Professional Documents
Culture Documents
FUD East Bunati Rev120318
FUD East Bunati Rev120318
Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
CONTENTS
1.1 PLC Hardware General ........................................................................................ 17
1.2 PLC Communication Hardware General ............................................................. 18
1.3 SCADA Hardware General .................................................................................. 20
1.4 SCADA Software General ................................................................................... 21
1.5 Coal Preparation Plant (CPP) PLC ...................................................................... 21
1.5.1 CPP PLC Communications ........................................................................... 22
1.6 CPP Operation Philosophy .................................................................................. 23
1.6.1 Synchronizing Generator ............................................................................. 23
1.6.2 DSE 8610 Synchronous Module................................................................... 24
1.7 1500 TPH Dump Hopper ...................................................................................... 25
1.8 Low Level Switch ................................................................................................ 25
1.9 Chain Feeder ........................................................................................................ 26
1.9.1 Chain Feeder VVVF and Motor .................................................................... 26
1.9.2 Variable Speed Drive ..................................................................................... 26
1.9.3 Hardwire Emergency Stop ............................................................................ 27
1.9.4 Motor temperature .................................................................................... 28
1.10 Chain Feeder Indication & Operation .............. Error! Bookmark not defined.
1.9.5.1 Motor Faceplate Indications ....................... Error! Bookmark not defined.
1.9.5.2 Motor Faceplate Operations........................ Error! Bookmark not defined.
1.9.5.3 Motor Faceplate Statistics Information’s .. Error! Bookmark not defined.
1.9.5.4 Chain Feeder Safety Devices & Faults ....... Error! Bookmark not defined.
1.9.5.5 Local Control Station .................................. Error! Bookmark not defined.
1.9.5.6 Startup Warning Horn ................................. Error! Bookmark not defined.
1.9.5.7 MCCB Main Circuit Breaker Status ......... Error! Bookmark not defined.
1.9.5.8 Chain Feeder Start Permissive .................... Error! Bookmark not defined.
1.9.5.9 Chain Feeder Process Interlocks ................. Error! Bookmark not defined.
1.9.5.10 Chain Feeder Operation ............................ Error! Bookmark not defined.
1.9.5.11 Divergator ................................................................................................. 28
1.9.5.12 Primary Crusher ........................................................................................ 28
1.9.5.13 Primary Crusher SS and Motor ................................................................. 28
1.9.5.14 Primary Crusher Indication & Operation.................................................. 30
1
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
2
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
2.8 Magnet Safety Device & Faults ....................... Error! Bookmark not defined.
2.8.1 Emergency Stop ............................................. Error! Bookmark not defined.
2.8.2 Main Switch ................................................... Error! Bookmark not defined.
2.8.3 Magnet Energized .......................................... Error! Bookmark not defined.
2.8.4 Magnetic Running Feedback Failed .............. Error! Bookmark not defined.
2.8.5 Magnet Start Permissive ................................ Error! Bookmark not defined.
2.8.6 Magnet Process Interlocks ............................. Error! Bookmark not defined.
2.8.7 Magnet Operation .......................................... Error! Bookmark not defined.
2.8.7.1 Magnet Operation Local Mode ................... Error! Bookmark not defined.
2.8.7.2 Magnet Operation Remote Mode ............... Error! Bookmark not defined.
2.8.8 Magnet Cleaning ............................................ Error! Bookmark not defined.
2.9 Secondary Crusher ................................................ Error! Bookmark not defined.
2.9.1 Soft Starter ..................................................... Error! Bookmark not defined.
2.9.2 Hardwire Emergency Stop ............................. Error! Bookmark not defined.
2.9.3 Motor temperature ......................................... Error! Bookmark not defined.
2.9.4 Motor Faceplate Indications .......................... Error! Bookmark not defined.
2.9.5 Motor Faceplate Operations........................... Error! Bookmark not defined.
2.9.6 Motor Faceplate Statistics information .......... Error! Bookmark not defined.
2.10 Secondary Crusher Safety Devices & Faults Error! Bookmark not defined.
2.10.1 Local Control Station ................................... Error! Bookmark not defined.
2.10.2 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
2.10.3 Secondary Crusher Start Permissive ............ Error! Bookmark not defined.
2.10.4 Secondary Crusher Process Interlocks ......... Error! Bookmark not defined.
2.10.5 Secondary Crusher Operation ...................... Error! Bookmark not defined.
2.10.6 Operation Local Mode ................................. Error! Bookmark not defined.
2.10.7 Operation Remote Mode .............................. Error! Bookmark not defined.
3.0 Transfer Conveyor CV-110 .................................................................................. 65
3.1 Transfer Conveyor VVVF and Motor .............................................................. 76
3.2 Hardwire Emergency Stop .................................................................................... 77
3.3 Motor temperature ............................................................................................ 77
3.4 Transfer Conveyor CV-110 Indication & Operation ........................................ 78
3.4.1 Motor Faceplate Indications .......................................................................... 78
3.4.2 Motor Faceplate Operations........................................................................... 79
3.4.3 Motor Faceplate Statistics information .......................................................... 80
3
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
4
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
5
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
6
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
7
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
9.3 Belt Plough 5 Safety Devices & Faults ............ Error! Bookmark not defined.
9.3.1 Local Control Station ..................................... Error! Bookmark not defined.
9.3.2 MCCB Main Circuit Breaker Status .............. Error! Bookmark not defined.
9.3.3 Stockpile Limit Switch (SLS) ........................ Error! Bookmark not defined.
9.3.4 Low Level Switch .......................................... Error! Bookmark not defined.
9.4 The Belt Plough 5 Start Permissive ...................... Error! Bookmark not defined.
9.5 The Belt Plough 5 Process Interlocks .............. Error! Bookmark not defined.
9.6 The Belt Plough 5 Operation............................ Error! Bookmark not defined.
9.6.1 Operation Local Mode ................................... Error! Bookmark not defined.
9.6.2 Operation Remote Mode ................................ Error! Bookmark not defined.
10.0 Transfer Conveyor CV-104 .............................. Error! Bookmark not defined.
10.1 Transfer Conveyor VVVF and Motor .......... Error! Bookmark not defined.
10.2 Hardwire Emergency Stop .................................. Error! Bookmark not defined.
10.3 Motor temperature .............................................. Error! Bookmark not defined.
10.4 Transfer Conveyor CV-104 Indication & Operation ......... Error! Bookmark not
defined.
10.4.1 Motor Faceplate Indications ........................ Error! Bookmark not defined.
10.4.2 Motor Faceplate Operations......................... Error! Bookmark not defined.
10.4.3 Motor Faceplate Statistics information ........ Error! Bookmark not defined.
10.5 Transfer Conveyor CV-104 Safety Devices & Faults . Error! Bookmark not
defined.
10.5.1 Local Control Station ................................... Error! Bookmark not defined.
10.5.2 Pull Wire Switches (PWS) ........................... Error! Bookmark not defined.
10.5.3 Belt Drift Switches (BDS) ........................... Error! Bookmark not defined.
10.5.4 Belt Rip Switch (BRS) ................................. Error! Bookmark not defined.
10.5.5 Take-Up Switch (TUS) ................................ Error! Bookmark not defined.
10.5.6 Under speeds Sensor (USS) ......................... Error! Bookmark not defined.
10.5.7 Startup Warning Horn .................................. Error! Bookmark not defined.
10.5.8 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
10.6 Transfer Conveyor CV-104 Start Permissive Error! Bookmark not defined.
10.7 Transfer Conveyor CV-104 Process Interlocks ........... Error! Bookmark not
defined.
10.8 Transfer Conveyor CV-104 Operation ......... Error! Bookmark not defined.
10.8.1 Operation Local Mode ................................. Error! Bookmark not defined.
10.8.2 Operation Remote Mode .............................. Error! Bookmark not defined.
8
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
9
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
12.3 Belt Plough 7 Safety Devices & Faults ........ Error! Bookmark not defined.
12.3.1 Local Control Station ................................... Error! Bookmark not defined.
12.3.2 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
12.3.3 Stockpile Limit Switch (SLS) ...................... Error! Bookmark not defined.
12.3.4 Low Level Switch ........................................ Error! Bookmark not defined.
12.4 The Belt Plough 7 Start Permissive .............. Error! Bookmark not defined.
12.5 The Belt Plough 7 Process Interlocks ................. Error! Bookmark not defined.
12.6 The Belt Plough 7 Operation .............................. Error! Bookmark not defined.
12.6.1 Operation Local Mode ................................. Error! Bookmark not defined.
12.6.2 Operation Remote Mode .............................. Error! Bookmark not defined.
13.0 Belt Plough 8 .................................................... Error! Bookmark not defined.
13.1 Belt Plough MCC and Motor ....................... Error! Bookmark not defined.
13.1.1 Motor Control Centre................................... Error! Bookmark not defined.
13.1.2 Hardwired Circuit ........................................ Error! Bookmark not defined.
13.1.3 Hardwire Healthy ......................................... Error! Bookmark not defined.
13.1.4 Running ........................................................ Error! Bookmark not defined.
13.1.5 Motor Overload............................................ Error! Bookmark not defined.
13.1.6 Earth Leakage .............................................. Error! Bookmark not defined.
13.1.7 MCC Main Circuit Breaker Status ............... Error! Bookmark not defined.
13.2 Belt Plough 8 Indication & Operation ................ Error! Bookmark not defined.
13.2.1 Motor Faceplate Indications ........................ Error! Bookmark not defined.
13.2.2 Motor Faceplate Operations......................... Error! Bookmark not defined.
13.3 Belt Plough 8 Safety Devices & Faults ........ Error! Bookmark not defined.
13.3.1 Local Control Station ................................... Error! Bookmark not defined.
13.3.2 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
13.3.3 Stockpile Limit Switch (SLS) ...................... Error! Bookmark not defined.
13.3.4 Low Level Switch ........................................ Error! Bookmark not defined.
13.4 The Belt Plough 8 Start Permissive .............. Error! Bookmark not defined.
13.5 The Belt Plough 8 Process Interlocks ........... Error! Bookmark not defined.
13.6 The Belt Plough 8 Operation .............................. Error! Bookmark not defined.
13.6.1 Operation Local Mode ................................. Error! Bookmark not defined.
13.6.2 Operation Remote Mode .............................. Error! Bookmark not defined.
14.0 Belt Plough 9 .................................................... Error! Bookmark not defined.
14.1 Belt Plough MCC and Motor .............................. Error! Bookmark not defined.
10
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
11
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
15.2.6 The Slide gate 1 Operation .......................... Error! Bookmark not defined.
16.0 Drawdown Hopper 2 ........................................ Error! Bookmark not defined.
16.1 Vibrator Bin 2 ............................................... Error! Bookmark not defined.
16.1.1 Vibrator Bin MCC and Motor ...................... Error! Bookmark not defined.
16.1.2 Vibrator Bin 2 Indication & Operation ........ Error! Bookmark not defined.
16.1.3 Vibrator Bin 2 Safety Devices & Faults ...... Error! Bookmark not defined.
16.1.4 The Vibrator Bin 2 Start Permissive ............ Error! Bookmark not defined.
16.1.5 The Vibrator Bin 2 Process Interlocks ......... Error! Bookmark not defined.
16.1.6 The Vibrator Bin 2 Operation ...................... Error! Bookmark not defined.
16.2 Slide gate 2 ................................................... Error! Bookmark not defined.
16.2.1 Slide gate MCC and Motor .......................... Error! Bookmark not defined.
16.2.2 Slide gate 2 Indication & Operation ............ Error! Bookmark not defined.
16.2.3 Slide gate 2 Safety Devices & Faults........... Error! Bookmark not defined.
16.2.4 The Slide gate 2 Start Permissive ................ Error! Bookmark not defined.
16.2.5 The Slide gate 2 Process Interlocks ............. Error! Bookmark not defined.
16.2.6 The Slide gate 2 Operation .......................... Error! Bookmark not defined.
17.0 Drawdown Hopper 3 ........................................ Error! Bookmark not defined.
17.1 Vibrator Bin 3 ............................................... Error! Bookmark not defined.
17.1.1 Vibrator Bin MCC and Motor ...................... Error! Bookmark not defined.
17.1.2 Vibrator Bin 3 Indication & Operation ........ Error! Bookmark not defined.
17.1.3 Vibrator Bin 3 Safety Devices & Faults ...... Error! Bookmark not defined.
17.1.4 The Vibrator Bin 3 Start Permissive ............ Error! Bookmark not defined.
17.1.5 The Vibrator Bin 3 Process Interlocks ......... Error! Bookmark not defined.
17.1.6 The Vibrator Bin 3 Operation ...................... Error! Bookmark not defined.
17.2 Slide Gate 3 .................................................. Error! Bookmark not defined.
17.2.1 Slide gate MCC and Motor .......................... Error! Bookmark not defined.
17.2.2 Slide gate 3 Indication & Operation ............ Error! Bookmark not defined.
17.2.3 Slide gate 3 Safety Devices & Faults........... Error! Bookmark not defined.
17.2.4 The Slide gate 3 Start Permissive ................ Error! Bookmark not defined.
17.2.5 The Slide gate 3 Process Interlocks ............. Error! Bookmark not defined.
17.2.6 The Slide gate 3 Operation .......................... Error! Bookmark not defined.
18.0 Drawdown Hopper 4 ........................................ Error! Bookmark not defined.
18.1 Vibrator Bin 4 ............................................... Error! Bookmark not defined.
18.1.1 Vibrator Bin MCC and Motor ...................... Error! Bookmark not defined.
12
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
18.1.2 Vibrator Bin 4 Indication & Operation ........ Error! Bookmark not defined.
18.1.3 Vibrator Bin 4 Safety Devices & Faults ...... Error! Bookmark not defined.
18.1.4 The Vibrator Bin 4 Start Permissive ............ Error! Bookmark not defined.
18.1.5 The Vibrator Bin 4 Process Interlocks ......... Error! Bookmark not defined.
18.1.6 The Vibrator Bin 4 Operation ...................... Error! Bookmark not defined.
18.2 Slide gate 4 ................................................... Error! Bookmark not defined.
18.2.1 Slide gate MCC and Motor .......................... Error! Bookmark not defined.
18.2.2 Slide gate 4 Indication & Operation ............ Error! Bookmark not defined.
18.2.3 Slide gate 4 Safety Devices & Faults........... Error! Bookmark not defined.
18.2.4 The Slide gate 4 Start Permissive ................ Error! Bookmark not defined.
18.2.5 The Slide gate 4 Process Interlocks ............. Error! Bookmark not defined.
18.2.6 The Slide gate 4 Operation .......................... Error! Bookmark not defined.
19.0 Reclaimer Conveyor CV-105 ........................... Error! Bookmark not defined.
19.1 Reclaimer Conveyor VVVF and Motor ....... Error! Bookmark not defined.
19.2 Hardwire Emergency Stop............................ Error! Bookmark not defined.
19.3 Motor temperature ........................................ Error! Bookmark not defined.
19.4 Reclaimer Conveyor CV-105 Indication & Operation Error! Bookmark not
defined.
19.4.1 Motor Faceplate Indications ........................ Error! Bookmark not defined.
19.4.2 Motor Faceplate Operations......................... Error! Bookmark not defined.
19.5 Motor Faceplate Statistics information......... Error! Bookmark not defined.
19.6 Reclaimer Conveyor CV-105 Safety Devices & Faults ..... Error! Bookmark
not defined.
19.6.1 Local Control Station ................................... Error! Bookmark not defined.
19.6.2 Pull Wire Switches (PWS) ........................... Error! Bookmark not defined.
19.6.3 Belt Drift Switches (BDS) ........................... Error! Bookmark not defined.
19.6.4 Blocked Chute Switches (BCS) ................... Error! Bookmark not defined.
19.6.5 Belt Rip Switch (BRS) ................................. Error! Bookmark not defined.
19.6.6 Take-Up Switch (TUS) ................................ Error! Bookmark not defined.
19.6.7 Under speeds Sensor (USS) ......................... Error! Bookmark not defined.
19.6.8 Start Up Warning Horn ................................ Error! Bookmark not defined.
19.6.9 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
19.7 Reclaimer Conveyor CV-105 Start Permissive .......... Error! Bookmark not
defined.
19.8 Reclaimer Conveyor CV-105 Process Interlocks ........ Error! Bookmark not
13
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
defined.
19.9 Reclaimer Conveyor CV-105 Operation ...... Error! Bookmark not defined.
19.9.1 Operation Local Mode ................................. Error! Bookmark not defined.
19.9.2 Operation Remote Mode .............................. Error! Bookmark not defined.
19.10 Conveyor Coal Flow Monitoring ................. Error! Bookmark not defined.
20.0 Reclaimer Conveyor CV-106 ........................... Error! Bookmark not defined.
20.1 Reclaimer Conveyor VVVF and Motor ....... Error! Bookmark not defined.
20.2 Hardwire Emergency Stop............................ Error! Bookmark not defined.
20.3 Motor temperature ........................................ Error! Bookmark not defined.
20.4 Reclaimer Conveyor CV-106 Indication & Operation Error! Bookmark not
defined.
20.4.1 Motor Faceplate Indications ........................ Error! Bookmark not defined.
20.4.2 Motor Faceplate Operations......................... Error! Bookmark not defined.
20.5 Motor Faceplate Statistics information......... Error! Bookmark not defined.
20.6 Reclaimer Conveyor CV-106 Safety Devices & Faults ..... Error! Bookmark
not defined.
20.6.1 Local Control Station ................................... Error! Bookmark not defined.
20.6.2 Pull Wire Switches (PWS) ........................... Error! Bookmark not defined.
20.6.3 Belt Drift Switches (BDS) ........................... Error! Bookmark not defined.
20.6.4 Blocked Chute Switches (BCS) ................... Error! Bookmark not defined.
20.6.5 Belt Rip Switch (BRS) ................................. Error! Bookmark not defined.
20.6.6 Take-Up Switch (TUS) ................................ Error! Bookmark not defined.
20.6.7 Under speeds Sensor (USS) ......................... Error! Bookmark not defined.
20.6.8 Start Up Warning Horn ................................ Error! Bookmark not defined.
20.6.9 MCCB Main Circuit Breaker Status ............ Error! Bookmark not defined.
20.7 Reclaimer Conveyor CV-106 Start Permissive ........... Error! Bookmark not
defined.
20.8 Reclaimer Conveyor CV-106 Process Interlocks ........ Error! Bookmark not
defined.
20.9 Reclaimer Conveyor CV-106 Operation ...... Error! Bookmark not defined.
20.9.1 Operation Local Mode ..................................... Error! Bookmark not defined.
20.9.2 Operation Remote Mode .............................. Error! Bookmark not defined.
20.10 Conveyor Coal Flow Monitoring ................. Error! Bookmark not defined.
21.0 Bypass Conveyor CV-107 ............................... Error! Bookmark not defined.
21.1 Bypass Conveyor VVVF and Motor ............ Error! Bookmark not defined.
14
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
15
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
21.18 Magnetic Running Feedback Failed ................. Error! Bookmark not defined.
21.19 Magnet Start Permissive ................................... Error! Bookmark not defined.
21.20 Magnet Process Interlocks ................................ Error! Bookmark not defined.
21.21 Magnet Operation ............................................. Error! Bookmark not defined.
21.21.1 Magnet Operation Local Mode .................. Error! Bookmark not defined.
21.21.2 Magnet Operation Remote Mode .............. Error! Bookmark not defined.
21.22 Magnet Cleaning ............................................... Error! Bookmark not defined.
22.0 Diverter Gate CV-107 .................................................................................... 108
22.1 Diverter Gate MCC and Motor................................................................... 108
22.1.1 Motor Control Centre................................................................................. 108
22.1.2 Hardwired Circuit ...................................................................................... 108
22.1.3 Hardwire Healthy ....................................................................................... 108
22.1.4 Running ...................................................................................................... 109
22.1.5 Motor Overload.......................................................................................... 109
22.1.6 Earth Leakage ............................................................................................ 109
22.1.7 MCC Main Circuit Breaker Status ............................................................. 110
22.2 Diverter Gate CV-107 Indication & Operation .......................................... 111
22.2.1 Motor Faceplate Indications ...................................................................... 111
22.2.2 Motor Faceplate Operations....................................................................... 111
22.3 Motor Faceplate Statistics information......... Error! Bookmark not defined.
22.4 Diverter Gate CV-107 Safety Devices & Faults ......................................... 112
22.4.1 Local Control Station ................................................................................. 112
22.4.2 MCCB Main Circuit Breaker Status .......................................................... 113
22.4.3 Position Switch .......................................................................................... 114
22.5 The Diverter Gate CV-107 Start Permissive .............................................. 114
22.6 The Diverter Gate CV-107 Process Interlocks ........................................... 115
22.7 The Diverter Gate CV-107 Operation ........................................................ 115
22.7.1 Operation Local Mode ............................................................................... 115
22.7.2 Operation Remote Mode ............................................................................ 116
22.7.3 Auto Coal Sampler ....................................... Error! Bookmark not defined.
22.8 Sample Plant Operation ................................ Error! Bookmark not defined.
22.8.1 Sample Plant Auto Mode (Remote) ............. Error! Bookmark not defined.
22.8.2 Sample Plant Local Mode ............................ Error! Bookmark not defined.
22.8.3 Sample Plant Manual Mode ......................... Error! Bookmark not defined.
16
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
22.8.4 Sample Plant off (Local or Remote) ............ Error! Bookmark not defined.
22.8.5 Sample Plant Auto (Local) ........................... Error! Bookmark not defined.
22.8.6 Sample Plant Auto Start ............................... Error! Bookmark not defined.
22.8.7 Sample Plant Auto Stop ............................... Error! Bookmark not defined.
22.8.8 Sample Plant Communications .................... Error! Bookmark not defined.
22.8.9 Sampler Process Interlocks .......................... Error! Bookmark not defined.
22.9 Dust Suppression .......................................... Error! Bookmark not defined.
22.10 Solenoid Faceplate Indication ........................... Error! Bookmark not defined.
22.11 Solenoid Faceplate Operations ......................... Error! Bookmark not defined.
23.0 Vvvf Warning & Fault Codes......................................................................... 117
1.0 General System Configuration
The entire plant Control System Consists of Siemens S7-1500 PLC
Hardware controlled With SIMATIC WinCC Professional Siemens offers a SCADA
system which is perfectly integrated in the WinCC Professional Siemens and with
which you are optimally prepared today for the requirements of the increasing
digitalization of production processes.
SIMATIC WinCC Runtime Professional is a PC-based operator control and
monitoring system for visualization and operator control of processes, production flows,
machines and plants in all sectors – from the simple single-user station through to
distributed multi-user systems and cross-location solutions with web clients.
All PLC Hardware used for the Coal Preparation Plant (CPP) East Bunati
Project will be Siemens S7-1500 Modular type with details as follows,
Power Supply – 1 ea. - Simatic S7-1500, System Power Supply Ps 60w 120/230v
Ac/Dc, Supplies the Operating Voltage for the S7-1500 via the Backplane Bus.
(6ES7507-0RA00-0AB0).
Simatic S7-1500 – 1 ea. CPU 1516-3 PN/DP, Central Processing Unit With working,
Memory 1 Mb For Program And 5 Mb For Data, 1. Interface: Profinet Irt with 2 Port
Switch, 2. Interface: Profinet RT, 3. Interface: PROFIBUS, 10 Ns Bit-Performance,
Simatic Memory Card Necessary. (6ES7516-3AN01-0AB0).
Simatic S7, Memory Card – 1 ea. For S7-1500 CPU/SINAMICS, 3.3 V Flash, 4
17
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
MByte. (6ES7954-8LC02-0AA0).
Communication Module – 1 ea. – Simatic S7-1500, Cm PTP RS422/485 HF
Communication Module For Serial Connection Rs 422, Rs 485, Freeport, 3964(R), Uss,
Modbus Rtu Master, Slave,- 1 ea. 115200 Kbit/S, 15-Pin Sub-D Female Connector
(6ES7541-1AB00-0AB0).
Digital Input Modules - 21 ea – Simatic S7-1500, Digital Input Module Di 32xdc 24v
Hf, 32 Channels In Groups Of 16; Input Delay 0.05, 20 Ms; Input Type 3 (IEC 61131);
diagnosis, Process alarms. (6ES7521-1BL00-0AB0).
Digital Output Modules – 4 ea – Simatic S7-1500, Digital Output Module Dq 32 X
24v Dc/0.5a Hf; 32 Channels In Groups Of 8, 4 A Per Group; Single-Channel
Diagnosis; Substitute Value.(6ES7522-1BL01-0AB0).
Analogue Input Modules – 2 ea – Simatic S7-1500, Analog Input Module Ai 8 X U/I
Hs, 16 Bits Of Resolution, Accuracy 0.3 %; 8 Channels In Groups Of 8; Common Mode
Voltage Appr. 10v; Diagnosis, Process alarms; 8 Channels in 0.0625 Ms
Oversampling Incl. Infeed Element, Shield Clamp and Shield Terminal. (6ES7531-
7NF10-0AB0).
Analogue Output Modules – 2 ea – Simatic S7-1500, Analog Output Module Aq 8 X
U/I Hs 16 Bits Of Resolution, Accuracy 0.3 %, 8channels In Groups Of 8, Diagnosis,
Substitute Value 8 Channels In 0.125 Ms Incl. Infeed Element, Oversampling Shield
Clamp And Shield Terminal.(6ES7532-5HF00-0AB0).
Simatic S7-1500, MOUNTING RAIL – 1 ea - 830 Mm (APPR. 32,7 Inch); Incl.
Grounding Element, Integrated Din Rail For Mounting Of Small Components Such As
Clamps, Fuses Or Relays.(6ES7590-1AJ30-0AA0).
Simatic S7-1500 - 18 ea - FRONT CONNECTOR SCREW-TYPE, 40pin, For 35mm
Wide Modules, Incl. 4 Jumpers, And Cable Strap( 6ES7592-1AM00-0XB0 ).
18
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
19
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
PLC Processor communication The Existing PLC Schneider for control BLC
CV-14 and CV-22 communications will be Fiber Cabled depending on the transmission
distance.
Industrial Ethernet switches equipment will be use Siemens Scalance X204-
2LD, managed IE Switch, 4x10/100 Mbit/s RJ45 Ports, 2x100.
The Coal Preparation Plant (CPP) East Bunati Project SCADA system will be a
server and client system for monitoring and operation of the East Bunati Plant.
A new full sized IT Cabinet will be installed in the Coal Preparation Plant (CPP)
Control Room which will house rack mounted hardware as follows,
Description for server computer is listed below:
Dell Power Edge R530 Server
Intel Xeon E5-2620v4 2.1GHz 20M Cache.
Redundant Power Supply 750W hot plug.
8GB+16GB RDIMM 2400MT/s.
DVD+/-RW.
Hardisk 3.5” Rack is available up to 8 Slot.
1Gigabit Ethernet 2 Port Tower x 2 Port Rack.
Description for client computer is listed below:
Dell OptiPlex 5050
Intel Core i5-7500TM 3.4GHz 4 core 6MB Smart Cache.
8+8GB Ram DDR4 2400 MHz
20
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
DVD+/-RW.
Integrated Gigabit Ethernet Speaker.
Dell E2417H Wide Screen LED Monitor 24” Monitor.
The Operator will be facilitated with 24” Wide Screen Samsung Monitors,
keyboards, and mouse which will be connected to the Display Client Computers
installed in the Coal Preparation Plant (CPP) Control Room.
A Hewlett Packard A4 Color Laser printer will be installed on the CPP Control
Room and connected to the USB port in the PC Operator Workstation.
21
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
00. Genset.
00. Dump Hopper
Sensor Low Level Dump Hopper when the level of BB at DH < 10%, then
chain feeder will die and will run auto when BB level at DH reach > 35%.
1. Chain Feeder DH-108.
2. Diverter Gate DH-108.
2. Primary Crusher.
3. Transfer Conveyor CV-109.
4. Magnet Separator CV-109.
5. Belt Scale CV-109.
5. Metal Detector CV-109.
6. Transfer Conveyor CV-110.
7. Diverter Gate CV-110.
8. Secondary Crusher.
9. Transfer Conveyor CV-111.
30. Dust Suppression – Dust Suppression Solenoid Valves at the head end of
conveyor.
31. Communications PLC with Plant Existing.
1.5.1.1 PROFIBUS DP
Siemens PROFIBUS DP communications is used for PLC to Remote
or monitoring Device Communications. PROFIBUS DP communications
of the CPP PLC S7-1500 1516-3 PN/DP CPU is connected to CPP MCC
all VSD, All Soft start, and Coal Sampler.
22
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
All read and write information and commands between PLC and all
VSD, All Soft start, Coal Sampler will be over the PROFIBUS DP
network.
23
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
24
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
25
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Hopper to receive the discharge from the coal handling Trucks with Capacity
1500 tph.
Chain Feeder is used to transport coal from the Dump Hopper to the Divergator
and Chain Feeder is controlled by Siemens SINAMICS G120 VVVF Drive. The VVVF
will control the speed of the Chain Feeder as selected by the CPP Control Room
Operator which will regulate the Coal transport onto the Divergator.
Status Information from the VVVF to the PLC will consist of the
following;
26
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Chain Feeder VVVF Fault Code. This will contain all available VVVF
fault information. (VVVF Fault codes will be described in more detail
later in this document).
Chain Feeder VVVF Warning Code. This will contain all the available
VVVF warning information. (VVVF Warning codes will be described in
more detail later in this document).
Chain Feeder VVVF Running Status.
Chain Feeder Actual Motor Current.
A VVVF Warning will not prevent the drive from starting, nor stop the
drive when running. The warning is for Operator Information and
investigation.
A VVVF Fault will prevent the drive from starting and will stop the drive
if it is running. Commands from the CPP Control System to the VVVF
will consist of the following;
Chain Feeder VVVF Start / Stop commands.
Chain Feeder VVVF Speed Adjustment, control speed chain feeder for
remote mode: speed VSD will reduce to 0% if hopper level sensor shows
value <10%. And when the hopper level > 35% then the VSD speed will
return to normal like the previous set point speed. This control functions
as a protection chain feeder so as not to fall directly to the coal.
Chain Feeder VVVF Fault Reset.
27
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Chain Feeder Run Command via the PROFIBUS network to the VVVF
drive is removed.
Chain Feeder fault condition shall be displayed and alarmed on the CPP
SCADA system.
The Chain Feeder Motor is equipped with two Motor Thermistors, one
for motor high temperature alarm, and the other for motor over
temperature trip. The Thermistors are connected to the VVVF which will
control motor over temperature protection. Motor Temperature alarm and
trip information is relayed to the CPP SCADA system over the PROFIBUS
network. VVVF Drive Fault and Warning codes will be described in more
detail later in this document.
28
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Status Information from the Soft start to the PLC will consist of the
following;
Primary Crusher SOFTSTART Fault Code. This will contain all
available SOFTSTART fault information. (SOFTSTART Fault codes
will be described in more detail later in this document).
Primary Crusher SOFTSTART Warning Code. This will contain all
the available SOFTSTART warning information. (SOFTSTART
Warning codes will be described in more detail later in this document).
Primary Crusher SOFTSTART Running Status.
Primary Crusher Actual Motor Current.
A SOFTSTART Warning will not prevent the drive from starting, nor
stop the drive when running. The warning is for Operator Information
and investigation.
A SOFTSTART Fault will prevent the drive from starting and will stop
the drive if it is running. Commands from the CPP Control System to the
SOFTSTART will consist of the following;
Primary Crusher SOFTSTART Start / Stop commands.
Secondary Crusher SOFTSTART Forward Commands for remote,
reverse motor crusher only use can do if in mode Local (maintenance)
and Running from LCS.
Primary Crusher SOFTSTART Fault Reset.
29
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
30
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Condition.
Primary Crusher Soft start Fault Code. Soft start No Fault (White Text)
/ cult Code (White Alpha Numeric Code) – Indicates when there is an
active fault code from the Soft start.
Manual Mode Select Button. The Manual Mode Select Button will
switch the Primary Crusher Control to manual start made by the
SCADA user. The Primary Crusher control can only be selected to
Manual Mode with this push button which will allow operation of the
Primary Crusher from the Local Control Station Start push button.
Local Mode Select push button will become disabled when the
31
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
equipment is running.
Start push button. The Primary Crusher can be started with this button
providing the drive is selected to Remote Operating Mode and the
Drive is ready.
Stop push button. The Primary Crusher can be stopped at any time with
this button regardless of operating mode.
Reset push button. Used to reset The Primary Crusher Faults, Soft start
Faults and Warnings. The Reset function will be held on within the
PLC Code for two seconds.
More Button. Pressing the Status Display Button will expand the
Motor Faceplate and present the operator with Fault, Warning,
Interlock and Drive Statistic information about the Primary Crusher.
32
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
room SCADA.
The Local Control Station is equipped with a Start push button. The
push button is activated when pressed and deactivated (spring return) on
release. The push button is equipped with a normally open contact which
relays the local start request to a Material Handling MCC PLC input.
33
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Which need to be turned off is the chain feeder, crusher still running
only when tilt switch is active. Because when the crusher died then it
was built up in divergator.
If the Blocked Chute input returns to its healthy state before two
seconds has expired, no action will be taken.
A blocked Chute Switch will not return to its healthy state until the
blockage has been cleared.
34
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Primary Crusher can start in remote mode if all safety device and
emergency stop de -energize. (Status Healthy and ready). Equipment in
front of is running CV-109.
35
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will
be reset again automatically whenever the equipment is started again in
any mode.
The operator will use the indications and controls explained previously to
monitor and operate the Primary Crusher as follows;
For all equipment requiring local mode operation, local operation can
only be done when SCADA is localized.
When LOCAL mode, then equipment can only be start from LCS in
field. LCS→ Start Button : Active
Stop Button : Active
(E-stop remains active)
SCADA→ Start Button : Active
Stop button : Active
(E-stop remains active)
36
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When REMOTE mode, then equipment can only be start from SCADA
in field. LCS → Start Button : Not Active
Stop Button : Not Active
(E-stop remains active)
SCADA→ Start Button: Active
Stop Button : Active
All events & alarms are logged in SCADA.
All horn warning must stay alive during starting motor, either local
mode or remote mode.
The Local Start push button on the Local Control Station is activated.
The Primary Crusher will start at the Local Speed Set point as selected
on the SCADA screen when logged in as Engineer.
37
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
SCADA cannot be switched to local mode. But if the equipment has been
left in local mode, then the SCADA selectors can be switched to remote
mode (with attention to permissive start and interlocking it;
The WinCC SCADA operator will start the using the Start Button on
the CPP WinCC Primary Crusher Faceplate.
Primary Crusher will start and the speed will be controlled to maintain
the production set point as set on the Face Plate. The Automatic
operation of CPP Primary Crusher will be described in more detail later
in this document.
The can be stopped by any hardwired interlock, any Safety Device, any
Start Permissive, any Process Interlock, any Sequential Stop or the
Stop Button on the CPP WinCC Primary Crusher Faceplate.
Transfer Conveyor CV-109 is used to transport the Coal from Primary Crusher
On to Secondary Crusher this Conveyor is controlled by Siemens SINAMICS G120
VVVF Drive. The VVVF will control the speed of the Conveyor as selected by the CPP
Control Room Operator.
38
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Status Information from the VVVF to the PLC will consist of the
following;
Transfer Conveyor CV-109 VVVF Fault Code. This will contain all
available VVVF fault information. (VVVF Fault codes will be described
in more detail later in this document).
Transfer Conveyor CV-109 VVVF Warning Code. This will contain all
the available VVVF warning information. (VVVF Warning codes will be
described in more detail later in this document).
Transfer Conveyor CV-109 VVVF Running Status.
Transfer Conveyor CV-109 Actual Motor Current.
A VVVF Warning will not prevent the drive from starting, nor stop the
drive when running. The warning is for Operator Information and investigation.
A VVVF Fault will prevent the drive from starting and will stop the drive
if it is running. Commands from the CPP Control System to the VVVF will
consist of the following;
Transfer Conveyor CV-109 VVVF Start / Stop commands.
Transfer Conveyor CV-109 VVVF Speed Adjustment.
Transfer Conveyor CV-109 VVVF Fault Reset.
39
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
mode when any Transfer Conveyor CV-109 Hardwire Healthy input is de-
energized the following action will occur;
The Motor Faceplate will present the SCADA user with the following
status indications, all alarms, events, warnings from plant equipment must
be logged on WinCC;
40
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Auto Mode Select Button. The Auto Mode Button will switch the
Transfer Conveyor CV-109 Control to Automatic and the speed will be
controlled by the PLC Chain Control can only be de-selected from
Automatic Mode when the SCADA user is logged in as engineer.
Manual Mode Select Button. The Manual Mode Select Button will
switch the Transfer Conveyor CV-109 Control to manual speed control
with speed adjustments made by the SCADA user. The Transfer
Conveyor CV-109 Control can only be selected to Manual Mode when
the SCADA user is logged in as engineer.
41
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Manual Speed Adjust. A Bar Controller and a text box are provided to
the SCADA user for the purpose of speed adjustment of Transfer
Conveyor CV-109in manual mode. The user can adjust the slide bar from
left to right for 0-100% speed adjustment. A numeric display of the speed
adjustment will also be provided which will display the requested speed
from 0-100%. It will only be possible for the SCADA user to manually
adjust Transfer Conveyor CV-109 speed using the slide bar or input a
numeric value with a keyboard when the SCADA user is logged in as
engineer.
Local Mode Select Button. The operator can select Local Mode with this
push button which will allow operation of the Transfer Conveyor CV-109
from the Local Control Station Start push button. Local Mode Select
push button will become disabled when the equipment is running.
Start push button. The Transfer Conveyor CV-109 can be started with
this button providing the drive is selected to Remote Operating Mode
and the Drive is ready.
Reset push button. Used to reset The Transfer Conveyor CV-109 Faults,
VVVF Faults and Warnings. The Reset function will be held on within
the PLC Code for two seconds.
More Button. Pressing the Status Display Button will expand the Motor
Faceplate and present the operator with Fault, Warning, Interlock and
42
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Motor Run Hours this Shift. Shows current accumulated Run Hours
(White Numeric) in Hours and Minutes for The Transfer Conveyor
CV-109this shift.
Motor Run Hours last Shift. Shows total accumulated Run Hours
(White Numeric) in Hours and Minutes for The Transfer Conveyor CV-
101 for the previous shift.
Motor Run Hours Total. Shows total accumulated Run Hours (White
Numeric) in Hours and Minutes for The Transfer Conveyor CV-109since
reset. A reset button will be provided to users with Engineer Login and
above.
43
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Average Flow Rate (Gross) this Shift. This will indicate the average
gross flow rate for the current shift. This will be calculated as follows,
Gross Average Flow Rate = Current Production Tones / Current time
expired from the shift period.
Average Flow Rate (Gross) last Shift. This will indicate the average
gross flow rate for the previous shift. This will be calculated as follows,
Gross Average Flow Rate = Total Production Tones last Shift / Total Shift
period last shift.
Average Flow Rate (Net) this Shift. This will indicate the average net
flow rate for the current shift. This will be calculated as follows, Net
Average Flow Rate = Current Production Tones / Current Utilized Run
Hours expired from the shift period.
Average Flow Rate (Net) last Shift. This will indicate the average net
flow rate for the previous shift. This will be calculated as follows, Net
Average Flow Rate = Total Production Tones last shift / Total Utilized
Run Hours from the previous shift.
Motor speed Transfer Conveyor CV-109 3.3 m/s; motor speed Transfer
Conveyor CV-110 3.3 m/s; motor speed Transfer Conveyor CV-111 3.3
m/s.
A Fault condition will prevent the plant equipment from starting and will
stop the plant equipment when running. The Transfer Conveyor CV-109 is
equipped with the following field devices;
44
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Local Control Station is equipped with a Start push button. The push
button is activated when pressed and deactivated (spring return) on release.
The push button is equipped with a normally open contact which relays the
local start request to a MCC PLC input.
A Pull wire Switch is still works in mode local remote, installed on either
side of the Transfer Conveyor CV-109 Each Pull wire Switch is equipped
with two normally closed contacts and one normally open contact. One of
the normally closed contacts are used in the hardwired circuit explained
previously, the other normally closed contacts are used for display and
45
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The normally open contact of the pull wire switches will close when in
its tripped state and will energize an indicating strobe light. The strobe will
extinguish when the pull wire is reset.
Belt Drift Switches are installed in carry return conveyor head tail. So
every conveyor there is 8 BDS. The Belt Drift switches are sprung loaded
roller arms that will be activated when the conveyor belt misaligns. Each
Belt Drift Switch is equipped with a normally closed contact connected
individually to Material Handling MCC PLC inputs as follows,
46
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When any Transfer Conveyor CV-109 Belt Drift Switch PLC input is
de-energized for more than five seconds continuously when the Transfer
Conveyor CV-109 is running in remote operating mode, the following
action will take place, to belt drive, please add warning before BDS text
conveyor, because in the BDS there are 2 contacts, 1 for Warning, 1 Her To
Trip;
If the Belt Drift Switch input returns to its healthy state before five
seconds has expired, no action will be taken.
If the equipment has stopped with the Belt Misaligned and the Belt Drift
switch still activated, the equipment must be placed into Local Operating
Mode and the Belt started from the Local Control Station. Once the belt
has run back into position, Remote operation from the CPP WinCC
SCADA may be restored.
47
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
positions within the chute to detect coal build-up within the chute
originating from the bottom of the chute upwards and originating midway
in the chute. Each Blocked Chute switch is connected individually to
Material Handling MCPPLC inputs as follows,
When the either of the normally closed contacts of the Blocked Chute
switches (Level tech Tilt Switch) is broken for more than two seconds
continuously when running in remote operating mode, the following action
will take place;
If the Blocked Chute input returns to its healthy state before two seconds
has expired, no action will be taken.
A blocked Chute Switch will not return to its healthy state until the
blockage has been cleared.
A Belt Rip Switch is installed at the tail end of the Transfer Conveyor
CV-109 and is installed to monitor the condition of the underside of the
carry belt. The Belt Rip Switch has a tensioned lanyard monitoring line
installed under the carry side of the belt which follows the contour of the
48
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
belt profile. When the Lanyard is connected to the switch body the internal
contact becomes healthy (closed). If running in Remote Operating Mode,
when a foreign object pierces the belt and hits the Belt Rip Lanyard it is
disconnects from the switch body. The switch contact connected to
Material Handling MCC PLC Input de-energized and the following actions
occur immediately;
The Belt Rip input will not become healthy again until the Belt Rip
Switch lanyard is again securely attached to the Belt Rip switch body.
The Trolley Upper & Lower Ultimate Limit Switches are mechanically
operated switches with a level arm that is activated when in contact with
the take-up trolley. When either Take-Up Ultimate upper or lower Limit
Input is de-energized with the Transfer Conveyor CV-109 running in
remote operating mode, the following action will take place;
49
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The PLC will calculate the tail pulley speed which will be displayed on
the CPP WinCC SCADA in meters/second.
The PLC will compare the measured tail pulley speed against the
requested speed command to the Transfer Conveyor CV-109. When
running in Remote Operating Mode, and the requested speed and actual
speed differ more than 15% for a continuous period greater than five
second the following actions will occur;
50
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The under speed trip fault will be matched by the PLC and will be reset
by pressing the reset button provided on the faceplate.
The PLC will ignore the Tail Pulley Speed for a period of ten seconds
during start-up allowing the equipment time to reach full speed.
If the speed difference falls below 15% before the five second delay has
expired, no action will be taken.
Using the pulse signal to the PLC from the under speed sensor connected
to the CPP Substation PLC, the PLC will calculate the distance that the
belt travelled after the Metal Detector Trip was activated. The result of the
calculation will be displayed on the SCADA screen “Metal 1” in Meters to
assist the operations personnel to locate the tramp metal on the conveyor.
51
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Input. This signal will pulse if a second or third foreign metal object is
detected after the initial Metal Detected Output has been driven as
described above. The PLC will also calculate and display “Metal 2” and
“Metal 3” distance in meters that belt has travelled after each count pulse
was detected.
52
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
53
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Transfer Conveyor CV-109 can be operated in Local mode with the
following sequence;
The Local Start push button on the Local Control Station is activated.
54
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Transfer Conveyor CV-109 will start at the Local Speed Set point as
selected on the SCADA screen when logged in as Engineer.
For all equipment requiring local mode operation, local operation can
only be done when SCADA is localized.
When LOCAL mode, then equipment can only be start from LCS in
field. LCS →Start Button: Active
Stop Button: Active
(E-stop remains active)
SCADA → Start Button: Not Active
Stop Button: Active
the local operator must monitor the equipment.
55
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The WinCC SCADA operator will start the using the Start Button on the
CPP WinCC Transfer Conveyor CV-109Faceplate.
The can be stopped by any hardwired interlock, any Safety Device, any
Start Permissive, any Process Interlock, any Sequential Stop or the Stop
Button on the CPP WinCC Transfer Conveyor CV-109 Faceplate.
56
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Magnet also has a Motorized Trolley that enables the magnet to be
auto self-cleaning and dump the collected tramp metal. Motor Starter and
Controls for the Motorized Trolley are installed in the Vendor Control Panel.
Even though it is obvious that the Magnet will stop if the MCC MCCB
trips or is isolated, if the PLC input is de-energized in any operating mode
the following actions occur;
Loss of the MCCB Closed signal will prevent the equipment from
starting and stop the equipment if running.
57
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Magnet Faceplate will present the SCADA user with the following
status indications;
Magnet Interlock Ready Status. Ready (Green Text) / Not Ready (Red
Text) indicates if all the Magnet Interlocks are Ready.
The Magnet Faceplate will present the SCADA user with the following
status indications;
Local push button. This will de-energize Material Handling PLC Output
and allow Magnet Operation from the Vendor Local Panel. Local Mode
Select push button will become disabled when the equipment is running.
Remote push button. This will energize Material Handling PLC Output
and allow Magnet Operation from the Terminal SCADA.
Magnet Start push button. The Magnet can be energized with this button
providing the magnet is selected to Remote Operating Mode and the
Magnet is ready.
Magnet Stop push button. The Magnet can be de-energized with this
58
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Status Display Button. Pressing the Status Display Button will expand
the Magnet Faceplate and present the operator with Fault, Warning,
Interlock and Magnet Statistic information about the Magnet.
59
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
button which when pressed will stop the operation of the Magnet and
Trolley with a Hardwired Circuit in the Vendor Local Panel. An additional
Contact from the Emergency Stop push button is also connected to MCC
Material Handling PLC Input and is used for display and alarming on the
control room SCADA.
Loss of the Main Switch signal will prevent the equipment from starting
and stop the equipment if running.
60
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
61
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will
be reset by pressing the reset button provided on the faceplate.
The required Local Start push button on the Local Vendor Panel is
activated.
62
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
WinCC Operator Can now Start the Magnet using the Magnet Start
Button on the WinCC Magnet Faceplate.
The above starting of the Belt Conveyor and Magnetic Separator can
also be started as part of Transfer Conveyor starting sequence.
63
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Input. Conveyor remains fault as long as it has not been reset in WIN CC
and its LCS MD, reset can be done from local reset panel push button,
reset which is remotely done via SCADA WinCC.
Using the pulse signal to the PLC from the under speed sensor connected
to the CPP Substation PLC, the PLC will calculate the distance that the
belt travelled after the Metal Detector Trip was activated. The result of the
calculation will be displayed on the SCADA screen “Metal 1” in Meters to
assist the operations personnel to locate the tramp metal on the conveyor.
A Metal Detector Count signal is connected to CPP Substation PLC Input. This signal
will pulse if a second or third foreign metal object is detected after the initial Metal
Detected Output has been driven as described above. The PLC will also calculate and
display “Metal 2” and “Metal 3” distance in meters that belt has travelled after each
count pulse was detected.
64
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Using the pulse signal to the PLC from the under speed sensor connected
to the CPP Substation PLC, the PLC will calculate the distance that the
belt travelled after the Metal Detector Trip was activated. The result of the
calculation will be displayed on the SCADA screen “Metal 1” in Meters to
assist the operations personnel to locate the tramp metal on the conveyor.
A Metal Detector Count signal is connected to CPP Substation PLC Input. This signal
will pulse if a second or third foreign metal object is detected after the initial Metal
Detected Output has been driven as described above. The PLC will also calculate and
display “Metal 2” and “Metal 3” distance in meters that belt has travelled after each
count pulse was detected.
65
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Status Information from the Soft start to the PLC will consist of the
following;
Secondary Crusher SOFTSTART Fault Code. This will contain all
available SOFTSTART fault information. (SOFTSTART Fault codes
will be described in more detail later in this document).
Secondary Crusher SOFTSTART Warning Code. This will contain
all the available SOFTSTART warning information.
(SOFTSTART Warning codes will be described in more detail
later in this document).
Secondary Crusher SOFTSTART Running Status.
Secondary Crusher Actual Motor Current.
A SOFTSTART Warning will not prevent the drive from starting, nor
stop the drive when running. The warning is for Operator Information
and investigation.
A SOFTSTART Fault will prevent the drive from starting and will stop
the drive if it is running. Commands from the CPP Control System to the
SOFTSTART will consist of the following;
Secondary Crusher SOFTSTART Start / Stop commands.
Secondary Crusher SOFTSTART Forward Commands for remote,
reverse motor crusher only use can do if in mode Local (maintenance)
and Running from LCS.
Secondary Crusher SOFTSTART Fault Reset.
66
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
67
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Secondary Crusher Soft start Fault Code. Soft start No Fault (White
Text) / cult Code (White Alpha Numeric Code) – Indicates when there
is an active fault code from the Soft start.
68
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Manual Mode Select Button. The Manual Mode Select Button will
switch the Secondary Crusher Control to manual start made by the
SCADA user. The Secondary Crusher control can only be selected
to Manual Mode with this push button which will allow operation of
the Secondary Crusher from the Local Control Station Start push
button. Local Mode Select push button will become disabled when the
equipment is running.
Start push button. The Secondary Crusher can be started with this
button providing the drive is selected to Remote Operating Mode and
the Drive is ready.
Stop push button. The Secondary Crusher can be stopped at any time
with this button regardless of operating mode.
Reset push button. Used to reset The Secondary Crusher Faults, Soft
start Faults and Warnings. The Reset function will be held on within
the PLC Code for two seconds.
More Button. Pressing the Status Display Button will expand the
Motor Faceplate and present the operator with Fault, Warning,
Interlock and Drive Statistic information about the Secondary Crusher.
69
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
will stop the plant equipment when running. The Secondary Crusher is
equipped with the following field devices;
The Local Control Station is equipped with a Start push button. The
push button is activated when pressed and deactivated (spring return) on
release. The push button is equipped with a normally open contact which
relays the local start request to a Material Handling MCC PLC input.
70
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Which need to be turned off is the chain feeder, crusher still running
only when tilt switch is active. Because when the crusher died then it
was built up in divergator.
If the Blocked Chute input returns to its healthy state before two
seconds has expired, no action will be taken.
A blocked Chute Switch will not return to its healthy state until the
blockage has been cleared.
71
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Secondary Crusher can start in remote mode if all safety device and
emergency stop de -energize. (Status Healthy and ready).
Equipment in front of is running CV-109.
72
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will
be reset again automatically whenever the equipment is started again in
any mode.
The operator will use the indications and controls explained previously to
monitor and operate the Secondary Crusher as follows;
73
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
For all equipment requiring local mode operation, local operation can
only be done when SCADA is localized.
When LOCAL mode, then equipment can only be start from LCS in
field. LCS→ Start Button : Active
Stop Button : Active
(E-stop remains active)
SCADA→ Start Button : Active
Stop button : Active
(E-stop remains active)
When REMOTE mode, then equipment can only be start from SCADA
in field. LCS → Start Button : Not Active
Stop Button : Not Active
(E-stop remains active)
SCADA→ Start Button: Active
Stop Button : Active
All events & alarms are logged in SCADA.
All horn warning must stay alive during starting motor, either local
mode or remote mode.
The Local Start push button on the Local Control Station is activated.
The Secondary Crusher will start at the Local Speed Set point as
selected on the SCADA screen when logged in as Engineer.
74
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The WinCC SCADA operator will start the using the Start Button on
the CPP WinCC Secondary Crusher Faceplate.
75
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The can be stopped by any hardwired interlock, any Safety Device, any Start
Permissive, any Process Interlock, any Sequential Stop or the Stop Button on the CPP
WinCC Secondary Crusher Faceplate
Transfer Conveyor CV-110 is used to transport the Coal from Secondary Crusher
onto Transfer Conveyor CV-111 and Transfer Conveyor CV-104 this Conveyor is
controlled by Siemens SINAMICS G120 VVVF Drive. The VVVF will control the
speed of the Conveyor as selected by the CPP Control Room Operator.
Status Information from the VVVF to the PLC will consist of the
following;
Transfer Conveyor CV-110 VVVF Fault Code. This will contain all
available VVVF fault information. (VVVF Fault codes will be described
in more detail later in this document), starting time with full load will
work then the motor will die for a moment. Starting time with empty
load will works then the motor dead motor does not work, transfer
76
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
77
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Motor Faceplate will present the SCADA user with the following
status indications, all alarms, events, warnings from plant equipment must
be logged on WinCC;
78
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Text) / VVVF Fault Code (White Alpha Numeric Code) – Indicates when
there is an active fault code from the VVVF.
Auto Mode Select Button. The Auto Mode Button will switch the
Transfer Conveyor CV-110 Control to Automatic and the speed will be
controlled by the PLC Chain Control can only be de-selected from
Automatic Mode when the SCADA user is logged in as engineer.
Manual Mode Select Button. The Manual Mode Select Button will
switch the Transfer Conveyor CV-110 Control to manual speed control
with speed adjustments made by the SCADA user. The Transfer
Conveyor CV-110Control can only be selected to Manual Mode when
the SCADA user is logged in as engineer.
Manual Speed Adjust. A Slide Bar Controller and a text box are provided
to the SCADA user for the purpose of speed adjustment of Transfer
Conveyor CV-110in manual mode. The user can adjust the slide bar from
left to right for 0-100% speed adjustment. A numeric display of the speed
79
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
adjustment will also be provided which will display the requested speed
from 0-100%. It will only be possible for the SCADA user to manually
adjust Transfer Conveyor CV-110 speed using the slide bar or input a
numeric value with a keyboard when the SCADA user is logged in as
engineer.
Local Mode Select Button. The operator can select Local Mode with this
push button which will allow operation of the Transfer Conveyor CV-110
from the Local Control Station Start push button. Local Mode Select
push button will become disabled when the equipment is running.
Start push button. The Transfer Conveyor CV-110 can be started with
this button providing the drive is selected to Remote Operating Mode
and the Drive is ready.
Stop push button. The Transfer Conveyor CV-110 can be stopped at any
time with this button regardless of operating mode.
Reset push button. Used to reset The Transfer Conveyor CV-110 Faults,
VVVF Faults and Warnings. The Reset function will be held on within
the PLC Code for two seconds.
More Button. Pressing the Status Display Button will expand the Motor
Faceplate and present the operator with Fault, Warning, Interlock and
Drive Statistic information about the Transfer Conveyor CV-110.
80
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Motor Run Hours this Shift. Shows current accumulated Run Hours
(White Numeric) in Hours and Minutes for The Transfer Conveyor
CV-110 this shift.
Motor Run Hours last Shift. Shows total accumulated Run Hours (White
Numeric) in Hours and Minutes for The Transfer Conveyor CV-110for
the previous shift.
Motor Run Hours Total. Shows total accumulated Run Hours (White
Numeric) in Hours and Minutes for The Transfer Conveyor CV-110since
reset. A reset button will be provided to users with Engineer Login and
above.
Average Flow Rate (Gross) this Shift. This will indicate the average
gross flow rate for the current shift. This will be calculated as follows,
Gross Average Flow Rate = Current Production Tones / Current time
81
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Average Flow Rate (Gross) last Shift. This will indicate the average
gross flow rate for the previous shift. This will be calculated as follows,
Gross Average Flow Rate = Total Production Tones last Shift / Total Shift
period last shift.
Average Flow Rate (Net) this Shift. This will indicate the average net
flow rate for the current shift. This will be calculated as follows, Net
Average Flow Rate = Current Production Tones / Current Utilized Run
Hours expired from the shift period.
Average Flow Rate (Net) last Shift. This will indicate the average net
flow rate for the previous shift. This will be calculated as follows, Net
Average Flow Rate = Total Production Tones last shift / Total Utilized
Run Hours from the previous shift.
Motor speed Transfer Conveyor CV-109 3.3 m/s; motor speed Transfer
Conveyor CV-110 3.3 m/s; motor speed Transfer Conveyor CV-111 3.3
m/s.
A Fault condition will prevent the plant equipment from starting and will
stop the plant equipment when running. The Transfer Conveyor CV-110 is
equipped with the following field devices;
82
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Local Control Station is equipped with a Start push button. The push
button is activated when pressed and deactivated (spring return) on release.
The push button is equipped with a normally open contact which relays the
local start request to a MCC PLC input.
A Pull wire Switch is installed on either side of the Conveyor; Each Pull
wire Switch is equipped with two normally closed contacts and one
normally open contact. One of the normally closed contacts are used in the
hardwired circuit explained previously, the other normally closed contacts
are used for display and alarming on the control room SCADA.
83
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The normally open contact of the pull wire switches will close when in
its tripped state and will energize an indicating strobe light. The strobe will
extinguish when the pull wire is reset.
Belt Drift Switches are installed in carry return conveyor head tail. So
every conveyor there is 8 BDS. The Belt Drift switches are sprung loaded
roller arms that will be activated when the conveyor belt misaligns. Each
Belt Drift Switch is equipped with a normally closed contact connected
individually to Material Handling MCC PLC inputs as follows,
When any Transfer Conveyor CV-110 Belt Drift Switch PLC input is de-
84
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
energized for more than five seconds continuously when the Transfer
Conveyor CV-110 is running in remote operating mode, the following
action will take place, to belt drive, please add warning before BDS text
conveyor. Because in the BDS there are 2 contacts, 1 for Warning, 1 her to
Trip;
If the equipment has stopped with the Belt Misaligned and the Belt Drift
switch still activated, the equipment must be placed into Local Operating
Mode and the Belt started from the Local Control Station.
Once the belt has run back into position, Remote operation from the CPP
WinCC SCADA may be restored.
85
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Material Handling MCP PLC inputs as follows, add BCS in tail CV-110 /
under secondary crusher. To anticipate the built-up material in the CV-110
tail;
When the either of the normally closed contacts of the Blocked Chute
switches (Level tech Tilt Switch) is broken for more than two seconds
continuously when running in remote operating mode, the following action
will take place;
If the Blocked Chute input returns to its healthy state before two seconds
has expired, no action will be taken.
A blocked Chute Switch will not return to its healthy state until the
blockage has been cleared.
A Belt Rip Switch is installed at the tail end of the Transfer Conveyor
CV-110 and is installed to monitor the condition of the underside of the
carry belt. The Belt Rip Switch has a tensioned lanyard monitoring line
installed under the carry side of the belt which follows the contour of the
belt profile. When the Lanyard is connected to the switch body the internal
86
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Belt Rip input will not become healthy again until the Belt Rip
Switch lanyard is again securely attached to the Belt Rip switch body.
The Trolley Upper & Lower Ultimate Limit Switches are mechanically
operated switches with a level arm that is activated when in contact with
the take-up trolley. When either Take-Up Ultimate upper or lower Limit
Input is de-energized with the Transfer Conveyor CV-110 running in
remote operating mode, the following action will take place;
87
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
removed.
The PLC will compare the measured tail pulley speed against the
requested speed command to the Transfer Conveyor CV-110. When
running in Remote Operating Mode, and the requested speed and actual
speed differ more than 15% for a continuous period greater than five
second the following actions will occur;
88
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The under speed trip fault will be matched by the PLC and will be reset
by pressing the reset button provided on the faceplate.
The PLC will ignore the Tail Pulley Speed for a period of ten seconds
during start-up allowing the equipment time to reach full speed.
If the speed difference falls below 15% before the five second delay has
expired, no action will be taken.
89
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Process Interlocks are required to keep the Transfer Conveyor CV- 102
running in Remote Operating Mode. When a Process Interlock becomes
unhealthy while the Transfer Conveyor CV-110is running the will be
stopped immediately in the same manner as a fault condition.
90
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will be reset
again automatically whenever the equipment is started again in any mode.
The Transfer Conveyor CV-110 feeds coal onto CV-111 or CV-104. The
Transfer Conveyor CV-110 is operated from the CPP Control Room
WinCC. The operator will use the indications and controls explained
previously to monitor and operate the Transfer Conveyor CV-110 as
follows. If belt plow leads to CV-111 then make sure CV-111 running to
CV-110 ready to start. If belt plow leads to CV-104 then make sure CV-104
running to CV-110 is ready to start.
The Local Start push button on the Local Control Station is activated.
The Transfer Conveyor CV-110 will start at the Local Speed Set point as
selected on the SCADA screen when logged in as Engineer.
91
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The WinCC SCADA operator will start the using the Start Button on the
CPP WinCC Transfer Conveyor CV-110 Faceplate.
92
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The can be stopped by any hardwired interlock, any Safety Device, any
Start Permissive, any Process Interlock, any Sequential Stop or the Stop
Button on the CPP WinCC Transfer Conveyor CV-110 Faceplate.
Transfer Conveyor CV-111 is used to transport the Coal from Transfer Conveyor
onto Stockpile 1, this Conveyor is controlled by Siemens SINAMICS G120 VVVF
Drive. The VVVF will control the speed of the Conveyor as selected by the CPP
Control Room Operator.
Status Information from the VVVF to the PLC will consist of the following;
Transfer Conveyor CV-111 VVVF Fault Code. This will contain all
available VVVF fault information. (VVVF Fault codes will be described
in more detail later in this document).
Transfer Conveyor CV-111 VVVF Warning Code. This will contain all
the available VVVF warning information. (VVVF Warning codes will be
described in more detail later in this document).
Transfer Conveyor CV-111 VVVF Running Status.
Transfer Conveyor CV-111 Actual Motor Current.
A VVVF Warning will not prevent the drive from starting, nor stop the
93
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
drive when running. The warning is for Operator Information and investigation.
A VVVF Fault will prevent the drive from starting and will stop the drive
if it is running. Commands from the CPP Control System to the VVVF will
consist of the following;
Transfer Conveyor CV-111 VVVF Start / Stop commands.
94
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Motor Faceplate will present the SCADA user with the following
status indications;
95
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Auto Mode Select Button. The Auto Mode Button will switch the
Transfer Conveyor CV-111 Control to Automatic and the speed will be
controlled by the PLC, Control can only be de-selected from Automatic
Mode when the SCADA user is logged in as engineer.
Manual Mode Select Button. The Manual Mode Select Button will
switch the Transfer Conveyor CV-111 Control to manual speed control
with speed adjustments made by the SCADA user. The Transfer
Conveyor CV-111Control can only be selected to Manual Mode when
the SCADA user is logged in as engineer.
Manual Speed Adjust. A Slide Bar Controller and a text box are provided
to the SCADA user for the purpose of speed adjustment of Transfer
Conveyor CV-111 in manual mode. The user can adjust the slide bar
from left to right for 0-100% speed adjustment. A numeric display of the
speed adjustment will also be provided which will display the
requested speed from 0-100%. It will only be possible for the
SCADA user to manually adjust Transfer Conveyor CV-111 speed using
the slide bar or input a numeric value with a keyboard when the SCADA
user is logged in as engineer.
Local Mode Select Button. The operator can select Local Mode with this
96
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
push button which will allow operation of the Transfer Conveyor CV-111
from the Local Control Station Start push button. Local Mode Select
push button will become disabled when the equipment is running.
Start push button. The Transfer Conveyor CV-111 can be started with this
button providing the drive is selected to Remote Operating Mode and the
Drive is ready.
Stop push button. The Transfer Conveyor CV-111 can be stopped at any
time with this button regardless of operating mode.
Reset push button. Used to reset The Transfer Conveyor CV-111 Faults,
VVVF Faults and Warnings. The Reset function will be held on within
the PLC Code for two seconds.
More Button. Pressing the Status Display Button will expand the Motor
Faceplate and present the operator with Fault, Warning, Interlock and
Drive Statistic information about the Transfer Conveyor CV-111.
Motor Run Hours this Shift. Shows current accumulated Run Hours
(White Numeric) in Hours and Minutes for The Transfer Conveyor
CV-111 this shift.
Motor Run Hours last Shift. Shows total accumulated Run Hours (White
97
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Numeric) in Hours and Minutes for The Transfer Conveyor CV-111 for
the previous shift.
Motor Run Hours Total. Shows total accumulated Run Hours (White
Numeric) in Hours and Minutes for The Transfer Conveyor CV-111 since
reset. A reset button will be provided to users with Engineer Login and
above.
Average Flow Rate (Gross) this Shift. This will indicate the average
gross flow rate for the current shift. This will be calculated as follows,
Gross Average Flow Rate = Current Production Tones / Current time
expired from the shift period.
Average Flow Rate (Gross) last Shift. This will indicate the average
gross flow rate for the previous shift. This will be calculated as follows,
Gross Average Flow Rate = Total Production Tones last Shift / Total Shift
98
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Average Flow Rate (Net) this Shift. This will indicate the average net
flow rate for the current shift. This will be calculated as follows, Net
Average Flow Rate = Current Production Tones / Current Utilized Run
Hours expired from the shift period.
Average Flow Rate (Net) last Shift. This will indicate the average net
flow rate for the previous shift. This will be calculated as follows, Net
Average Flow Rate = Total Production Tones last shift / Total Utilized
Run Hours from the previous shift.
Motor speed Transfer Conveyor CV-109 3.3 m/s; motor speed Transfer
Conveyor CV-110 3.3 m/s; motor speed Transfer Conveyor CV-111 3.3
m/s.
A Fault condition will prevent the plant equipment from starting and will
stop the plant equipment when running. The Transfer Conveyor CV-111 is
equipped with the following field devices;
99
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
mode when Transfer Conveyor CV-111 Emergency stop - LCS PLC input
is de-energized the following action will occur;
The Local Control Station is equipped with a Start push button. The push
button is activated when pressed and deactivated (spring return) on release.
The push button is equipped with a normally open contact which relays the
local start request to a MCC PLC input.
A Pull wire Switch is installed on either side of the Conveyor. Each Pull
wire Switch is equipped with two normally closed contacts and one
normally open contact. One of the normally closed contacts are used in the
hardwired circuit explained previously, the other normally closed contacts
are used for display and alarming on the control room SCADA.
100
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The normally open contact of the pull wire switches will close when in
its tripped state and will energize an indicating strobe light. The strobe will
extinguish when the pull wire is reset.
Belt Drift Switches are installed in carry return conveyor head tail. So
every conveyor there is 8 BDS. The Belt Drift switches are sprung loaded
roller arms that will be activated when the conveyor belt misaligns. Each
Belt Drift Switch is equipped with a normally closed contact connected
individually to Material Handling MCC PLC inputs as follows,
When any Transfer Conveyor CV-111 Belt Drift Switch PLC input is
de-energized for more than five seconds continuously when the Transfer
Conveyor CV-111 is running in remote operating mode, the following
action will take place, to belt drive, please add warning before BDS text
conveyor. Because in the BDS there are 2 contacts, 1 for Warning, 1 her to
Trip;
101
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
If the equipment has stopped with the Belt Misaligned and the Belt Drift
switch still activated, the equipment must be placed into Local Operating
Mode and the Belt started from the Local Control Station. Once the belt
has run back into position, Remote operation from the CPP WinCC
SCADA may be restored.
A Belt Rip Switch is installed at the tail end of the Transfer Conveyor
CV-111 and is installed to monitor the condition of the underside of the
carry belt. The Belt Rip Switch has a tensioned lanyard monitoring line
installed under the carry side of the belt which follows the contour of the
belt profile. When the Lanyard is connected to the switch body the internal
contact becomes healthy (closed). If running in Remote Operating Mode,
when a foreign object pierces the belt and hits the Belt Rip Lanyard it is
disconnects from the switch body.
The switch contact connected to Material Handling MCC PLC Input de-
energized and the following actions occur immediately;
102
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Trolley Upper & Lower Ultimate Limit Switches are mechanically
operated switches with a level arm that is activated when in contact with
the take-up trolley. When either Take-Up Ultimate upper or lower Limit
Input is de-energized with the Transfer Conveyor CV-110 running in
remote operating mode, the following action will take place;
103
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Even though it is obvious that the Transfer Conveyor CV-111 will stop if
the MCC MCCB trips or is isolated, if the PLC input is de-energized in
any operating mode the following actions occur;
104
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will be reset
again automatically whenever the equipment is started again in any mode.
105
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Transfer Conveyor CV-111 feeds coal onto the stock pile. The
Transfer Conveyor CV-111 is operated from the CPP Control Room WinCC. The
operator will use the indications and controls explained previously to monitor
and operate the Transfer Conveyor CV-111 as follows;
The Transfer Conveyor CV-111 can be operated in Local mode with the
following sequence;
The Local Start push button on the Local Control Station is activated.
The Transfer Conveyor CV-111 will start at the Local Speed Set point as
selected on the SCADA screen when logged in as Engineer.
106
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Operating mode without the need for stopping the plant item. If any faults,
start permissive or process interlock conditions are unhealthy when
switched to Remote Operating mode the plant item will be tripped in the
same manner as previously described. It shall not be possible to switch a
plant item from Remote Operating Mode to Local Operating Mode at any
time after a Start has been initiated in remote operating mode, this shall
include the start-up warning time period.
The WinCC SCADA operator will start the using the Start Button on the
CPP WinCC Transfer Conveyor CV-111 Faceplate.
Transfer Conveyor CV-111 will start and the speed will be controlled to
maintain the production set point as set on the Face Plate. The Automatic
operation of CPP Transfer Conveyor CV-111 will be described in more
detail later in this document.
107
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Diverter Gate CV-107 is used to transport the Coal from Bypass Conveyor CV-
107 onto Existing Conveyor CV-14 & CV-22 this Conveyor is controlled by Forward
Reverse Starter. The starter will control the movement of the Diverter Gate as selected
by the CPP Control Room Operator.
108
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Loss of Diverter Gate Ready signal will prevent that equipment from
starting and stop the equipment if running.
14.1.4 Running
A Drive Running Signal will originate from the MCC Motor Starter
module and connect to Material Handling PLC Input. The PLC must detect
the PLC Input is energized before it is confirmed that the Diverter Gate
motor is Running.
A Motor Overload Trip Signal will originate from the MCC Motor
Starter module and connect to Material Handling PLC Input
A Motor Overload fault will prevent the equipment from starting and
stop the equipment if running.
An Earth Leakage Trip Signal will originate from the MCC Motor Starter
module and connect to Material Handling PLC Input.
109
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
An Earth Leakage fault will prevent the equipment from starting and stop
the equipment if running.
Even though it is obvious that the Diverter Gate CV-107will stop if the
MCC MCCB trips or is isolated, however if the Diverter Gate MCCB
Closed PLC input is de-energized the following action will occur;
Loss of the MCCB Closed signal will prevent the equipment from
starting and stop the equipment if running.
110
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Motor Faceplate will present the SCADA user with the following
status indications, all alarms, events, warnings from plant equipment must
be logged on WinCC;
Diverter Gate CV-107 Interlock Ready Status. Ready (Green Text) / Not
Ready (Red Text) indicates if all the drive Interlocks are Ready.
Diverter Gate CV-107 Drive Status. Drive Stopped (Green Text) / Drive
Running (Red Text) – Indicates if the equipment is running or stopped,
Drive Fault (Yellow Text) – Indicates that the Drive has a Fault
Condition.
The Motor Faceplate will present the SCADA user with the following
control functions;
Local Mode Select Button. The operator can select Local Mode with this
push button which will allow operation of the Diverter Gate CV-107
from the Local Control Station Start push button. Local Mode
Select push button will become disabled when the equipment is
running. It should be noted that all Diverter Gate and hardwired
Emergency stop circuit will be ignored in this operating mode.
111
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Start push button. Diverter Gate can be started with this button providing
the drive is selected to Remote Operating Mode and the Drive is ready.
Stop push button. Diverter Gate can be stopped at any time with this
button regardless of operating mode. Status Display Button. Pressing the
Status Display Button will expand the Motor Faceplate and present the
operator with Fault, Warning, Interlock and Drive Statistic information
about the Diverter Gate Auto Mode Select Button.
A Fault condition will prevent the plant equipment from starting and will
stop the plant equipment when running. The Diverter Gate CV-107 is equipped
with the following field devices;
112
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Diverter Gate CV-107 Fault MCC Material Handling PLC Output
shall be de-energized.
The Diverter Gate CV-107 fault condition shall be displayed and alarmed
on the CPP SCADA system.
The Local Control Station is equipped with a Start push button. The push
button is activated when pressed and deactivated (spring return) on release.
The push button is equipped with a normally open contact which relays the
local start request to a MCC PLC input.
Even though it is obvious that the Diverter Gate CV-107 will stop if the
MCC MCCB trips or is isolated, if the PLC input is de-energized in any
operating mode the following actions occur;
113
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Diverter Gate CV-107 fault condition shall be displayed and alarmed
on the CPP SCADA system. The MCC Circuit Breaker Position will be
displayed in the fault message.
Start Permissive are required to start The Diverter Gate CV-107 Remote
Operating Mode. When a Permissive condition becomes unhealthy while The
Diverter Gate CV-107 is running the Diverter Gate CV-107 will be stopped
immediately in the same manner as a fault condition.
114
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
When a process interlock fault occurs stopping the equipment, the fault
will be matched by the PLC, recorded in the WinCC Alarm Log and will be reset
again automatically whenever the equipment is started again in any mode.
The Diverter Gate CV-107 Transport coal onto the Transfer CV-111. The
Diverter Gate CV-107 is operated from the CPP Control Room WinCC. The
operator will use the indications and controls explained previously to monitor
and operate The Diverter Gate CV-107 as follows;
115
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
The Local Start push button on the Local Control Station is activated.
The Diverter Gate CV-107 can be operated in Remote mode with the
following sequence;
The WinCC SCADA operator will start the using the Start Button on the
CPP WinCC the Diverter Gate CV-107 Faceplate.
116
BUNATI-CPP STOCKPILE & PORT Dir. Ref: BIB-LDP-I-E-001
PLANT CONTROL SYSTEM Date : 22-12-2017
CONTROL PHILOSOPHY
Process Interlock, any Sequential Stop or the Stop Button on the CPP
WinCC The Diverter Gate CV-107 Faceplate.
VVVF Warning and Fault Codes are relayed from the VVVF to the PLC over
the local PROFIBUS Link at each substation. The VVVF Warning and Fault codes have
a vast amount of information. These VVVF Warnings and Faults will be displayed on
the corresponding Motor Faceplates and will also be logged into the SCADA alarm
logs.
117