Professional Documents
Culture Documents
Table of Contents
Power Transformer Faults
o Oil & Winding Insulation Faults
o Core Faults
o Windings Faults
o Overload Faults
o Overheating Faults
Power Transformer Protection
o Built-On Protection
o Differential Protection
o Over-Current Protection
o Restricted Earth Fault Protection
o Overload Protection
o Lightning Protection
o Transformers Fire Protection System
Today, we will discuss about different types of transformer protection and faults in
details.
Transformers are vital equipment in transmission and distribution network and so
the protection against internal and external faults is a very important factor in the
design of those networks.
Transformers faults may occur:
In the dielectric (insulating) materials, namely in the oil.
In the windings.
In the core (less frequent).
For transformers equipped with cooling fans and pumps, the temperature devices are
used to automatically start and stop the forced cooling. They are also equipped
to initiate an alarm and a trip for very high transformer temperatures.
Oil-filled sealed transformers
Gas detection and oil level, pressure and temperature in one single equipment (DGPT
2 – Detection of Gas, Pressure and Temperature) with 2 levels (alarm and trip)
Dry type transformers
Temperature of windings with 2 levels (alarm and trip) – resistance temperature
detector PT 100 (platinium probe) or PTC (“Positive Temperature Coefficient”), that is
a thermistor (semi conductive material sensitive to temperature).
These protections have a direct action on the tripping coils of the circuit
breakers.
Differential Protection
The ideal way of protecting any piece of power system equipment is to compare the
current entering that piece of equipment, with the current leaving it.
Under normal healthy conditions the two are equal. If the two currents are not equal,
then a fault must exist.
This is done through “differential protection” (ANSI / IEEE / IEC code 87T), which
diagram is shown in Figure 1 and the functioning principle is based in Kirchhoff
current law.
Good to know:
Figure –
Transformer differential protection diagram
Nowadays, with electronic and microprocessed protection units, this compensation is
done through software.
Function of the protection is based on the transformation ratio “n” that can be expressed
by the equation:
n = (U1 / U2) = (I2 / I1)
(U1: primary voltage; U2: secondary voltage; I1: primary current; I2: secondary
current).
The above relation is a consequence of the equation of the rated power (S) of the
transformer:
S = √3 x U1 x I1 = √3 x U2 x I2
Problem relating to the transformer inrush current
Transformer switching causes a very high transient current (from 8 to 15 In),
which only flows through the primary winding and lasts several tenths of a second.
It is thus detected by the protection as a differential current and it lasts far longer than
the protection operating time (30 ms). Detection based only on the difference
between the transformer primary and secondary currents would cause
the protection to be activated. Therefore, the protection must be able to distinguish
between a differential current due to a fault and a differential inrush current.
Experience has shown that the inrush current wave contains at
least 20% of second harmonic components (current at a frequency of 100 Hz), while
this percentage is never higher than 5%upon occurrence of an overcurrent due to a fault
inside the transformer.
The protection must therefore simply be locked when the percentage of second
harmonic component in relation to the fundamental harmonic component (current at 50
Hz) is higher than 15%, i.e., “I2 / I1 > 15%”.
Problem relating to the magnetizing current upon occurrence of an overvoltage of
external origin
Magnetizing current, or exciting current, is the current that flows through the primary
winding of a power transformer when no loads are connected to the secondary
winding; this current establishes the magnetic field in the core and furnishes energy
for the no-load power losses in the core. It is responsible for “iron losses”.
The magnetizing current constitutes a difference between the transformer primary
and secondary currents. It is therefore detected as a fault current by the differential
protection even though it is not due to a fault.
In normal operating conditions, this magnetizing current is very low and does not
reach the protection operating threshold.
However, when an overvoltage occurs outside the transformer, the magnetic material
saturates(in general the transformers are dimensioned to be able to operate at
saturation limit for the nominal supply voltage), and the magnetizing current
value greatly increases. The protection operating threshold can therefore be
reached.
Experience has shown that the magnetizing current due to the magnetic saturation has
a high rate of fifth harmonic components (current at a frequency of 250 Hz).
Transformer differential therefore requires fairly complex functions as it must be
able to measure second and fifth harmonic current or, in order to avoid
measuring fifth harmonic currents, it must be able to detect overvoltages of
external origin.
The characteristics of transformer differential protection are related to the
transformer specifications:
Transformation ratio
Vector group
Inrush current
Permanent magnetizing current
Over-Current Protection
MV transformers with rated power up to 2.5 MVA are usually only protected against
overcurrents using over current relays.
Three phase or phase-to-phase short circuit, instantaneous (ANSI/IEEE/IEC code 50).
Three phase or phase-to-phase short circuit, time delayed (ANSI/IEEE/IEC code 51).
Phase-to-earth short circuit, instantaneous (ANSI/IEEE/IEC code 50N).
Phase-to-earth short circuit, time delayed (ANSI/IEEE/IEC code 51N).
This set of protections is used on HV and MV transformers with rated power above 3-4
MVA as a “back-up” protection, in addition to the differential protection.
In some installations and networks MV transformers with rated power up to 630
kVA may be protected against overcurrents by fuses associated to switch-
disconnectors, as shown in Figure 2.
In these situations the switch-disconnectors must have a tripping coil to allow the
action of the built-on protections of transformers.
Figure 2 – Switch-disconnector
associated with fuses
Fuses must have a mechanical latch to indicate the fusion and to provoke three-pole
opening of the switch-disconnector, to avoid the functioning of the installation only with
two phases.
Manufacturers provide tables to choose the rated current of a fuse, taking into account
the rated voltage and power, like the one shown in the Table 1, according to IEC
standards.
Tables vary from manufacturer to manufacturer, according to the standards
used, being recommended to use the table provided by the selected
manufacturer.
Overload Protection
The basic criterion for transformer loading is the temperature of the hottest spot of the solid
insulation (hot-spot). It must not exceed the prescribed value, in order to avoid insulation
faults, since loading capability of power transformers is limited mainly by winding
temperature.
The temperature of solid insulation is the main factor of transformer ageing.
With temperature and time, the cellulose insulation undergoes a depolymerization
process. As the cellulose chain gets shorter, the mechanical properties of paper such
as tensile strength and elasticity degrade. Eventually the paper becomes brittle and
is not capable of withstanding short circuit forces and even normal vibrations that
are part of transformer life. This situation characterizes the end of life of the solid
insulation. Since it is not reversible, it also defines the transformer end of life.
Transformer overloads can occur during contingency conditions that are the product
of one, two, or various system elements being isolated from the power the system. They
can also occur when transformers are already at 80%-90% of their full nameplate
rating and extra capacity is needed, especially during hot summers.
Traditionally, inverse-time overcurrent relays (an inverse-time
curve is characterized by the inverse variation of current with the time, as shown in
Figure 4) for overload protection, but a difficulty is that transformers are usually
outdoors where ambient temperature affects their loadability, and hence
the optimum pickup settings of such relays.
Figure 4 – Inverse-time characteristic curve
However, for liquid-immersed power transformers, the temperature of the winding
hot-spot is the important factor in the long-term life of the transformer.
The insulating oil temperature is dependent on the winding temperature, and is used
to indicate the operating conditions of the transformer. Many numerical transformer
protection relaysavailable today include protection functions that operate on insulating
oil temperatures, calculated loss-of-life due to high oil temperature, and predicted
oil temperatures due to load.
These types of functions are not routinely applied, but modern utility operating
practices try to maximize the utilization of power transformers, which may increase
the occurrence of over-temperature conditions and transformer ageing. Over-
temperature conditions and accelerated aging are adverse system events that must
be identified and protected against.
The most common function provided for thermal protection of power transformers is
the thermal overload (ANSI/IEEE/IEC code 49) function.
The thermal capacity used is calculated according to a mathematical model which takes
into account:
Current rms values
Ambient temperature
Negative sequence current.
The protection gives a trip order when the heat rise E, calculated according to the
measurement of an equivalent current Ieq, is greater than the set point Es.
The protection tripping time is set by the time constant T.
The thermal overload protection function may be used to protect equipment with two
operating rates, for example transformers with two ventilation modes, with or without
forced ventilation (ONAN / ONAF).
Lightning Protection
Control (make or break) a circuit manually or by remote control under normal and fault
conditions.
Break a circuit automatically under fault conditions (like over current, Short circuit, etc).
Air Circuit Breaker
Operates in air (where air-blast as an arc quenching medium) at atmospheric pressure.
It has completely replaced by oil circuit breaker.
No chance of oil fire like in oil circuit breaker.
Rated Current up to 10k A.
Trip thresholds and delays are adjustable.
Electronically and microprocessor controlled.
It is used in large industrial plant for main power distribution.
To know more about ACB, read the article “Air Circuit Breaker (ACB) – Construction,
Operation, Types and Applications.
What is MCB (Miniature Circuit Breaker) ?
MCB stands for “Miniature Circuit Breaker”.
Rated current under 100 amps.
Interrupting rating of under 18,000 amps.
Trip characteristics may not be adjusted.
Working principle based on thermal or thermal magnetic operation.
Suitable for low current circuits (low energy requirement), i.e. home wiring.
Generally, used where normal current is less than 100 Amps.
To know more about the MCB, check the previous post “MCB (Miniature Circuit
Pollution Degree 2 3
Application Current AC AC or DC
Anyhow, You will have to read the next article about the proper selection of MCB or
MCCB according to your needs.
Difference between ICS & ICU in term of Circuit Breakers.
ICS = Service Braking Capacity (means, Circuit breaker can remove the fault, but it may
not be usable afterwards.)
ICU = Ultimate Braking Capacity (means, Circuit breaker can remove the fault and remain
usable)
Characteristic of MCB and FUSE
Both MCB and Fuse rated in Amperes which is known as Nominal Current or Rated Current.
Keep in mind that an MCB or Fuse with rated current of 50A will not trip when current of
more than 50A is flowing through it.
The reason is that MCB and Fuse with same rated current has different properties.
For a 63A MCB and 60A Fuse where it should trip in 0.2 sec, MCB will trip at 260A and fuse
will trip at 600A. It shows Fuse delay is very high as compared to MCB.
Sometimes, fuse blow itself without a reason. It may be due to the previous overloads for
specific time which has not been noticed.
In case of Fuse, if the rated current is 60A, it will carry up to 80A for an hour or two. This is
the same like modern PVC cables hold 50% overload for an hour.
A previous post can be read for more details under the title of “Main Difference between
Fuse and MCB“
What is ELCB (Earth Leakage Circuit Breaker)
ELCB stands for “Earth Leakage Circuit Breaker” and it is used for protecting a
person from electric shock and injury. The needs of these devices arise because of the
number increasing in injuries as well as deaths because of electric shock. This device is
invented almost 50 years ago, but nowadays ELCB is not suitable because of its some
disadvantages hence another device RCB (Residual circuit breaker) or RCD (Residual
Current Devices) whose functionality is same with more advantages, but theory of
operation is entirely different from ELCB. some of ELCB characteristic are as follow:
ELCB Construction:
It is international standard that each electronics device enclosure should be earthed. So, there
would be no chance of electrocutions. For proper operation of ELCB, its need to bury a metallic
rod deep in the soil and ELCB is connected between the wire coming from the rod to the wire
attached to the external metallic body of the Electrical device or you can say that ELCB is
connected to the Earth wire.
ELCB Operation:
When the live wire (accidentally) touches the metallic body of the connected device or
appliance, then there is potential generated between the earthed rod and the metallic
enclosure of that device. The circuitry (inside the ELCB) senses the potential difference
and when this potential difference reached at 50volt then ELCB cuts off the main supply
from the connected device. This way it ensures the safety of the human beings.
Related Post: How to Connect a Portable Generator to Home Supply System (Three
Methods)
To know the operation time of ELCB, lets see the following example.
The safest limit of current which human body (depends on multiple factors) can
withstand is 30mA sec. Suppose the human body resistance (hands to feet) is 500Ω
and he touches to the live wire having voltage of 230V AC to the ground. The current
flowing through body to the ground will be:
I = 220V/100Ω = 440mA
Now, The ELCB must be opertaed in
30mA sec / 440A = 0.068m sec.
However, it is not used widely nowadays because of its some major disadvantages
mentioned in the next section.
Electrical Shock Hazards & Effects on
Human Body
Disadvantages of ELCB:
Without proper earth connection, ELCB will not work. If the wire attached to the earthed rode
is loose or broken, then ELCB would not able to sense the potential hazardous voltage on
the metallic body of the electrical/electronic device.
ELCB is attached between earthed wire and metallic body of the electrical appliances. But
there are many other parallel paths for the currents to flow from the connected device body
to earth without going through earthed wire. E.g. there are many metallic pipes in the house,
which can provide a parallel path for the current to flow towards the earth. In this way,
sometime ELCB is not able to detect the hazardous voltage on the metallic body of the
device, which may cause serious injury.
If someone gets in touch with live phase wire, ELCB will not Trip because in this case, there
will be no current flow in the earth wire. In fact, current is flowing from the live wire to earth
through the person’s body.
When a live wire comes in contact with neutral wire, short circuit will occur, hence, ELCB will
not trip because there will be no current in the earth wire.
There are many cases in which, there is a current flow in the earth wire, but the situation is
not hazardous in such cases, but it gives false trip e.g. lightening strike, current starts flowing
in the earth wire and ELCB trips.
To overcome with the above disadvantages of ELCB, another Device named Residual
Current Breaker (RCB) is invented to use for earth leakage protection.
Related Post: How to Find the Rated Cable & Wire Size for Electrical Wiring Installations
What is RCD , RCB or RCCB ?
Residual Current Device (RCD) is also known as Residual Current Breaker (RCB)
Advantages of RCD:
If there is no connection between the ground and the enclosure of the device, and a person
touches the metallic body of that device. In this case, incoming and outgoing current will be
different and RCB will Trip in contrast with ELCB.
Functionality of RCB (Residual Current Breaker) does not effect by lightning strikes.
It does not trip falsely.
Related Post: Types of Switches – Construction, Working & Applications
Disadvantages of RCD:
RCD don’t provide protection against Current Overload. But the main MCB will trip the
circuit as RCCD won’t trip in case of a live or neutral faults i.e. short circuit and overload. For
this reason, RCBO (MCB with RCD in a single unit) are used for proper protection.
It operates only on normal supply wave forms i.e. it will not detect the pulsating DC and
half wave rectified waveform. For these reason, special RCCB are used which is also
operating on rectified pulsating DC voltage.
Annoyance operation of RCD in case of sudden changes in load current. RCDs are
very sensitive and operate on even a very small amount of faulty current very quickly. In
case of switching of old electrical appliances, there is a small constant current flow through
earth which lead to trip the circuit.
RCD will not protect against overheating, Live – Neutral Shocks, and Socket outlet
being wired with its Live & Neutral Terminals.
RCBO (Residual Circuit Breaker with Overload)
As we know that RCD won’t provide protection against Overload, hence an MCB and
RCD are presented in a single unit known as RCBO (Residual Circuit Breaker with
Overload). The operating principles are same as above but it provide more and reliable
operation with overload protection in single box.
Related Post: Different Types of Electrical Wiring Systems and Methods of Electrical Wiring
Installation
Difference between ELCB and RCCB
Characteristic ELCB RCCB (Also known as RCD or RCB)
Voltage Operated Device (Old Name, Current Operated Device (New Name,
Operation
Old Technology). New Technology).
Only detects earth faults that flow back It will detect any earth fault. That’s why
Fault Detection
through the main earth wire. they are using now instead of ELCB.
Not recommended. Replace it with Almost all wiring systems use RCCD
Applications
RCCD. nowadays.
Keep in mind that both ELCB and RCCB are used for the same purpose but wiring
connection is different i.e. in RCCB, only phase and neutral wire should be connected
through it whereas in ELCB, main earth wire is connected through it.