‘Arabian chlor Vingl Company a
Copia bivmat —
‘abst uneg rp) Loy 'gSoly
a
Flow rate : Design 4.6 MMSCFD
Normal (Allocated) 1.8 MMSCFD
Minimum (0.84 MMSCFD
Normal Operating Pressure 340 psig*
‘Minimum Operating Pressure 300 psigh*
Maximum Operating Pressure 385 psig®
Normal Operating Temperature 110
Design Pressure 710 psig, ANSI 300Lb
Reference Base Pressure 14.73 psi
: Design Temperature 150° F
Reference Base Temperature CPF
‘Molecular Weight 18.27 - 21.16
Density 4.22 of
Viscosity 0.013¢P
High Heating Value (HV) 930 BTUISCF minimum
[Hydrogen Sutfide 1 graind100 SCF
Total Sulfur 20 grains/100 SOF
Moisture 7 LbIMMSCF
* Dela from OSPAS via email by third party project coordination engineor (NAPD! NAPED/ PCG)
Dated 20May12
* Saudi Aramco Dry Gas Product Spec, A-120
72 Metering Systems
‘The metering system will be designed and specified to accommodate a range of Seles Gas fow
up fo 4.6 MMSCFD, The metering system will comply with SAES-Y-101, Custody Metering of
Hydrocarbon Gases. Analysis of Sales Gas is not required for BI-21-00047 as this is done by
Saudi Aramco upstream of the Jubail Royal Commission Pipeline Corridor and moreover, this
feature is not required for Small metering systems. Provision for sampling is. provided
downstream of the new custody metering skid per standard installatons shown on Standard PID
AB-039181
‘An Oriice flow meter will be used. Saudi Aramco wil review and approve the Functional
Spectication Document (FSD) and the vendors design for the metering system.
7.3 Piping and Valve Specifications
Piping wil be designed to accommodate the maximum design pressure. The piping will be
designed in accordance with ASME B31.3 and will comply with all relevant Saudi Aramco
standards including SAES--310, Design of Plant Piping, SAES-L-350, Construction of Plant
Piping, SAES-L-132, Material Selection of Piping Systems, and SAES-W.O11, Welding
Jane 2012 Page Sof 15 FLUOR.