Professional Documents
Culture Documents
OF
TRANSMISSION LINE TOWER FOUNDATIONS
A DISSERTATION
Submitted in partial fulfillment of the
requirements for the award of the degree
of .
MASTER OF TECHNOLOGY.
In
CIVIL ENGINEERING
(With Spedialikatiohin. Ctimputer Aided Design)
By
RAKESH RANJAii
I hereby certify that the work presented in this dissertation entitled "COMPUTER AIDED
DESIGN OF TRANSMISSION LINE TOWER FOUNDATIONS" in partial fulfillment
of the requirements for the award of the degree of MASTER OF TECHNOLOGY in Civil
Engineering, with specialization in Computer Aided Design, submitted to the Department
of Civil Engineering, Indian Institute of Technology Roorkee, Roorkee is an authentic record
of my own work carried out for a period from July, 2005 to June, 2006 under the supervision
of Dr. G. Ramasamy, Professor, Department of Civil Engineering, Indian Institute of
Technology Roorkee, Roorkee.
The matter embodied in this dissertation has not been submitted by me for the award of any
other degree.
gkeol PO A'
CERTIFICATE
This is to certify that the above statement made by the candidate is correct to the best of my
knowledge.
(Dr. G. Ramasamy)
Professor, Department of Civil Engineering,
Indian Institute of Technology Roorkee,
Roorkee -247667, India.
ACKNOWLEDGEMENT
I express my appreciation and thanks to all the faculty members of the department of
Civil Engineering, IIT Roorkee for free exchange of ideas and discussions which proved
helpful.
Special Thanks are also due to Utpal Kumar Nath, Arup Bhattacharjee, Subhash Chandra
and Ranjeet Kumar fellow student for their constant help to complete this dissertation
report.
I wish to acknowledge the affection and moral support of my family members, for being
so understanding and helpful during this period.
Finally, I am thankful and grateful to God the Almighty for ushering His blessings on all
of us.
ii
ABSTRACT
The transmissions line towers are used to connect the grid from power plant and one
power grid to another grid. So they may often pass through very steep ground,
mountainous ranges, marshy land, and rivers and even to that area where bearing capacity
of soil is very low. Foundations of most of the structures are designed for compressive
loads and some of them may in addition be subjected to lateral loads. Because of wind
load and pull due to broken wire condition, uplift loads are created which are very
significant and may be even critical. Further these types of foundations may be subjected
to uplift and tilting force simultaneously.
Isolated footing, piles and well foundations are the types of foundations generally
adopted as foundation of transmission line towers depending on the magnitude and types
of uplift or lateral forces expected in the given situation.
In this dissertation software has been developed to analyze and design the
different types of foundation used for transmission line tower .The developed software
provide flexibility to the user to select the different type of foundations on the basic i2f
soil types, loads etc. The selected foundation has been :-...;:aiyseci and designed by software
and finally design components will be represented graphically.
CONTENTS
Page No.
Certificate
Acknowledgement II
Abstract III
List of Tables
VI
List of Figures
VII
Notations
IX
1 Introduction 1
2 Transmission Line Tower Foundation. 3
2.1. Types of Foundation 3
2.2. Types of Loads 3
2.3.1. Pad and Chimney Foundation 3
2.3.2. Combined Raft Foundation 5
2.3.3 Pile Foundation 5
2.3.4 Well Foundation. 7
3 Design of Pad and Chimney Foundation 8
3.1. Analysis of Foundation 8
3.2. Design of Foundation 15
3.2.1 Design of Chimney 15
3.2.2 Design of Pad 16
4 Design of Pile Foundation 20
4.0 General 20
4.1. Analysis and. Design of Pile Foundation for Normal Condition 20
4.2.4.1.1 Analysis of Pile Foundation for Normal Condition 20
4.1.2 Design of Pile Foundation for Normal Condition 20
4.2. Analysis and Design of Pile Foundation for Scour Condition 27
4.2.1. Analysis of Pile Foundation for Scour Condition 27
iv
Page No.
4.2.2. Structural Design of Pile Foundation for Scour Condition 32
4.3. Analysis and Design of Under-Reamed Pile 32
5 Well Foundation 37
5.0 General 37
5.1. Elements of well foundation for Transmission Line Tower 37
5.2. Determination of maximum depth of scour 39
5.3. Allowable bearing Pressure 40
5.4. Load Calculation 40
5.5.Analysis of Well Foundation 43
5.5.1.Elastic Theory Approach 43
5.5.2.Ultimate Resistance Approach 45
5.6. Structural Design 47
6 Flow Chart of the Package 52
7 Summary and Conclusion 54
8 References 55
9 Annexure 1: Design Problem for Pad and Chimney Foundation 57
10 Annexure 2: Design Example of Pile Foundation for Transmission Line 65
Tower
11 Annexure 3 :Design example of well foundation for transmission line 79
Tower
LISTS OF TABLES
vi
LISTS OF FIGURES
3.5 H 13
Ultimate Lateral Resistance, (For Non-Cohesive Soil)
yK pb3
vii
Figure No. Title Page No.
viii
NOTATIONS
ix
Pb=perimeter of block in m
E=Young's modulus of the pile material in MN/m2
I=moment of inertia of pile cross-section in m4, and
Tlb= coefficient of modulus variation in MN/m3
Q= discharge in cumecs,
f = silt factor
m= mean size of particle in mm
p = intensity of pressure due to flowing water in kN/m2
V =the velocity of current at the point considered
N = Corrected standard penetration resistance value
Df =Depth of foundation below scour level
IB= moment of inertia of base of the well about the axis normal to the direction of
horizontal force passing through its C.G
o =maximum base pressure of well.
Transmission line towers are exclusively tall structure i.e. the height of the tower being more than
the width. The purpose of transmission line tower is to support conductor carrying electric power
and one or two ground wires at suitable distance from ground level and at some appropriate distance
from each other. These transmissions line towers are used to connect the grid from power plant and
one power grid to another grid. So they often pass through very steep ground, mountainous ranges,
marshy land, and rivers and even to that area where bearing capacity of soil is very low. These
towers are spaced frames, almost exclusively built with steel section.
1
Transmission line tower consists of four legs. Normally, foundations of most of the structures are
designed for compressive loads and some of them may in addition be subjected to lateral loads. But
the loads, coming on transmission line towers, like wind load and pull due to broken wire condition
cause uplift loads which are very significant and may be even critical. These types of foundations
may be subjected to uplift and tilting force simultaneously. Design of transmission line tower
foundation to support large compressive load does not create a problem but the design of suitable
foundation to withstand uplift loads has in the past been primarily a matter of experience and
Isolated footing, piles and well foundations are the types of foundations generally adopted as
foundation of transmission line towers depending on the magnitude and types of uplift or lateral
forces expected in the given situation. Accordingly, the present work deals with design of these
2
CHAPTER 2
2. 1. TYPES OF FOUNDATION
The following types of foundations can be considered for transmission line tower foundation:
3. Pile foundation:
b. Pile foundation
If there is probability of scour then one should go for designing either pile foundation or well
foundation.
1.Compressive load
2. Uplift load
3. Horizontal load
Pad and chimney foundation are applied to the normal ground where is no scouring except
3
2. Undercut Pad and chimney foundation which is excavated perpendicularly, and base
GL
Fig.2.1.1 Undercut Pad and Chimney Fig.2.1.2 Pad and Chimney
Foundation Foundation
The foundation is composed of chimney part and pad part. Both of them are cast- in —situ
reinforced concrete members. The size and depth of these members are based either on the
bearing capacity of soil or from consideration of uplift resistance required. The stub angle is
taken inside and effectively anchored at bottom pad by cleat angle. In this type of footing,
chimney is comparatively slender; the lateral load acting at top of the chimney will create
bending moment. Therefore the chimney should be checked for direct load as well as
bending stress.
4
Fig 2.2 Reinforced pad and chimney foundation
Raft foundation is provided where the area cover by the isolated footing is more than 50% of
plan area. The loads are transmitted through pedestal to the raft. The uplift and compressive
loads govern the dimension and the depth of footing. In raft foundation the leg of tower
attached to individual pedestal and these pedestals attached to a common raft. The raft
Pile foundation is a deep foundation; provide a suitable foundation for transmission line tower.
As in the case of transmission line tower foundation the main governing force is uplift force
and pile foundation both plain and under-reamed gives quite satisfactory resistance to uplift. As
transmission line tower passes even through those areas where there is possibility of scouring
5
deep foundation is provided. In deep foundation both well and pile foundations are provided,
but due to ease in construction and economy pile foundation is the first preference to the
designers. Generally bored cast- in- situ piles are provided for this purpose.
6
2.3.3.2. Under-reamed Pile Foundation
An Underreamed pile is a special type of bored pile which is provided with a bulb at end.
This type of foundation is suitable for uplift load and also in the case of black cotton soil.
The uplift load is resisted by skin friction and self weight of pile and Underreamed bulb.
7
CHAPTER 3
DESIGN OF PAD AND CHIMNEY FOUNDATION
The analysis and design part has been dealt in this chapter.
3.1 ANALYSIS OF FOUNDATION
There are two conditions of load application
1.Broken wire condition (B.W.C)
2. Normal condition (N.C)
A load factor of 1.5 is taken for B.W.0 and a load factor of 2 is taken for N.C.
Followings are Steps of designing of Footing:
Stepl. Determine the ultimate compressive load, uplift load and horizontal load by
multiplying appropriate load factor i.e.2 for N.0 and 1.5 for B.W.C.
Step2. Determine the area of footing required:
Ultimate Compressive load=Po kN
Ultimate Uplift load = Uu kN
Ultimate Horizontal thrust = Ho kN
Safe bearing capacity of soil = Po kN/m2
Select any trial depth of foundation =D
8
GL
GL
Cohesive Soil
Fig. 3.1 Resistance against Uplift by Weight of Frustum of Earth plus Weight of
Concrete in cohesive soil
IS: 4091, Clause 5.1.3.2 and clause 5.1.3.3, 30° cones are used to be taken for average firm
cohesive soil and 20° cones are used to be taken for non-cohesive material like sand and
gravel.
CL
Cohesionless SoII
Fig. 3.2 Resistance against Uplift by Weight of Frustum of Earth plus Weight of
Concrete in cohesion-less soil
9
Vertical Loads from superstructure = P CosO
Where,
O - Inclination of leg of footing with vertical
For Square footing:
Volume of frustum of soil (V)
V= —
D (3L2 + 4D2 tan2 +6LD tan a)
Friction Angle 4 20 25 30 35 40 45 48
10
B. GREAT DEPTH
Fig. 3.3 Failure of Soil above a Strip Footing Under Uplift Load
Where
1,--= width of footing,
H = height up to which failure surface reach from foundation level as shown in Fig3.3,
and Fig.3.4
C= cD = cohesion along vertical plane through footing edge,
W= weight of soil wedge + weight of footing , and
Ku =Normal uplift coefficient of earth pressure on vertical plane through footing edge.
Varies from 0.7 to 1 for simplicity take it as 0.85.
11
Factor of safety against uplift=Fi=
U ult
As per IS: 11233-1985, clause 5.4.1 specifies that in case of foundations with an undercut, the factor
of safety of 1.25 may be adopted and a factor of safety of 1.5 is taken for footing without undercut.
So if F1 <1.5 for footing without undercut then increase the depth of foundation
So if F1<1.25 then increase the depth of foundation,
3.1.2. Check for horizontal stability
20
8.5C.b
10 20 30 40 50 60 70 80
12
20
15
EMBEDMENT DEPTH,d/b
10
Calculate d/b ratio and h/b ratio, and then from the Fig.3.4 and. Fig 3.5 get the value of
Where,
Cu=un-drained cohesion
b= width of pedestal
I+ Sin0
K p-
1— Sin0
Get the value of H=Ultimate horizontal force resistance
13
For calculation resisting moment lever arm (g) is given by:
H +b
g=
8.5Cub
g = 0.9
yK pb
14
UL PcosOxL
+H(D+h)
W' 3
3
2 S L.
6
Where, W'=weight of soil cone/ pyramid for stability
Up= Uplift on leg of tower
H=horizontal shear on tower leg
L= length of footing
dl =clear cover,
D=Overall depth of cross-section of shaft, and
b=width of cross-section of shaft
From design aids
d' P
For the value of , and
D f ek bD fa bD 2
15
3.3.2. Design of Pad
P.O P0,1
p PO2
) X b)) kN/sq m
P'o=i 02 -I- (P01
9L
16
P +P
P"— " kN/sq m
2
Where,
Po' Intensity of pressure at the face of pedestal
P"= Average Pressure intensity
L—b
Maximum bending moment occurs at face A-B, cantilever length=l=
2
— br
Moment at face A-B= M — 24 + P'0 ) kNm
1
For the moment of resistance the effective width is b'=b + — b)
8
L—b
Maximum bending moment occurs at face A-B, cantilever length=l=
2
L(L — )2
Moment at face A-B= M — 01 + P'0 ) kNm
24 (2P
1
For the moment of resistance the effective width is b'= b + —(L — b)
8
M, x 1o6
Effective depth required = mm
(0.138 x bt x.ick
Check for Punching Shear
The critical section for punching shear is at a distance d/2 from section A-B
1)0= b + d
Shear force = F = Pu — P" b0 2
F
ry =
4bod 0
r, = K,rc
F
d=
° 4bor
17
Thickness of footing at a section d/2 from face of pedestal =
1= 200+r d
d„1=
200
x(L—b — d))
L—b
dot should not be greater than clo, otherwise increase the depth.
Check for one-way shear
Critical section is at a distance d from face of shaft at section C-D.
L—b
The cantilever length to the right of C D-1"— dm
2
Intensity of pressure at face C-D is given by
(d-200))xr L—b d
Effective depth at this section = d'= 200 +
(L, 2
L—b)x
Width of sectional neutral axis= b2= b'+ d2
d'-200
+ P" 0
Shear force at section C-D=V= L x /nx P02
2
Tv— (
b2x
d')
f A
0.87fyAsa, =
fa bd
Get the value of Ast
Providing the same reinforcement of both faces in both directions.
18
Sectional Elevation
19
CHAPTER 4
4.0. GENERAL
Pile foundation is generally provided as foundation for transmission line towers. The
transmission line tower may passes through different topographical conditions like river,
marshy land hills etc. The design of pile foundation is divided into two categories i.e. (1).Pile
situated in normal condition. (2).Pile situated where scour is expected to occur.
For transmission line tower foundation two types of piles are provided, these are:
1. Pile Foundation
2. Underreamed Pile Foundation
4.1. ANALYSIS AND DESIGN OF PILE FOUNDATION FOR NORMAL
CONDITION
4.1.1 Analysis of Pile Foundation
There are two conditions of load application
1.Broken wire condition (B.W.C)
2. Normal condition (N.C)
A load factor of 1.5 is taken for B.W.0 and a load factor of 2 is taken for N.C.
Steps of designing of Footing:
Stepl. Determine the ultimate compressive load, Uplift load and horizontal load by
multiplying appropriate load factor i.e.2 for N.0 and 1.5 for B.W.C.
Step2. Determine of loads coming on each Pile:
Ultimate Compressive load=Pu kN
Ultimate Uplift load = Uu kN
Ultimate Horizontal thrust = Hu kN
Step3. Soil profile study
From SPT Standard Penetration Test value get the value of a and unconfined compressive
strength respectively from table 4.1.1 and table 4.1.2
20
Table 4.1 Relationship between SPT value and a
Consistency N Value Value of a
Soft to very soft <4 1
Medium 4 to 8 0.7
Stiff 8 to 15 0.4
Stiff to Hard >15 0.3
Table 4.2 Relationship between SPT value and undrained compressive strength
Unconfined Compressive
N value
strength(KN/m2)qu
<2 <25
2 —4 25 - 50
4—8 50-100
8 — 16 100-200
16 — 32 200-400
>32 >400
21
For non cohesive soil:
The uplift resistance is provided by the skin friction resistance with a reduction factor of 0.6
plus the weight pile. Safe uplift capacity of single pile is given by
fs 2,1 x RF
a afe =
FOS
+ W
Where
fs = average unit skin friction = Ka, tan 8 ,
As = Surface area of pile shaft below GL,
K= coefficient of horizontal pressure =0.35 (for bored pile),
av= effective vertical stress at mid depth of pile below GL,
8= angle of wall friction =2/34),
RF=reduction factor= 0.6 for cohesion less soil
W = weight of pile.
Uplift capacity of group of pile = nO
,safe
Step6. Calculate ultimate load resistance of each pile:
1. For cohesive soil:
Qu = Ap.Nec p +a.c.A T
Where
Qu= ultimate bearing capacity of pile (in IN/ sq m),
Nc= bearing capacity factor, usually taken as 9 ,
cp= average cohesion of soil at pile tip IN/sq m,
a = adhesion factor from table 4.1,
c= average cohesion throughout the length of pile, and
Ap= cross Sectional area at pile toe in m2
2. For Cohesionless soil:
22
K= coefficient of earth pressure,
8= angle of wall friction between pile and soil in degree, and
As, = surface area of stem in m2.
From the above formula determine the value of ultimate bearing capacity Quit of single pile.
Step7: Determination of group capacity of pile
Select a spacing of pile
There are two types of failure of pile group.
1. By block failure
2. By individual pile failure
In block failure the whole group of pile acts like a single individual pile. The ultimate load
capacity of pile group by block failure, Qug is given by
Qug = cubNA,+ pb Leu
Where
cub = undrained strength of clay at base of pile group,
c'= average undrained strength of clay along the length of block,
Nc= bearing capacity factor, taken as 9 ,
Ap= cross Sectional area at block in m2,
Pb perimeter of block in m, and
L= embedded length of pile in m .
In individual pile failure mode, ultimate failure mode is given by
Qug = Pah
Where, Quit= ultimate bearing capacity of single pile
The ultimate load capacity of group is taken as the smaller of these two values.
Step8.Spacing of pile
As per IS: 2911 (Part1), if the pile is founded on very hard stratum and deriving there
capacity mainly from end bearing, minimum spacing in such case should be 2.5 times the
diameter of pile.
If the pile is founded get there bearing capacity mainly from the friction resistance minimum
spacing in such case should be 3 times the diameter of pile.
Step9. Effect of lateral load
Calculate the depth of fixity for calculating bending moment induced by horizontal load.
23
Following steps to be followed for determining that:
1. The long flexible pile, fully or partially embedded, is treated as cantilever fixed at some
depth below the ground level
Determine the depth of fixity
For Granular Soil
EI
Stiffness factor T (in m) = s (4.1)
gb
Where
E=Young's modulus of the pile material in MN/m2,
I=moment of inertia of pile cross-section in m4, and
lb= coefficient of modulus variation in MN/m3 from table 4.1.3
ih KN/m3 X 103
Soil Type N (blow/30cm)
Dry Submerged
Very Loose Sand 0-4 0.4 -
E1
Stiffness Factor R in m= 141 (4.2)
KB
Where, K= 1.5K1 , the value of K1 in MN/m3 from table 4.4
24
Table 4.4.The Value of Subgrade Modulus K1 in KN/m3
Unconfined compression Range of K1 IN/m3 X 103
Soil Consistency
strength qu kN/m2
Depth of point of fixity can be obtained from Figure 4.1(Ramasamy,G.,Gopal Ranjan, &
Jain,N.K.-1987)
F
NOOR PILLELSYIN
RMA ADE
LOSANDDAN
Cays
25
The fixed end moment of equivalent cantilever is given by: (Ramasamy, G., Gopal Ranjan, &
Jain, N.K.-1987)
.....for
MF =-"Q(Li + free head pile (4.3)
+
...for fixed head pile (4.4)
2
Actual maximum moment =M= m x M F
1.2
FOR PILES IN SAND OR NORMALLY LOADED CLAY
z0
E 0.8
1,11
0 1.5 2 2.5
Piles are attached to pile cap so it is the case of fixed head pile.
Step.10. Using SP: 16 and IS: 456-2000, gets the area of steel for this moment (M)
Minimum area of longitudinal reinforcement in pile should not be less than 0.4%.
Step.11. At top piles are attached to pile cap. The function of pile cap is to distribute the load
coming to it equally to all piles beneath it. The thickness of pile cap such that it provides
necessary anchorage of column and pile reinforcement. Clear cover for main reinforcement
should not be less than 60n-irn.Pile should project 50mm into the pile cap.
26
4.1.2. Design of Pile Foundation for Normal Condition
Design of pile
The ultimate MOMellt=-Mult= MF
Ultimate compressive load = Puit = Pu
Ultimate Uplift load = Uu kN
d'
Calculate the value of
Pu and
M u for particular value of —
fag fag
Where
d'= clear cover , and
D = diameter of pile
Using the SP: 16 get the value of percentage of steel
Is 456:2000, clause26.5.3 specify that
• Minimum diameter of longitudinal reinforcement = 12mm
■ Spacing of longitudinal bars measured along the periphery of pile shall not exceed
300mm.
• Diameter of lateral tie shall not be less than one fourth of the diameter of longitudinal
bar and in no case less than 6mm.
As per IS: 2911(Part-2), the minimum area of longitudinal reinforcement is 0.4% of sectional
area calculated on the basis of outside diameter.
Clear cover to all main reinforcement in pile shaft shall be not less than 50mm. the minimum
diameter of the links shall not be less than 6mm and minimum spacing should not be less
than 150mm.
d-
(0.138xbxfck )
Compare the depth calculated with the development length required for pile reinforcement.
27
The maximum among these two will be provided
f AstL
0.87 f yilsthc/( J= M
1 f abd
D = 0 .473( 2 ) 3
Where
D = normal depth of scour,
Q= discharge in cumecs,
f = silt factor =1.76Vin , and
m= mean size of particle in mm.
[RC: 78- 2000 recommends that scour calculations for foundation may be made for a
. ischarge larger than the design discharge as per the table 4.5.
28
Table 4.5 Increase over Discharge for Foundation
Catchments area ,km2 Increase over design discharge in present
0-3000 30
3000-10000 30-20
10000-40000 20-10
above 40000 10
For determining the maximum depth of scour, the normal depth of scour is multiplied by the
given factor as shown in table 4.6
Table.4.6 Factor for Determining Maximum Depth of Scour
Condition of river. Factors
In straight reach 1.27
At moderate bend 1.50
At a severe bend 1.75
At right angle bend 2.0
At noses of Pier 2
Where,
As --surface area of pile below maximum scour level,
29
cu= undrained cohesion of soil, and
W= weight of soil + Pile.
For non cohesive soil:
The uplift resistance is provided by the skin friction resistance with a reduction factor of 0.6
plus the weight pile. Safe uplift capacity of single pile is given by
fsilc x RF w
Qsaj = r
e FOS
Where
fs=average unit skin friction = Ka, tan g ,
As= area of pile shaft below maximum scour level,
K= coefficient of horizontal pressure =0.35 (for bored pile),
av= effective vertical stress at mid depth of pile below maximum scour level,
8= angle of wall friction =2/30,
RF= reduction factor = 0.6 for cohesion less soil, and
W = weight of pile.
Uplift capacity of group of pile =nQsafe
Factor of safety against uplift should not be less than 2.5 to 3.
Where
Qu= ultimate bearing capacity of pile (in kN/ sq m),
bearing capacity factor, usually taken as 9,
cp= average cohesion of soil at pile tip kN/sq m,
a = adhesion factor,
c= average cohesion throughout the length of pile, and
AP cross Sectional area at pile toe in m2
30
For Cohesionless soil:
n
Qn = crvil p(N g —1)+ E Kpa tan SAS,
Where
D=Stem diameter in m,
Pn=effective overburden pressure at pile toe in kM/m2,
Nc, Nq=bearing capacity factor depends upon the value of 4:1),
K= coefficient of earth pressure,
8= angle of wall friction between pile and soil in degree, and
As; = surface area of stem in m2.
From the above formula determine the value of ultimate bearing capacity Quit of single pile.
Safety against Lateral Load
The scour under design flood results in large length of pile laterally unsupported. In addition
the flowing water exerts additional lateral load on the foundation,
(1) Estimation of lateral load on pile
Load from the tower:
The leg of the tower is inclined and transmits an axial load Qum'. The axial load has a
horizontal component, Ht obtained as:
Ht = Qaxial x Sin a
Where
a = inclination of the leg to vertical.
The intensity of pressure due to flowing water is given by:
p = 0.52KV2
Where
p = intensity of pressure due to flowing water in kN/m2,
V =the velocity of current at the point considered, and
K =a constant: 1.5 for square / rectangular end shapes 0.66 for semi -circular end
shapes.
The velocity of water current varies linearly with maximum at HFL to zero at the scour line.
The maximum pressure component is obtained as,
31
p = 0.52K (-5V)2
Then moment is calculated by using equation 4.3 and 4.4 and using figure 4.2
Structural Design
Structural design of Pile and pile cap remain same as mentioned earlier in section 4.1.2.
32
Step4. Refer Table4.7 and choose suitable diameter and length of pile.
Step5. Check the capacity of the pile by following steps:
• Let the safe bearing capacity of the pile selected pile for standard length of 3.5 m
from table be = WI kN.
• Let, L meter be the total length of pile and let the difference between the total length
of pile and the standard length of 3. 5 m is represented by x.
x = (L-3.5) m,
• Refer column (10) in Table (4.7) and work out allowable increase in capacity (W2) of
pile due to increased length x
w _xxp
2 — 0.3
33
d. If the water table is high, the safe load shall be reduced by 25%. Thus, in situation,
where conditions (a), (b) and (c) above are also applicable, the modified safe load
becomes
W7= W6— 0.25 W6=0.75 W6
e. In case the moment due to wind or earthquake is considered in working out the load
on pile, the safe load shall be increased by 33%. (Since the stresses can be increased
by 33% when either of the forces i.e., winds or earthquake is considered). Thus, in
situation where all the above conditions are also applicable, the modified safe load
becomes
W8 = W7 + 0.33W7= 1.33W7
The value of final modified safe load should work out to be same or slightly more than P, the
design load for pile. In case the modified safe load works out to be lesser than P, revise the
design by adopting increased diameter and/or length of pile.
Step7. Using table 4.7 calculate the ultimate bearing capacity of pile
IS: 2911(Part3) specify that this FOS should not be less than 2.5
Step8. In the similar way uplift capacity of pile will be calculated
Uurt
Factor of safety (FOS) = F.O.S =
URes
Where
Ures = uplift resistance of pile.
IS: 2911(Part3) specify that this FOS should not be less than 3
Step9. In the similar fashion uplift capacity of pile will be calculated
34
Fig.4.3 A typical Reinforced Under-Reamed Pile
35
-7,
.- -0 at ,,,
eL), _ N oo -1- ..c. c)
= oo nr
0 (t) = ,,
o ‘-' .—."
—. N• en' vr• vo• kr)'
A it:.
Late:
4.0 I
Resist
1:11) 7:1 8
.5 ,_5 a
... Lel •cs-•
—• ri en m kr)
4
v) .) ?I?
0
2 0 U "S v") o kr) c) kr)
0.85
a) tio
0.7
lei I-4 ,—$ (e•I et
,
)
C.. Cn =
a) k-, 0 6 .-- — — —
o
A
a) E
Safe loadin uplift
cn
co c> vn ton kr) ,r) kr, o o
I-. c) o
a) en `0
_,„ °°
_. c:°. cl 't. `tp. °°.
.a.) ago —.
I
Il v■I 1■1 ,-/
= 1
I■1 04 "
1).
.0 lai
a) o
25.75
CI) SL
31.5
= -0 kr) 0. N
18
IZ
o =
A Q `'f
Table 4.7 Safe loads for vertical, Bored cast-in-situ Underremmed pile in sandy and clayey soil
i
ob)
..g4 4 la
5 -1. ,.0 oo
14
r-: N
2
.5 5 a
cn Q 1:1(4)
a) e
Eo u t s cr, . 6.1
S'I
.3 en o ci. 6 ,....1
a) 6. 0
A a
a> E
t)
a, c) ...,t, kr)
--. °°. (:7 --.• N
kr,
Compression
,-. en 0 c) • --. - -
c.)
0 t N
.-, " ),
rn
a> 0 U
.0
0 0 U
52.5
N
18
7:1
§
63
36
42
24
0 0 ,-.
0 0 il2
a) 4 I?,
of) 43 g N
oo — —
28
35
24
42
■D
.5 = a
C/3 4,2
tO .s I .s ,
18
30
30
30
30
ZZ
SZ
*g k3) ■0 '-:
,3
ta, 0
vi 4-■ • .
"0
0
... OONNNNN
— — 1-... e-4 o■I v•-•I v■.,
reinforcement
Longitudinal
CI
I-.
a)
-0
E n-et v- kr) 2 N C'
g
Z
a) 4, 'lc ,,
..0 0) (I) 5
3.75
-0 E
3.5
3.5
4.0
4.5
5
0 o co .5 en
t) A P2. '...-'
0
a)
,--1 a.) 4. -o
a, ,..,
a> 5
OA ..0
3.5
3.5
3.5
3.5
3.5
S.£
S.£
.5 c co .5
v) 5, ..._.
0) 4 Ica ....N
,n• un
112.5
to .8 E cz, N
125
100
....
94
a) .5 = a3 .5 -,,
N
■4:) ,
..•
a) v) 5 ......
§
.5 s c> , o kr) o
kon o ..._.
A o N N M ,en- Tr •zr vl
CHAPTER 5
WELL FOUNDATION
5.0. GENERAL
Well foundations are widely used as foundation for transmission line tower, where the uplift
loads are large. When tower passes through river bed or bank, scouring takes place due to
flow of water, and then well foundation is designed. Well foundation is a massive sub-
structure; it is monolithic and relatively rigid in its structural behavior.
Circular well are provided for well foundation, as the legs of tower are symmetrical and
equidistant to each other. Circular well is simplicity in construction, ease in sinking and its
uniform strength in all directions. It has only one dredge hole. Its weight per square meter of
peripheral surface is highest and hence the sinking effort is less, thus facilitating easier
sinking. It can be more easily controlled against tilt and tilt correction is also easier in this
case.
5.1. ELEMENTS OF WELL FOUNDATION FOR TRANSMISSION LINE TOWER
The various elements for foundation for transmission line tower are as follow:
PEDESTAI.
WELL STEINING
SCOUR LEVEL
GRIP LENGTH
WELL CURB
37
5.1.1 Pedestal
Short section of leg angle embedded in the concrete along the slope of tower leg. Slope of
pedestal is provided along the slope of leg of tower. The leg of tower is anchored to the
concrete by clit angle. The function of pedestal is to transfer the load of tower to well. It is a
reinforced concrete section having thickness at the junction of pedestal and well cap is
1000mm.
5.1.2 Cantilever Beam
Pedestal used to transfer the load from tower to well cap through cantilever beam. Provide
an outstanding of 100 mm on each side pedestal.
5.1.3 Well Cap
It is a R.C.0 slab of sufficient strength to transmit the load from superstructure to well
foundation. Its top level of well cap is generally kept at L.W.L or river bed level. It is
monolithically constructed with well steining.
5.1.4 Well Steining
It is hollow cylindrical reinforced concrete member, having sufficient thickness to transmit
all the loads coming to it through well cap. As per IRC, dredge hole should be large enough
to permit easy dredging, the minimum dimension not being less than 2 m.
The minimum thickness of the well steining should not be less than 500 mm. Thickness of
steining should be such that it is possible to sink the well without excessive kentledge and
without getting damaged during sinking or during rectifying the excessive tilts and shifts.
Stress at various levels of steining should be within the permissible limits under all
conditions of loads that may transfer to the well.
5.1.5 Well Curb
The curb of the well have to transfer the entire load through the cutting edge to the ground
during sinking. RCC well curb with steel cutting edge for any type of well are commonly
used. Steel cutting edges are used as a possibility of coming across small builder during
sinking cannot be ruled out. Curb cut through the soil by the dead weight of the well steining
and kentledge if any, when the inside of the well is dredged. The well curb is slightly
projected beyond the steining by about 75 mm.
38
5.1.6 Bottom Plug
After the well is sunk to required depth, the base of the well is plugged with concrete. It is
called as bottom plug. It transfers the loads to the subsoil and acts as raft against the soil
pressure from below. Generally M20 grade of concrete are generally provided.
D = 0 .473( 2 )3
Where
D = normal depth of scour,
Q= discharge in cumecs,
0-3000 30
3000-10000 30-20
10000-40000 20-10
above 40000 10
39
For determining the maximum depth of scour, the normal depth of scour is multiplied by the
given factor as shown in table 5.2.
Where,
qa = allowable bearing pressure, Kg/m2,
N = Corrected standard penetration resistance value,
B = Smaller dimension of well cross-section (in m), and
Df =Depth of foundation below scour level
40
5.4.2 Dead Load:
The dead load carried by foundation consists of its own weight
5.4.3 Seismic Force:
An earthquake is perceptional motion of the ground; it is irregular and random both in
magnitude and direction. Motion of ground in the form of vibration can be both horizontal
and vertical in all coordinal directions. The horizontal motion usually greater than the vertical
.Vertical acceleration usually varies from 1/10th to 1/5th of the horizontal acceleration. Only
the weight of structure above the maximum scour level should be considered in calculating
the seismic force. The seismic force assumed to act at the center of gravity of each member
or mass.
5.4.4 Water Current Force
Any part of foundation which may be submersed in running water shall be designed to
sustain safely the horizontal pressure due to force of the current.
Intensity of pressure parallel to direction of water current P
P = 0.52KV 2
Where,
P = Intensity of pressure due to water current in kN/m2,
V = the velocity of the current at the point where the pressure intensity is
being calculated (in m/s), and
K = a constant having different values for different shapes.
In case of the water current striking the piers at an angle, for calculating the pressure due to
the components of velocity perpendicular to the pier, constant K should be taken as 1.5 in all
cases except in the case of circular piers where the constant should be taken as 0.66.
For calculating the pressure on the pier, angle 0 that the current makes with the axis
of the pier should be taken into account. The pier should then be designed for variation of
current angle between (20° ±0°). Thus the pressure along the axis of the pier and transverse
to it will respectively be given by
41
Table 5.3 Value of K for Different Shape of Pier
Shape K values
1.5
Square ended piers
0.66
Circular piers or piers with semicircular ends
42
1.The effects of buoyancy are to be considered in the design of a steining, in case of a
submersible well foundation. In such a case, it is assumed that the filling behind the steining
is washed away or removed by scouring action.
2. For the design of submerged masonry or concrete structure, the buoyancy effect
through pores is limited to the extent of 15 per cent of full buoyancy effect.
3. If the member under consideration displaces water only, the reduction in weight due to
buoyancy for that member is taken equal to the volume of the displaced water.
43
Step 1: Determine the value of W, H and M under combination of normal loads without wind
and seismic loads assuming the minimum grip length below maximum scour level.
Where
W = total downward load acting at the base of the well, including the self weight of well.,
H = external horizontal force acting on the well at scour level, and
M = total applied external moment about the base of the well.
Step 2: Compute IB, L, and I;
Where
113 = moment of inertia of base of the well about the axis normal to the direction of
horizontal force passing through its C.G.
Ir B 4 for circular well,
=--
12
I = I B +Ma ± 2,u' a), and
Iv= moment of inertia of the projected area in elevation of soil mass offering resistance. =
LD f 3
12
Where
L= projected width of the soil mass offering resistance multiplied by appropriate value of
shape factor. The value of shape factor for circular wells shall be taken as 0.9,
Df = depth of well below scour level,
m = KH/K; ratio of horizontal to vertical coefficient of subgrade reaction at base,
W=tan8 , where 8 is the angle of wall friction between well and soil, and
diameter
a = (for circular well).
RD
Step 3: Ensure the following:
M + SIC') — ,uW ,
H >—
Where
/ Df
r
m/v 2
44
,u = coefficient of friction between the base and the soil. Taken as tan 0 , and
0 = angle of internal friction of soil.
Step 4: Check the elastic state
mM
y(Kr )
I
mM mM
If > p K a ) , get new grip length by equating it i.e. = ykK p — K
Cos 0
Active pressure coefficient Ka
■V cos + V sin(( + g )sin0
Step 5: Calculate
W ,u ' P + MB
a1 =
A 2 I
W — ,u' P MB
62 =
A 21
Where
& 62 =maximum and minimum base pressure respectively,
A=area of base of well,
B= width of base of well in the direction of force and moments, and
P= M/r
Step 6: Check a2 0 , i.e. no tension
45
combinations and the ultimate resistance is reduced by appropriate under-strength factors and
the two are compared. The steps to be taken are as shown below:
Step 1. The various applied loads i.e. uplift load, moment and down thrust load are computed
.In the ultimate resistance case, the point of rotation is assumed to occur at 0.2Df above the
base of the well. The moment to be calculated about this point instead of base of well.
Step 2. Check for maximum average pressure at base:
W. < qu
A 2
Where, qu= the ultimate bearing capacity of the soil below base of well, and
Wu ultimate downward load acting at base, including the self weight of well,
A = area of base of well
WEI < qu
A 2
If this condition is not satisfied then increase the diameter of the well.
Step 3. Compute the base resistance moment Mb at the plane of rotation by following
formula:
Mb = QW.B tan 0
Where, Q = A constant depend upon the shape of the well as well as the ratio D/B ratio. A
shape factor 0.6 is to be multiplied for wells with circular base.
Table.5.4 Value of Q
D
0.5 1 1.5 2 2.5
B
Q 0.41 0.45 0.5 0.56 0.64
Step 4. Compute the ultimate moment of resistance on the well sides. This has two parts, one
due to passive resistance and other due to frictional resistance.
Ms = 0.107 (K p —KA )D f3L
Where
y=submersed density of soil,
L = 0.9 times the diameter of the well,
46
Df = depth of grip below the maximum scour level, and
Kp, KA= passive and active pressure coefficient to be calculated using Coulomb's
2
theory assuming "8" angle of wall of friction between well and soil equal to — 0:1) but
3
limited to a value of 22.5°.
Step 5. Compute the resisting moment due to friction at front and back faces (Mf) about the
plane of rotation by following formulae:
M f = 0.11y (K p — K A )D f 2 B2 sin 8
Step 6. Check the applied ultimate moment with the total ultimate moment of resistance
0.7y(Mb +M, +M f )
47
Calculate the designing moment= Muit at the base of pedestal
Neglecting tension in concrete, the steel required resisting the direct pull
U x 1 000
Ast-
0.87fi,
d i=clear cover,
D=Overall depth of cross-section of shaft, and
b=width of cross-section of shaft
From design aids
P
For the value of , '1 and
D f cic bD fck bD2
Get percentage of steel required =p using the SP: 16 codes
Asti required = p x Area of section of shaft
As per IS 456:2000, percentage of longitudinal reinforcement should not be less than 0.8%
d= Mtn
Mithfck b
0.137x
48
As per Table 23 of IS 456:2000 get the value of tic
If T, > (0.5-cc) provide shear reinforcement
If the depth of beam >750 mm, provide side face reinforcement of 0.1% of cross sectional
area of beam
Step4.Design of Well Cap
Thickness of well cap will remain same as that of the cantilever beam at the external face of
well staining. Providing a nominal reinforcement of 0.12 % of gross section area of cap
Step 5.Design of Well Steining
As per IRC: 78-2000 clauses 708.2.3.1
h= KdVi
Where
h = minimum thickness of steining in mm,
d = external dia of steining,
1= depth of well below Bed Level, and
K = 0.03 for RCC.
Calculate the downward load V ult , bending moment (M) and horizontal load (H) at the scour
level due to dead load, seismic load, buoyant force, water current force and force coming
from tower.
Calculate depth of zero shear force below scour level
[ 2FH 12
X =
y(K p — K A )B
Where
F=constant whose value = 2, and
B= external diameter of well
Net downward load about this point V
Eccentricity on top of well due to
As per IRC: 78-2000: Permissible tilt of 1 in 80 and Permissible shift =150 mm
Calculate Moment due to tilt and shift and total moment
Moment of inertia of well steining I
49
, V My )
f1,2=1.J(— ± —
A I
50
03 \ bd)
Design hoop tension = HT=1.5 x ( --71,K A (2D f b )--4–
16r
Hoop reinforcement =
HT
—
fy
As per IRC: 78-2000, clause708.7.3
Minimum reinforcement = 72Kg/m3
Step7. Design of Bottom Plug
Using M20 grade of concrete for bottom plug
Thickness of bottom plug=t
t= 1.18r 2q
Where,
r = external diameter of well
51
CHAPTER 6
FLOW CHART
C Start
/ Input Compressive Loari(P),uplift Load(U)
and Lateral Load coming from tower in
B.W.0 and N.0 ,
Inclination of tovwr leg, properties of soil
Well Foundation
Is it a rasr
Calculate length of footing Enter Discharge of river, Velocity of scouring
of water and mean size of particle
Increase Diameter
of Pile
52
Select Diameter and Length
of Pi le and Bulb
V
Select Diameter and Length Calculate Uplift resistance
of Pile of single Pile
53
SUMMARY AND CONCLUSION
54
REFERENCES
1. Wiggins, R.L (1969),"Analysis and Design of Tower Foundation" Proc. ASCE, Jr.
Power Division, Vol. 95, No. P01
2. Down,Dallas.I,and Chierzzi, Robart,"Transmission Tower Foundations" Proceedings,
Journal of Power Division, ASCE, Vol. 92, No P02.Proc. Paper 4750, April, 1966.
3. Radhakrishna.H.S and Adams.J.I (1973) "Long Term Uplift Capacity of Augured
Footing in Fissured Clay" Canadian Geotechnical Journal , Vol.10
4. Mayerhoff,G.G. and Adams,J.I. 1968."The uplift capacity of foundations." Canadian
Geotechnical Journal , 5 (4) ,pp.225-244
5. Richard,L.Wiggins,A.M-1969,"Analysis and Designing of Tower
Foundations"Journal of Power Division, Proceedings of the American Society of
Civil Engineering.
6. IS: 4091-1979, "Indian Standard code of practice for Design and construction of
foundations for Transmission Line Tower and Piles". Bureau of Indian Standards,
New Delhi
7. IS: 11233-1985, "Indian Standard code of practice for Design and construction of
Radar, Antenna, Microwave and T.V. Tower foundations" Bureau of Indian
Standards, New Delhi
8. IS: 2911 sec.2 Part.2," Indian Standard Code of practice for design and construction
of Pile foundation" Bureau of Indian Standards, New Delhi
9. IS: 3955 (1967), "Indian Standard Code of Practice of Design and Construction of
Well Foundations", Bureau of Indian Standards, New Delhi.
10.IRC: 78-2000, "Code of Practice for Road Bridges - Section VII, Foundations and
Substructure", The Indian Road Congress, New Delhi..
11.IRC: 45-1972, "Recommendations for estimating the resistance of soil below the
maximum scour level in the design of well foundations of bridge" The Indian Road
Congress, New Delhi.
12.IRC: 6-1966, "Indian Specifications and Code of Practice for Road Bridges —Section
2 (Load and Stresses)"The Indian Road Congress, New Delhi.
55
13. McCarthy (1988), "Essentials of Soil Mechanics and Foundations", Prentice Hall,
New Jersey.
14.Ramasamy, G. (2006), "Soil Investigations - Ganga River Crossing of Nehtaur-Metor
220 kV Transmission Line, Bijnor (U.P.)", A report submitted by Deptt. of Civil
Engg., NT, Roorkee.
15.Tomlinson, M.J. (1977), "Pile Design and Construction Practice", A Viewpoint
Publication.
16.Varghese, P.C. (2005), "Foundation Engineering", Prentice Hall of India, New Delhi.
17.SP: 34, (1987)"Handbook on Concrete Reinforcement and Detailing" Bureau of
Indian Standards, New Delhi.
18.Down,D.I and Chieurzzi.R,(1966)"Transmission Tower Foundation" Journal of
Power Division ,A.S.C.E ,Vol 92,No P02
19.IS: 456-2000,"Indian Standard Code of Practice of Plain and Reinforced Concrete
(Fourth Revision)." Bureau of Indian Standards, New Delhi.
20. IS: 1904(1986) ," Indian Standard Code of Practice for Design and Construction of
Foundation in Soil :General Requirement (Third Revision)" Bureau of Indian
Standards, New Delhi.
21. IS: 2911 (Part 3)-1980, Indian Standard Code of Practice for Design and Construction
of Pile Foundation: Under reamed Pile (First Revision)" Bureau of Indian Standards,
New Delhi.
22. Mayerhof,G.G. and Ranjan,G.-1973,"The bearing Capacity of rigid piles under
inclined loads in sand III:Pile Groups. "Canadian. Geotech.Journal.
23. Ramasamy,G., Ranjan . G and Jain,N.K.(1987) ," Modefication of Indian Standard
Code Practice on Lateral Capacity of Piles" , Indian Geotechnical Journal ,Vol-
17,No.-3
24. Balwant Rao, B. and C.Muthuswami (1963),"Considerations in the Design and
sinking of well foundation for Bridge Piers," Journal of the Indian Road Congress,
New Delhi, Vol XXVII.
25. Saran,S. "Design of Sub Structure"
56
ANNEXURE I
DESIGN PROBLEM FOR PAD AND CHIMNEY
FOUNDATION
DESIGN PROCEDURE:
Taking a factor of safety of 2 for load in Normal condition (NC) and 1.5 for Broken wire
condition (BWC)
Table A.1.2 Load for Normal Condition and Broken Wire Condition
N.0 BWC
Ultimate Compressive load 360 352.5
Ultimate uplift load 250 270
57
Assuming weight of footing =10% of compressive load=26 kN
Total down thrust= 357.3+35.7 kN =393 kN
393 2
Area of footing required= — m =3.275m2
120
Proportioning Of Footing:
Length of footing =1= J.TS m = 1.81 m
Let us provide 1.9 x1.9 m2 footing
58
Hence change the dimension,
Increase depth = 2.5 m, and Length =2.6
Volume of frustum of soil V=37.78m3
Weight of frustum of soil (WI) =VxYsub kN = 37.78 x 10 kN X377.8 kN
Weight of footing=W2 = (2.6 x 2.6 x 0.2 x 25) =33.8 kN
1B1 = 4
For (1)=30°, m=0.15, s=1.6, —
H=2.6 x 4 = 10.4 m
As D (=2.5 m) <H, so it is a case of shallow depth.
Qu = 4cDB +2sByD2 Ku tan 0 + W
59
UpL Pcosex L (268x2.6), 44x 2.8) 357.3x 2.6
+H(D+h) +k
3 3 3 3
—21.26 kN
5L 5
. — x 2.6
6 6
Pcost9xL
, PL +H(D+h)
W 3 3
2 5
L
6
Hence safe in overturning moment
Now dlb= ratio of depth of footing and width of pedestal = 2.5/0.4 = 6.25
h 0`2 _
0.2 d 2.5
-7 = 0.5, — = — =6.25, then H — 5
b 0.4 b 0.4 yK pb3
1 +Sin30
Ku— —3
' 1— Sin30
H=10 x 3 x 0.43 x 5 kN = 9.61th
As Hu>H,so it is shallow shaft
Design of Pedestal
As we selected dimension of pedestal as 400 x 400 mm
Pu= ultimate compressive load = 352 kN
Mu = Ultimate Moment = 486 kNm
P. — 352x103 —
0.11
fabD 20 x 400 x 400
60
Mu _ 31.6x106
—0.025
fthbD 2 20 x 400 x 4002
P is negligible
fck
Design of Footing
Dimension of footing that we provide is 2.6 x 2.6 sq m.
Depth of foundation = 2.5m
Moment occurring at foundation = Muir = 31.61cNm
Net Upward pressure =
61
6M 352 6 x 31.6
P01= + — + — 62.86 kN/m2
L2 L3 2.62 2.63
Pu 3
P0_2= L2 6M
L =41.3 kN/m2
_ 62.86+ 41.3 _
P"= P01 P02 kNisq m
52.08 kN/m2
2 2
L—b
Maximum bending moment occurs at face A-B, cantilever length=l= — 1.1m
2
LL
Moment at face A-B= M — ( (2Po, + P' ) kNm
24
— 2.62.6 — 0.4)2 (
(2 x 62.86) + 44.06) =89kNm
24
1
For the moment of resistance the effective width is b'= b + — — b) = 0.675m
89 x106
Effective depth required = mm = 218 mm
(0.138x 675x 20)
F 337.2x103 2
T= — 0.64n/mm
4b0 d0 4x 620x 212
62
r, = Ks r,=1.118 N/mm2
F 337.2x103
do1 = = —121.6 mm
4bor, 4x 620x1.118
Providing total thickness at edge is 200mm, effective depth at edge =d1 =140mm
Thickness of footing at a section d/2 from face of pedestal =
2x(d—d1)( B—b—d 2x(220-140)(2600-400-220)
do= d + )-140+ -212
1 ()
B —bL 2 (2600— 400) 2
V )
Tv— —0.033
b2 x d'
Reinforcement
63
f
0.87fyAs,L41 y M =89 x 106 Nmm
fa bid
AstL= 1390.7mm2
Using 16 mm dia bar (A4)=201mm2)
(1000x201)
S pacing = —144.5mm
1390.7
280
200MM 8NOS-16MM DIA BAR
STUB ANGL
Sectional
Elevation AT SECTION A-A
OLOOMON MMMMMM IMMOMUNIOUN
111111011111111111111101111111101111111111111114111111
1141111112411:11112111111
........ MMMMMM OVII4SIOMUMM
iiiiiiiiiiiiiiiiiiiiiii
OMMMOMMIOmmilIMM MEM
11IMM DIA BARC#140MM C/C ON
BOTH FACE IN BOTH DIRECTION
1111111111141111111111
rf
e i
lithil i
itaina ill ii
i
M M
UMPAMM MMM MUMMIMMONOM
OWINOMM MMOIMMOMN
O M
VORT!!!!!!!!!!!!!!!0
2600 MM
PLAN
64
ANNEXURE 2
LINE TOWER
The data has been taken from the project -"Design of Transmission Line Tower Foundations
- 220 KV Nehtaur - Metor Line Crossing Ganga Near Bijnor for analysis and design of the
River Data
RL of HFL= 77.0m
65
Poorly graded sand (SP) - Up to about 15 m below bed level
d =0.47342)3
f
Where , d = normal depth of scour in m,
Q = design discharge in cumecs,
0-3000 30
3000-10000 30-20
10000-40000 20-10
Above 40000 10
66
A barrage with a design discharge of 15,000 cumecs is located at a distance of about 16 km
upstream of the tower alignment crossing the river. Thus, the maximum discharge is likely to be
only marginally higher than 15,000 cumecs. Accordingly, the design discharge of 18,700
cumecs is adopted for scour depth calculation.
Adopting the average size of the top erodable soil as 0.25 mm
x(18700)3—
d =0.473 13.10m
0.88
Further, IS:3955 (1967) recommends that the maximum depth of scour may be increased to 1.27
d if the foundation is located at a section of the river having straight reach. Accordingly, the
maximum depth of scour dmax is taken as,
dmax = 1.27 x13.1m = 16.6 m
HFLV
RL 77.0m
21V1.
RL 75.0m BED LEVEL
R041,0m 1m
16.6m
6mm THICK MS LINEAR,1Om LONG
1m
SCOUR LEVEL.
22,OM
im
8.4m
67
The estimated depth of scour below bed level (Fig. A.2.1)
75.0 - (77. 0-16.6) =14.6m
The soil investigation report (Ramasamy, 2006) suggests that the depth of scour in' the recent
past could be about 5.0 m below the bed level based on results of penetration resistance.
Accordingly, the above estimated scour depth is on the safe side.
As the scour depth below bed level is large, pile foundation may be adopted. From
scour considerations, the base of the foundation may be at a minimum depth of 1.33 times the
maximum scour depth measured from HFL.
Accordingly, the pile may be taken upto a minimum depth of 1.33 x 16.6 = 22.0 m below HFL
(i.e. upto RL 55.0 m). This provides an embedment length of 5.4 m below scour line.
However, considering the importance of the structure, the pile may be taken upto a depth
providing a depth of embedment of about 8 m below the scour level. Thus, the foundation
details may be as below (Fig. A.2.1):
Type of pile = Bored cast-in-situ piles
Dia. of pile = 1.0m
Tip of pile at 52.0 m
Length of pile below pile cap = 22 m
Length of pile below scour line = 8.4 m
HFL = 77.0 m
Bed level = 75.0 m
Cut-off level of pile = 74.0 m
Scour line = 60.4 m
Choose a group of four piles under each leg. A MS liner of 6mm thick may be used upto a
depth of 10 m below the top of pile.
68
(i) Safe Uplift capacity of pile (Qsafe)
_ f s xAs xRF +w
Qsafe (2)
FOS
Where
fs = average unit skin friction, = Kcry tan S,
AS area of the pile shaft below scour level,
K= coefficient of horizontal pressure = 0.35 (for bored piles),
= effective vertical stress at mid depth of the pile below the scour line,
8 4- xl0xtan22)x7rx1x8.4x 0.6
(0.35x--*- x12
2
Qsafe = 2 x 22x(24-10)}
3 4
= 31 + 242 = 275 kN
Uplift load / leg = 486.9 kN, Say 487 kN
= Uplift load/pile = 487/4= 122 kN < 275 kN; safe.
(b) Safety against compressive loads:
For 4=33.0°, Ng = 40
Substituting the appropriate values and adopting a factor of safety of 3, the safe compressive
load,
69
gx 12
(0.35x 21xl0xtan22x7rx1x8.4)+(8.4x10x39x )
2 4
—910 IN
3
p = 0.52K (-502
70
9.36kN/ sq, m
R,L 77,0m HFL
8.0 kN/
R,L 74,6m
4kN sq•m
R.L 67.5m
SCOUR LINE
R.L 60.4 m
71
LP/ ROR1,t/ T
L1/Ft OR Ll/T
El 2.5x10' x x14
Thus, T = 5 = 5 - 3.0m
nh 5000 x 64
Maximum fixed end moment on the pile due to all the lateral forces,
Mmax = 29x [(74.6-54.88)/2] +15.5x [(74.6-54.88)/2] +35.9[(70.3-54.88)/2]
= 286 + 152.8 + 276.8 = 715.5kN-m
Factored moment = 715.5 x 1.5 = 1073 kN-m
Pile need to be structurally designed as column subjected to axial load and moment. The pile
cap shall also be subjected to a moment of 1073 kN-m and be designed to resist the same.
72
Load on each pile
Compressive load = 587/4 = 147 kN
Uplift load= 487/4 = 122 kN
Projection of pile above scour level = 74.0-60.4 =13.6m
The depth of virtual fixity may be taken as 1 m or 3 times the dia. of pile below scour level in
good ground conditions (Tomlinson, 1971). Thus, the effective length = 13.6 + 3.0 = 16.6m.
Slenderness ratio = 16.6/1.0 > 12
The pile may be designed as long column.
Using M-25 grade of concrete
Compressive load on pile = 147 kN x Load factor (1.5) = 221 kN
The safe structural capacity (design load) is calculated assuming the pile is un-reinforced and
the maximum allowable stress in concrete is 0.25 fck (Varghese, 2005, IS: 2911, Sec. 2 Part 2).
Thus, the safe Compressive load = 0.25 fck x Area of pile
0.25x25 rx10002
– 4908 kN > 221 kN (Safe)
1000 x 4
Longitudinal reinforcement:
Minimum % steel to be provided = 0.8%
0. 7r
8 x 10002 _
Area of steel required = — 6283 mm
100 4
x
6283-
Number of bars required = 13
490.7
73
P 221x103
For u –8.84 x 10-3
fa D2 25 x10002
The depth of the pile cap should be adequate to provide minimum anchorage of the main
reinforcement of the pile.
0.874,0
Minimum anchorage required = La –
4rbd
0.87x 415x 25
L – 1465 mm
d = 4x1.54
Choose D of cap as 1200 mm and bend the bars to provide addition anchorage length of 400
mm.
Check from bending moment consideration M = Rbd2
Where,
M= maximum bending moment = 1073 kN-m
d =effective depth
b = width of pile cap
R = a factor =0.138 fck for Fe 415 steel.
74
d= \IM = 1073x106
—269 mm
Rb 0.138x 25x 4300
Providing an effective cover of 75 mm, d provided = 1125 mm > 269mm
The critical section for two way shear is the peripheral section at half the effective depth from
the face of the pedestal, i.e. on a peripheral cylindrical area of (1 + 1.25) m dia. The
compressive load transmitted by the pedestal under the breaking wire condition is 587 IN.
Adopting a load factor of 1.5,
1.5
1. x 587 x
Shear stress= r = — 0.117N/mm2<permissible shear stress ( 0.25j: )
ir(1000+1125)x1125
Reinforcement
Minimum reinforcement required = 0.12% of cross sectional area for deformed bars.
0.12 x 4300 x1200
= 6192mm 2
100
Choosing 20 mm dia. bars,
X 202
Spacing of bars required = x 4300— 218mm
4x6192
Provide 20 mm dia. bars at a spacing of 200 mm in both ways. As the pile cap is subjected to
uplift, provide 20 mm dia. bars at 200 mm spacing in both the directions at the top also.
7r X 202
Area of steel provided = x 4300— 6751mm
4x 200
Moment capacity is given by
75
Design of Pedestal
The stub angle of the tower leg may be encased in a reinforced concrete pedestal as shown in
Fig. A.2.4. A reinforced concrete pedestal of lm dia. is provided. Pedestal may be reinforced
as column providing a minimum reinforcement of 0.8% of area of the pedestal.
Provide 25mm dia bars 16 Nos. as in piles.
Area of steel provided = 1.0%
Providing Lateral ties of 8mm dia @ISO mm c/c.
Thus, the load on the pile cap is transferred through the pedestal.
Embedment of Stub into the Pedestal
Maximum uplift force transmitted by the stub = 487 kN
Design bond stress = 0.9 N/mm2 (Adopted same as for plain bars)
Required embedment of stub (stub angle 150 x 150 x 16)
Ld x (150 x 4) x 0.9 = 487 x 103 x 1.5 = 1353 mm
Provide a minimum embedment of 2.0 m of stub length into the pedestal.
Mu _ 725x106
=0.029
fd D3— 25 x10003
d 75
= = 0.075
D 1000
Referring to chart 56 of SP 16: 1980,
76
P =0.02
fk
77
1..--tic Pedes t al —
nt°
Stub Anglt
TIL 111m
111110m 33m RI713m
•
WO Mg(
1.0m Dia Bored Pie _L
'5mm
Distance belvfafft Lags
The Totorqa the Top---I T
of ql 01 Pile Op
Blot
00 00
Ties 69ISISI/a 0t09
00 00 2SM,1 CN00
Pitt
qc Spacing A
01 lower legs
of Pile Cop
LevtI
1 00 00 11cAt
Pea( slot 4.3m
2.011 dimensions in mm
3:Not to Scale
,A, -I.
--\
-1---- 1
NOTES :
Ir , Ai, 1
1. WRITTEN DIMENSIONS ARE TO BE FOLLOWED 2 5$,16 NOS '111/1110" 1
2. CLEAR COVER TO MAIN REINFORCEMENT SHALL BE 75 MM ISO do
LINE TOWER
The data has been taken from the project -"Design of Transmission Line Tower Foundations
- 220 KV Nehtaur - Metor Line Crossing Ganga near Bijnor for analysis and design of the
1. Details of Towers
A sketch of the river course at the proposed alignment of towers is shown in Fig A.3.1.
The details of the proposed towers and river data relevant to foundation design, are given in
Table A.3.1
Table A.3.1 Details of the Proposed Towers
SI. Tower C/C Spacing . .Max. Compression Max. Max. Leg inclination
Type BWC
No. No. between legs of N.C. (kN) Uplift Uplift with vertical,
, i 4 J. 1 ' ,-,11 ,,l(- . ; I ;.)-, ,,I. ,),,,,,T,'
tower km-N) N.C. (kN) BWC degree
/1,1■T1
1 83 C 12124.90 515.6 586.9 414.9 486.9 11.3
2 84 A+3 7,491.2 180.3 234.3 125.2 179.8 7.0
3 85 C 12124.90 515.6 586.9 414.9 486.9 11.3
4 86 A 6,750.0 180.3 234.3 125.2 179.8 7.0
5 87 A 6,750.0 180.3 234.3 125.2 179.8 7.0
6 88 A 6,750.0 180.3 234.3 125.2 179.8 7.0
River Data
RL of HFL = 77.0m
79
RL of bed level = f 75.0m
Fig A.3.1 River Course and Crossing of Tower- Ganga near Bijnor
80
Soil Data (Report on 'Soil Investigations, Ramasamy, 2006)
Angle of internal friction,() = 330
d = 0.473 x (PI
f
Where,,,, ,.;ft.,., , i; (i)
d = normal depth of scour
Q = design discharge in cumecs
f = Leacy's silt factor =1.76V7n , and
m= mean size of particle in mm
IRC: 78-2000 recommends that scour calculations for foundation may be made for a
discharge larger than the design discharge as per Table A.3.2.
Table A.3.2 Increase over Design Discharge for Foundation
Catchments area, km2 Increase over design discharge in percent
, , 0-3000 30
3000-10000 30-20
10000-40000 20-10
Above 40000 10
81
A barrage with a design discharge of 15,000 cumecs is located at a distance of about 16 km
upstream of the tower alignment crossing the river. Thus, the maximum discharge is likely
to be only marginally higher than 15,000 cumecs. Accordingly, the design discharge of
18,700 cumecs may be adopted for scour depth calculation.
Adopting the average size of the top erodable soil as 0.25 mm
Silt factor = f =1.76 0.25 =0.88
(18700ji
Depth of scour = d = 0.473 x — 13.10m
0.88
Further, IS:3955 (1967) recommends that the maximum depth of scour may be increased to
1.27 d if the foundation is located at a section of the river having straight reach. Accordingly,
the maximum depth of scour dmax is taken as,
dm. = 1.27 x,13.1m.= 16.6'm
As per IRC: 78-2000 clauses 705.3.1
(in] hL\ adopted for sco ur Lierth
Grip length = — x dn. =5.5 rn
3 ‘, ;12C 04. ,`1 0, II
Providing a grip length of 8m
Thus total depth =D=16.6+8 m 24.6 m from HFL
C/C spacing between leg of tower diagonally at bed level =13.04-5 m = 18.5 m
Assuming length of square pedestal = lm.
Maximum lateral dimension at top =18.5+1 m = 19.5 m
If cantilevers are provided as shown in Fig A.3.2 with projected length beyond well cap
equal to 60% of external diameter of well.
Now,
Let external dia of steining = x
x +1.2x=19.5rn
82
pt..!ut)1:11
,t1 n :11 I, ! •
x =8.9 m
Let us provide external dia of steining =9 m
Length of Cantilever part of beam = 0.6 x 9m z5.4m
,N, •
t" ..
5 ,.:. 4
i
83
t= 0.03x 9x.,52.6m=1.28m
Providing thickness of steining 1.5 m
Internal dia of well = 9-3 =6 m
2.3 M .0M
12 RIVER BED
1 .5 M
14.5M
13.5M
BM
M GRIP LENGTH
KA
cos
— cos 33 —0.2671
q cos 8 + Vsin(0 + 8)sin
0 [ Vcos16.5 + Vsin(33 + 16.5)sin 33
12 r
cosq$ cos 33
Kp— , , - = 6.243
[1/cos — Vsint0 + 8)sin 0 Licos16.5 — Vsin(33 +16.5)sin 33
84
3. ELASTIC THEORY
Load calculation
Water current force,As per IRC: 6-1966 clause213.2
Intensity of pressure at free surface of water =P=0.52KV2 kN/sq m
V=1.414 x mean velocity=1.414 x 3= 4.242 m/s
At free surface of water P=0.52 x 0.66 x 4.2422 =6.18 kN/sq m
P at level of river bed=6.18 x 14.5/16.5 = 5.43 kN/sq m
Area of exposure =A = 9 x 14.5 = 130.5sq m
(2 x34.5)
1
Water current force = 0.5 x 5.43 x 130.5 kN =354.3 kN at = 9.66m from scour
level
Table A.3.3 Load Calculation for Elastic Theory
Lever arm
LI; • 1". • ( , I. ). ,
from scour
level Moment
Force (in kN) Direction
( M m) (in kNm)
1.Force on
586.9Cos11.3 x 4=2302 vi•
Tower
2.Dead Load
2.3 xlx1 x25x 4=230
a. Pedestal
vir
.
b. Well cap E x 92 x 1 x 25= 1590.4
4 i•
85
Lever arm
from scour Moment
Force (in kN) Direction level (in kNm)
( in m)
Taking
3. Seismic Force
aH=0.1
on D.L
av=0.1 x 0.5=0.05
a. Pedestal 23 4-- 16.8 386.4
11.5
Iv
b. Well cap 159 14 2226
79.5 ,iv
(13.5 x18996.8 x 0.1)/21.5 .--
C. Well steining 6.75 8051.4
=1192.8
596.4
iv
13981.7 x 13.5 x 0.1/21.5
D. Sand Filling 6.75 5926
-878
439
24.3
Jr
3.Water current
on well and well 354.3 4.---
9.66 3422.5
cap
f.x92 x 21.5x10x0.15=
4.Buoyancy 4
2051.7
86
Moment at Scour level =M 28383.1 kNm
Dia of well = B = 9m
L= Projected width of soil mass offering resistance multiplied by appropriate shape factor
(0.9 for circular well) =0.9 x 9 =8.1 m
.
4-
113=(';14B Hr x9 j
– 322 m4
64 64
v _. LD/ )_(8.1x j
-345.6m3
I[ 12 12
a_ B 9 )
–0.358
rxD f )
I x D f j_r 740.8 8)
r R 57m
= ( MiV 2 x 345.6 x 2) ---
1)() ()
28383.1
—(1+,/.40-= pW, = + (0.649 x 0.296)) – (0.649 x 36685.9)
r 8.57 '
3948-23809 = - 19861 IN < H (3111.8 kN)
mxM lx 28383.1
–38.3 kN/m3
1 740.8
y(Kp-KA) = 10 x (6.243-0.267) =59.76 kN/m3
mM
As <7(KP-KA) . Hence safe
( -- 0.269x 28383.1 \
36685.9
MB , 8.57 28383.1x 9
a- I =ti pp A- Mr F (o) 6-i' ,<)(( )92')(1))--(■; f ' ;+
, 2'x'740.8
4
=561.3+172.4 = 733.67. kN/m2
W '
62 = r MB –388.8 kN/m2
A 21
/
87
Allowable Soil Pressure = 5.4N2B +16 x 100 + N 2 )D j kg/M2
Qallowable 1(5.4 x 202 x 9)+ (16 x (100 + 202 )x 8)j= 832.24 x 102 kg/m2 =832.24 kN/m2
at and a2 both < Qallowable. Hence Safe
H.Pi
RIVER BED
873
2.Dead Load
2.3 x 1 x 1 x 25 x4 =230
a. Pedestal
7r
—x9 2 xlx 25= 1590.4
b. Well cap
4 -iv
-x 2
5 . )X 21.5x 25=
c. Well steining 4
, , r1
,r, ,c(18996.8 , ,,,(1 ,
LT x 62 x21.5x 23=
d. Sand filling 4 4.
13981.7
e. Cantilever 0.75x1.2 x 5.4 x25 x 4
beam = 486 1
Taking
3. Seismic Force
ax=0.1
on D.L
av=0.1 x 0.5=0.05
a. Pedestal 23 4--- 22 506
11.5
i St).-1;, ',
b. Well cap 159 20.4 3243.6
79.5 ,I,
89
Lever arm Moment
from point (in kNm)
Force (in kN) Direction of rotation
( in m)
C. Well steining (13.5 x18996.8 x 0.1)/21.5 4-- 13.15 15685.3
=1192.8
596.4
D. Sand Filling 13981.7 x 13.5 x 0.1/21.5 i 13.15 11545.7
=878 ie---
439
24.3
3.Water current
on well and well 354.3 4----- 16.06 5690
cap
4.Buoyancy
Ex 92 x 21.5x10x 0.15=
4
2051.7
35501:12
576.66 kN/sq m
A ) flx 92
(W
4
Ultimate bearing capacity of the soil below the base of well:
Qu= Pv(Ncr1)+0.3yBNy
.1 .90
Pv=ysubx Df=10 x 8 =80 kN/ sq m
For SPT value=20 ,N,4=25, Ny=25
Qu=80(25-1)+(0.3 x 10 x 9 x 25) --2587.5kN/sq
- m
Qui2 = 1293.75 kN/m2
(---
w )<(-91-̀) Hence safe
A 2
From IRC: 45-1972
Base resisting moment = Mb = QWB tang
B= dia of well = 9m
Df/B = 8/9 =0.9, 4)=33°
From IRC: 45-1972,table 1
Q=0.6 x 0.442 =0.2652
W= 36685.9 kN
Mb= 0.2652 x 36685.9 x 9 x tan 33 = 56863.3 kNm
Resisting moment due to friction
Mf = 0.11y(Kp-KA)B2D2sin6 =0.11 x 10 x (6.243-0.2671) x 9 2 x 82 x sin 16.5.
=9678 4kNm --
Ms=0.107(1(p-KA)D3L =0.1 x 10 x (6.243-0.2671) x 83 x (0.9 x 9)
=24783.2 kNm
0.7(Mf+Mb+Ms) =63927.5 kNm >M (48334 kNm)
Hence Safe
5. STRUCTURAL DESIGNING
Designing of Cantilever Beam:
Providing thickness of beam as 0.75 m at edge as there is no bending moment and thickness
oir‘ )1/4 , n.
at face of staining is 1.25m for bending moment and development length requirement.
; ) .• ts :111
91
Fig A.3.5 Cross Section of Cantilever Beam
Total dead load of cantilever part
t't ri• •-; • ■ ..;
= (0.75 x 1.2 x 5.4 x 25) + ((1.25-0.75) x 5.4 x 1.2 x 25/2) kN
=121.5+40.5kN=162kN
Point load from each tower = (586.9 x Cos 11.3) = 575.5 kN
The shear force at face of staining = V = 162 + 575.5 kN = 737.5 kN
Bending moment at face of staining = M
M = (121.5 x 2.7) + (40.5 x 5.4 / 3) + (575.5 x 4.8) kNm
= 3163.4 kNm
Putt = 1.5 x 737.5 kN = 1106.25 kN
Mutt = 1.5 x 3163.4 kNm = 4745;1 k1\1m ‘t
0.1379f,kbd2= 4745.1x 106 Nmm
Using M25 grade of concrete and Fe415 grade of steel
4745.1x 106
d — mm =1075 mm
0.137x 25x1200
Considering the requirement of development length we provide total depth D
=1350mm
Providing a clear cover of 75 mm
Dia of bar = 25 mm
Effective depth d = 1350 —100 —12.5 mm =1162.5 mm
‘.
\h
92
Area of steel required Ast
M = 0.87f y il„41
bd f ck)
(AstfY )
(4„ x415) )
4745.1 x 106=0.87x 415x As, x1162.541
1200 x1162.5x 25
Ast = 13462 mm2
For balance section % of steel required .
p= 1.196%
Ast — (1.196 x1162.5x1200) 2
MM
100
= 16684.2 mm2
Providing Ast/2= 0.5 x 16684.2 mm2 = 8342.1 mm2 on each face
Providing 25mmcb (A0=490.87 mm2)
8342.1
No of bars required = — 17 nos
490.87
The shear force at face of staining V = Puit= 1106.25 IN
93
As depth of beam >750 mm, so providing side face reinforcement of 0.1% of cross
sectional area of beam
0.1x1200x(1250+750I
Side face reinforcement = l
l 2 ) —1200mm2
100
lommtiiplA:BARS
1200 MM
94
t:i. ■‘..s1! cap \\ r,m
-taintncr. PrCwidaii<< a nominal IcH . or') i'-'
1•11111111111111MININIEENNEW
1111111111111111111111111111111111•WAIMP
71111110.111111111=11111•%•111W
11•11110.41■111•Miram51.2r 20MMct @ITOMMCrC
- grumlismotwur
- 1p
h= KdVi
Where,
95
h= 0.03 x 911275 = 1.266 m < 1.5m
Table A.3.5 Load Calculation for Staining
Lever
arm
' from
scour Moment
Force (in IN) Direction
level (in kNm)
( in m)
1.Force on
575.5 x 4=2302
Tower
2.Dead Load
2.3 xlx1x25x4=230
a. Pedestal
3.14 x 92x0.25x1.25x25
b. Well cap 1,
=1988 '
Taking
3. Seismic Force- ---i -
I \ '). )
.
oH=0.1
on D.L
ocy=0.1 x 0.5=0.05
96
Lever
arm
from
Force (in kN) Direction Moment
scour
(in kNm)
level
(inm)
99.4
C. Well steining 11928x 0.1= 1192.8 6.75 8051.4
596.4
1r
D. Cant. Beam 680.4x 0.1=68 14 952
.4--
34
Jr
2FH 2 [ 2x 2x 2288.1 2
=4.14m
[
y(K p - K A )B 10(6.243 - 0.2671) x 9
97
2 2
Mmax= M + - x HX = 23175.7 + - x 2288.1x 4.14 = 29490.86 kNm
3 3
7r(92 -62
Additional weight of steining - x 4.14 x 25 =3658 kN
4
x9 2
Buoyancy on this part - x 4.14 x10 x 0.15 = 395 kN
494 - 64j
I- - 258.4 m4
64
, c V , My) = .5 x (19048 ± 32748.16x 9)
f,2=1 ..3
51( - - 1
A I l 35.34 258.4 x 2 )
f1= 1663.4 kN/m2
ff= -46.96 kN/m2
f„=0.45 Tr
. a, =0.45 x 5 = 22501(1\1/m2
98
(6)2
2 2 -
p 12 2
r + r2 +
Maximum hoop stress along outer face= 36.06 ( 2 2
) ) (
r —r22
(.92) — 6
2)
= 93.756 kN/m2=0.093756 N/mm2
As per IRC: 78-2000 clauses 708.35
Minimum vertical reinforcement =0.2% of gross area
0.2x 35.34x106 2 2
1MM = 70680 mm
100
Using 25 mm dia bar (A0=490.8 mm2)
No of bars = 70680/490.8 144
Minimum Ast on inner face =0.06 of gross cross sectional area
0.06x 35.34 x106
-21204 mm2
100
;ni Ci l' (`111 IR (.' 7c:
99
00- 20 x 0.87fy _ 25x 0.87 x 415
La s — 1288.75 mm
4rbd 4x1.25x1.4 4x1.25x1.4
BOND RODS-20MM
8 NOS-2600MM LONG
9000 Mlti
y.
Fig A.3.8 Reinforcement Detail of Well Steining
100
Net vertical weight=
=187.5 kN.
Net Hoop Tension = 6584.9-187.5 kN = 6397.4 kN
Design hoop tension =1.5 x 6397.4 kN = 9596.1 kN
x
Hoop reinforcement = 9596.1 103 — 23123 mm2
415
23123 —
No of 25 min dia bar= 48 Nos
490.8
As per IRC: 78-2000, clause708.7.3
Minimum reinforcement =-72Kg/m3
Arrangement of, i;cinf7orRement is as shown in figure A.3.8
18 7 5 kN
101
1 6MM(i) VERTICAL BAR. EMBEDED IN
CURB,EMBEDED LENGTH NOT LESS
THAN 1000 MM
75MM 1-
12 MM DIA BAR
1200. M
CUTTING EDGE
ANGLE IRON ,150x150x12 MM
Design of bottonniPlug
!S ri
Using I■420 gradei o cpncrete for bottom plug
Thickness of bottom plug=t
92
1 18x— x578.9
1.18r2q _ . 4 —6.9m
t=
woo x 0.45V20
Providing thickness of bottom plug = 3000mm
102
SIB ANGIE rib,A4NINELL
FOUNDATION- TOWER TYPE'C' 5 NOS-25M4 BARS ON EACH
NEHTAUR-METOR LINE FACE(TOTAL 16NOS)
HFl
iNtS
@AMOS
B Rom%
VERT)/ INt92914
BARS 02111U AT EACH IOMM,STIRRUPS(IWO SETS)EACH 00MM CIC PLACED
FAGGOT STININGTOBE lit SET
2nd SET
TORN IXON MOH STIRRUP ALTERNATEDISTANCE BETWEEN 1ST 8, 2ND SET(150MM CIC
TOP RUG STIRRUP
48 NOS -25MM OS
5 MM THICK M.S.SHEET
17 NOS-24 MM BARS
BOTH
CUTTING EDGE AT TOP AND BOTTOM
ANGLE IRON 151(150)(12 MM
;2 10M4-4LEGGED STIRRUPS@250MM
1 CIC
SHIFTING FLAT 400)(12 MM
SECTIONAL ELEVATION AT P P
75MM CLEAR COVER
SECTION OF BEAM AT AA
ILEGGED.10MMISTIRRUPS#200=
17 N09.25MMIIBARS AT
TOP AND BOTTOM