422 fail freeze series

Current to pressure, (I/P) electronic converter

>> Port size: 1/4” >> Minimum vibration


(NPT) effects
>> Advanced electronic >> IP65 environment
control protection
>> Fail freeze operation
(output pressure
retained on
power failure)

Technical features
Medium: Response time: Electromagnetic compatibility: Materials:
Oil free, dry air, filtered to 5 µm <8 sec (typically <3 sec) from Compliant and CE marked Body: zinc diecasting
Output pressure: 10 % ...90 % of output pressure in accordance with the EC Directive passivated and epoxy painted
0,2 ... 1 bar (3 ... 15 psi) into a 0,5 litre volume 2004/108/EC tested to Cover: Glass reinforced nylon
Supply pressure: <8 sec (typically <3 sec) from BS EN 61000-6-2:2005, Diaphragms: NBR
at least 0,7 bar (10 psi) above 90 % ...10 % of output pressure BS EN 61000-6-4:2007
maximum required output pressure into a 0,5 litre volume Ambient/Media Temperature:
maximum 2 bar (29 psi) gauge Temperature sensitivity: -20 ... +70°C (-4 ... +158°F)
Flow capacity: Typically < 0,034 % span/°C Air supply must be dry enough to
Up to 300NL/min between -10°C and +60°C avoid ice formation at temperatures
Air consumption: (+14 and +140 °F) below +2°C (+35°F).
<0,4 Nl/min Supply sensitivity: Maintenance:
Linearity: < 0,1% of span for full supply No user serviable parts
≤0,5 % of span pressure range Mounting position:
Hysteresis: Port sizes: Operation in any orientation is
≤ 0,5 % of span Main ports: 1/4 NPT female possible without recalibration;
Vibration effect: Gauge ports: 1/4 NPT female integral surface mounting bracket
≤0,5 % of span for vibration I.P. Rating: provided for vertical mounting
level up to 3 g, 5 ... 500 Hz IP65
in any orientation.

Technical data
Symbol Output pressure Weight (kg) Model Options to special order:
• Alternative pressure ranges
0,2 ... 1 bar 0,98 AC2100
• Conduit entry (M20 / ½” NPT)
3 ... 15 psi 0,98 AC0100
• 50mm pipe mounting bracket
0,2 ... 1 kg/cm2 0,98 AC138X • Captured Bleed

For other port sizes or options please contact your sales representative.

Electrical parameters
Input Signal 4-20 mA (two wire). Terminal voltage typically 7,5 V at 20 mA
Failure Mode Output pressure held at previous value when input signal fails; drift rate ≤ 0,2 % in 5 minutes
Overload protection 100 mA max. overload current. Unit unaffected by short duration reverse current
Connections 30mm square connector provided (DIN 43650, form A) mountable in 4 directions
Span/Zero Independently adjustable up to 20 % output range

base@basesistemas.com
www.basesistemas.com
976 587 019
Our policy is one of continued research and development. We therefore reserve the right to amend, 05/16
without notice, the specifications given in this document. (2006 - 117i) © 2015 Norgren Ltd. en 6.6.360.01