Professional Documents
Culture Documents
CABLE STRUCTURE
CONDUCTOR : Solid and stranded annealed copper,
Sizes 0.5 mm2 up to 500 mm2
INSULATION : PVC, Any color
CLASSIFICATION : Maximum conductor temperature70 0C
Circuit voltage not exceeding 750 volts
TESTING VOLTAGE : 2,500 volts
REFERENCE : TIS 11-2531, Table 4
C: Packing in coil.
D: Packing in drum.
CABLE STRUCTURE
CABLE STRUCTURC
C: PACKING IN COIL.
CABLE STRUCTURE
CONDUCTOR : Flexible stranded annealed copper wire,
Sizes. 0.5 mm2 up to 2.5 mm2
INSULATION : PVC- Any color
CLASSIFICATION : Maximum conductor temperature 70oC
Circuit voltage not exceeding 300 volts
TESTING VOLTAGE : 2,000 Volts
REFERENCE : TIS 11-2531, Table 10
C: PACKING IN COIL.
CABLE STRUCTURE
CABLE STRUCTURE
Number Nominal Number Insulation Sheath Overall diameter Minimum Maximum Cable Standard
Of cross and thickness Thickness insulation continuous weight Length
core sectional diameter (mm) resistance current rating (approx.)
0
area of wire at 70 C in free air
Lower Upper
2
(mm ) (No/mm) (mm) (mm) limit limit (MΩ-Km) (Ampere) (Kg/Km) (m)
CABLE STRUCTURE
CABLE STRUCTURE
Nominal Number Insulation Nominal Thickness Overall diameter Minimum Maximum Cable Standard
Cross and Thickness Cross sectional Of ground insulation continuous weight Length
Sectional diameter area of ground insulator (mm) resistance current rating (approx.)
0
area of wire Conductor at 70 C in free air
Lower Upper
2 2
(mm ) (No/mm) (mm) (mm ) (mm) limit limit (MΩ-Km) (Ampere) (Kg/Km) (m)
C : PACKING IN COIL.
CABLE STRUCTURE
CABLE STRUCTURE
CABLE STRUCTURE
Number Nominal Number Insulation Overall diameter Minimum Maximum Cable Standard
of core cross and thickness insulation continuous weight length
Sectional diameter (mm) resistance current rating (approx.)
area of wire Lower Upper at 70 0C in free air
(mm2) (mm) limit limit (MΩ-Km) (Ampere) (Kg/Km) (m)
C : PACKING IN COIL.
CABLE STRUCTURE
NUMBER OF CORE : 2-3 cores with safety-ground
CONDUCTOR : Solid and stranded annealed copper,
sizes 1 mm2 up to 35 mm2
GROUND WIRE : Ground conductor size 1 mm2 up 10 mm2
INSULATION : PVC
Color: 2 core-Light grey and Black
3 core-Light grey, Black and Red
Ground core-Green/Yellow
SHEATH : PVC
Color: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 300 volts
TESTING VOLTAGE : 2,000 volts
REFERENCE : TIS 11-2531, Table 11
Number Nominal Number Insulation Nominal Ground Sheath Overall diameter (mm) Minimum Maximum Cable Standard
of core cross and thickness cross insulation thickness Approx. insulation continuous weight length
sectional diameter sectional thickness resistance current (approx.)
0
area of wire area of Lower limit Upper limit at 70 C rating in
ground free air
conductor
2 2
(mm ) (No./mm) (mm) (mm ) (mm) (mm) (MΩ-Km) (Ampere) (Kg/Km) (m)
1.5 1/ 1.38 0.6 1 0.6 1.2 4.8X9.4 5.8X11.5 0.0100 15 100 100/C
1.5 7/ 0.53 0.6 1 0.6 1.2 4.9X9.8 6.0X12.0 0.0094 15 110 100/C
2.5 1/ 1.78 0.7 1.5 0.6 1.2 5.4X10.5 6.4X13.0 0.0092 20 140 100/C
2 2.5 7/ 0.67 0.7 1.5 0.6 1.2 5.6X11.5 6.8X14.0 0.0084 20 140 100/C
4 1/ 2.25 0.8 2.5 0.6 1.2 6.0X12.5 7.2X15.0 0.0086 27 190 100/C
4 7/ 0.85 0.8 2.5 0.6 1.2 6.2X13.0 7.6X16.0 0.0078 27 210 100/C
35 19/ 1.53 1.2 10 0.6 1.4 12.0X27.0 14.5X31. 0.0043 109 1,100 500/D
CABLE STRUCTURE
NUMBER OF CORE : 2-3 cores
CONDUCTOR : Solid and stranded annealed copper
Sizes 0.5 mm2 up to 35 mm2 for2-core and up to 16 mm2 for
3-cores
INSULATION : PVC
Color: 2 core-Light grey, Black
3 core-Light grey, Black, Red
SHEATH : PVC
Color: White
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit voltage not exceeding 300 volts
TESTING VOLTAGE : 2,000 volts
REFERENCE : TIS 11-2531, Table 2
Number Nominal Number Insulation Sheath Approx. overall Minimum Maximum Cable Standard
of core cross and Thickness Thickness Diameter (mm) insulation continuous weight length
section diameter resistance current (approx.)
0
area of wire Lower limit Upper limit at 70 C rating in
free air (Kg/Km) (m)
2
(mm ) (No./mm) (mm) (mm) (MΩ-Km) (Ampere)
CABLE STRUCTURE
CONDUCTOR : Compact stranded hard drawn aluminium wires
Sizes 10 mm2 up to 500 mm2
INSULATION : PVC
Color: Black
CLASSIFICATION : Maximum conductor temperature 70oC
Circuit voltage not exceeding 750 volts
TESTING VOLTAGE : 2,500 volts
REFERENCE : TIS 293-2541, Table 2
120 17.37 15 12.75 1.7 16.5 0.253 18,518 248 450 100/C
150 144.15 15 14.13 1.9 18.5 0.206 22,457 287 550 500/D
185 181.06 30 15.83 2.1 21.0 0.164 28,974 337 700 500/D
240 237.55 30 18.28 2.3 24.0 0.125 37,506 410 900 500/D
300 296.94 30 20.43 2.5 26.0 0.100 45,642 479 1,100 500/D
400 381.67 53 23.17 2.7 29.0 0.0778 56,992 571 1,400 500/D
500 490.81 53 26.27 3.1 33.0 0.0605 72,195 680 1,800 500/D
CABLE STRUCTURE
CONDUCTOR : Solid hard and stranded hard drawn aluminum wires,
Sizes 10 mm2 up to 500 mm2
INSULATION : PVC
Color: Black
CLASSIFICATION : Maximum conductor temperature 70oC
Circuit voltage not exceeding 750 volts
TESTING VOLTAGE : 2,500 volts
REFERENCE : TIS 293-2541, Table 1
C : PACKING IN COILS.
D : PACKING IN DRUM.
CABLE STRUCTURE
CONDUCTOR : Solid hard drawn aluminum wires,
Sizes. 10 mm2 and 16 mm2
INSULATION : PVC
Color : Blue
CLASSIFICATION : Maximum conductor temperature 70oC
Circuit voltage not exceeding 750 volts
TESTING VOLTAGE : 2,500 volts
REFERENCE : TIS 293-2541, Table 1
CABLE STRUCTURE
CONDUCTOR : Solid and stranded annealed copper,
Sizes 0.5 mm2 up to 500 mm2
INSULATION : PVC, Any color
CLASSIFICATION : Maximum conductor temperature 70 0C
Circuit Voltage not exceeding 300 volts
TESTING VOLTAGE : 2,000 volts
REFERENCE : TIS 11-2531, Table 1
C: Packing in coil.
D: Packing in drum.