Professional Documents
Culture Documents
Jic Electrical Standards PDF
Jic Electrical Standards PDF
FOREWORD
THE BUILDERS AND USERS of machine tools and Membership in the JIC is open to interested and affected
similar industrial equipment as well as the manufacturers companies, associations and organizations that desire to
of electrical apparatus have long realized that safety of the participate in the fulfillment of these objectives.
machine operator and maintenance of production are of Paralleling the old standards, two new ones have been
cardinal importance in the design and purchase of such written, one for General Purpose Machine Tools and one
equipment. To fulfill this realization in the area of for Mass Production Equipment. These new standards are
equipment electrification, this standard is the latest in a intended to be basic in nature; that is. they do not contain
series which has been issued in the last 25 years. any requirements specific to anyone company. division or
The first form of the machine tool electrical standards was plant. It is anticipated that purchasers using JIC standards
issued by the National Machine Tool Builders' Association will also add their own particular requirements to
(NMTBA) in 1941. The NMTBA standard has been purchase specifications in ordering equipment.
revised and reissued periodically until 1960 when the Furthermore, the purchaser must clearly state which
most recent issue was released. version he requires adherence to, if either .
In 1948 the first electrical standard for industrial Additional requirements for particular equipment such as
equipment was issued by the Joint Industry Conference. furnaces, welders. presses. etc., have not been included in
The revision and re-issuance of this standard continued either of the standards. It is anticipated that these will be
until 1957. covered by addendum sheets to be issued later. Electronic
While the two standards were very similar, the Joint applications will also be covered more thoroughly in
Industry Conference standard also included equipment another standard.
other than machine tools and laid particular emphasis on All JIC Standards are advisory on/y. Their use in industry
maintenance problems peculiar to the mass production or trade is entire/y voluntary.
industries. The JIC assumes no liability for any patent infringements
In 1963 both standards were in need of review and or asserted patent infringement which may result from the
revision. For this purpose a new organization, the Joint use of these standards.
Industrial Council (JIC), was formed in order to provide Comments or requests for information regarding JIC
direction, coordination and continuity of effort in the activities or interpretations of the JIC standards should be
development, advancement, and referral to the United addressed to the Secretary of the Joint Industrial Council,
States of America Standards Institute (USASI) of care of the National Machine Tool Builders' Association.
standards which will encourage the safe and reliable 2139 Wisconsin Avenue. N.W., Washington. D. C. 20007.
application of controls to machines and equipment used in
industrial applications.
ACKNOWLEDGEMENT
These standards are reproduced with the expressed permission of the Joint Industrial Council This portion is a reproduction
of the JIC Electrical Standards for Mass Production Equipment. EMP-1-1967.
SCOPE AND APPLICATION OF STANDARDS
These standards supersede the Chrysler Corporation Electrical Standards for Industrial Equipment dated june.1963.
They shall apply to all electrical systems, furnished as a part of the machine tool or mass production industrial equipment,
which operate from a supply voltage of 600 volts or less, commencing at the power supply terminals on the disconnecting
means (See E1.2 for exceptions to this rule).
The Sample Electrical Equipment Data Form attached hereto as Appendix F shall accompany all purchase inquiries for the
particular equipment specified herein.
See the Foreword for instructions for ordering specialized equipment such as furnaces, welders and mechanical presses.
E1. General granted shall apply only to the order in question and shall
E1.1 Purpose. The purpose of this Electrical Standard is not be considered as permanent.
to provide detailed specifications for the application of E1.7 Use of .'Shall" and "Should". The word '.shall'. is
electrical systems to mass production industrial equipment understood as a requirement; the word "should" as a
which will promote. recommendation.
(1) Safety to personnel. *E1.8 Conformity to JIC Standards. When the
(2) Uninterrupted production. purchaser requires that electrical equipment and the
(3) Long life of the equipment. installation of such equipment by the supplier shall
(4) Ease and low cost of maintenance. conform to this standard and other requirements, it shall
This standard is not intended to limit or inhibit be so specified on the purchase inquiry. (See E 1.9)
advancement in the art of electrical or mechanical *E1.9 Additional User Requirements The purchase
engineering. inquiry shall be accompanied with an Electrical
E1.2 Scope. The provisions of this standard shall apply to Equipment Data Form and shall be confirmed on the
all electrical systems, furnished as part of the mass purchase order. (See Appendix F for Sample Electrical
production industrial equipment, which operate from a Equipment Data Form)
supply voltage of 600 volts or less, commencing at the **E1.10 Approvals and Final Drawings. The industrial
power supply terminals on the disconnecting means. equipment builder shall submit to the purchaser diagrams
Exception No. 1: Hazardous Locations. This standard and data specified on the Electrical Equipment Data
shall not be considered adequate for mass production Form.
industrial equipment intended for use in locations **E1.10.1 Approvals. Approval shall be obtained be- fore
designated as hazardous in the National Electrical Code. electrical components are installed on the industrial
*Exception No 2. Fixed or Portable Tools. This standard equipment. After preliminary approval any deviations
is not intended to apply to 115 volt, single phase, portable made by the equipment builder shall have the approval of
type equipment, using cord connections. unless such the purchaser in writing before changes are made.
equipment is auxiliary to the mass production industrial **E1.10.2 Final Drawings. On completion of the
equipment. industrial equipment and not later than the date of
shipment, a complete set of non-folded tracings or
E1.3 Definitions.
reproducible copies of final diagrams shall be forwarded
*E1.3.1 Mass Production Industrial Equipment. Mass
to the purchaser. The quality of the tracings or
production industrial equipment is defined as any
reproducible copies shall permit making changes and
equipment electrically powered or controlled, used in or
clearly legible prints. If any field changes are made by the
necessary for manufacturing processes and assembly
industrial equipment builder. they shall be recorded and a
equipment
reproducible copy of the changed drawing shall be
E1.3.2 Electrical Systems. Electrical systems shall
forwarded to the purchaser or other designated person
include:
(1) Electrical equipment consisting of motors, solenoid- E 2. Diagrams, Data, Nameplates and Identification
operated devices, limit switches, pressure switches, E2.1 Diagrams. General
control station electrical components and similar contact- *E2.1.1 Drawing Size. The electrical diagrams. including
making devices, together with the associated wiring. panel layout. stock list and sequence of operations should
(2) Electronic equipment together with the associated be shown on the same sheet. The foundation drawing
wiring and devices. should be shown on a separate sheet. Multiple sheets shall
(3) Static control equipment together with the associated be cross-referenced. All information shall be clearly
wiring and devices. legible Sheet size shall be 24" x 36". (For sample
E1.3.3 Nominal Voltages. All voltages hereinafter will be diagrams, see Appendix B)
considered nominal 115 volts, 230 volts and 460 volts. *E2.1.2 Diagrams Supplied. Diagrams of the electrical
(See Appendix C for definition of nominal voltage.) system shall be furnished. The diagrams shall show the
E1.4 Additional Codes and Specifications. On any point equipment serial number. the purchaser's drawing
for which specific provisions are not made in this number. purchase order number or similar identification
standard. the provisions of the National Electrical Code which will indicate the particular equipment to which the
(NEC) and state and local codes shall be observed. The diagrams apply. Diagrams shall show all equipment in the
National Fire Protection Association (NFPA) Standard 79, electrical system including internal wiring of sub-
included with the National Electrical Code applies assemblies. Diagrams of sub-assemblies may be furnished
specifically to machine tools. Articles 500 through 540 of on separate sheets.
the National Electrical Code apply, as applicable, to Exception. On industrial equipment having only one
Hazardous Locations. motor and one starter. the diagram normally furnished
E1.5 Specific Standards and Revisions. Whenever a with the combination starter is satisfactory. provided the
specific standard is mentioned in this standard, it is diagram shows all of the electrical apparatus on the
under- stood it will be "the latest revision thereof" unless industrial equipment.
other- wise specified. E2.1.3 Symbols and Device Designations.
E1.6 Deviations. Deviations from this standard shall have E2.1.3.1 Standard electrical symbols as shown in
the approval of the purchaser in writing. Any waivers Appendix A shall be used for all diagrams For symbols
not shown in Appendix A refer to United Stales of E2.2 Elementary (Schematic) Diagram.
America Standard Y32.2. Symbols for logic devices shall E2.2.1 An elementary diagram shall be furnished for each
be in accordance with NEMA Standard IC-I. Industrial electrical system. A logic diagram may be furnished in
Control. lieu of or in combination with an elementary diagram .
Exception. Special symbols may be used where there is no E2.2.2 The elementary diagram shall be drawn between
standard symbol; such symbols shall be identified and vertical lines which represent the source of control power .
explained both on the diagrams and in instruction All control devices shall be shown between these lines.
manuals. Actuating coils of control devices shall be shown on the
E2.1.3.2 The symbols for devices shall be identified by a right-hand side. All contacts shall be shown between the
number or number-Ietter combination, using abbreviations coils and the left vertical line.
shown in Appendix D. For special abbreviations not Where the internal wiring diagrams of sub-assemblies are
listed. refer to NEMA Standard IC-1. Industrial Control. furnished on separate sheets. they shall be shown as a
E2.1 3.3 The following alphabetical designations shall be rectangle in the elementary diagram with all external
used for the devices indicated and shall not be used for points identified and cross-referenced to the separate
other identification purposes: sheet(s) of the control circuit. Coils and contacts internal
Items Examples to the sub-assemblies shall be shown in the rectangle
Relays-General Use CR, 1CR, 2CR connected to their terminal points.
-Master CRM Exception No. 1: Where relay and electronic circuits are
-Automatic CRA mixed. diagrams may be drawn between horizontal lines
-Electronically which represent the source of control power .
CRE, 1CRE, 2CRE
Energized Exception No.2. Overload relay contacts may be
-Manual(hand) CRH connected to the right of the coil (common) if the
-Latch CRL, 1CRL, 2CRL conductors between such contacts and the coils of the
-Unlatch CRU, 1CRU, 2CRU magnetic devices do not extend beyond the control
Timers TR, 1TR, 2TR enclosure.
Overload Relay OL, 1OL, 2OL E2.2.2.1 Control device symbols should be shown in the
Motor Starters 1M, 2M, etc. order in which the controls are energized and positioned
Reversing Motor 1 M F ( Forward)- 1 M R on the diagram for clarity.
Starters (Reverse) *E2.2.2.2 A cross-referencing system shall be used in
Example: 2M F conjunction with each relay coil so that associated
Starter Number contacts may be readily located on the diagram. Where a
relay contact appears on a sheet separate from the one on
Forward
Plugs 1PL, 2PL, etc. which the coil is shown. the purpose of the contact shall
be described on the same sheet.
Example: 2PL 6
E2.2.2.3 Only contacts actually used shall be shown.
Plug Number E2.2.2.4 Limit. pressure. float, flow. temperature-sensitive
Pole Number and similar s\\itch symbols shall be shown on the
Solenoids 1SOL. 2SOL, 3SOL elementary diagram with all utilities turned off (electric
Limit Switches 1LS, 2LS, 3LS power, air. gas. oil, water. lubrication. etc.) and with the
Pressure Switches 1PS, 2PS, 3PS equipment at its normal starting position.
E2.1.3.4 Special abbreviations not covered by the above E2.2.2.5 Contacts of multiple-contact devices (e.g..
paragraphs may be used and shall be identified on the selector switches) shall be shown on the line of the
diagram:; and In the instruction manual. elementary diagram where they are connected in a circuit.
E2.1.4 Conductor Identification. Each conductor shall be A mechanical connection between the multiple contacts
identified by a number. letter or number-Ietter shall be indicated by a dotted line or arrow. This does not
combination. Consecutive numbering is preferred. The apply to control relays. starters or contactors.
identification shall be used only once in the electrical E2.2.2.6 Additional charts or diagrams may be used to
system. Each conductor shall have the same identification indicate the positIon of multiple-contact devices such as
at all terminals and tie points. All conductors connected to drum, cam and selector switches.
the same terminal or tie point shall have the same E2.2.2.7 The connections between push buttons. limit
identification. Where multiconductor cable is used. a color switches and similar items connected in series shall be
code may be used to supplement the above identification. shown as test points on the diagram as required in E
Where color- coded multiconductor cable is used for 12.4.14.
wiring identical components. such as limit switches. the E2.2.2.8 The purpose or function of all switches shall be
color code used shall he consistent and charted on related shown either adjacent to the symbols. or in a switch
diagrams. description chart. The chart shall be on the same sheet as
E2.1.5 Sub-assembly Terminal Identification. Terminal the symbol.
numbers. letters or number-Ietter combinations for sub- *E2.2.2. 9 The purpose or function of controls such as
assemblies or components shall be identified distinctively- relays, starters. contactors. solenoids, sub-assemblies and
and associated with the sub-assembly or component. timers shall be shown on the diagram adjacent to their
respective symbols. The number of positions of the
solenoid valve shall be shown adjacent to the valve and chassis comprising the complete electrical system.
solenoid symbol. Each connection shall be identified as shown on the
E2.2.2.10 Values of capacitors and resistors shall be elementary diagram Blank spaces and spare terminals
shown on the diagram. shall be shown.
E2.2.2.11 Descriptive terms for command and status **E2.4.4 For logic control systems, a panel layout
functions shall be in the present or past tense. For diagram shall (1) consist of an outline of the control
example. Raise Transfer-Transfer Raised: Advance panel, and (2) show the general physical arrangement of
Transfer-Transfer Advanced. Terms such as " Transfer the panel-mounted devices. Each device may be
Up'. shall not be used. represented a square or rectangle. Each device shall have
**E2.2.2.12 Coils of relays and other control devices the same identification as on the elementary diagram.
should be grouped and drawn in the following order E2.5 Stock List The stock list shall show quantity,
(1) Sequencing and position indicating relays. etc. manufacturers name, type or model and catalog number of
(2) Solenoids for valves. each device used: motor horsepower, frame size. type of
Within each group. control devices shall be shown in the enclosure, and speed: and any other information necessary
order or energization. to order replacement electrical and electronic items
Exception: Solenoids common to a valve should be E2.6 Sequence of Operation. The sequence of operation
grouped together; for example: “Clamp" and "Un-clamp." shall indicate the progression of operations of all push-
E2.2.3 Electronic Diagram. Electronic diagrams shall buttons, limit switches. relays. solenoids and other de-
include pertinent data for maintenance purposes as vices as shown and identified on the elementary diagram.
follows. Graphical representations, such as bar charts. may be used
(1) Voltage and current data necessary for maintenance to supplement written descriptions.
purposes. E2.7 Instruction Manuals. On complex equipment. such
(2) Normal voltages on transformer windings. as numerical control systems. servo controls, electrical
(3) Signal input and output voltages. variable-speed drives. etc.. an instruction manual shall be
(4) Potentials applied to tube elements. furnished. The following shall be included:
(5) Oscilloscope traces. showing wave form and peak- to- (1) Information necessary for calibrating and adjusting
peak voltages where meter readings are inadequate. components. devices and sub-assemblies.
(6) The type and sensitivity or test instruments to be used (2) Operation instructions. including all information
and the condition of the circuit. necessary to describe the operation of the: complete
(7) The instantaneous polarity or each transformer system.
winding in phase sensitive circuits. (3) Maintenance instructions, including information and
(8) The electrical values of capacitors. resistors. suggestions for locating and replacing faulty components.
inductances and other electronic components. suggested maintenance schedules and related data.
E2.3 Block and Logic Diagrams. (4) A recommended spare parts list with complete
E2.3.1 Block Diagram. Where the complexity or the ordering information and suggested quantities.
control system warrants. a block diagram of control E2.8 Electrical Layout. The electrical layout shall consist
functions shall be furnished. Each block shall be or an outline or the equipment, not necessarily to scale.
identified and cross-referenced in a manner that the showing the control panel enclosure and its dimensions,
internal circuitry may be found readily on the elementary operator's console and accessory units not attached
diagram. directly to the equipment. such as hydraulic power units.
E2.3.2 Logic Diagram. A logic diagram of the electrical in their relative locations The drawing shall also show the
system shall be furnished when static control or logic location or control devices whose location cannot be
modules are supplied. The diagram need not show power readily determined from the elementary and other
connections. electrical diagrams. such as limit switches used on
indexing
E2.4 Panel Layout and Interconnection Diagram.
mechanisms. All devices shall be identified as shown on
*E2.4.1 The panel layout shall show the general physical
the elementary diagram.
arrangement of all components on the control panel.
E2.9 Foundation Drawing. On equipment requiring
Devices may be represented by rectangles or squares and
conduit in the foundation. the minimum size, purpose and
shall be identified with the same marking as used on the
location of the conduit to be used shall be shown on a
elementary diagram Spare panel space shall be
foundation drawing.
dimensioned The drawings shall include a layout of the
operator's console or push button station, but terminal E2.10 Equipment Nameplates.
numbers need not be shown. This layout may be combined E2.10.1 Main Nameplate. A permanent non-corrodible
on the same drawing with the interconnection diagram or nameplate shall be attached to the control enclosure door
wiring table. (See Sample Diagram in Appendix B.) This nameplate shall list the following:
E2.4.2 Photographs of electronic chassis and similar (1) Equipment serial number
complex devices ma} he furnished in lieu of panel layouts, (2) Supply voltage, phase and frequency.
provided each component is clearly visible and identified. (3) Rated K V A or full-Ioad current (see E 2.10.1.1).
E2.4.3 -An interconnection diagram or wiring table shall (4) NEMA interrupting capacity of the circuit breaker (if
be furnished to Indicate the Interconnecting conductors supplied)
between all terminals on each terminal block for all panel, (5) Ampere rating of the largest motor .
(6) Supplier's electrical diagram number. **E2.12.2 Plates for devices mounted external to the
Exception. Where only a single motor and motor control enclosure shall be non-corrodible metal. a mini-
controller are used, the motor nameplate may serve as the mum of 0.031 inch thick for engraving stock or 0.012
electrical equipment nameplate if it is plainly visible. inch thick for embossing stock. Plates shall be held in
E2.10.1.1 .The full-load current shown on the name- plate place with metallic drive screws.
shall be not less than the sum of the full-Ioad currents E3. Supply Circuit Disconnecting Means
required for all motors and other equipment which may be *E3.1 Scope. This section shall apply to all industrial
in operation at the same time under normal conditions of equipment, including portable and semi-portable
use. Where unusual loads, duty cycles, etc.. require equipment except: (1) small bench-type tools powered by
oversized conductors, the required capacity shall be a single motor rated less than 1/4 horsepower operating
included in the .”full-load current" rating as marked. from a 115 volt supply, and (2) welding transformers and
E2.10.1.2 Where more than one Incoming supply circuit their control circuits.
is provided, the nameplate: shall state the above in- E3.2 Type.
formation for each circuit E3.2.1 Where nominal 115 volt, single phase, is the only
E2.10.1.3 Where overcurrent protection is provided in power supply to the equipment, a fused disconnect switch
accordance with E 4 3. Main and Branch Circuit Over- or circuit breaker of suitable size shall be installed.
current Protection. the: nameplate shall be permanently E3.2.2 On all other equipment the builder shall furnish,
marked "Overcurrent protection provided at equipment as specified by the purchaser, one of the following
supply terminals. A separate nameplate may be used for disconnecting means:
this purpose (1) A fusible or non-fusible motor circuit switch con-
E2.10.1.4 Where the builder wishes to indicate forming to all requirements, except enclosures, listed in
compliance with this and other standards, it is NEMA Standard KS-I, Enclosed Switches, for heavy duty
recommended that the nameplate be marked with a type HO switches, or
notation similar to the following: '.The electrical (2) A circuit breaker conforming with N EMA Standard
equipment and wiring on this machine conform to the AB-I, Molded Case Circuit Breakers, or
following standard(s) ...” (3) A fusible or non-fusible circuit interrupter.
E2.10.2 Additional Nameplates Where electrical E3.2.3 When a separately mounted safety switch is
equipment is removed from the original enclosure, or specified by the purchaser as auxiliary equipment, it shall
where equipment is so placed that the manufacturer's be a NEMA heavy duty industrial type, manually-
nameplate is not readily visible, an additional nameplate operated, fusible or non-fusible (as specified) and
shall be permanently attached to the equipment or en- mounted in a NEMA Type 12 enclosure.
closure. Nameplates shall not be removed from electrical
E 3.3 Rating.
equipment.
E3.3.1 The ampacity of the disconnecting means shall be
E2.11 Device Identification Control and power devices
not less than 115 percent of the sum of the full-Ioad
shall be plainly and permanently identified. using the
currents required for all equipment which may be in
same identification as shown on the elementary diagram.
operation at the same time under normal conditions.
Identification shall be shown on a plate mounted adjacent
E3.3.2 The interrupting capacity of the disconnecting
to, not on, the device. Control station components shall be
means shall be not less than the sum of the locked rotor
identified by function. (See E 9.3.2)
current of the largest motor plus the full-load current of
Exception No.1. Where the size or location of the devices
the other connected operating equipment.
make individual identification impractical. such as on
E3.4 Application. The disconnecting means shall be
electronic assemblies, group identification shall be used.
applied in accordance with E4, Protection.
Exception No.2. Where panel layouts do not permit
E3.5 Position Indication. The disconnecting means shall
mounting identification plates adjacent to components,
plainly indicate whether it is in the open or closed
such as relays, the permanent relay identification shall be
position. (See E 3.11.3)
placed on the relay where it is plainly visible. and a
E3.6 Supply Conductors to be Disconnected. The
second identification provided on the top of the panel
disconnecting means shall disconnect all ungrounded
wireway cover directly below the relay. The wireway
conductors of the supply circuit simultaneously. Where
covers shall be identified to show their proper location.
there is more than one supply source, additional
**E2.12 Identification Plates.
individual disconnecting means shall be provided for each
**E2.12.1 Plates for devices mounted inside the control
supply circuit so that all supply conductors may be
enclosure shall be one of the following:
interrupted.
(1) Non-corrodible metal for engraving stock; a minimum
E3.7 Supply Line Connection. The incoming supply
of 0.031 inch thick.
conductors shall terminate at the disconnecting means
(2) Non-corrodible metal for embossing stock; a minimum
with no connection to terminal blocks or other devices
of 0.012 inch thick.
ahead of the disconnecting means.
(3) Laminated phenolic for engraving stock; a mini- mum
E3.8 Exposed Live Parts There shall be no exposed live
of 0.062 inch thick.
parts when the disconnecting means is in the open
Plates shall be held in place with metallic drive screws or
position.
the equivalent. Permanent adhesives shall be used for
attaching nameplates to wireway covers.
E3.9 Mounting. **E3.10.4 Mechanical interlocking shall be provided
E3.9.1 The disconnecting means shall be mounted within between the disconnecting means and its associated door
the control enclosure. to accomplish both of the following:
*Exception: Where panel-mounting or an 800 ampere or (1) Prevent closing of the disconnecting means while the
larger disconnecting means is impractical, the equipment enclosure door is open, unless an interlock is operated,
builder shall furnish a circuit breaker in a NEMA Type 12 and
enclosure for installation by the purchaser . (2) Prevent closing of the disconnecting means while the
*E3.9.2 If more than one disconnecting means is provided door is in the initial latch position or until the door
for multiple supply circuits in a single enclosure, they hardware is fully engaged
shall be grouped in one location and mechanically E3.11 Operating Handle.
interlocked with the door(s). E3.11.1 Location. The operating handle of the
E3.9.2.1 When disconnects are mounted in separate disconnecting means shall be readily accessible. The
enclosures, each supplying power to part of a complete center of the grip, when in its highest position, shall not
machine or equipment, the following provisions shall be be more than 6 1/2 feet above the floor and should not be
made: lower than 3 feet above the floor .
(1) A main disconnecting means shall be furnished to de- **E3.11.1.1 The operating handle shall be mounted on
energize the entire system, and the front of the control compartment or enclosure, not on
(2) The disconnecting means in any of the separate a door.
control enclosures shall de-energize all current- carrying *E3.11.2 Locking. The operating handle of the
components in that enclosure when placed in the “OFF” disconnecting means shall be so arranged that it may be
position. locked in the “OFF" position. Provision shall be made for
Exception: Control devices and terminals located in the a minimum of three locks having shackles 0.375 inch in
enclosure but energized from a remote source need not be diameter.
de-energized if identified by yellow wiring. *E3.11.3 Position Indication. The operating handle shall
*E3.9.3 The disconnecting means shall be mounted at the plainly indicate at all times whether the disconnecting
top of the control panel; no other equipment shall be means is in the open or closed position. (See E 3.5)
mounted directly above it. In enclosures with more than **E3.11.4 Linkage. Mechanical linkage between the
three doors, the disconnecting means shall be on the panel disconnecting means and its operating handle shall be 12
at either the extreme right or left. inches or less in length and shall be such that the
**E3.9.4 On bench-type equipment the combination operating handle is in control of the disconnect at all
starter need not be mounted on the equipment. times.
E3.10 Interlocking. E4. Protection
E3.10.1 Where there are two or more sources of power to *E4.1 Scope. This section shall apply to all industrial
the equipment or where there are two or more equipment, except bench-type machines powered by a
independent disconnecting means. not mechanically inter- single motor rated less than 1/4horsepower.
locked with each other. power wiring from each E4.2 General.
disconnecting means shall be run in separate conduit, and E4.2.1 Figure 4-1 shows typical circuits which are
shall not terminate in or pass through common junction acceptable for protection of electrical systems.
boxes. *E4.2.2 Fuses for power and control shall be dual element
*E3.10.2 When the disconnecting means is mounted types having a minimum interrupting capacity of 100.000
within the control enclosure. it shall be interlocked amperes at rated voltage. Fuses shall meet the
mechanically with the control enclosure door(s). A performance standards outlined in NEMA Standard FU-1,
suitable device, operated by a screwdriver or other Low Voltage Fuses. Fuse dimensions shall conform to
common hand tool, shall be provided so that the those listed for NEMA Class H.
interlocks may be by- passed and the panel doors opened Exception: The interrupting capacity requirement does not
without disconnecting the power. Interlocking must be apply to fuses in the control circuit below the main control
reactivated automatically when panel doors are closed. circuit protective device(s). Examples are those used for
Progressive interlocking, door to door, shall not be used. protection of individual solenoids and small sub-
**E3.10.3 All doors on multiple-door enclosures shall be assemblies.
interlocked simultaneously with the door which is
E4.3 Main and Branch Circuit Overcurrent
interlocked with the main line disconnecting means.
Exception No. 1. When the disconnecting means is Protection.
separately mounted, it shall be mechanically or E4.3.1 The main overcurrent protection shown in line “C"
electrically interlocked with the control enclosure door(s). of Figure 4-1, Typical Diagrams, Columns 1 through 4
Exception No.2: The interlock requirements of this inclusive, may or may not be furnished as part of the
paragraph do not apply to industrial equipment such as electrical system as specified In E 3.2. Where furnished as
electric power for resistance welders or electric furnaces part of the system, it shall consist of a single circuit
unless specified by the purchaser. However, it does apply breaker or set of fuses, and the nameplate shall bear the
to motor control for such apparatus. marking required in E 2.10.1.3.
E4.3.2 Additional Overcurrent Protection. On a machine
with more than one branch circuit, additional over-
current protection as shown on line ..D" of Figure 4-1, supplied, (2) is suitably protected from physica1 damage.
Typical Diagrams, Columns 3 and 4, shall be furnished as (3) is not over 25 feet long, and (4) terminates in a single
part of the electrical system. Overcurrent protection, such circuit breaker or set of fuses.
as fuses or overcurrent trip units of a circuit breaker, shall Exception No. 2. Where all of the following conditions are
be placed in each ungrounded branch circuit conductor. complied with: the conductor (1) has an ampacity of not
Where a circuit breaker is used, it shall open all un- less than the sum of the maximum continuous load
grounded conductors of the branch circuit. currents, (2) is not over 10 feet long, and (3) does not
E4.3.3 Overcurrent protective devices shall be located at extend beyond the control panel enclosure.
the point where the conductor to be protected receives its E4.3.4 Selecting Overcurrent Devices. If the calculated
supply except as follows: value for overcurrent (short circuit) devices does not
Exception No. 1: Where all of the following conditions correspond to standard ratings or sizes, the next larger
are complied with: the conductor (1) has an ampacity of at size or rating may be used.
least one-third that of the conductor from which it is
Figure 4-1 Typical diagrams electrical system protection
Line Reference Single Multiple Motors
Motor
A Supply, NEC Article 670
B Disconnecting Means, Sect. E3
E4.3.5 Individual Motor Overcurrent Protection. devices shall be rated at not more than 125 percent of the
E4.3.5.1 The overcurrent protective (short circuit) device current rating of the transformer and shall interrupt short
for a branch circuit supplying a single motor shall be circuits without damage to the transformer or conductors.
capable of carrying the starting current of the motor. E4.4.2 The rating of overcurrent protective devices in the
Overcurrent protection shall be considered as obtained control circuit shall be as low as practicable and shall not
when the overcurrent device has a rating or setting not exceed the values given in Table 4-4 for the smallest
exceeding that shown in Table 4-1. conductor in the circuit. In Tables 4-4 and 4-5, the smaller
*E4.3.5.2 Where the overcurrent protection specified in of the computed overload ratings shall be used.
Table 4-1 is not sufficient for the starting current of the E4.4.3 The transformer for the control circuit shall be
motor. it may be increased to a maximum of 200 percent protected in the secondary circuit against overloads and
of the motor full-load current for dual element fuses and short circuits with overcurrent devices selected in
400 percent for circuit breakers. accordance with Table 4-5.
E4.3.6 Several Motors on One Branch Circuit. Two or **E4.4.4 Solenoids mounted external to the control panel
more motors and their control equipment may be and having an inrush current exceeding 150 percent of the
connected to a single branch circuit provided all of the sealed value shall be individually protected by an
following requirements are complied with: indicating-type overcurrent protective device rated
(1) The maximum size of conductors connected to a motor approximately 130 percent of the sealed solenoid current.
controller shall be in accordance with Table 4-2. Where a fuse is used, it shall be a dual element type. The
(2) The rating or setting of the overcurrent protective device shall be connected between the solenoid and the
device shall be as low .as practicable and shall not exceed control relay contact.
the values shown in Table 4-3 for the smallest conductor
in the circuit, and
(3) Motor and control circuits shall be arranged so that a
minimum number of branch-circuit overcurrent protective
devices are required.
E4.3.7 lighting Branch Circuits. Overcurrent protection
for lighting branch circuits shall not exceed 15 amperes.
E4.4 Control-Circuit Overcurrent Protection
*E4.4.1 The control conductors shall be protected against
steady overloads and short circuits. An overcurrent device
shall be connected in series with each ungrounded leg of
all branch control circuits. Solenoids and control shall be
considered separate branch circuits. The overcurrent
*Table 4-1—Motor Overcurrent Protective Device 12 80 40
Rating 10 100 50
Percent of Full-Load Current 8 150 80
Thermal 6 200 100
Magnetic 4 250 125
Dual Element 3 300 150
Type of Motor Circuit Breaker,
Fuse Maximum 2 350 175
Maximum
Rating 1 400 200
Rating of
Setting 0 500 250
00 600 300
Motors Marked with Code Letter Indicating Locked-Rotor
000 700 350
KVA
0000 800 400
All AC Single
Phase and
Polyphase Squirrel Table 4-4—Control Conductor Overcurrent Protection
Cage and Conductor Size,
Maximum Rating, Amperes
Synchronous AWG
Motors 22 3 1/2
Code Letter A 125 150 20 6 1/2
Code Letter B to E 125 200 18 8
Code Letter F to V 125 250 16 10
Motors Not Marked with Code Letter Indicating Locked- 14 15
Rotor KVA 12 20
Single Phase, All 10 30
125 250 8 40
Types
Squirrel Cage and 6 60
125 250 4 70
Synchronous
High Reactance 3 80
Squirrel Cage 2 100
Not More than 30 1 110
Amperes Full Load 125 250 0 125
Current 00 150
More than 30 000 175
Amperes Full Load 125 200 0000 200
Current
Wound Rotor 125 150
Direct Current 125 150
For motors not included in the table refer to National
Electrical Code, Article 430, Table 430-16.
If the calculated value for the overcurrent (short circuit)
devices do not correspond to standard ratings or sizes, the
next larger size or rating may be used.
*Table 4-2—Maximum Conductor Size for NEMA
Motor Controllers (Starters)†
Maximum Conductor Size,
Controller Size
AWG or MCM
1 8
2 4
3 0
4 000
5 500
†See USA Standard C19.1, Industrial Control Apparatus
ACTUATED
R R
PLUGGING SELECTOR ROTARY SELECTOR
W/LOCK-OUT 2-POSITION 3-POSITION
COIL NON-BRIDGING CONTACTS †BRIDGING CONTACTS
1 2 3
1 2
OR OR
1
LO
†TOTAL CONTACTS TO SUIT NEEDS
1 - +
NORMALLY
CLOSED
2 - +
Appendix A-Typical Graphic Symbols for Electrical Diagrams (Continued)
CONNECTIONS. (CONT’D) CONTACTS
PLUG TIME DELAY AFTER COIL RELAY, ETC THERMAL
GROUND CHASSIS OR AND ENERGIZED DE-ENERGIZED NORMALLY NORMALLY OVER-
FRAME NOT REC’P. OPEN CLOSED LOAD
NECESSARILY NORMALLY NORMALLY NORMALLY NORMALLY
GROUNDED OPEN CLOSED OPEN CLOSED
COILS
RELAYS, SOLENOIDS, BRAKES, ETC. THERMAL CONTROL CIRCUIT
TIMERS, 2-POSITION 3-POSITION 2-POSITION OVERLOAD TRANSFORMER
GENERAL
ETC. HYDRAULIC PNEUMATIC LUBRICATION ELEMENT
H1 H3 H2 H4
X1 X2
COILS (CONTINUED)
LINEAR VARIABLE DIFFERENTIAL VARIABLE
AUTO TRANSFORMER TRANSFORMER AUTO-TRANSFORMER
COILS (CONTINUED)
SATURABLE REACTORS
TRANSFORMER SATURABLE CORE SATURABLE CORE
H
Appendix A-Typical Graphic Symbols for Electrical Diagrams (Continued)
RESISTORS, CAPACITORS, ETC. (CONTINUED)
CAPACITORS METERS METER SHUNT
FUSES (ALL
POLARIZED VOLT AMP
TYPES)
FIXED ADJUSTABLE ELECTROLYTIC
+ -
VM AM
R R
SHIELD
CONDUCTOR
SEMICONDUCTORS
RECTIFIER RECTIFIER ARC SUPPRESSORS ZENER
DIODE BRIDGE DIODE
AC DC AC AND DC
AC
+ -
AC
LIST VALUES OF RES. AND CAPT
Appendix A-Typical Graphic Symbols for Electrical Diagrams (Continued)
SEMICONDUCTORS (CONTINUED)
TUNNEL VARICAP TRANSISTOR TRANSISTOR TRANSISTOR SILICON TRANSISTOR
DIODE DIODE PNP NPN UNIJUNCTION CONTROLLED SURFACE
RECTIFIER BARRIER
SEMICONDUCTORS (CONTINUED)
TRANSISTOR TRANSISTOR
TETRODE
TRINISTOR TRIGISTOR BINISTOR VARISTOR
FIELD
EFFECT
SEMICONDUCTORS (CONTINUED)
THERMISTOR PHOTOSENSITIVE CELLS
ASYMMETRICAL SYMMETRICAL
MISCELLANEOUS
TERMINAL SYNCRHRO OR TACHOMETER CORE OF SQUARE
BLOCK RESOLVER GENERATOR LOOP MATERIAL
LOCATION OF RELAY CONTACTS
1 CLAMP
1 CR
10 TG 1CR
(2–3–4)
11 2
1CR
12
3
DIFFERENTIAL SYMMETRICAL NON-
15 SYNCHRO LINEAR
1CR
RESISTOR 1
SEQUENCE CHARTS
PROGRAM OR SEQUENCE TIMER CAM SWITCH
OPERATION TIME
TIMER RESET TIMING (MINUTES) (MINUTES) DEGREES DEGREES
CONTACT POSITION SWITCH OPERATION
1 2 3 4 5 6 7 8 9 CLOSES OPENS 90 180 270
1TR - 1 0 2 1CS 22º TO 180º
1TR - 2 3.75 7.2 2CS 0º TO 194º
ITR - 3 1.9 8.5 3CS 225º TO 360º
SHADED PORTION INDICATES CONTACT CLOSED SHADED PORTION INDICATES CONTACT CLOSED
*Appendix B—Sample Electrical Diagrams
The drawings which follow are intended only to illustrate proper electrical drafting practices outlined in the standard.
Diagram shown is for ungrounded control circuit.
DISC
1FU 1M 1OL 1T1
1L1
L1
HYDRAULIC PUMP
2FU 1L2 1T2 MOTOR
460V L2 1MTR 3 HP 1800 RPM
3Ø 3FU 1T3 FRAME 213
1L3
60 L3
15 AMP 2OL 2T1
H2
X1 115 V
10 AMP 10 AMP 10 AMP 10 AMP
6FU 4FU 5FU 7FU
2PB 1LT
1PB START MOTORS R
MASTER STOP 1OL 2OL
3 8 9 10 1 2 4
1 1M
1 7 1M
2 CR
M
3 AUTOMATIC CRM
CRM CRH MASTER RELAY
11 4PB 12 13 6 3,3
CR
4 AUTOMATIC
5 2LT A
3PB CRA 5, 14, 16, 21
5 RESET R
5PB 5 “AUTOMATIC”
11 MANUAL 14
CR MANUAL
6 H 6, 7, 15, 18, 23
3LT
CRH
7 “MANUAL”
A
CYCLE START 6LS 5
2CR 1LS 2LS 5LS 7CR 6CR
5 16 17 18 19 20 21 22 23 1 6 CLAMP PART
8 CONTROL
7PB CR
6PB 15 9, 33, 33, 35, 35
1CR 26 26 22 21 21
9
1PS
10 R “LUBE FAULT”
1FS
11
5CR
5 24 25 26 28 29 ANTI-REPEAT
2 6
12 CONTROL
CR 8, 13
2CR
28
13
7CR 8CR 9CR 3LS 4CR 5CR
CRA 30 33 36 HEAD FORWARD
31 32 34 35 3
14 CONTROL
HEAD FORWARD CR 37, 37
8PB 37 CRH
15
CRA 38 5CR HEAD IS FORWARD
16
7CR
5 9CR 39 40 6 HEAD RETURN
4
17 CONTROL
HEAD RETURN CR
14, 38, 38
9PB 41 CRH HEAD RETRACTED
18
4LS FULL DEPTH
42 43 5
19 CR CONTROL
5CR 8CR 5LT 12, 14, 17, 20, 21
44 43
20 A
CRA 8 8 “FULL DEPTH”
5CR 8CR 5
5 45 46 47 48
21
7CR
5LS 6LS 49 50 6 UNCLAMP
10PB 6
22 CR CONTROL
UNCLAMP 8, 22, 34, 34, 36, 36
6CR CRH
51
23
52 HEAD RETRACTED
7
24 INDICATOR
CR
6LT 8, 14, 17, 22, 28
25 1 8 8 G “HEAD RETRACTED”
1LS 5
2LS
5 53 54 8 6 CLAMPS ARE IN
26 INDICATION
CR
2PB 7LT 14, 20, 21, 29
11PB
27 EMERGENCY A “CLAMPS ARE IN”
RETUREN 9CR 7CR 5
55 56 57 9
28 CR
EMERGENCY
RESET 8CR
29
12PB 8LT 6
5 9CR 58
30 R “EMERGENCY RETURN
ACTIVE”
5
3 4
CHANGES
9LT GROUND DETECTOR LIGHTS 10LT
31
59
2 1
32
1CR 1CR
60 8FU† 60 2-H SOL A 61
33 LH CLAMP
SEQUENCE OF OPERATION
A. PRESS “START MOTORS” PUSHBUTTON “2PB” MOTORS START “MOTORS RUNNING” LAMP “1LT” ARE ENGERGIZED.
B. PRESS EITHER AUTOMATIC “4PB” OR MANUAL “5PB” PUSHBUTTON, CORRESPONDING RELAY AND LAMP ARE ENERGIZED.
NOTE: TO SWITCH FROM MANUAL TO AUTOMATIC. OPERATOR MUST PRESS “RESET” PUSHBUTTON “3PB” BEFORE
PRESSING AUTOMATIC PUSHBUTTON “4PB”.
C. AUTOMATIC CYCLE WITH MOTORS RUNNING AND “CRA” ENERGIZED. MACHINE IS SET FOR AUTOMATIC CYCLE HEAD MUST
BE RETRACTED AND PART UNCLAMPED TO START CYCLE.
1. OPERATOR LOADS PART IN FIXTURE AND PRESSES BOTH “CYCLE START” PUSHBUTTONS “6PB” AND “7PB”
ENERGIZING “1CR” (SOL A AND SOL C) TO CLAMP PART
2. CLAMPED PART TRIPS “1LS” AND “2LS”. ENERGIZING “8CR” RELAY “3CR” (SOL E) IS ENERGIZED MEMENTARILY.
STARTING HEAD FORWARD IN RAPID ADVANCE. HEAD CAMS VALVE INTO FEED.
5. WHEN HEAD IS FULY RETRACTED, “4LS” IS TRIPPED, DE-ENERGIZING “4CR” AND ENERGIZING “7CR” WHICH ENERGIZES
“6CR” (SOL B AND SOL D) UNCLAMPING PART.
6. WHEN PART IS UNCLAMPED, “5LS” AND “6LS” ARE TRIPPED, DE-ENERGIZING RELAY “6CR”.
7. “2CR” RELAY PREVENTS MACHING RE-CYCLING IF BOTH “CYCLE START” PUSHBUTTONS ARE NOT RELEASED.
D. MANUAL CYCLE:
1. WITH HEAD RETRACTED AND PART UNCLAMPED, PRESS “CYCLE START” PUSHBUTTONS “6PB” AND “7PB”, ENERGIZING
RELAY “1CR” (SOL A AND SOL C) TO CLAMP PART.
2. PRESS “HEAD FORWARD” PUSHBUTTON “8PB”, ENERGIZING “3CR” (SOL E) TO START HEAD FORWARD.
3. TO RETURN HEAD TO RETRACTED POSITION, PRESS “HEAD RETURN” PUSHBUTTON “9PB”, ENERGIZING “4CR” (SOL F).
4. WITH HEAD RETRACTED, PRESS “UNCLAMP” PUSHBUTTON “10PB”, ENERGIZING “6CR” (SOL B AND SOL D) TO
UNCLAMP PART.
LIMIT SWITCHES
1” X 3”
460 V
1T1 EMERG.
14 TERM.
12 TERM.
1T2
MOTORS RETURN 1
1T3
AUTOMATIC MANUAL 51
RUNNING ACTIVE
1TB
271
DISC CYCLE
2 52
1 1/2” X 3”
272
2OL START
2T3
1M R 1LT R 2LT A 3LT R 4LT
9” 5 53
6PB 6 54
9 1/2” START EMERG.
1FU 2FU 3FU MANUAL 7
115 V
MOTORS AUTOMATIC RESET 55
115 V
1OL 10 58
CYCLE START 2PB 4PB 5PB 12PB
11
STATION
1 MASTER EMERG. 12
2 1 1/2” X 3” STOP RESET RETURN
36 TERM.
5TB
13
4FU
5FU
4
5
1PB 3PB 11PB 14
460V
4TB
27
CLAMPS FULL HEAD LUBE
T CRM CRA CRH ARE IN DEPTH RETRACTED FAULT 37
6FU
7FU
CYCLE 43
115 V
CONTROL STATION
1 1/2” X 3”
9 TERM.
GROUND DETECTOR
29 TERM.
26 TERM.
26 TERM.
47 LIGHTS
51
6CR 7CR 8CR 9CR
52 6 1/2” 1T1 11 51 R R
460 V
53 1T2 12 52
55 7 1/8” 1T3 13 53 9LT
2T1 14 54 10LT
2T2 15 55
6TB
2T3
1 1/2” X 3”
1 1/2” X 3”
115 V
115 V
115 V
11 TERM.
26 1/2” 1
115 V
2
7 1/2” 3
8TB
9TB
3TB
4
5
7TB
AMT SYM
1 1/2” X 3” DESCRIPTION
SHEET SHEETS DWG.NO. Purchasers
PART. NO. XY 100 2 dwg. no
1FT8 8 TERM
DES. BY DET. BY
10FU
12FU
13FU
60 62 64 66 68 70
11FU
8FU
9FU
J.I.C. W.T.
15 1/8” SAMPLE ELECTRICAL DIAGRAMS
60 62 64 66 60 70 CHECKED SAFETY
5 1/2” BY R.S. OK P.N.
115 V”
MASTER TERMINAL BOX PANEL DATE SCALE PLANT
8-2-66 DIVISION XYZ MACHINE CO.
MAIN CONTROL PANEL
Appendix C-Glossary of Terms Conduit. Flexible, Metal A flexible metal conduit is a
Actuator The cam, arm or similar mechanical device used flexible raceway of circular cross section specially
to trip limit switches. constructed for the purpose of the pulling in or the
Ambient Conditions. The condition of the atmosphere withdrawing of wires or cables after the conduit and its
adjacent to the electrical apparatus. The specific reference fittings are in place (USAS C42.95)
may apply to temperature, contamination, humidity, etc. Conduit. Flexible Non-metallic. A flexible non- metallic
Ambient Temperature. Ambient temperature is the conduit is a flexible raceway of circular cross section
temperature of the surrounding cooling medium, such as specially constructed for the purpose of the pulling in or
gas or liquid, which comes into contact with the heated the withdrawing of wires or cables after the conduit and
parts of the apparatus. its fittings are in place
Ampacity Current-carrying capacity expressed in Conduit, Rigid Metal. A rigid metal conduit is a raceway
amperes. (NEC-NFPA No.70) specially constructed for the purpose of the pulling in or
Anti-Plugging Protection. Anti-plugging protection is the the withdrawing of wires or cables after the conduit is in
effect of a control function or a device which operates to place and made of metal pipes of standard weight and
prevent application of counter-torque by the motor until thickness permitting the cutting of standard threads.
the motor speed has been reduced to an .acceptable value. (USAS C42.95).
(NEMA IC-1 Contactor. A contactor is a device for repeatedly
Apparatus. Control apparatus is a set of control devices establishing and interrupting an electric power circuit.
used to accomplish the intended control functions. (USAS (USAS C42.25)
C42.25) Continuous Rating Continuous rating is the rating which
Auxiliary Contacts. Auxiliary contacts of a switching defines the substantially constant load which can be
device are contacts in addition to the main-circuit contacts carried for an indefinitely long time. (NEMA IC-1 )
and function with the movement of the latter. (NEMA IC- Control. See "controller electric.”
1) Control Circuit. The control circuit of a control apparatus
Auxiliary Device. Any electrical device other than motors or system is the circuit which carries the electric signals
and motor starters necessary to fully operate the machine directing the performance of the controller, but does not
or equipment. carry the main power circuit. (NEC-NFPA No.70)
Block Diagram. A block diagram is a diagram showing Control Circuit Transformer. A control circuit
the relationship of separate sub-units (blocks) in the transformer is a voltage transformer utilized to supply a
control system. voltage suitable for the operation of control devices.
Bonding Conductor. .A, bonding conductor is one which (USAS C42.25)
serves to connect exposed metal surfaces together. Control Circuit Voltage The control circuit voltage is the
Branch Circuit. A branch circuit is that portion of a voltage provided for the operation of shunt coil magnetic
wiring system extending beyond the final overcurrent devices.
device protecting the circuit. (A device not approved for Control Compartment. A control compartment is a space
branch circuit protection, such as a thermal cutout or within the base, frame, or column of the machine used for
motor overload protective device, is not considered as the mounting the control panel.
overcurrent device protecting the circuit.) (NEC-NFPA Control Panel. See "panel."
No.70) Control Station. See "operator's control station."
Captive Screw. Screw-type fastener that is retained in Controller Electric. An electric controller is a device, or
some manner when unscrewed and cannot easily be group of devices, which serves to govern, in some pre-
separated from the part it secures. determined manner, the electric power delivered to the
Chassis. Sheet metal box, frame, or simple plate on which apparatus to which it is connected. (USAS C42.25)
electronic components and their associated circuitry can Device(Component). A control device is an individual
be mounted.. device used to execute a control function. (USAS C42.25)
Circuit Breaker. A device designed to open and close a Disconnecting Means. A disconnecting means is a device
circuit by non-automatic means, and to open the circuit whereby the current-carrying conductors of a circuit can
automatically on a predetermined overload of current, be disconnected from their source of supply.
without injury to itself when properly applied within its Disconnect Switch ( Motor Circuit Switch). A motor
rating. (NEC-NFPA No.70) circuit switch is a switch intended for use in a motor
Circuit Interrupter A circuit interrupter is a non- branch circuit. It is rated in horsepower, and it is capable
automatic manually operated device designed to open, of interrupting the maximum operating overload current
under abnormal conditions. a current-carrying circuit of a motor of the same rating at the rated voltage. (USAS
without injury to itself C42.25) (Also see NEMA IC-I for definition of operating
Combination Starter. A magnetic starter having a overload.)
manually operated disconnecting means built into the Dynamic Braking Dynamic braking of an electric drive is
same enclosure with the magnetic contactor. a system of braking in which the motor is used as a
Compartment A space within the base, frame or column generator, and the kinetic energy of the motor and driven
of the equipment. machinery is employed as actuating means of exerting a
Component See "device." retarding force. (USAS C42.25)
Electrical Equipment. In this standard the term Isolating Transformer. See "insulating transformer ."
”Electrical Equipment" includes electro-magnetic, Insulating (Isolating ) Transformer. An insulating (or
electronic and static apparatus as well as the more isolating) transformer is a transformer used to insulate
common electrical devices. one circuit from another. (USAS C42.15)
Electrical System. The organized arrangement of all Interconnecting Wire The term .”interconnecting wire"
electrical and electro-mechanical components and devices refers to those connections between sub-assemblies,
in away that will properly control the particular machine panels, chassis and remotely mounted devices and does
tool or industrial equipment. not necessarily apply to the internal connections of these
Electro-Mechanical. Electro-mechanical is the term units. .
applied to any device in which electrical energy is used to Interconnection Diagram A diagram showing all
magnetically cause mechanical movement. terminal blocks in the complete system with each terminal
Electronic Control The term applied to define electronic, identified.
static, precision and associated electrical control Interlock. An interlock is a device actuated by the
equipment. operation of some other device with which it is directly
Elementary (Schematic) Diagram. An elementary associated, to govern succeeding operations of the same or
(schematic) wiring diagram is a diagram using symbols allied devices. NOTE: Interlocks may be either electrical
and a plan of connections to illustrate in simple form the or mechanical. (ASA C42.25)
scheme of control. Intermittent Duty. Intermittent duty is a requirement of
Enclosure The case, box or structure surrounding the service that demands operation for alternate intervals of
electrical equipment, which protects it from (l) load and no-load; or (2) load and rest; or (3) load, no-
contamination. The degree of tightness is usually specified load and rest; such alternate intervals being definitely
(e.g., NEMA Type 12). (See NEMA Standard IC-1 for specified. (NEMA IC-1)
various enclosure descriptions and USAS C42.95, Section Interrupting Capacit. Interrupting capacity is the highest
91, Qualifying Terms.) current at rated voltage that the device can interrupt.
External Control Devices. All control devices mounted Jogging ( Inching ). Jogging is the quickly repeated
external to the control panel. closure of the circuit to start a motor from rest for the
Eyelet. Eyelets are used on printed circuit boards to make purpose of accomplishing small movements of the driven
reliable electrical connections from one side of the board machine. (ASA C42.25)
to the other side. Joint. A joint is a connection between two or more
Fail-Safe Operation. An electrical system so designed conductors. (ASA C42.95)
that the failure of any component in the system will pre Large Enclosures See E7 .2 of these JIC Standards.
vent unsafe operation of the controlled equipment. Latching Relay. A latching relay is one that can be
Feeder. A feeder is the circuit conductors between the mechanically latched in a given position manually, or
service equipment, or the generator switchboard of an when operated by one element, and released manually or
isolated plant, and the branch circuit overcurrent device. by the operation of a second element. (ASA C42.20)
(NEC-NFPA No.70) Legend Plates. Legend plates identify the function of
Field Loss Re/ay. See “motor-field failure relay ." operator controls, indicating lights, etc.
Grounded. Grounded means connected to earth or to Limit Switch. A limit switch is a switch which is operated
some conducting body which serves in place of the earth.. by some part or motion of a power-driven machine or
(NEC-NFPA No.70) equipment to alter the electric circuit associated with the
Grounded Circuit. A grounded circuit is a circuit in machine or equipment. (ASA C42.25)
which one conductor or point (usually the neutral or Locked-Rotor Current. The locked-rotor current of a
neutral point of transformer or generator windings) is motor is the steady-state current taken from the line with
intentionally grounded (earthed), either solidly or through the rotor locked and with rated voltage (and rated
a grounding device. (USAS C42.15) frequency in the case of alternating-current motors)
Grounding Conductor. A grounding conductor is one applied to the motor. (ASA C42.10)
which, under normal conditions, carries no current, but Logic Control Panel Layout. The physical position or
serves to connect exposed metal surfaces to an earth arrangement of the devices on a chassis or panel.
ground, to prevent hazards in case of breakdown between Logic Diagram. A logic diagram is a diagram showing
current-carrying parts and the exposed surfaces. The the relationship of standard logic elements in a control
conductor, if insulated, is colored green, with or without a system. No internal detail of the logic elements need be
yellow stripe. shown.
Guarded Covered, shielded, fenced, enclosed or other- Magnetic Device A magnetic device is a device actuated
wise protected by means of suitable covers or casings, by electro-magnetic means.
barriers, rails or screens, mats or platforms to remove the Magnetic Starter. A magnetic starter is a starter actuated
likelihood of dangerous contact or approach by persons or by electro-magnetic means.
objects to a point of danger. (USAS C42.95) Master Terminal Box. The main enclosure on the
Inching. See .”jogging” equipment containing terminal blocks for the purpose of
Inrush Current. The inrush current of a solenoid or coil is terminating conductors from the control enclosure.
the steady-state current taken from the line with the (Normally associated with equipment requiring a
armature blocked in the rated maximum open position. separately mounted control enclosure.)
Motor-Circuit Switch. See “disconnect switch." of flexible cord or conduit, but supported by a separate
Motor Junction (Conduit) Box. An enclosure on a motor cable
for the purpose of terminating a conduit run and joining Plugging. Plugging is a control function which provides
motor to power conductors. braking by reversing the motor line voltage polarity or
Motor-Field Failure Relay (Field Loss Relay). A motor- phase sequence so that the: motor develops a counter-
field failure relay is a relay which functions to disconnect torque while exerts a retarding force. (NEMA IC-1)
the motor armature from the line in the event of loss of Plug-in Device Component or group of components and
field excitation. (NEMA IC-1) their circuitry while can be easily installed or re moved
Nominal Voltage. Nominal voltage is the utilization from the equipment. Electrical connections are made by
voltage. See the appropriate NEMA Standard for device mating contacts.
voltage ratings. Polarized Plug A plug so arranged that it may be inserted
Normally Open and Normally Closed. The terms in its receptacle only in a predetermined position.
”normally open" and “normally closed," when applied to a Potting. Potting is a method or securing a component or
magnetically operated switching device, such as a group of components by encapsulation.
contactor or relay, or to the contacts thereof, signify the Precision Device. A precision device is a device that will
position taken when the operating magnet is de-energized. operate within prescribed limits and will consistently
These terms apply only to non-latching types of devices. repeat operations within those limits.
(NEMA IC-1) Pressure Connector. A conductor or terminal applied
Operating Floor A floor or platform used by the operator with pressure so as to make the connection mechanically
under normal operating conditions. and electrically secure.
Operating Overload Operating overload is the over- -Proof (used as a suffix). Apparatus is designated as
current to which electric apparatus is subjected in the splashproof, dustproof, etc., when so constructed,
course of normal operating conditions that it may protected or treated that its successful operation is not
encounter. (USAS C42.25) . interfered with when subjected to the specified material or
(Note 1: The maximum operating overload is considered condition.
to be six times normal full-load current for alternating- Pushbutton Station. See "Operator’s control station."
current industrial motors and control apparatus; four Raceway. Any channel for holding wires, cables or bus
times normal full-load current for direct- current bars, which is designed expressly for, and used solely for,
industrial motors and control apparatus used for reduced- this purpose. (NEC-NFPA No.70)
voltage starting: and ten times normal full-load current Readily Accessible. Capable of being reached quickly for
for direct-current industrial motors and control used for operation, renewal, or inspection without requiring those
full-voltage starting.) to whom ready access is requisite to climb over or remove
(Note 2: It should be understood that these overloads are obstacles or to resort to portable ladders, chairs, etc.
currents that may persist for a very short time only, (NEC-NFPA No.70)
usually a matter of seconds.) Relay. A relay is a device which is operative by a variation
Operator’s Control Station (Pushbutton Station). A push in the conditions of one electric: circuit to effect the
button station is a unit assembly of one or more externally operation or other devices in the same or another electric
operable pushbutton switches, sometimes including other circuit.(NEMA IC-1)
pilot devices such as indicating lights or selector switches Schematic Diagram. See “elementary diagram."
in a suitable enclosure. (USAS C42.25) Semiconductor. A device which can function either as a
Outline Drawing. Drawing showing approximate overall conductor or a non-conductor, depending on the polarity
shape with no detail. of the applied voltage such as a rectifier or transistor
Overcurrent. Overcurrent in an electric circuit is that which has a variable conductance depending on the
current which will cause an excessive or dangerous control signal applied.
temperature in the conductor or conductor insulation. Sequence of Operation A written detailed description of
Overcurrent Protective Device A device operative on the order in which electrical devices and other parts of the
excessive current and maintains the interruption of power equipment should function.
in the circuit. Shielded Cable, Shielded cable is single or multiple
Overlapping Contacts Overlapping contacts are conductor cable surrounded by a separate conductor (the
combinations of two sets of contacts, actuated by a "shield") intended to minimize the effects of adjacent
common means, each set closing in one of two positions, electrical circuit"
and so arranged that the contacts of one set open after the Short-Time Rating The short-time rating is the rating that
contacts of the other set have been closed. (NEMA IC-1). defines the load which can he carried for a short and
Overload Relay A device that provides overload definitely specified time; the machine. apparatus or device
protection for electrical equipment. being at approximately room temperature at the time the
Pane. A subplate upon which the control devices are load is applied (NEMA IC-1)
mounted inside the control compartment or enclosure. Small Enclosure See E7.2 of these: JIC Standards
Panel Layout. The physical position or arrangement of Solenoid A solenoid magnet (solenoid) is an electro-
the components on a panel or chassis. magnet having an energized coil approximately
Pendant (Station) A pendant station is a pushbutton cylindrical in form and an armature whose motion is
station suspended from overhead and connected by means
reciprocating within and along the axis of the coil, (USAS
C42.25)
Starter. A starter is an electric controller for accelerating
a motor from rest to normal speed, (NOTE' A device
designed for starting a motor in either direction of
rotation includes the additional function of reversing and
should be designated a controller,) (NEMA IC-1)
Static Device. As associated with electronic and other
control or information handling circuits, the term “static”
refers to devices with switching functions that have no
moving parts.
Stepping Relay (Switches) A multi-position relay in
which moving wiper contacts mate with successive sets of
fixed contacts in a series of steps, moving from one step to
the next in successive operations of the relay, (USAS
C83.16)
Sub-Assembly. A sub-assembly is an assembly of
electrical or electronic components mounted on a panel or
chassis which forms a functional unit by itself,
Subplate A rigid metal panel on which control devices
can be mounted and wired,
Swingout Panel A panel which is hinge-mounted in such
a manner that the back of the panel may be made
accessible from the front of the enclosure.
Symbol. A sign, mark or drawing agreed upon to
represent an electrical device or component part thereof.
Temperature Control. A control device responsive to
temperature,
Terminal. A point of connection in an electrical circuit.
Terminal Block. A terminal block is an insulating base or
slab equipped with one or more terminal connectors for
the purpose of making electrical connections thereto,
(NEMA IC-1).
Tie Point. A distributing point in circuit wiring, other
than a terminal connection, where junctions of leads are
made.
-Tight (used as a suffix). Apparatus is designated as
watertight, dust-tight, etc., when so constructed that the
enclosing case will exclude the specified material, ( USAS
C42.95)
Undervoltage Protection Undervoltage or low-voltage
protection is the effect of a device, operative on the
reduction or failure of voltage" to cause and maintain the
interruption of power to the main circuit, (USAS C42.25)
Vault-Type Hardware See E7.6 of these JIC Standard.
Wire-Wrapping. Wire-wrapping is a technique used to
terminate conductors.
Wireway. Wireways are sheet metal troughs with hinged
covers for housing and protecting electrical conductors
and cable and in which conductor are laid in place after
the wireway has been installed as a complete system.
Wobble Stick. A wobble stick is a rod extending from a
pendant station to operate the ”Stop” contacts and will
function when pushed in any direction.
MR Motor Starter -Reverse
Appendix D-Device Designations MSH Meter Shunt
The device designations given below are intended for use on MTR Motor
diagrams in connection with the corresponding graphical NLT Neon Light
symbols to indicate the function of the particular device. These OL Overload Relay
device designations are based on the assignment of a standard PB Pushbutton
letter or letters to the fundamental function that is performed by PC Printed Circuit
PL Plug
a component or device. Suitable prefix numbers ( I, 2, 3, 4, etc.) PLS Plugging Switch
and suffix letters (A, B, C, D, etc.) may be added to the basic POT Potentiometer
designation to differentiate between devices performing similar PRS Proximity Switch
functions. PS Pressure Switch
The assignment of a designation to a device on a specific PSC Photosensitive Cell
equipment Is governed by the function of that device on that Q Transistor
QBN Binistor Transistor
particular equipment and not by the type or nature of the device QFE Field- Effect Transistor.
or its possible use for other functions in other equipment. The QSB Surface-Barrier Transistor.
same type of device may perform different functions on different QT Tetrode
equipment or even on the same equipment and, consequently, QTG Trigistor
may be identified by different designations. QTM Thermistor
QTN Trinistor
QU Transistor, Unijunction
Designation Device QVR Varistor
A Accelerating Contactor or Relay R Reverse
ABE Alarm or Annunciator Bell REC Rectifier
ABU Alarm or Annunciator Buzzer RECP Receptacle
AH Alarm or Annunciator Horn RES Resistor
AM Ammeter RH Rheostat
AT Autotransformer RSS Rotary Selector Switch
B Brake Relay S Switch
CAP Capacitor SCR Silicon Controlled Rectifier
CB Circuit Breaker SOC Socket
CH Chassis or Frame (not necessarily grounded) SOL Solenoid
CI Circuit Interrupter SS Selector Switch
CON Contactor ST Saturable Transformer
COS Cable Operated (Emergency) Switch SX Saturable Core & Reactor
CR Control Relay SYN Synchro or Resolver
CRA Control Relay, Automatic T Transformer
CRE Control Relay, Electronically-Energized TACH Tachometer Generator
CRH Control Relay, Manual TAS Temperature-Actuated Switch
CRL Control Relay, Latch TB Terminal Block
CRM Control Relay, Master T/C Thermocouple
CRU Control Relay, Unlatch TCS Thermocouple Switch
CS Cam Switch TGS Toggle Switch
CT Current Transformer TR Time Delay Relay
CTR Counter D Diode TRE Timer Relay. Electronically-Energized
DAS Diode Arc Suppressor TVM Tachometer Indicator
DB Dynamic Braking Contactor or Relay V Electronic Tube
DISC Disconnect Switch VAT Variable Autotransformer
DT Tunnel Diode VM Voltmeter
DVC Varicap Diode VS Vacuum Switch
DZ Zener Diode F Forward WLT Work Light
FA Field Accelerating Contactor or Relay WM Wattmeter
FB Fuse Block X Reactor
FD Field Decelerating Contactor or Relay
FF Full Field Contactor or Relay
FL Field Loss Contactor or Relay
FLD Field
FLS Flow Switch
FS Float Switch
FTB Fusible Terminal Block
FTS Foot Switch
FU Fuse
FW Field Weakening
GRD Ground
HTR Heating Element INST Instrument
IOL Instantaneous Overload
LO Lock-Out Coil (located in plugging switch)
LS Limit Switch
LT Pilot Light
LVT Linear Variable Differential Transformer
M Motor Starter
MAX Magnetic Amplifier Winding
MB Magnetic Brake
MC Magnetic Clutch
MCS Motor Circuit Switch
MF Motor Starter -Forward
Appendix E-References to Other Codes and Standards
ABC COMPANY
DATE
DESCRIPTION OF EQUIPMENT