coil;
7. Total current input to unit;
17. Water condensed in outdoor side compartment;
8. Control dry bulb and wet bulb temperatures of
air (room side calorimeter compartment) 18. Temperature of condensed water leaving outdoor
(see 12.2.7); side compartment;
9. Control dry bulb and wet bulb temperatures of 19. Volume of air flow through measuring nozzle of
air (outdoor side calorimeter compartment) separating partition flow meter; and
(see 12.2.7); 20. Static air pressure difference across separating
10. Average air temperature outside the calorimeter partition calorimeter compartments.
21
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards : Monthly Additions’.
This Indian Standard has been developed from Doc No.: MED 03 (1391).
(Third Revision)
(Page 1, clause 1.1) ― Substitute the following for the existing clause:
‘1.1 This standard specifies safety and performance requirements of single or three phase non-ducted split with
single, two stage, multi-stage, fixed and variable speed air conditioner and heat pumps (residential application)
rated capacity up to and including 18 000 W employing air cooled condensers. Air conditioners above 18 000
W will be covered in IS 8148. This standard is limited to systems utilizing single refrigeration circuit and
having one evaporator and one condenser.’
(Page 1, clause 3.8) — Substitute the following for the existing clause:
3.8.1 Room Calorimeter — It is a test facility consisting of two contiguous calorimeters with a common
partition. One is designated as the room side compartment, and the other as the outdoor compartment. Each side
is equipped with instrumented reconditioning equipment whose output may be measured and controlled to
counterbalance the room side humidifying and cooling effect and the outdoor side humidifying and heating
effect of the split air conditioner under test.
3.8.2 Room Psychrometric — It is facility consisting of two contiguous test rooms with a common partition.
One is designed as the room side compartment and the other as the outdoor compartment. Each side is equipped
with reconditioning equipment for maintaining the required room temperature and humidity.
‘3.11 Fixed Capacity Unit — Equipment which does not have possibility to change its capacity. This definition
applies to each cooling and heating operation individually.
3.12 Two-stage Capacity Unit — Equipment where the capacity is varied by no more than two steps. This
definition applies to each cooling and heating operation individually.
3.13 Multi-stage Capacity Unit — Equipment where the capacity is varied by three or four steps. This
definition applies to each cooling and heating operation individually.
3.14 Variable Capacity Unit — Equipment where the capacity is varied to represent continuously variable
capacity. This definition applies to each cooling and heating operation individually.
3.15 Indian Seasonal Energy Efficiency Ratio (ISEER) — Ratio of the total amount of heat that equipment
can remove from the indoor air when operated for cooling in active mode to the total amount of energy
consumed by equipment during the same period.
In the standard wherever the word cooling seasonal performance factor (CSPF) occurs, it should be considered
as ISEER.
Price Group 13
1
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
3.16 Cooling Seasonal Total Load (CSTL) — Total annual amount of heat that is removed from indoor air
when equipment is operated for cooling active mode
3.17 Cooling Seasonal Energy Consumption (CSEC) — Total annual amount of energy consumed by
equipment when it is operated for cooling active mode.’
(Page 1, clause 4.1) — Substitute the following for the existing clause:
(Page 2, clause 5.2.1) — Substitute the following for the existing clause:
‘5.2.1 Materials used in the construction of cabinet, front panel, etc. shall comply with the corresponding
Indian/International Standards if any except where the specific requirement and compliance are specified in this
standard.’
(Page 2, clause 5.3.5) — Substitute the following for the existing clause:
‘5.3.5 Supply cord used shall be either PVC insulated and sheathed cables conforming to IS 694 or elastomer
insulated and sheathed conforming to IS 9968 (Part 1).’
5.3.6 Conductors for supply cord shall have a nominal cross-sectional area not less than those specified in 25.8
of IS 302-1.’
(Page 2, clause 5.4.1) — Substitute the following for the existing clause:
‘5.4.1 The refrigerant pipes and fittings shall be of approved quality and shall withstand maximum working
pressures in refrigeration circuits of air conditioners and should conform to IS 10773 or equivalent
National/International standard.
(Page 3, clause 5.7) — Substitute the following for the existing clause:
Standard filters of following specification shall be provided on indoor units to prevent dust to enter in coils:
2
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
(Page 3, clause 5.8) — Substitute the following for the existing clause:
(Page 3, clause 5.10) — Substitute the following for the existing clause:
‘5.10 Motor
Fan/blower motor, driven by squirrel cage induction motors shall conform to IS 996.’
(Page 3, clause 6.1) — Substitute the following for the existing clause:
Cooling capacity ratings shall be based on tests conducted under conditions specified in 8.1.1 and with test
methods described in 9.9.4. Ratings shall include the total cooling capacity stated in watt(W).
NOTE—The pipe length between indoor unit and outdoor unit shall be minimum 3 m or higher as declared by the manufacturer
for wall mounted and 5 m for floor and ceiling mounted.’
(Page 3, clause 6.3) — Substitute the following for the existing clause:
‘6.3 Power Consumption Ratings for Cooling and Heating by Heat Pump
6.3.1 The rate of power consumption for cooling by air conditioner shall be based on tests conducted as per 9.7
and shall be stated in W.
6.3.2 The rate of power consumption for heating by heat pump shall be based on tests conducted under the
conditions as per 9.8 and shall be stated in W.’
(Page 3, clause 6.6, line 5) — Substitute ‘±10 percent’ for ‘±15 percent’.
[Page 3, clause 7.2 k)] — Substitute the following for the existing:
3
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 4, clause 8.1.1 b) 2)] — Substitute the following for the existing:
[Page 4, clause 8.1.1 e)] — Substitute the following for the existing:
‘e) Fan / Blower speed— Speed declared by manufacturer to attain room discharge air flow as per clause 6.4.’
[Page 4, clause 8.1.2 b) 2)] — Substitute the following for the existing:
[Page 4, clause 8.1.2 c)] — Substitute the following for the existing:
[Page 4, clause 8.1.2 e)] — Substitute the following for the existing:
‘e) Fan / Blower speed— Speed declared by manufacturer to attain room discharge air flow as per 6.4.’
[Page 4, clause 8.1.3 c)] — Substitute the following for the existing:
[Page 4, clause 8.1.3 e)] — Substitute the following for the existing:
‘e) The controls, fan speeds, dampers and grilles of the equipment shall be set to maximize the tendency to
produce frost or ice on the evaporator, provided such settings are not contrary to the manufacturer’s operating
instructions.’
[Page 4, clause 8.1.4 b) 2)] — Substitute the following for the existing:
[Page 4, clause 8.1.4 e)] — Substitute the following for the existing:
‘e) The controls, fans, dampers and grilles of the equipment shall be set to produce the maximum tendency to
sweat, provided such settings are not contrary to the manufacturer’s operating instructions.’
[Page 4, clause 8.2.1 a) 2)] — Substitute the following for the existing:
‘e) On the indoor-side of the heat pump, grille positions, damper positions, fan speeds, etc. shall be set in
accordance with the manufacturer’s published installation instructions, which are normally provided with the
equipment. In the absence of such installation instructions, grille positions, damper positions, fan speeds, etc.
shall be set to provide the maximum heating capacity when testing at the temperature conditions as per 8.2.1.’
(Page 4, clause 8.2.2, last line) — Substitute ‘Test voltage — 90 percent and 110 percent of rated voltage’
for ‘Test voltage — 85 percent and 115 percent of rated voltage’
4
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 4, clause 9.1 a), b)] — Substitute the following for the existing:
b) ±0.3oC for the specified dry bulb temperature, ±0.2oC for the specified wet bulb temperature during the
cooling capacity test and ±0.5oC for the specified temperature for all other test.’
‘9.2 Safety
Electrical safety tests to be carried as per 15.3.3 and safety conditions for units using A3 refrigerants as per
IS 16678/ISO 5149 (Part 2)’
(Page 4, clause 9.3) — Substitute the following for the existing clause:
When operating under full load capacity under the test conditions specified in 8.1.1 with controls set for
maximum cooling and with ventilating air damper and exhaust damper, if any, closed, the split air conditioner
shall have overall power factor, measured at rated voltage and frequency of not less than 0.90.’
(Page 5, clause 9.4.3, line 1) — Substitute sentence one for the existing sentence:
‘Test voltages should be as specified in 8.1.2 for cool only and 8.2.2 for heat pumps.’
(Page 5, clause 9.4.4) — Substitute the following for the existing clause:
‘9.4.4 Procedure
9.4.4.1 The split air conditioner shall be operated continuously for 1 h after the specified air temperatures and
equilibrium condensate level have been established.
5
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9.4.4.2 All power to the split air conditioner shall then be cut off for 3 min and then restored. During this test no
water should be sprinkled on to the condenser by external means other than what is condensed in the evaporator.
9.4.4.3 The operation of the equipment may be restarted either automatically or through the use of a remote
controller or similar device. The test shall continue for 60 min after the equipment restarts.’
(Page 5, clause 9.4.5.2) — Substitute the following for the existing clause:
‘9.4.5.2 The split air conditioner fan / blower motor should operate continuously for the first 1 h of the test
without tripping of the motor overload protective devices.
After the interruption of power, the equipment shall resume operation within 30 min and run continuously for
1 h.’
(Page 5, clause 9.4.5.4, lines 3 and 4) — Substitute ‘the unit may remain out of operation for not longer
than 30 min’ for ‘the unit may remain out of operation for not longer than 60 min’.
(Page 5, clause 9.5.4.1, line 1) — Substitute ‘The unit should be operated for 4 h with the room side’ for
‘The unit should be operated for 6 h with the room side’
(Page 5, clause 9.5.4.2, line 1) — Substitute ‘After 4 h operating period, the unit should be’ for ‘After 6 h
operating period, the unit should be’
(Page 6, clause 9.7.3) — Substitute ‘(see 9.9)’ for ‘(see 9.9 and Annex D)’.
‘The rate of power consumption for air conditioners tested under the conditions laid in 8.1.1 shall not exceed
110 percent of the rated energy for cooling by air conditioner.’
‘NOTE— The power consumption value declared or stated by manufacturer shall not exceed by + 10 percent of the declared
value provided the measured value does not exceed the value given in the Table 1. Cooling capacity beyond 10 500 W is under
consideration.’
(Page 6, clause 9.8.3) — Substitute ‘(see 9.11)’ for ‘(see 9.11 and Annex D)’.
(Page 7, clause 9.9.4) — Substitute the following for the existing clause:
The capacity test can be conducted using one of the following procedures:
a) This procedure shall be applicable when the air conditioner is tested in calorimeter. The air conditioner
shall be tested in calorimeter complying with Annex G. Simultaneous methods for determining
capacities shall be used. One method shall determine capacity on the room side and the other shall
determine the capacity on the outdoor side (These two simultaneous determinations shall agree within 4
percent of the value obtained on the room side for the test to be valid).
b) This procedure shall be applicable when the air conditioner is tested in Psychrometric room. The
capacities will be determined from measurements of entering and leaving wet-bulb and dry-bulb
temperatures and the associated airflow rate. Air leaving the equipment under the test shall lead directly
to the discharge chamber. If a direct connection cannot be made between the equipment and the
discharge chamber, a short plenum shall be attached to the equipment. The static pressure difference
6
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
between the discharge chamber and intake opening of the equipment under test shall be zero. Airflow
measurements shall be made in accordance with Annex F.
Test conditions shall be maintained until equilibrium has been reached, and maintained for not less than 1 h
before recording data for the capacity test. The test shall then be run for 1h recording data every 10 min, giving
7 sets of reading.’
‘9.9.5 Requirements
The capacity of production unit as determined on the room side shall not be less than as 95 percent of rated
cooling capacity for single phase units upto 10 465W and for remaining units it shall not be less than 90 percent
of rated cooling capacity.’
(Page 7, Table 3) — Substitute ‘Table 2 Variations Allowed in Capacity Test Readings’ for ‘Table 3
Variations Allowed in Capacity Test Readings’.
(Page 7, clause 9.10) — Substitute ‘Sound Test’ for ‘Noise Test’. Also substitute wherever it is given in
the text.
(Page 7, clause 9.10, line 6) — Substitute ‘described in 14 and shall not exceed the value given in Table 3’
for ‘described in 15 and shall not exceed the value given in Table 3’
(Page 7, clause 9.11) — Substitute the following for the existing clause:
‘The installation of the air conditioner in the test room as specified in Annex E.
The measured heating capacity shall not be less than 90 percent of the rated heat pump capacity.’
The test condition for measurement of ISEER for cooling shall be as specified in 8.3 of this standard. The
method of calculation and the bin temperature distribution shall be as given in Annex J. The ISEER of the
production unit shall be not less than 95 percent of the name plate rating. Capacity and power at half load shall
be within ±5 percent of the rated half load capacity.’
(Page 7, clause 10) — Substitute the following for the existing clause:
‘10 CALCULATIONS
7
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 9, clause 11.1.2 c)] — Substitute the following for the existing:
(Page10, clause 11.2.1) — Substitute the following for the existing clause:
‘11.2.1 Accuracy of pressure measuring instruments not including barometers shall be ± 1 percent and shall
have resolution of 0.01 mbar (in case of pascal 0.1)’.
(Page 10, clause 11.2.3) — Substitute the following for the existing clause:
‘11.2.3 Barometric pressure shall be measured by a barometer having scale markings permitting readings with
an accuracy within ±0.5 percent.’
(Page 11, clause 11.6.1) — Substitute ‘±2 percent’ for ‘±0.2 percent’.
14.3.1 Purpose
Verify the sound pressure level (dB level) for indoor or outdoor units in connected conditions.
Test condition:
a) Indoor : 27+5 oC
b) Outdoor : 35+5 oC
c) Power supply : Rated power of the units
d) Test voltage : Rated voltage
Minimum 10 dB lower than rated sound pressure level or 20 dB, whichever is higher.
8
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
For ducted and package units use attachments (duct, damper, etc) for simulating site conditions’
(Page 16, clause 15) — Substitute the following for the existing clause:
‘15 TESTS
These shall consist of routine tests that would be conducted on each and every unit after completion at the
manufacturer’s works.
Outdoor unit of the air conditioner / heat pump shall be run (by connecting with dummy indoor unit of run test
facility after the final assembly) at the rated voltage and measure the power. The measured power meets the
limit set by the quality assurance with respect to prevalent ambient temperature.
Indoor unit (to be tested after the final assembly) of the air conditioner / heat pump and shall be run alone to
check the proper running of blower.
Outdoor unit of the air conditioner / heat pump shall be tested for leak before charging at the appropriate
pressure corresponding to the refrigerant used.
10
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
The electrical insulation of all circuits shall be such as to withstand a test voltage of 1 000 V rms applied for not
less than 1 s when tested as per Annex A of IS 302-1.
The leakage current shall not exceed 3.5 mA when tested as per 13.2 of IS 302-1.
The earth resistance of the unit shall not exceed 0.1 Ω when tested as per 27 of IS 302-1.
NOTE — The tests at 15.2.1 may be carried out separately on each indoor and condensing units without interconnecting. These
tests on the inter-connected units may be carried out as per sampling plan agreed between manufacturer and purchaser.
The type tests shall consist of the tests that would be necessary to check up the performance and characteristics
of the units and components, and shall be carried out by a recognized testing authority. Once a room air
conditioner has undergone type tests, any minor or essential alterations which the manufacturer intends to make
shall be reported to the testing authority.
Air conditioners shall be sent along with manufacturer’s detailed specifications to the recognized testing
authority for purposes of type tests. The samples shall be picked up at random from stock or routine factory
production.
15.3.1 Besides all the production routine tests outlined in 15.2, the type tests shall comprise of the following:
Air conditioners shall be sent along with manufacturer’s detailed specifications to the recognized testing
authority for purposes of type tests. The samples shall be picked up at random from stock or routine factory
production motor.
15.3.2 The type test report shall also contain the name-plate particulars of the air conditioners for purposes of
identification.
11
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
lf the purchaser desires any of the production routine tests to be repeated at the time of purchase, then, where
agreed to between the purchaser and the manufacturer, the tests may be carried out at the manufacturer’s works;
alternatively, the tests may be repeated at the place specified by the purchaser provided that all the arrangements
for tests are made by the purchaser at the specified place.The following shall constitute acceptance tests.
Measurements shall be made of the following when tested as per 9.9 and the performance parameters shall be
compared with the unit which has already passed the type test:
No part of the assembly under test shall show signs of leakage when tested with a leak detector after the panel
cover removed to access the tubing joints of the unit.’
(Page 18, clause 17) — Substitute the following for the existing clause:
‘17 Marking
17.1 The split air conditioner shall have the following information marked on a name plate in a location where
it is accessible and visible:
Each split air conditioner may also be marked with the Standard Mark.
17.2.1 The use of the Standard Mark is governed by the provisions of Bureau of Indian Standards Act, 2016
and the Rules and Regulations made thereunder. The details of conditions under which the license for the use of
Standard Mark may be granted to manufacturers or producers may be obtained from the Bureau of Indian
Standards.’
12
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX E
(Clause 9.11)
TEST REQUIREMENTS
E-1.1 If an indoor condition test room is required, it shall be a room or space in which the desired test conditions
can be maintained within the prescribed tolerances. It is recommended that air velocities in the vicinity of the
equipment under test not exceed 2.5 m/s.
E-1.2 If an outdoor condition test room or space is required, it shall be of sufficient volume and shall circulate
air in a manner such that it does not change the normal air circulating pattern of the equipment under test. It
shall be of such dimensions that the distance from any room surface to any equipment surface from which air is
discharged is not less than 1.8 m and the distance from any other room surface to any other equipment surface is
not less than 1.0 m, except for floor or wall relationships required for normal equipment installation. The room
conditioning apparatus should handle air at a rate not less than the outdoor airflow rate, and preferably should
take this air from the direction of the equipment air discharge and return it at the desired conditions uniformly
and at low velocities.
E-2.1 The equipment to be tested shall be installed in accordance with the manufacturer’s installation
instructions using recommended installation procedures and accessories. In all cases, the manufacturer’s
recommendations with respect to distances from adjacent walls, amount of extensions through walls, etc. shall
be followed.
E-2.2 No other alterations to the equipment shall be made except for the attachment of the required test
apparatus and instruments in the prescribed manner.
E-2.3 If necessary, the equipment shall be evacuated and charged with the type and amount of refrigerant
specified in the manufacturer’s instructions.
E-2.4 All standard ratings for equipment in which the condenser and the evaporator are two separate assemblies
shall be determined with minimum 3 m or higher as declared by the manufacturer for high wall mounted and
minimum 5 m length or higher as declared by the manufacturer for ceiling mounted and floor mounted of
connecting refrigerant tubing on each line. The lengths shall be actual lengths and not equivalent lengths. The
length of the connecting tubing shall be measured from the enclosure of the indoor unit to the enclosure of the
outdoor unit. Such equipment in which the interconnecting tubing is furnished as an integral part of the unit and
not recommended for cutting to length shall be tested with the complete length of tubing furnished. Not less than
40 percent of the total length of the interconnecting tubing shall be exposed to the outdoor conditions with the
rest of the tubing exposed to the indoor conditions. The line diameters, insulation, details of installation,
evacuation and charging shall be in accordance with the manufacturer’s published recommendations.
A short plenum shall be attached to the outlet of the equipment. This plenum shall have cross-sectional
dimensions equal to the dimensions of the equipment outlets. A static pressure tap shall be added at the centre of
each side of the discharge plenum, if rectangular, or at four evenly distributed locations along the circumference
of an oval or round plenum. These four static pressure taps shall be manifolded together. The minimum length
13
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
of the discharge plenum and the location of the static pressure taps relative to the equipment outlets shall be as
shown in Fig. 9, if testing a split-system.
14
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX F
[Clause 9.9.4 b)]
AIRFLOW MEASUREMENT
F-1.1 Airflow should be measured using the apparatus and testing procedures given in this annex.
Air from the equipment under test is conveyed via a duct to the receiving chamber, passes through the nozzle(s)
in discharge chamber and is then exhausted to the test room or channelled back to the equipment’s inlet.
F-2.2 Diffusers
a) Option 1 — installed in the receiving chamber (at a distance at least 1.5 times the largest nozzle
throat diameter, Dn) upstream of the partition wall and in the discharge chamber (at a distance at
least 2.5 times the largest nozzle throat diameter, Dn) downstream of the exit plane of the largest
nozzle.
b) Option 2 — installed in the discharge chamber (at a distance at least 1.5 times the largest nozzle
throat diameter, Dn) upstream of the inlet plane of the largest nozzle and (at a distance at least 2.5
times the largest nozzle throat diameter, Dn) downstream of the exit plane of the largest nozzle.
F-2.3 Exhaust Fan, capable of providing the desired static pressure at the equipment’s outlet, installed in one
wall of the discharge chamber and provided with a means of varying its capacity.
F-2.4 Manometers / Differential Pressure Gauge, for measuring the static pressure drop across the nozzle(s).
a) Option 1— One end of the manometer should be connected to a static pressure tap located flush
with the inner wall of the receiving chamber and the other end to a static pressure tap located flush
with the inner wall of the discharge chamber, or preferably, several taps in each chamber should be
connected to several manometers in parallel or manifolded to a single manometer. Static pressure
connections should be located so as not to be affected by airflow.
b) Option 2 — One end of the manometer should be connected to a static pressure tap located flush
with the inner wall of the discharge chamber (inlet plane of the nozzles) and the other end to a
static pressure tap located flush with the inner wall of the discharge chamber (exit plane of the
nozzles), or preferably, several taps in each chamber should be connected to several manometers in
parallel or manifolded to a single manometer. Static pressure connections should be located so as
not to be affected by airflow.
15
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
F-2.5.1 The throat velocity of any nozzle in use should be not less than 15 m/s or more than 35 m/s.
F-2.5.2 Nozzles should be constructed in accordance with Fig. 11 and applied in accordance with the provisions
of F-2.5.3 and F-2.5.4.
F-2.5.3 The nozzle discharge coefficient, Cd, for the construction shown in Fig. 11, which has a throat length to
throat diameter ratio of 0.6, may be determined using equation 1.
7.006 134 .6
𝐶𝐶d = 0.998 6 − + …1
�𝑅𝑅e 𝑅𝑅e
16
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
where
Va = mean airflow velocity at the throat of the nozzle;
Dn = diameter of the throat of the nozzle; and
v = kinematic viscosity of air.
F-2.5.4 Nozzles may also be constructed in accordance with appropriate national standards, provided they can
be used in the apparatus described in Fig. 10 and result in equivalent accuracy.
F-3.1 The pressure taps should consist of 6.25 ± 0.25 mm diameter nipples soldered to the outer plenum
surfaces and centred over 1 mm diameter holes through the plenum. The edges of these holes should be free of
burrs and other surface irregularities.
F-3.2 The plenum and duct section should be sealed to prevent air leakage, particularly at the connections to the
equipment and the air measuring device, and should be insulated to prevent heat leakage between the equipment
outlet and the temperature measuring instruments.
17
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
F-4.1 The outlet or outlets of the equipment under test should be connected to the receiving chamber by adaptor
ducting of negligible air resistance, as shown in Fig.10.
F-4.2 To establish zero static pressure with respect to the test room at the discharge of the air conditioner or
heat pump in the receiving chamber, a manometer should have one side connected to one or more static pressure
connections located flush with the inner wall of the receiving chamber.
a) Barometric pressure;
b) Nozzle dry-bulb and wet-bulb temperatures or dew point temperatures; and
c) Static pressure difference at the nozzle(s) or optionally, nozzle velocity pressure;
F-5.2 Air mass flow rate, qm, through a single nozzle is determined using equation 3
2𝑃𝑃v
𝑞𝑞m = 𝑌𝑌 × 𝐶𝐶d × 𝐴𝐴n � …3
𝑣𝑣 ′ 𝑛𝑛
𝑌𝑌 = 0.452 + 0.548 α …4
Pv
α=1− …5
Pn
Air volume flow rate, qv, through a single nozzle is determined using equation 6:
𝑞𝑞v = 𝑌𝑌 × Cd × An �2Pv V ′ n …6
Air volume flow rate expressed in terms of standard air qs is calculated by equation 8
qv
𝑞𝑞s = …8
1.204 v ′ n
F-5.3 Airflow through multiple nozzles may be calculated in accordance with F-5.2, except that the total flow
rate is then the sum of the qm or qv values for each nozzle used.
18
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX G
[Clauses 9.9.4 a), 10.1 and 10.2]
G-1 GENERAL
G-1.1 The calorimeter provides a method for determining capacity simultaneously on both the indoor-side and
the outdoor-side. In the cooling mode, the indoor-side capacity determination should be made by balancing the
cooling and dehumidifying effects with measured heat and water inputs. The outdoor-side capacity provides a
confirmative test of the cooling and dehumidifying effects by balancing the heat and water rejection on the
condenser side with a measured amount of cooling.
G-1.2 The two calorimeter test chambers, indoor-side and outdoor-side, are separated by an insulated partition
having an opening into which the non-ducted, single-packaged unitary equipment is mounted.
The indoor unit of split unit is mounted on the frame away from the partition wall and at a suitable height. The
outdoor unit of the split system is kept on table or trolley of height >0.4m above the chamber floor. The distance
around the indoor and outdoor unit shall be as per manufacturer instructions.
The equipment should be installed in a manner similar to a normal installation. No effort should be made to seal
the internal construction of the equipment to prevent air leakage from the condenser side to the evaporator side
or vice versa. No connections or alterations should be made to the equipment which might in any way alter its
normal operation.
G-1.3 A pressure-equalizing device, as illustrated in Fig.12, should be provided in the partition wall between the
indoor-side and the outdoor-side test chambers to maintain a balanced pressure between these test chambers and
also to permit measurement of leakage, exhaust and ventilation air. This device consists of one or more nozzles
of the type shown in Fig.11, a discharge chamber equipped with an exhaust fan and manometers for measuring
test chamber and airflow pressures.
Since the airflow from one test chamber to the other may be in either direction, two such devices mounted in
opposite directions or a reversible device should be used. The manometer pressure pickup tubes should be
located so as to be unaffected by air discharged from the equipment or by the exhaust from the pressure-
equalizing device. The fan or blower, which exhausts air from the discharge chamber, should permit variation of
its airflow by any suitable means, such as a variable speed drive or a damper as shown in Fig.12. The exhaust
from this fan or blower should be such that it does not affect the inlet air to the equipment.
The pressure equalizing device should be adjusted during calorimeter tests or airflow measurements so that the
static pressure difference between the indoor-side and outdoor-side test chambers is not greater than 1.25 Pa.
19
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-1.4 The size of the calorimeter should be sufficient to avoid any restriction to the intake or discharge
openings of the equipment. Perforated plates or other suitable grilles should be provided at the discharge
opening from the reconditioning equipment to avoid face velocities exceeding 0.5 m/s. Sufficient space should
be allowed in front of any inlet or discharge grilles of the equipment to avoid interference with the airflow.
Minimum distance from the equipment to side walls or ceiling of the test chamber(s) should be 1 m, except for
the back of console-type equipment, which should be in normal relation to the wall. Ceiling-mounted equipment
should be installed at a minimum distance of 1.8 m from the floor.
Table 5 gives the suggested dimensions for the calorimeter. To accommodate peculiar sizes of equipment, it
may be necessary to alter the suggested dimensions to comply with the space requirements.
20
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
Sl No. Rated Cooling Capacity of Suggested Minimum Inside Dimensions of Each Room of the Calorimeter
Equipment1) (m)
W
Width Height Length
(1) (2) (3) (4) (5)
i) 3 000 2.4 2.1 1.8
ii) 6 000 2.4 2.1 2.4
iii) 9 000 2.7 2.4 3.0
iv) 12 0002) 3.0 2.4 3.7
1)
All figures are round numbers.
2)
Larger capacity equipment requires larger calorimeters.
G-1.5 Each test chamber should be provided with reconditioning equipment to maintain specified airflow and
prescribed conditions. Reconditioning apparatus for the indoor-side test chamber should consist of heaters to
supply sensible heat and a humidifier to supply moisture. Reconditioning apparatus for the outdoor-side test
chamber should provide cooling, dehumidification and humidification. The energy supply should be controlled
and measured.
G-1.6 When calorimeters are used for heat pumps, they should have heating, humidifying and cooling
capabilities for both rooms (see Fig. 13 and Fig. 14) or other means, such as rotating the equipment, may be
used as long as the rating conditions are maintained.
G-1.7 Reconditioning apparatus for both test chambers should be provided with fans of sufficient capacity to
ensure airflows of not less than twice the quantity of air discharged by the equipment under test in the
calorimeter. The calorimeter should be equipped with means of measuring or determining specified wet-bulb
and dry-bulb temperatures in both calorimeter test chambers.
G-1.8 It is recognized that in both the indoor-side and outdoor-side test chambers, temperature gradients and
airflow patterns result from the interaction of the reconditioning apparatus and test equipment. Therefore, the
resultant conditions are peculiar to and dependent on a given combination of test chamber size, arrangement and
size of reconditioning apparatus and the air discharge characteristics of the equipment under test.
The point of measurement of specified test temperatures, both wet-bulb and dry-bulb, should be such that the
following conditions are fulfilled:
a) The measured temperatures should be representative of the temperature surrounding the equipment
and should simulate the conditions encountered in an actual application for both indoor and outdoor-
sides, as indicated above.
b) At the point of measurement, the temperature of air should not be affected by air discharged from
any piece of the equipment. This makes it mandatory that the temperatures are measured upstream of
any re-circulation produced by the equipment.
c) Air sampling tubes should be positioned on the intake side of the equipment under test.
G-1.9 During a heating capacity test, the temperature of the air leaving the indoor-side of the heat pump shall
be monitored to determine if its heating performance is being affected by a build-up of ice on the outdoor-side
heat exchanger. A single temperature measuring device, placed at the centre of the indoor air outlet, is sufficient
to indicate any change in the indoor air discharge temperature caused by a build-up of ice on the outdoor-side
heat exchanger.
G-1.10 Interior surfaces of the calorimeter test chambers should be of non-porous material with all joints sealed
against air and moisture leakage. The access door should be tightly sealed against air and moisture leakage by
use of gaskets or other suitable means.
21
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-1.11 If defrost controls on the heat pump provide for stopping the indoor airflow, provisions shall be made to
stop the test apparatus airflow to the equipment on both the indoor and outdoor-sides during such adefrost
period. If it is desirable to maintain operation of the reconditioning apparatus during the defrost period,
provisions may be made to bypass the conditioned air around the equipment as long as assurance is provided
that the conditioned air does not aid in the defrosting. A watt-hour meter shall be used for obtaining the
integrated electrical input to the equipment under test.
G-2.1 Heat leakage may be determined in either the indoor-side or outdoor-side test chamber by the following
method: All openings should be closed. Either test chamber may be heated by electric heaters to a temperature
of at least 11 °C above the surrounding ambient temperature. The ambient temperature should be maintained
constant within ±1 K outside all six enveloping surfaces of the test chamber, including the separating partition.
If the construction of the partition is identical to that of the other walls, the heat leakage through the partition
may be determined on a proportional area basis.
22
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-2.2 For calibrating the heat leakage through the separating partition alone, the following procedure may be
used: a test is carried out as described above. Then the temperature of the adjoining area on the other side of the
separating partition is raised to equal the temperature in the heated test chamber, thus eliminating heat leakage
through the partition, while the 11 °C differential is maintained between the heated test chamber and the
ambient surrounding the other five enveloping surfaces.
The difference in heat input between the first test and the second test permits determination of the leakage
through the partition alone.
G-2.3 For the outdoor-side test chamber equipped with means of cooling, an alternative means of calibration
may be to cool the test chamber to a temperature of at least 11 °C below the ambient temperature (on six sides)
and carry out a similar analysis.
G-2.4 The indoor-side calorimeter including the central partition and the outdoor-side calorimeter shall be
insulated so that heat leakage (including radiation) does not exceed 5 percent of the equipment capacity. Space
where enough air circulation is available shall be secured under the floor of the room-type calorimeter.
23
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-3.1 The balanced ambient room-type calorimeter is shown in Fig.14 and is based on the principle of
maintaining the dry-bulb temperatures surrounding the particular test chamber equal to the dry-bulb
temperatures maintained within that test chamber. If the ambient wet-bulb temperature is also maintained equal
to that within the test chamber, the vapour-proofing provisions of G-1.10 are not required.
G-3.2 The floor, ceiling and walls of the calorimeter test chambers shall be spaced a sufficient distance away
from the floor, ceiling and walls of the controlled areas in which the test chambers are located in order to
provide a uniform air temperature in the intervening space. It is recommended that this distance be at least
0.3 m. Means shall be provided to circulate the air within the surrounding space to prevent stratification.
G-3.3 Heat leakage through the separating partition shall be introduced into the heat balance calculation and
may be calibrated in accordance with G-3.4 or may be calculated.
G-3.4 It is recommended that the floor, ceiling and walls of the calorimeter test chambers be insulated so as to
limit heat leakage (including radiation) to no more than 10 percent of the test equipment’s capacity, with an
11 °C temperature difference, or 300 W for the same temperature difference, whichever is the greater, as tested
using the procedure given in G-2.2.
G-4.1 The energy flow quantities used to calculate the total cooling capacity, based on indoor-side and outdoor-
side measurements, are shown in Fig. 15.
24
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-4.2 The total cooling capacity on the indoor-side, ϕtci, as tested in either the calibrated or balanced ambient,
room-type calorimeter, is calculated using equation 9:
NOTE ― If no water is introduced during the test, hw1 is taken at the temperature of the water in the humidifier tank of the
conditioning apparatus.
When a cooling coil of the indoor-side calorimeter is used for testing of small capacity units, in order to stabilize
the test condition, equation 10 shall be used. Φci in equation 10 is the amount of heat exchanged in the cooling
coil of the indoor-side calorimeter.
G-4.3 When it is not practical to measure the temperature of the air leaving the indoor-side test chamber to the
outdoor-side test chamber, the temperature of the condensate may be assumed to be at the measured or
estimated wet-bulb temperature of the air leaving the test equipment.
G-4.4 The water vapour condensed by the equipment under test, Wr, may be determined by the amount of water
evaporated into the indoor-side test chamber by the reconditioning equipment to maintain the required humidity.
G-4.5 Heat leakage, ϕlp, into the indoor-side test chamber through the separating partition between the indoor-
side and outdoor-side test chambers may be determined from the calibrating test or, in the case of the balanced-
ambient room-type test chamber, may be based on calculations.
G-4.6 The total cooling capacity on the outdoor-side, ϕtco, as tested in either the calibrated or balanced-ambient,
room-type calorimeter is calculated using equation 11:
∅𝐭𝐭𝐭𝐭𝐭𝐭 = ∅𝐜𝐜 − ∑ 𝑃𝑃oc − 𝑃𝑃t + (ℎw3 − ℎw2 )𝑊𝑊r + ∅lp + ∅lo …11
NOTE ― The hw3 enthalpy is taken at the temperature at which the condensate leaves the outdoor-side test chamber of the
reconditioning apparatus.
G-4.7 The heat leakage rate into the indoor-side test chamber through the separating partition between the
indoor-side and outdoor-side test chambers, ϕlp, may be determined from the calibrating test or, in the case of
the balanced-ambient room-type test chamber, may be based on calculations.
NOTE ― This quantity is numerically equal to that used in equation 9 if, and only if, the area of the separating partition exposed
to the outdoor-side is equal to the area exposed to the indoor-side test chamber.
G-4.8 The latent cooling capacity (room dehumidifying capacity), ϕd, is calculated using equation 12.
G-4.9 The sensible cooling capacity, ϕsci, is calculated using equation 13:
∅𝐬𝐬𝐬𝐬𝐬𝐬
SHR = �∅ …14
𝐭𝐭𝐭𝐭𝐭𝐭
G-5.1 The energy flow quantities used to calculate the total heating capacity, based on indoor-side and outdoor-
side measurements, are shown in Fig.16.
25
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
G-5.2 Determination of the heating capacity by measurement in the indoor-side test chamber of the calorimeter,
ϕhi, is calculated using equation 15.
NOTE ― ΣPic is the other power input to the indoor-side test chamber (for example illumination, electrical and thermal power
input to the compensating device, heat balance of the humidification device), in watts.
G-5.3 Determination of the heating capacity by measurement of the heat absorbing side, ϕho, is calculated for
equipment where the evaporator takes the heat from an airflow using equation 16.
26
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX H
(Clauses 10.1 and 10.2)
INDOOR AIR ENTHALPY TEST METHOD
H-1 GENERAL
In the air enthalpy test method, capacities are determined from measurements of entering and leaving wet-bulb
and dry-bulb temperatures and the associated airflow rate.
H-2 APPLICATION
H-2.1 Air leaving the equipment under the test shall lead directly to the discharge chamber. If a direct
connection cannot be made between the equipment and the discharge chamber, a short plenum shall be attached
to the equipment. In this case, the short plenum shall have the same size as the discharge opening of the
equipment or shall be constructed so as not to prevent the leaving air from expanding. The cross-section area of
the airflow channel through the discharge chamber shall be such that the average air velocity is less than
1.25 m/s against the airflow rate of the equipment under test. The static pressure difference between the
discharge chamber and intake opening of the equipment under test shall be zero.
H-2.2 Airflow measurements shall be made in accordance with the provisions specified in Annex F.
The total cooling capacity based on the indoor-side test data, ϕtci, shall be calculated using equation 17.
𝑞𝑞 𝑣𝑣𝑣𝑣 (ℎ a 1 −ℎ a 2 ) 𝑞𝑞 vi (ℎ a 1 −ℎ a 2 )
∅tci = = …17
vn 𝑣𝑣 ′ 𝑛𝑛 (1+𝑊𝑊𝑛𝑛 )
The sensible cooling capacity based on the indoor-side test data, ϕsci, shall be calculated using equation 18.
𝑞𝑞 vi (c pa 1 t a 1 −c pa 2 t a 2 ) 𝑞𝑞 vi (c pa 1 t a 1 −c pa 2 t a 2 )
∅sci = = …18
vn v ′ n (1+W n )
The latent cooling capacity based on the indoor-side test data, ϕd, shall be calculated using equation 19 and 20.
Total heating capacity based on indoor-side data, ϕthi, shall be calculated using equation 21.
𝑞𝑞 vi (c pa 2 t a 2 −c pa 1 t a 1 ) 𝑞𝑞 vi (c pa 2 t a 2 −c pa 1 t a 1 )
∅thi = = …21
𝑣𝑣n 𝑣𝑣 ′ n (1+W n )
The equipment to be tested is typically located in a test room or rooms. An air measuring device is attached to
the equipment air discharge (indoor). This device discharges directly into the test room or space, which is
provided with suitable means for maintaining the air entering the equipment at the desired wet-bulb and dry-
bulb temperatures (see Fig.17). Suitable means for measuring the wet-bulb and dry-bulb temperatures of the air
entering and leaving the equipment and the external resistance shall be provided.
27
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
28
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX J
(Clause 9.12)
CALCULATIONS
The cooling seasonal performance factor (CSPF), FCSP, of the equipment shall be calculated by equation 22.
𝐿𝐿CST
𝐹𝐹CSP = …22
C CSE
where
LCST = cooling seasonal total load (CSTL) and
CCSE = cooling seasonal energy consumption (CSEC);
The defined cooling load shall be represented by a value and the assumption that it is linearly changing
depending on the change in outdoor temperature.
Where t100 is the outdoor temperature at 100 percent load and t0 is the outdoor temperature at 0 percent load.
Reference values of defined cooling load to be used shall be as follows:
In case of setting other cooling load, refer to the setting method as described in Annex M.
Defined cooling load LC(tj) at outdoor temperature tj, which is necessary to calculate the cooling seasonal energy
consumption, shall be determined by equation 23.
𝑡𝑡 j −𝑡𝑡 0
𝐿𝐿c �𝑡𝑡𝑗𝑗 � = ∅ful (𝑡𝑡100 ) × …23
𝑡𝑡 100 −𝑡𝑡 0
Where ∅ful (𝑡𝑡100 ) is the cooling capacity at 𝑡𝑡100 at full-load operating conditions.
Cooling seasonal performance factor (CSPF) shall be calculated at the reference climate condition in Table.
The calculation of cooling seasonal performance factor may also be done for other climate conditions.
29
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
Average 527 590 639 660 603 543 451 377 309 240 196 165 130 101 79 59 44 31 20 10 5774
Annual
hours
Fraction 9.1 10.2 11.1 11.4 10.4 9.4 7.8 6.5 5.4 4.2 3.4 2.9 2.3 1.7 1.4 1.0 0.8 0.5 0.3 0.2 100
Bin hours 146 163 177 183 167 150 125 104 86 67 54 46 36 28 22 16 12 9 6 3 1 600
Bin hours of each outdoor temperature may be calculated by multiplying the fractional bin hours by the total
annual cooling hours if the fractional bin hours are applicable.
In case of setting other outdoor temperature bin distribution, refer to the setting method as described in
Annex M.
Operational performance at each test, which is used for calculation of seasonal performance factor, shall be in
accordance with table.
Capacity ∅ful (𝑡𝑡j ) (W) of the equipment when it is operated for cooling at outdoor temperature tj linearly changes
depending on outdoor temperatures, and it is determined by formula 24 from two characteristics, one at 35oC
and other at 29oC.
Power input Pful(tj)(W) of the equipment when it is operated for cooling at outdoor temperature tj linearly
changes depending on outdoor temperatures as shown in Fig.18, and it is determined by equation 25 from two
characteristics, one at 35oC and other at 29oC.
30
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
FIG.18 COOLING CAPACITY, POWER INPUT AND COOLING LOAD FOR FIXED CAPACITY UNITS
Cooling seasonal total load (CSTL), LCST, shall be determined using equation 26 from the total sum of cooling
load at each outdoor temperature tj multiplied by bin hours nj.
𝐿𝐿CST = ∑𝑚𝑚 𝑛𝑛
𝑗𝑗 =1 𝐿𝐿c �𝑡𝑡𝑗𝑗 � × 𝑛𝑛j + ∑𝑗𝑗 =𝑚𝑚 +1 ∅ful (𝑡𝑡j ) × 𝑛𝑛j …26
a) In the range of LC(tj) ≤ ɸful(tj) (j=1 to m): LC (tj) shall be calculated by equation 23.
b) In the range of LC(tj) >ɸful(tj) (j=m+1 to n): ɸful(tj) shall be calculated by equation 24.
Cooling seasonal energy consumption (CSEC), CCSE, shall be determined using equation 27 from the total sum
of cooling energy consumption at each outdoor temperature tj.
𝑛𝑛 𝑗𝑗
𝐶𝐶CSE = ∑𝑛𝑛𝑗𝑗=1 𝑋𝑋 (𝑡𝑡j ) × 𝑃𝑃ful (𝑡𝑡j ) × …27
𝐹𝐹PL (𝑡𝑡 j )
31
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
𝐿𝐿𝑐𝑐 (𝒕𝒕𝐣𝐣 )
𝑋𝑋�𝑡𝑡𝑗𝑗 � = …28
∅(𝒕𝒕𝐣𝐣 )
Part load factor (PLF), FPL(tj), caused by the equipment when it is cyclically operated at outdoor temperature tj,
shall be determined by equation 29 using degradation coefficient CD.
a) Cyclic operation (LC(tj) >∅𝑓𝑓𝑓𝑓𝑓𝑓 (𝑡𝑡𝑗𝑗 )): In equation 27 X(tj) shall be calculated by equation 28. In equation
28, ɸ(tj)=∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡j �.
b) Full capacity operation (LC(tj) >∅𝑓𝑓𝑓𝑓𝑓𝑓 (𝑡𝑡j )): In equation 27, X(tj)=FPL(tj)=1.
Table 8 Temperature and Humidity Conditions and Default Values for Cooling at T1
Moderate Climate Condition
(Clause J-5)
32
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
Capacity ∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡j �(𝑊𝑊) of the equipment when it is operated for cooling full capacity at outdoor temperature 𝑡𝑡j
shall be defined by equation 24.
Capacity ∅𝑚𝑚𝑚𝑚𝑚𝑚 �𝑡𝑡j �(𝑊𝑊) of the equipment when it is operated for cooling minimum capacity at outdoor
temperature 𝑡𝑡j shall be defined by equation 30.
Power input 𝑃𝑃𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡j �(𝑊𝑊) of the equipment when it is operated for cooling full capacity at outdoor temperature
𝑡𝑡j shall be defined by equation 25.
Power input 𝑃𝑃𝑚𝑚𝑚𝑚𝑚𝑚 �𝑡𝑡j �(𝑊𝑊) of the equipment when it is operated for cooling minimum capacity at outdoor
temperature 𝑡𝑡j shall be defined by equation 31.
Cooling seasonal total load (CSTL), LCST, shall be determined using the equation 32 from the total sum of
cooling load at each outdoor temperature tj multiplied by bin hours nj.
𝐿𝐿cst = ∑𝑚𝑚 𝑛𝑛
𝑗𝑗 =1 𝐿𝐿𝑐𝑐 �𝑇𝑇𝑗𝑗 � × 𝑛𝑛𝑗𝑗 + ∑𝑗𝑗 =𝑚𝑚 +1 φ𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡j � × 𝑛𝑛𝑗𝑗 …32
Cooling seasonal energy consumption (CSEC), CCSE, shall be calculated by equation 35.
Relation of cooling capacity characteristics and power input characteristics to cooling load at outdoor
temperature tj is shown in fig. 19.
33
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
b) Second stage cyclic operation (∅𝑚𝑚𝑚𝑚𝑚𝑚 �𝑡𝑡𝑗𝑗 �< LC(tj) ≤ ∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡𝑗𝑗 �, j=k+1 to m):
𝑃𝑃mf �𝑡𝑡j � = 𝑋𝑋mf �𝑡𝑡j � × 𝑃𝑃min �𝑡𝑡j � + (1 − 𝑋𝑋mf �𝑡𝑡j �) × 𝑃𝑃ful (𝑡𝑡𝑗𝑗 ) …36
FIG. 19 COOLING CAPACITY, POWER INPUT AND COOLING LOAD FOR TWO-STAGE CAPACITY UNITS
Capacities ∅ful �𝑡𝑡j � and ∅min �𝑡𝑡j � (W) of the equipment when it is operated for cooling at outdoor temperature tj
are shown in Fig. 20 and shall be determined by equations 24 and 30, respectively.
34
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
FIG. 20 COOLING CAPACITY, POWER INPUT AND COOLING LOAD FOR MULTI-STAGE CAPACITY UNITS
Power input Pful(tj) and Pmin(tj) (W) of the equipment when it is operated for cooling at outdoor temperature tj
shall be determined by equations 25 and 31, respectively.
When the minimum capacity data are available, then the cooling seasonal energy consumption (CSEC), CCSE,
shall be calculated by equation 40.
35
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
c) Third stage cyclic operation (∅ℎ𝑎𝑎𝑎𝑎 �𝑡𝑡j � < 𝐿𝐿𝐶𝐶 (𝑡𝑡j ) ≤ ∅ful �𝑡𝑡j �, j=p+1):
𝑃𝑃hf �𝑡𝑡j � = 𝑋𝑋hf �𝑡𝑡j � × 𝑃𝑃haf �𝑡𝑡j � + (1 − 𝑋𝑋hf �𝑡𝑡j �) × 𝑃𝑃ful (𝑡𝑡j ) …43
∅ful �𝑡𝑡 j �−𝐿𝐿𝐶𝐶 (𝑡𝑡 j )
𝑋𝑋hf �𝑡𝑡j � = …44
∅ful �𝑡𝑡 j �−∅haf (𝑡𝑡 j )
d) Full capacity operation (𝐿𝐿𝐶𝐶 (𝑡𝑡𝑗𝑗 ) > ∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡j �, j=m+1 to n):
𝑃𝑃hf �𝑡𝑡j � shall be calculated by equation 25.
When the minimum capacity data are not available, then the cooling seasonal energy consumption (CSEC),
CCSE, shall be calculated alternatively by equation 45.
a) First stage cyclic operation (𝐿𝐿C (𝑡𝑡j ) ≤ ∅ℎ𝑎𝑎𝑎𝑎 �𝑡𝑡j �, j=1 to p):
In equation 45, 𝑋𝑋(𝑡𝑡j ) shall be calculated by equation 28.
In equation 28, ∅�𝑡𝑡j � = ∅ful �𝑡𝑡j �
b) Second stage cyclic operation (∅ℎ𝑎𝑎𝑎𝑎 �𝑡𝑡j � < 𝐿𝐿C (𝑡𝑡j ) ≤ ∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡𝑗𝑗 �, j=p+1 to m):
In equation 45, 𝑃𝑃hf �𝑡𝑡j � and 𝑋𝑋hf �𝑡𝑡j � shall be calculated by equations 43 and 44 respectively.
c) Full capacity operation (𝐿𝐿𝐶𝐶 (𝑡𝑡𝑗𝑗 > ∅𝑓𝑓𝑓𝑓𝑓𝑓 �𝑡𝑡𝑗𝑗 �, j=p+1 to m):
𝑃𝑃ful (𝑡𝑡j ) shall be calculated by equation 25.
Capacities ϕful(tj), ϕmin(tj) and ϕhaf(tj) (W) of the equipment when it is operated for cooling at outdoor
temperature tj are shown in Fig. 21 and shall be determined by equations 24, 30 and 38, respectively.
36
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
FIG. 21 COOLING CAPACITY, POWER INPUT, COOLING LOAD AND EER FOR VARIABLE CAPACITY UNITS
Power input Pful(tj), Pmin(tj) and Phaf(tj) (W) of the equipment when it is operated for cooling at outdoor
temperature tj shall be determined by equations 25, 31 and 39, respectively.
37
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
When the minimum capacity data are available, then the cooling seasonal energy consumption (CSEC), CCSE,
shall be calculated by equation 40.
When the minimum capacity data are not available, then the cooling seasonal energy consumption
(CSEC), CCSE, shall be calculated alternatively by equation 45.
Relation of cooling capacity, power input and EER characteristics to cooling load at outdoor temperature tj is
shown in Fig. 21.
Pmh(t j) , power input between minimum and half capacity operation, shall be calculated from Lc(t j) cooling
load and E ER, mh(t j) by equation 47.
𝐿𝐿𝑐𝑐 (𝑡𝑡 𝑗𝑗 )
𝑃𝑃mh �𝑡𝑡𝑗𝑗 � = …47
𝐸𝐸𝐸𝐸𝐸𝐸 ,mh (𝑡𝑡 𝑗𝑗 )
c) Variable capacity operation between half and full capacity (ϕhaf(tj) <Lc(tj) ≤ ϕful(tj), j = p+1 to m):
tc is outdoor temperature when cooling load is equal to cooling half capacity (refer to Annex K)
𝐸𝐸𝐸𝐸𝐸𝐸,ℎ𝑎𝑎𝑎𝑎 (𝑡𝑡𝑐𝑐 ) , Energy Efficiency Ratio (EER) at outdoor temperature 𝑡𝑡𝑐𝑐 at half capacity operation, shall be
calculated from ∅ℎ𝑎𝑎𝑎𝑎 (𝑡𝑡𝑐𝑐 ) and 𝑃𝑃ℎ𝑎𝑎𝑎𝑎 (𝑡𝑡𝑐𝑐 ) by equation 48.
∅ℎ 𝑎𝑎𝑎𝑎 (𝑡𝑡 𝑐𝑐 )
𝐸𝐸𝐸𝐸𝐸𝐸,ℎ𝑎𝑎𝑎𝑎 (𝑡𝑡𝑐𝑐 ) = …48
𝑃𝑃 ℎ 𝑎𝑎𝑎𝑎 (𝑡𝑡 𝑐𝑐 )
𝑡𝑡𝑏𝑏 is outdoor temperature when cooling load is equal to cooling full capacity (refer to Annex K)
𝐸𝐸ER ,ful (𝑡𝑡b ) , Energy Efficiency Ratio (EER) at outdoor temperature 𝑡𝑡𝑏𝑏 at full capacity operation, shall be
calculated from ∅ful (𝑡𝑡b ) and 𝑃𝑃ful (𝑡𝑡b ) by equation 49.
∅ful (𝑡𝑡 b )
𝐸𝐸ER ,ful (𝑡𝑡b ) = …49
𝑃𝑃 ful (𝑡𝑡 b )
It assumed that EER linearly changes depending on outdoor temperature when the capacity of equipment
changes continuously.
𝐸𝐸ER ,ful (𝑡𝑡 b )−𝐸𝐸ER ,haf (𝑡𝑡 c )
𝐸𝐸ER ,hf �𝑡𝑡j � = 𝐸𝐸ER ,haf (𝑡𝑡c ) + × (𝑡𝑡j − 𝑡𝑡c ) …50
𝑡𝑡 b −𝑡𝑡 c
38
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
𝑃𝑃hf �𝑡𝑡j � , power input between half and full capacity operation, shall be calculated from 𝐿𝐿𝐶𝐶 (𝑡𝑡𝑗𝑗 ) cooling load and
𝐸𝐸ER ,hf �𝑡𝑡j � by equation 51
𝐿𝐿C (𝑡𝑡 j )
𝑃𝑃hf �𝑡𝑡j � = …51
𝐸𝐸ER ,hf (𝑡𝑡 j )
d) Full capacity operation (∅ful �𝑡𝑡j � < 𝐿𝐿C (𝑡𝑡j ), j=m+1 to n):
𝑃𝑃ful �𝑡𝑡j � shall be calculated by equation 25.
In case that the minimum capacity is not measured, the cooling seasonal energy consumption (CSEC), CCSE,
shall be calculated by equation 45.
1) Cyclic operation 𝐿𝐿C (𝑡𝑡j ) ≤ ∅haf �𝑡𝑡j �, j=1 to p):
In this range, calculation shall be made assuming that the air conditioner cyclically operates with the
half operating capacity.
In equation 45, X(𝑡𝑡j ) shall be calculated by equation 28.
In formula (7), ∅�𝑡𝑡j � = ∅ful �𝑡𝑡j �.
2) Variable capacity operation between half and full capacity (∅haf �𝑡𝑡j � < 𝐿𝐿C (𝑡𝑡j ) ≤ ∅ful �𝑡𝑡j �, j=p+1 to m):
This calculation shall be made by using equations 48 to 51
3) Full capacity operation (∅ful �𝑡𝑡j � < 𝐿𝐿C (𝑡𝑡j ), j=m+1 to n):
𝑃𝑃ful �𝑡𝑡j � shall be calculated by equation 25.
39
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX K
(Clause J-7.4)
CALCULATING METHOD FOR TEMPERATURE WHEN DEFINED LOAD LINE CROSSES EACH
CAPACITY LINE
�𝑡𝑡 j −𝑡𝑡 0 �
𝐿𝐿C �𝑡𝑡j � = ∅ful (𝑡𝑡100 ) × (𝑡𝑡 …52
100 −𝑡𝑡 0 )
Crossing point of full capacity operation line and load line, tb, is calculated by equations 52 and 53.
Then, tb is given by
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅ful (35)(𝑡𝑡 100 −𝑡𝑡 0 )+35�∅ful (29)−∅ful (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡𝑏𝑏 = …57
6∅ful (𝑡𝑡 100 )+�∅ful (29)−∅ful (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
Crossing point of half capacity operation line and load line, tc, is calculated by equations 52 and 54
(𝑡𝑡 −𝑡𝑡 ) ∅ (29)−∅haf (35)
∅ful (𝑡𝑡100 ) × 𝑐𝑐 0 = ∅haf (35) + haf
(𝑡𝑡 100 −𝑡𝑡 0 )
× (35 − 𝑡𝑡𝑐𝑐 ) (35−29)
…58
Then, tc is given by
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅haf (35)(𝑡𝑡 100 −𝑡𝑡 0 )+35�∅haf (29)−∅haf (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡𝑐𝑐 = …59
6∅ful (𝑡𝑡 100 )+�∅haf (29)−∅haf (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
Crossing point of minimum capacity operation line and load line, tp, is calculated by equations 52 and 55
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅min (35)(𝑡𝑡 100 −𝑡𝑡 0 )+35�∅min (29)−∅min (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡p = …61
6∅ful (𝑡𝑡 100 )+�∅min (29)−∅min (35)�(𝑡𝑡 100 −𝑡𝑡 0 )
0.077 �35−𝑡𝑡 j �
∅ful �𝑡𝑡j � = ∅ful (35) × �1 + � …62
6
Crossing point of full capacity operation line and load line, tb, is calculated by equations 52 and 62.
Then, tb is given by :
40
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅ful (35)(𝑡𝑡 100 −𝑡𝑡 0 )+0,077 ×35∅ful (35)(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡b = …64
6∅ful (𝑡𝑡 100 )+0.077 ∅ful (35)(𝑡𝑡 100 −𝑡𝑡 0 )
In the same way, crossing point of half capacity operation line and load line, tc, is given by
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅haf (35)(𝑡𝑡 100 −𝑡𝑡 0 )+0.077 ×35∅haf (35)(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡c = …65
6∅ful (𝑡𝑡 100 )+0.077 ∅haf (35)(𝑡𝑡 100 −𝑡𝑡 0 )
In the same way, crossing point of minimum capacity operation line and load line, tp, is given by
6∅ful (𝑡𝑡 100 )𝑡𝑡 0 +6∅min (35)(𝑡𝑡 100 −𝑡𝑡 0 )+0.077 ×35∅min (35)(𝑡𝑡 100 −𝑡𝑡 0 )
𝑡𝑡p = …66
6∅ful (𝑡𝑡 100 )+0.077 ∅min (35)(𝑡𝑡 100 −𝑡𝑡 0 )
41
Free Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commercial
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
ANNEX M
(Clause J-2)
CALCULATING METHOD FOR SEASONAL PERFORMANCE FACTOR WHEN SETTING A
SPECIFIC COOLING LOAD
M-1 GENERAL
A specific cooling load widely varies from region to region on the globe depending on climate conditions,
building structures and the situations in which air conditioners and heat pumps (hereinafter referred to as
equipment) are used.
In order to evaluate and compare different seasonal performance factors of the equipment, it is desirable that a
representative cooling load is established.
For this purpose, this annex is given to establish a minimum, representative cooling load and to show an
evaluation method of the equipment operating at the conditions fixed by this load.
This annex also specifies a calculation method for seasonal performance factor of the equipment installed in a
specific region or in a specific building.
Calculation of cooling seasonal performance factor (CSPF) is made in accordance with the provisions specified
in the main body for each type of equipment.
Bin hours of each outdoor temperature which requires cooling during the cooling season shall be set.
Outdoor temperature characteristics of equipment relative to cooling capacity and power input are obtained from
the main body.
(MED 03)
Publication Unit, BIS, New Delhi, India
42
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
(Third Revision)
[Page 2, clause 5.3.5 (see also Amendment No. 1)] — Substitute the
‘Supply cord and the interconnecting cord between the indoor and outdoor unit’
for ‘Supply cord’.
[Page 3, clause 5.7, line 2 (see also Amendment No. 1)] — Substitute
‘+5 percent’ for ‘±5 percent’.
[Page 6, clause 9.9.4 b) (see also Amendment No. 1)] — Insert the
following the existing clause:
[Page 7, clause 9.11 (see also Amendment No. 1)] ― Substitute the
following for the existing clause:
Price Group 2
1
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9.11.1.1 For all heating capacity tests, the requirements specified in Annex E
shall apply. Testing shall be conducted using the Calorimeter test method (see
Annex G) or Indoor Air Enthalpy test method (see Annex H).
9.11.1.2 Selectable resistive elements used for heating indoor air shall be
prevented from operating during all heating capacity tests, except those used
only during a defrost cycle.
9.11.1.4 Standard rating conditions for heating capacity tests are specified
in 8.2.1.
On the outdoor side of the heat pump, all resistance elements associated with
inlets, louvers and any ductwork and attachments considered by the
manufacturer as normal installation practice shall be installed. On the indoor
side of the heat pump, grille positions, damper positions, fan speeds, etc. shall
be set in accordance with the manufacturer's published installation instructions,
which are normally provided with the equipment. In the absence of such
installation instructions, grille positions, damper positions, fan speeds, etc, shall
be set to provide the maximum heating.
Each heating capacity test shall be conducted with the external static pressure at
each indoor unit maintained at 0 Pa. For the heating capacity calculations
described in Annex H, the indoor-side air volume flow rate shall be expressed in
units of cubic metre per second (m3/s) of the air-water vapour mixture. For
reporting purposes, the indoor-side air volume flow rate shall be expressed in
units of cubic metre per second of standard air.
2
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9.11.3.2 If the heat pump turns the indoor fan off during the defrost cycle,
airflow through the indoor coil shall cease.
9.11.5.1 The test room re-conditioning apparatus and the heat pump under test
shall be operated until the test tolerances specified in Table 2 are attained for at
least 10 min.
9.11.6.2 The heat pump shall operate while meeting the Table 2 test tolerances.
3
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9.11.7.1 The data collection period immediately follows the equilibrium period.
9.11.7.2 Data shall be collected as specified for the test method(s) chosen from
9.11.1.1. If using the calorimeter method, heating capacity shall be calculated as
specified in Annex G. If using the indoor air enthalpy method, heating capacity
shall be calculated as specified in Annex H.
9.11.7.5 For heat pumps that automatically cycle off the indoor fan during a
defrost, the contribution of the net heating delivered and/or the change in
indoor-side dry-bulb temperature shall be assigned the value of zero when the
indoor fan is off, if using the indoor air enthalpy method. If using the
calorimeter test method, the integration of capacity shall continue while the
indoor fan is off.
9.11.8 The measured heating capacity shall not be less than 90 percent of the
rated heat pump capacity.’
[Page 7, clause 9.12, sentence 4 (see also Amendment No. 1)] — Substitute
the following for the existing sentence:
‘Capacity and power at half load shall be within ±5 percent of the rated full load
capacity and rated full load power respectively.’
[Page 7, clause 9.12 (see also Amendment No. 1)] — Insert the following
new clause:
The conditions given in 8.2.2 shall be used during the maximum heating
performance test. The test voltages given in 8.2.2 shall be maintained at the
4
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
9.13.3.1 Pre-conditions
The controls of the equipment shall be set for maximum heating. All ventilating
air dampers and exhaust air dampers, if provided, shall be closed.
The equipment shall be operated for 1 h after the specified air temperatures have
been attained. The equipment shall be permitted to stop and start under the
control of an automatic limit device, if provided.
[Page 7, clause 10 (see also Amendment No. 1)] — Insert the following at
the end:
[Page 7, clause 10.3 (see also Amendment No. 1)] — Insert the following
at the end:
‘NOTE — The ISEER may be calculated as per the methodology prescribed by Bureau of
Energy Efficiency in the S.O. 2528(E) dated 8th August, 2017.’
[Page 17, clause 15.3.1, b) (see also Amendment No. 1)] — Delete.
5
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 17, clause 15.3.1 (see also Amendment No. 1)] – Insert the following
to the existing:
k) Sound test.’
[Page 21, clause J-1 (see also Amendment No. 1)] — Insert the following
at the end:
‘NOTE — The ISEER may be calculated as per the methodology prescribed by Bureau of
Energy Efficiency in the S.O. 2528(E) dated 8th August, 2017.’
[Page 21, clause J-4.4 a) (see also Amendment No. 1)] — Substitute the
following with the existing:
[Page 21, Annex K, equation 55(see also Amendment No. 1)] — Substitute
‘∅min (29)’ for ‘𝑣𝑣min (29)’.
[Page 21, clause M-1 (see also Amendment No. 1)] — Insert the following at
the end:
‘NOTE — The ISEER may be calculated as per the methodology prescribed by Bureau of
Energy Efficiency in the S.O. 2528(E) dated 8th August, 2017.’
(MED 03)
Publication Unit, BIS, New Delhi, India
6
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
TO
[Page 3, clause 5.8 (see also Amendment No. 1)] ― Substitute the following
for the existing:
[Page 3, clause 5.10 (see also Amendment No. 1)] ― Substitute the following
for the existing clause:
‘5.10 Motors
The motor used for driving the fan/blower motor shall be either capacitor type
induction motors or brushless d.c. motor (BLDC).
Price Group 1
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
The capacitor type induction motor shall comply with the requirements given in
IS 996 as applicable for fan duty motors.
In the case of BLDC motors, the test for full load test shall be carried out at the
rated frequency declared by the manufacturer. The measured power input and
the speed shall be within ± 10 percent of the declared value. In addition, BLDC
motors shall comply with the following requirements as specified in the respective
clauses of IS 996 as applicable:
a) Dimensions (see 7.1);
b) Terminal box (see 9.2);
c) Mounting (see 9.3);
d) Constructional features (see 9.4);
e) Enclosure (see 10 of IS 996 and IP code as per IS/IEC 60529 : 2001);
f) Method of cooling (see 11);
g) Full load test for measurement of power input and full load speed at the
declared frequency (see 12.5 and F-6.2.4);
h) Insulation resistance excluding the requirement of temperature rise test
(see 12.7);
j) High voltage (see 13.1); and
k) Moisture proofness (see 13.2).
NOTE ― Separate standards for BLDC motor is under development. Requirement of overload
protector, the centrifugal switch and capacitor from IS 996 does not apply for BLDC motor.’
2
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 3, clause 7.2 b)] ― Substitute the following for the existing:
‘b) Model;’.
[Page 3, clause 7.2 g) (see also Amendment No. 2)] ― Insert the following
for the existing:
‘g) Overall dimensions;’.
[Page 3, clause 7.2 j)] ― Substitute the following for the existing:
‘j) Mass of the refrigerant charged into the unit;’.
[Page 4, clause 8.1.1 e), (see also Amendment No. 1)] — Delete.
[Page 7, clause 9.11.2.2, line 1 (see also Amendment No. 2)] ― Substitute the
following for the existing:
‘9.11.2.2 Heating capacity test shall be conducted with the external static pressure
at each indoor unit maintaining the zero static pressure difference between the
discharge chamber and intake opening of the equipment under test.’
[Page 7, clause 9.11.2.2 (see also Amendment No. 2)] ― Insert the following
at the end:
‘NOTE ― This test is applicable for fixed speed only.’
(MED 03)
Publication Unit, BIS, New Delhi, India
3
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
TO
( Third Revision )
[Page 2, clause 5.2.5, para 2 (see also Amendment No. 3)] ― Delete.
[Page 2, clause 5.4.1 (see also Amendment No. 1)] ― Substitute the following
for the existing:
‘5.4.1 The refrigerant pipes and fittings shall be of approved quality, shall withstand
maximum working pressures in refrigeration circuits of air conditioners, and
shall conform to IS 10773 or material specified in Annex B of IS 11329.’
[Page 3, clause 5.7 (see also Amendment No. 1 and Amendment No. 2)] ―
Substitute the following for the existing:
Price Group 2
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 5, clause 9.2 (see also Amendment No. 1)] ― Substitute the following
for the existing:
‘9.2 Safety
Electrical safety tests shall be carried as per 15.3.3. Air conditioner using A3
refrigerants shall comply with the requirements of 5.2.16 for protection against
explosion hazards and 5.3.3 tightness tests specified in IS 16678 (Part 2)/
ISO 5149-2.’
[Page 6, clause 9.7.4 (see also Amendment No. 1)] ― Substitute the following
for the existing:
‘9.7.4 Requirements
The power consumption for air conditioner tested under the conditions laid
in 8.1.1 shall not exceed the values as given in Table 1.’
2
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 6, Table 1 (see also Amendment No. 1)] ― Substitute the following for
the existing table:
Table 1 Power Consumption Rating
( Clause 9.7.4 )
Sl No. Rating Cooling Capacity Maximum Power Consumption at
(W) Rated Conditions
(W)
(1) (2) (3)
i) ≤ 3 500 1 270
ii) 3 501 ≤ 5 200 1 900
iii) 5 201 ≤ 7 000 2 540
iv) 7 001 ≤ 8 700 3 170
v) 8 701 ≤ 10 500 3 800
vi) 10 501 ≤ 12 000 4 440
vii) 12 001 ≤ 13 500 5 180
viii) 13 501 ≤ 15 000 5 930
ix) 15 001 ≤ 16 500 6 700
x) 16 501 ≤ 18 000 7 500
NOTE — The power consumption under rated conditions shall not exceed by 10 percent of
the declared or stated value provided the measured value does not exceed the value given in
the Table 1.
(Page 10, clause 11.5) ― Substitute the following for the existing:
3
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 16, clause 15.2.1 (see also Amendment No. 1)] ― Substitute the
following for the existing:
[Page 16, clause 15.2.2 (see also Amendment No. 1)] ― Substitute the
following for the existing:
[Page 16, clause 15.2.3 (see also Amendment No. 1)] ― Substitute the
following for the existing:
4
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 16, clause 15.2.4 (see also Amendment No. 1)] ― Substitute the
following for the existing:
[Page 16, clause 15.4.2 (see also Amendment No. 1)] ― Insert the following
at the end of the clause:
[Page 18, clause 17.1 (see also Amendment No. 1)] ― Substitute the
following for the existing:
‘17.1 The split air conditioner shall have the following information marked on a
name plate in a permanent and legible manner in a location where it is accessible
and visible. The details of marking on outdoor unit (ODU) and indoor unit (IDU)
shall be as given below:
17.1.1 Marking on ODU
a) Manufacturers name, trademark, or identification mark;
b) Model number and serial number of the unit;
c) Name and quantity of the refrigerant charge;
d) Rated voltage or voltage range, frequency and phase;
e) Cooling capacity at rated conditions;
f) Total power consumption at the rated conditions;
g) Nominal current at rated conditions;
h) ISEER at rated conditions; and
j) Country of manufacture/origin.
5
e Standard provided by BIS via BSB Edge Private Limited to Quality Solutions - Alpha Commer
Belt,(Info@qualitysolutions.co.in) 103.76.139.9 [for non-commercial use only].
[Page 18, clause 17.2, para 1 (see also Amendment No. 1)] ― Substitute the
following for the existing:
‘Each split air conditioner may also be marked with the Standard Mark on both
indoor and outdoor units.’
(MED 03)
Publication Unit, BIS, New Delhi, India