PROJECT : Design.

by: BCC
DOC.TITLE: Check.by BCC
DOC. NO : Rev:No 0 Appr. by

WIND LOAD CALCULATIONS AS PER EN-1991-1-4


Notes
·         The wind load is applied by using pressure coefficient method.
·         The variation of wind pressure  along the height of building is NOT considered.

Fundamental Value of the Basic wind Velocity vb,0 = 24 m/s Cl. 4.2 - EC1-1-4

Directional Factor cdir = 1.0 Cl. 4.2 - EC1-1-4

Seasonal Factor cseason = 1.0 Cl. 4.2 - EC1-1-4

Basic Wind Velocity vb = 24 m/s Eq. 4.1 - EC1-1-4

Probability Factor for exceedence cprob = 0.95 Eq. 4.1 - EC1-1-4

Height of Structure ( top most point of rafter ) h = 3.0 m

Width of Structure b = 4.0 m

Length of Structure l = 20.0 m

Roughness Factor cr(z) = 0.778

Reference Height z = ze = 3 m Fig. 7.4 - EC1-1-4

Terrain Category = 2 Tab. 4.1 - EC1-1-4

Roughness length z0 = 0.05 m Tab. 4.1 - EC1-1-4

Minimum height zmin = 2 m Tab. 4.1 - EC1-1-4

Maximum height zmax = 200 m Cl. 4.3.2 - EC1-1-4

Terrain Factor kr = 0.190 Eq. 4.5 - EC1-1-4

Orography Factor co(z) = 1.0 Cl. 4.3.3 - EC1-1-4

Mean Wind Velocity vm(z) = 18.7 m/s Eq. 4.3 - EC1-1-4

Turbulence Intensity Iv(z) = 0.243 Eq. 4.7 - EC1-1-4

Trubulence Factor kl = 0.995 Cl. 4.4 - EC1-1-4

Density of Air r = 1.161 kg/m3 Cl. 4.5 - EC1-1-4

Peak Velocity Pressure qp(z) = 546.76 N/mm2 Eq. 4.8 - EC1-1-4

Structural Factor cscd = 1.0 Cl. 6.2 - EC1-1-4

Roof Angle a = 25.0 degrees

Blockage j = 0.00 Tab. 7.6 - EC1-1-4

Positive Overall Force Coeff +cf = 1.00 Tab. 7.6 - EC1-1-4

Negative Overall Force Coeff -cf = -1.60 Tab. 7.6 - EC1-1-4

-Z
Orientation of Module = Potrait
Module dimensions
L B kN No of Purlins kN/m -X +X
-cf -1.60 1.956 0.992 -1.697 2 -0.856
+cf 1.00 1.956 0.992 1.061 2 0.535
+Z