DATASHEET

D510C DIGITAL AVR


FOR SHUNT, AREP or PMG EXCITATION

CHARACTERISTICS

••Voltage regulation: ± 0.25%


••Function: regulation of voltage, PF,
kVAR and manual regulation

••Response time depending on PID


settings

••Rated field current: 6 A


••Maximum field current: 15 A/10 s
••Power supply range for voltage
sensing: up to 530 V

••Protection:
- Short-circuit / Loss of voltage
reference / Overvoltage /
Overexcitation / High Temperature /
The D510C is a digital voltage regulator, which monitors and regulates the - Speed drop / Diode fault / Stator
alternator 
output voltage. It is designed for alternators with SHUNT, AREP current unbalance / Current
or PMG excitation. limitation

The D510C is an AVR which can be configured using the Easyreg® software. ••Engine assistance:
- Soft start : 0 - 100 s
• There are 4 possible regulation modes: voltage, P.F., kVA, manual - U/F adjustable from 0.5 to 3 in
• The I/O can be configured: increments of 0.1
- 2 x I: analog - LAM : 0 to 30%
- 1 x O: analog - Gradual increase : 0.1 to 30 s/Hz
- 2 x I: digital ••Grid code function
- 3 x O: digital
• 1 dry contact
• 1 USB port
• DB9 plug for CAN

It complies fully with the requirements of IEC standard 60034-1 and UL 708 and
CSA certifications.

D510 C DI G I TA L AV R - REF. 4552en-2018 .05/g www.leroy-somer.com/epg


CONNEXION AND SETTING OPERATION CONDITIONS

The AVR is set using the Easyreg® software.


••Operating temperature: ••Vibrations:
- 40°C to + 65°C - Less than 10 Hz : 2 mm half-peak
••This can be used to: amplitude
- Set the AVR parameters ••Storage temperature: - 10 Hz to 100 Hz : 100 mm/s
- Configure the inputs and outputs - 55°C to + 85°C
- Above 100 Hz : 8 g
- Display faults and parameter
measurements ••Shocks on the base : 9 g depending on
the 3 axes

OPERATION RANGE

LSA 40 42.3 44.3 46.3 47.2 49.3 50.2 52.3 53.2 54.2
SHUNT
AREP or
PMG

Electric Power Generation

115 mm
Ø6

©
D510C Field excitation system
AREP: X2, Z1, X1, Z2
PMG: X2, X1, Z2
175 mm

Hz
X2 Z1 X1 Z2

Volt
SHUNT: X1, X2
Exc.

Fault

Manu
Excitation
F+ = E + field winding
PF

F- = E - field winding
U=U

Power
F+ F

USB

Port for Battery: + and -


CAN J1939
+

LS proprietary
Voltage sensing
-

+10V -

Mains: L1 and L2
A|1 -
A|2 -
0V -
A01 -
L1 L2 U V W

0V -
D|1 -

Digital I/O
D|2 -
0V - Voltage sensing
D01 -
AL.1 -
AL.2 -
Alternator:
1 phase = V and W
3 phases = U, V, and W

W V U

USB port Temperature sensor Current transformer


- PTC Placing in parallel and
- PT 100 measurement: CT on U
Measurement: CTs on V and W

© Nidec 2017. The information contained in this brochure is for guidance only and does not form part of any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of
development and reserve the right to change the specification of their products without notice.