You are on page 1of 1

7.

0 CALCULATION FOR SHORT TIME WITHSTAND CAPABILITY OF ACSR MOOSE CONDUCTOR:

7.1 INPUT DATA:

Sl. NO DESCRIPTION SYMBOL UNIT VALUE REFERENCE


1. System voltage V kV 220 kV Technical Specification
2. Short Time rating of the system kA 31.5 Technical Specification
3. Conductor Code Name Moose
4. Conductor type ACSR
5. Overall Diameter of the conductor D mm 31.77 Manufacturer Data
6. No. of Strands and Aluminium diameter 54/3.53 Manufacturer Data
Sectional Area of Moose Conductor A sq. mm 520 Manufacturer Data
7. sq. mtr 0.00052
8. Symmetrical Short Circuit Current Isc A 31500 Technical Specification
9. Duration of fault Tfd Sec. 1 Technical Specification
10. Initial Conductor temperature before short circuit Tbf ⁰C 75 Technical Specification
11. Final Conductor temperature before short circuit Taf ⁰C 200 As per IEC 865-1,Table 6
12. Specific conductivity at 20℃ K20 Ω-1m-1 3.48*10^7 As per IEC 865-1,pg no:50
3
13. Density ρ kg/m 2700 As per IEC 865-1,pg no:50
14. Specific heat Capacity C J/(kg K) 910 As per IEC 865-1,pg no:50
15. Temperature co-efficient α20 1/K 0.00403 As per IEC 865-1,pg no:50

7.2 REFERENCES:
• IEC: 865- Short circuit currents-calculation of effects.

7.3 SHORT TIME WITHSTAND CAPABILITY FOR ACSR CONDUCTOR:

𝐾𝑠𝑐=√((𝐾20 𝐶 ρ)/𝛼20 𝑙𝑛[(1+𝛼20 (𝑇𝑎𝑓−20))/(1+𝛼20 (𝑇𝑏𝑓−20) )] )

𝐾𝑠𝑐=√((3.48∗107∗910∗2700)/0.00403 𝑙𝑛[(1+0.00403(200−20))/(1+0.00403(75−20) )]
)
KSC= 85587553.28

Short time withstand current 𝐼𝑆𝐶=(𝐾𝑆𝐶∗𝐴)/√𝑇𝑓𝑑

ISC = 44505.53 A
= 44.51 kA

7.4 RESULT & SUMMARY:-

System Short time Withstand Calculated Short time


Current Withstand Current

31.5kA 44.51 KA

2827252_R0 8 of 97