You are on page 1of 12

Paper No.

1411
621.313.32 SUPPLY SECTION

OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES


By J. H. WALKER, M.Sc, Ph.D., Member.
(The paper was first received 26th May, and in revised form 21st August, 1952.)

SUMMARY the region of operation corresponding to rated load and power


By using the well-known 2-axis theory of Blondel the paper develops factor, whilst the more important characteristics of synchronous
on a simple geometrical basis the steady-state characteristics of syn- machines, such as stability, usually relate to the under-excited
chronous salient-pole machines. From these it is shown that appre- (more-or-less unsaturated) condition where the error is negligible.
ciable economies can be realized by relating the short-circuit ratio, If in the first case it is desired to allow for the effects of satura-
and thus the synchronous reactance, of an alternator to the stability tion, the direct- and quadrature-axis synchronous reactances Xd
characteristics required by the load. It is also shown that further and Xq used in the paper can be replaced by the corresponding
economies can be obtained in both alternators and synchronous
condensers by designing the excitation system to supply positive and equivalent reactances Xd(fiq) and Xq{eq) in the manner described
negative field currents. by Crary. 5 The use of these reactances will considerably
Power-station operation can be simplified and made more reliable increase the labour of preparing the diagrams and charts described
by the use of a combined watt- and VAr-meter with a dial based on in the paper.
the power chart evolved in the paper.
The common basis underlying the operation of the salient-pole
alternator, synchronous motor and condenser, and synchronous (2.2) The Vector Diagrams of the Salient-Pole Machine
reluctance machine is shown by a simple generalized diagram, and The conventional 2-axis vector diagram of a salient-pole
the operation of these types of motors is briefly discussed. alternator supplying a lagging-power-factor load is shown in
Equations are evolved for determining machine characteristics with Fig. 1. The line OA represents the terminal e.m.f. E, and /
greater accuracy than is given by the geometrical method.

(1) INTRODUCTION
The fundamental 2-axis theory underlying the operation of
salient-pole machines was first enunciated by Blondel, and since
then many papers have been published1 that develop from this
theory the appropriate equations for design and operation. For
instance, the equations appropriate to transient conditions were
developed by Park in his classic contribution; again Gibbs, 2 in
a recently published monograph, comprehensively covered opera-
tion under both transient and steady-state conditions, but since
he expressed his results in the notation of matrix algebra they
are not in a form suitable for ready application to practical
problems. Although other papers, such as those by David 3 and
Angelini,4 have dealt with particular aspects of the application
of 2-axis theory to steady-state operation, there appears to be Fig. 1.—Two-axis voltage vector diagram.
no comprehensive analysis suitable for immediate practical Salient-pole alternator
application to normal running conditions. Xa 1 1 per unit, Xq = 0-7 per unit.
Power factor == 0-9 lagging.
The present paper develops for the various types of synchronous
salient-pole machines the diagrams and general equations suitable the armature current lagging behind the terminal voltage by the
for practical use under steady-state conditions; it further shows angle <f>. The line AB is drawn at the angle <f> to the perpendicular
how the application of these results may in certain cases lead to AY, a length AF proportional to IXq is marked off on it and the
improvements in design and operation. imaginary pole axis is then drawn through F from O. The two
hypothetical components Id and Iq of the armature current can
(2) THE VECTOR DIAGRAM then be obtained by drawing the vector representing ld per-
(2.1) Assumptions pendicular to the pole axis (imaginary), OF, and the vector
(a) All load changes take place within a time interval longer representing Iq parallel to the same axis. The mutually per-
than the short-circuit transient time-constant of the machine. pendicular vectors IdXd and IqXq can then be drawn, the extenr
The analysis in the paper is thus restricted to steady-state con- sion of OF to OG then giving the internal voltage EQ. It should
ditions as defined by this assumption. be noted that throughout the paper the "per unit" system is
(b) In all cases the machine is operating in parallel with a used so that rated r.m.s. current per phase is unit current, rated
large-capacity system, i.e. it is connected to a so-called "infinite" r.m.s. voltage per phase is unit voltage, direct-axis reactance Xlf
busbar whose voltage is unaffected by load changes in the machine is direct-axis reactance in ohms times rated current and divided
in question. by rated voltage, and similarly for Xq. It thus follows that Eo
(c) Magnetic saturation can be neglected. This is justified on is the per-unit internal voltage. If the line AF is extended to B
the grounds that saturation has an appreciable influence only in such that AB represents IXd, OBA is the conventional vector
triangle of the cylindrical-rotor synchronous machine.
Written contributions on papers published without being read at meetings are It can be seen that the internal voltages obtained by the two
invited for consideration with a view to publication.
Dr. Walker is with the British Thomson-Houston Co., Ltd. methods scarcely differ, but the pole angle 8 obtained by the
13]
14 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES
2-axis method is substantially less than given by round-rotor
theory.
The corresponding diagram for an alternator operating at a
leading power factor is shown in Fig. 2. It can be seen that

Fig. 4.—Two-axis current vector diagram.


Salient-pole a l t e r n a t o r
Xd ••- 1-1 per unit, Xq •• •-- 0 - 7 per unit.
Power factor - 0 - 9 lagging.

Fig. 2.—Two-axis voltage vector diagram. representing the contribution from the salient-pole effect to the
Salient-pole alternator internal voltage; in Fig. 4 it can be represented as the similar
Xd 1 • 1 per unit, Xv 0 - 7 p e r unit. contribution to the load field current.
Power factor - - 0 - 9 leading.
By eliminating all but essentials, the simple vector diagram of
there is an appreciable difference between both the internal Fig. 5 can now be drawn, which shows quite clearly the relation-
voltages and pole angles given by the two different methods. ships between short-circuit current, armature current and load
In both Figures the polygon OAHG represents a voltage field current. This simplified current vector diagram now
vector diagram. The terminal voltage is constant so that the affords a ready means of determining the relationships between
only operational variables are armature current, power factor armature current, power factor and field current. If Xq — Xd
and field current. It is therefore necessary to transform the the diameter of the semicircle becomes zero, and the vector
voltage vector polygons of Figs. 1 and 2 into those appropriate diagram reduces to the simple diagram of the round-rotor
to currents; in addition, for simplicity of representation, it is machine as shown by the dotted line.
desirable that the vector polygon be replaced, in effect, by a
vector triangle corresponding to that normally associated with (3) POWER DIAGRAMS
the cylindrical-rotor theory. The latter change is shown in
Fig. 3, in which HG has been extended to B so that HB represents (3.1) The Alternator Power Diagram
With a fixed terminal voltage it is obviously possible to
determine from Fig. 5 the active- and reactive-power loading of

Fig. 3.—Two-axis voltage vector diagram.


Salient-pole alternator
Xd •-- I • 1 per unit, X,, =- 0 - 7 per unit.
P o w e r factor = 0 - 9 lagging.

lqXd and AB represents IXd. Then BC is drawn parallel to OG


and a semicircle is drawn on the diameter OC. By simple
geometry DB = OG == Eo and OC --= E(Xd/Xq - 1), so that Fig. 5.—Simplified 2-axis vector diagram.
the triangle CBA together with the semicircle CDO give the Salient-pole alternator
Xd — 1 • 1 p e r unit, Xq •--•• 0 - 7 p e r unit.
vector polygon of the alternator in a simpler form than that of Power factor =•• 0 - 9 lagging.
Fig. 1. In order to transform this into a current polygon it is
merely necessary to divide the four parameters—represented by an alternator for a given armature current and power factor.
the four sides of the polygon ODBA—by Xd, thus obtaining As an example Fig. 6 shows the variation of field current and
the current vector polygon OABD of Fig. 4. In this Figure, OA load angle for varying power factors, the armature current
represents E/Xd, the short-circuit current of the alternator with being maintained constant. A constant armature current simply
no-load excitation, AB the armature current, and DB the internal requires the locus of the extremity of the current vector / to
voltage divided by Xd, i.e. the short-circuit current with full-load move on a semicircle with its centre at O. Thefieldcurrent is
excitation. Since, with the assumption of no saturation, Eo also given as in Fig. 5 by the intercepts of the two semicircles on the
represents the full-load field. current /y, E0/Xd can also be rays drawn from C to the extremities of the current vectors.
written l//Xd. In Fig. 3 the vector OD may be considered as Since power-factor angles are measured from the ordinate Oy
WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES 15

!
Per-uriit kW
Power factor

0-6

0-25 0-50 0-75


Per-unit K.VA. lagging

Fig. 6.— Circle diagram for constant armature current / with varying power factor and field current If.
Salient-pole alternator
= 1 • 1 per unit, Xq -•— 0-7 per unit.
Power factor = 0-9 lagging.

Fig. 7.—Diagram for rated^constant field current If with varying power factor and armature current /.
Salient-pole alternator
Xd — 1-1 per unit, Xq — 0-7 per unit.
Power factor — 0-9 lagging.
16 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES
as zero, projections of the current vectors on the vertical axis maximum and then falls again. Similar considerations apply
represent active power and similar projections on the horizontal in Fig. 8 to operation either as a generator or a motor.
axis represent reactive power. A counter-clockwise rotation of
vectors is assumed in all these diagrams to be positive, and (3.3) Machine Stability
negative values of <f> correspond to lagging power factors and It is now necessary to consider the question of stable operation.
positive values to leading ones. It then follows that in Fig. 6 In general when an alternator is operating on full load any small
projections of current vectors falling on the horizontal axis to fortuitous increase in the torque of the prime mover is followed
the right of Oy represent lagging reactive power, and to the by a corresponding increase in the pole angle 8; the latter
left leading reactive power. This Figure is thus an elementary increase leads to an increase in the active-power output of the
form of power chart. alternator which restores the rotor—more or less—to its original
An alternator connected to a large power system may be pole angle. However, if the alternator is initially operating at
subjected to substantial output variations, and under these its maximum active-power output point the small fortuitous
conditions it is useful to the power engineer to have a diagram increase in the torque of the prime mover is followed by a
showing, for a given initial steady-state condition (e.g. rated decrease in the output of the alternator. The prime mover will
load), the variation of armature current and power factor caused thus continue to increase the pole angle S until finally the speed
by output variations with constant field current. An elementary of the alternator rises above synchronism and the unit falls out
form of such a diagram is shown in Fig. 7, and in this the locus of step. The corresponding condition in a synchronous motor
of the armature vector is determined by drawing a number of may occur for example in a rolling-mill drive. If the motor is
rays through C and then marking off along each ray from the running on afixedfieldexcitation, the introduction of a piece of
periphery of the semicircle a length representing I//Xd; this material which is either too thick or not hot enough may lead
construction is an extension of that given in Fig. 5. to an increase in the active-power output which exceeds the
The resulting smooth curve drawn through the extremities of maximum output for that particular field excitation and the
these rays is called the "limacon of Pascal," although in Fig. 7 motor will immediately drop out of synchronism.
it appears to be a semicircle. It is thus important that a power diagram should indicate for
the various possible operating conditions the maximum output
(3.2) The Generalized Power Diagram points at various values of field current. As can be clearly
seen from Fig. 8 these points are the maximum and minimum
In the diagrams so far considered, the power-factor angle <f> ordinates of the limacons, and the two smooth curves joining
has been restricted to the range ±90', i.e. they have covered the these points indicate the limits of stable operation; the dotted
operation of synchronous salient-pole machines as generators portions of the limacons thus indicate the unstable region of
operating from zero lagging to zero leading power factor. It the diagram.
is obvious that by extending the diagram of Fig. 7 to cover the
These stability limits start from the intersection of the per-
full range of <f>, i.e. O-36O;>, it will also give the performance of
pendicular at E/Xq with the horizontal axis and decrease
the machine as a synchronous motor operating from zero
asymptotically towards the perpendicular at E\Xd. This per-
leading to zero lagging power factor. This has been done in Fig. 8,
pendicular is, of course, the theoretical stability limit of the
Generator y cylindrical-rotor machine in which the loci of the extremities of
the armature-current vectors are circles with centres at O. It
can thus be seen that when a salient-pole alternator is operating
2: -1-77
at about rated output and power factor, the maximum output
given by the 2-axis theory is slightly greater than that given by
cylindrical-rotor theory. However, if the machine is operating
at a low leading power factor, e.g. charging a long transmission
line during periods of light load, the 2-axis theory shows that
under these conditions the machine has a much higher maxi-
RVA lagging., mum output than is given by cylindrical-rotor theory. This
K.VA leading- increased output, however, can in general only be obtained
by operating with reversed field current in the rotor winding, the
maximum value being obtained in the stable region of the
diagram at the abscissa corresponding to EfXq, i.e. at zero
leading power factor. The armature current and thus the output
at this point are represented by E/Xq, and the required negative
field current, E(llXg — \IXd), corresponds to the diameter of
the circle between the ordinates at E/X and E/Xd.
(3.4) Properties of the Armature Current Loci (Limacons)
It is of interest to note in Fig. 8 that, for the given values of
Xd and Xq, the limacon for full-load field current is almost
Fig. 8.—Armature-current loci for fixed field currents. indistinguishable from a circle, for If = 1-2 amp it has a slight
Salient-pole machine flattening at one side, for If ~ 0-57 amp the limacon takes on
Xri 1 • 1 per unit, Xq -~ 0-7 per unit.
Rated power factor = 0-9 lagging. the special form known as a cardioid with the cusp at the abscissa
E\Xq, and for lower values of If the limacon develops a
and in addition the limacons (armature-current loci) correspond- loop inside the circle as shown in the example for If • 0 18.
ing to various fractions of full-load field current have been This loop can be considered either, in the normal case, as the
included. locus of armature current with negative field current, or as the
In Figs. 6 and 7 it can be seen that as the power-factor angle cf) same locus with positive field current after the machine has
varies from —90° to +90°, the active-power output rises to a traversed a pole angle S greater than 180° and resumed stable
WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES 17
operation on the loop. The curves showing the relationship negative. This final condition corresponds to operation on the
between torque and pole angle can be obtained from Fig. 8 by loop of Fig. 8. In normal operation such a procedure is im-
plotting the projection of / on the vertical axis against the pole practicable, and operation on the loop is initiated with the
angle 8. The resulting curves shown in Fig. 9 demonstrate more required negative field current. Fig. 9 brings out in a simple
manner the concept of saliency as a constant-amplitude second-
harmonic torque superimposed on a fundamental sinusoidal
Round-rotor theory torque whose amplitude varies with the field excitation; and the
same concept, although not so obvious, underlies the geometrical
construction of Fig. 8.

(4) THE ALTERNATOR POWER CHART


(4.1) Constant Voltage
300 360
The form of power diagram shown in Fig. 8 is not suitable for
practical application by power-system engineers, since it does
not indicate, for example, the limitations imposed on the armature
field currents by the permissible temperature rises of the windings.
A practical power chart for cylindrical-rotor alternators has
already been proposed by Szwander,5 and the chart for salient-
pole machines in Fig. 10 follows similar lines.
Since it would be inadvisable to operate an alternator close to
-1-6 the theoretical stability limit, the latter is replaced by a practical
Motor stability limit. In the diagram, the curve is arbitrarily reduced
Fig. 9.—Variation of active-power output with pole angle d. by a constant power value corresponding to (for example) 10 ° o
Salient-pole machine of the rating of the machine, so that at any load on the practical
Xa — 1-1 per unit, Xq — 0-7 per unit.
Rated power factor = 0-9 lagging.
stability limit curve such as 0 • 2 or 0 • 7 kW per unit the kW-load
can be increased to 0-2 + 0 1 = 0-3kWperunit or 0-7 + 0 1
clearly the effect of operating with a field current which produces = 0-8kW per unit before reaching the theoretical stability
a loop in the limagon as in the case discussed above. If, for limit.
instance, the machine is operating at a load of 0-1 kW per unit Large alternators are usually supplied with main and pilot
and /^.= +0-18 per unit, then under carefully controlled exciters with no provision for supplying negative current to the
conditions the load could be correspondingly varied to follow rotor field. In addition the main exciter is often, for simplicity,
the harmonic curve corresponding to If— 0 18 per unit until not fitted with a bias field to overcome residual effects. Under
the load finally resumed its steady value of 0 1 kW per unit. these conditions the excitation system is not capable of reducing
During this procedure the rotor would have traversed a pole the alternator-field voltage (and current) to zero, and it is usual
angle S of approximately 190', and although the absolute here to limit the minimum field voltage to 5 % of that required
direction of the field current has not changed, nevertheless, on rated load. This limit is shown as the segment on the left-
relative to the stator flux, it is 180° out of phase and is thus hand side of the diagram.

Theoretical stability limit Armature


(Round rotor theory) heating limit Power factor
Limit without KW restraint
kW limit

Field heating limit

(Round rotor theory)

10
5% excitation
margin
Fig. 10.—Power chart for salient-pole alternator connected to constant-voltage system.
Xa = 1 • 1 per unit, Xg = 0-7 per unit.
Rated power factor = 0-9 lagging.
VOL. 100, PART II.
18 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES
It is of interest to note that, if for simplicity the power chart
of this particular machine had been based on cylindrical-rotor
theory, the capacity of the machine in the region of leading power
would have been as shown by the dotted stability line and thus
considerably less than that given by the appropriate theory.
This form of chart can be of considerable assistance to the
power-system engineer in determining the capabilities of machines
under varying conditions of active-power loading and power
factors; it is, however, not in a form which can be readily
interpreted by the engineer responsible for the actual operation
of the alternators in a station. The diagram of Fig. 10 may be
modified into the form shown in Fig. 11 which is suitable for

Field current, amp per unit


KVAR
LCADING UAO OINO
3 •t 1 0 • •3 •*

•*= V k\

A \ \
\
\
\ •• 1
V j •7 1
J / •
S .

/
(
/
A \

)
\

L\
S
\
\
i
\
1
\ •J- \ \

\
7_\
Y\ V1 I y \
x
\
;
\

r
\
w1 1
1
1-0 0-8 0-G 0-4 0-2 0 0-2 0-4 0-6
-« Leading kVAr Lagging +*
Fig. 11. Simplified power chart.
Salient-pole alternator.

use by the station engineer. This gives a simple closed curve


within which the loading of the alternator must be confined
under all steady-state conditions of running. At present a
station engineer has in front of him a voltmeter (terminal
voltage), two ammeters (armature current and field current), a Fig. 12.—Combined watt- and VAr-meter with power-chart dial.
wattmeter, a VAr-meter and a power-factor meter. These instru-
ments may or may not be marked to indicate values correspond- operator to see at a glance what action is required to avoid
ing to limitations relative to heating of the alternator windings, instability. This meter arrangement thus eliminates the six
etc., and in either case it is far from common practice, nor is meters mentioned above and at the same time gives the operator
it easy, for the operator to relate the readings on these instruments a clear and precise picture of the extent to which the set is
to the values given on a simple power chart such as that shown operating within its designed limits.
in Fig. 11. This difficulty can be overcome by using a power This can be illustrated by the operation of an alternator in a
chart of the form shown in Fig. 11 as the dial of a combined station whose total output is a relatively small fraction of that
watt- and VAr-meter. The latter has already been described7 of the system to which it is connected. In such a station the
and this so-called "vectormeter" with the power chart of Fig. 11 terminal voltage is normally maintained constant by the system,
as dial is shown in Fig. 12. From this the operator can see at a and the alternator voltage regulator will only operate during
glance both the active- and reactive-power loading on the machine large load changes.
and the corresponding field and armature currents. A power A machine in such a station and with a chart similar to that
chart can be constructed only for one particular voltage, so that of Fig. 11 may, during the night, be operating at 0 • 1 kW and
in stations where the terminal voltage varies over a range a 0-6kVAr (leading) with a field current of 0-2 amp. In the
modification to the above chart is necessary. Assuming the morning there may be a request to increase the active power
normal operating voltage range of the station is ±10%, five quickly to 0-8 kW, and if the turbine governor is set up to give
charts are drawn on a film strip each corresponding to a 4% this power the apparent-power change will proceed along the
change in voltage. This film strip passes across the illuminated 0 • 2-ampfield-currentcurve leading to the alternator falling out of
front of the meter, and the appropriate chart is automatically step. However, if the operator has the vector meter and chart
moved in front of the screen by a mechanism in the meter in front of him, he can see at a glance that before such an active-
actuated from a contact-making voltmeter. power increase takes place he must increase the field current to,
If the excitation and voltage-regulating systems are fitted with say, 0-6 so that the subsequent active-power increase will still
some form of reactive-power limiter which follows very approxi- be within the stable range of operation of the alternator.
mately the contour of the left-hand side of the chart, the instru-
ments merely inform the operator of the loading of the machine, (4.2) Effect of Variable Voltage
and furthermore this limiting device does not permit transient In most large power stations it is necessary to be able to vary
overloads. However, no such limiting device is required when the continuous operating voltage of the alternators between
the vector meter and chart are provided since they enable the limits, such as ±10%, of the normal operating voltage. The
WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES 19
effect of such a variation can be determined by redrawing the extent by the successful operation of machines similar in size
charts of Figs. 10 and 11, in which £ = 1 0 per unit, for a and operating conditions. It is common knowledge that in
terminal voltage of, say, 0-9 per unit. The effect of such a Great Britain many large steam-turbine-driven sets operate with
change on a machine designed for a range of 10 000 to 12 000 volts short-circuit ratios as low as 0 • 5, admittedly under loading con-
is shown in the isometric solid of Fig. 13. ditions which usually differ from those of a hydro-electric unit
and with a different type of alternator. Here again the choice of
ratio seems to have been determined by past successful operation.
It would thus appear that there is now a need to put the choice
of short-circuit ratio and thus of Xd on a firmer basis, and the
analysis given here enables this to be done. There are two
main considerations which determine the correct choice of the
value of Xd for a salient-pole alternator.

(5.1) Loading at Zero Leading Power Factor


Hydro-electric generators are frequently required to excite
long transmission lines during periods of light load, and this
condition sometimes involves, particularly during the early
stages of the development of a hydro-electric system, the
generators supplying the full rated power at zero leading
Per-unit kVA Per-u,hit. kV/ power-factor. As can be seen from Fig. 8, the correct value of
Leading Is Lagging synchronous reactance for this condition depends on the system
Ij-0-09p.u. If*177p.vL. of excitation used.
Fig. 13.—Diagram showing variations in alternator power charts with (5.1.1) Excitation System capable of supplying Positive Excitation Only.
variations in terminal voltage. In this case, the value of Xd must be slightly less than 1 -0 per
As in Fig. 10 the x-axis represents reactive power, but here unit to enable the machine to carry the rated output at the rated
the z-axis represents active power and the y-axis terminal volt- voltage E. This can be seen from Fig. 8, which shows that for
age. Plane E, which is parallel to the base plane F, represents this condition E/Xd must be slightly greater than 1 -0.
constant active power, the cylindrical surfaces G and K represent (5.1.2) Excitation System capable of supplying Positive or Negative
per-unit values of armature current / of 1 -0 and 0-2 amp respec- Field Currents.
tively, and plane H represents a constant limiting stability surface. In this case, for rated output at zero power factor (leading),
The concentric limacoid surfaces A, B, C and D represent the safe operating limit is determined by the condition that
constant per-unit exciting currents of 1 -77 (full load), 1-5, 0-44 E/Xq must "be slightly greater than 1 0 ; thus here it is Xq which
and 0 09 per unit respectively, the last corresponding to the must be slightly less than 1 0 and not Xd as in the previous case.
minimum field current permissible with the particular excitation Apart from the slight increase in cost of the excitation system,
system employed in this case. this alternative could be provided at about 12% lower cost than
Fig. 13 shows clearly the effect of varying voltage on the in the conditions given in Section 5.1.1, since a value of X of
reactive power the alternator is capable of carrying. At 1 0 would give a value of Xd of about 1-6, compared to
12 000 volts the lagging power at zero power factor is given by Xd = 1 0 for the conditions of Section 5.1.1 for the same
pq, whilst at 10 000 volts the corresponding value is the much operating conditions.
greater value given by rs. Conversely at 10 000 volts the leading A further point to be considered here is that a value of Xq,
power at zero power factor is given by ur, whilst at 12 000 volts which gives stable operation at rated output and zero leading
this figure is considerably greater as shown by tp. Similarly power factor with negative field current, may not give stable
at 12 000 volts the alternator can operate at leading power operation at the same rating but at, say, 0-2 leading power
factors with full-load armature current over the substantial factor. This is due to the concavity of the stability limit curve
range represented by the back edge of surface G; the correspond- as shown for example in Fig. 8.
ing range of full-load armature current at 10 000 volts is repre-
sented by the very short front edge of surface G. (5.1.3) Excitation System capable of supplying Positive or Negative
Field Currents and also of ensuring Stable Operation of the
Although such a solid can be used for determining the per- Machine in the Unstable Region of the Power Chart.
formance of an alternator over the practical range of all its In addition to the stability limit already discussed, there is also
parameters, its greatest usefulness is probably in the sphere of the constant-flux stability limit that, as shown by David,3 is
academic exposition; in this latter case the two-dimensional produced by the use of a special excitation system as defined
representation could profitably be replaced by a Perspex or above, and considerably extends the region of stable operation.
wire model. However, since the calculation of this limit involves, inter alia,
transient constants of the machine, it is not really a steady-state
(5) SYNCHRONOUS REACTANCE OF ALTERNATORS. condition and is thus outside the scope of the paper.
DETERMINATION OF THE APPROPRIATE VALUE
It has been common practice in the past for purchasers of (5.2) Operation at or near Rated Power Factor
large generators to specify, inter alia, the value of short-circuit The location of a power station near to the main load centre
ratio and thus the value of its approximate inverse (the syn- usually obviates the necessity of the generator supplying leading
chronous reactance) that they consider appropriate. A common power output to the system, and it is in these cases that there
value of the short-circuit ratio for hydro-electric generators has been the greatest lack of clarity and reliance on past experi-
operating at 0-85-0-90 power factor has been 10, corresponding ence concerning the correct choice of the value of Xd.
to a value of synchronous reactance of about 1 • 1 per unit. It A consideration of Fig. 8 suggests two possible methods of
would appear that the choice has been determined to a large determining the most suitable value of Xd.
20 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES
(5.2.1) Stability at Rated Load and Power Factor. the inertia of the rotor and flywheel that avoid the possibility of
With this condition the alternator can be designed to be stable resonance between the engine impulses and the natural electro-
(with a suitable margin) at rated load and power factor only; mechanical period of oscillation of the rotor and flywheel.
the machine would, of course, operate stably from the rated This condition has to-day lost its importance, since it is now
power factor to zero lagging power factor, though with reduced possible to design the damper winding on the rotor in such a
output, in order not to exceed constant full-load field current. manner that it reduces to negligible proportions any such
Under these conditions the synchronous reactance could have the resonance effects.
values shown in Table 1.
Table 1 (5.4) Inherent Voltage Regulation
All industrial and central-station alternators are now supplied
Output at rated with automatic voltage regulators as standard equipment. Under
Rated volts
power Xd
Short- these circumstances the value of the inherent voltage regulation
Stability criterion circuit
factor (per unit) ratio is practically worthless as a criterion of satisfactory performance;
(lagging) Zero p.f. Zero p.f.
(lead) (lag) it should therefore neither be specified by the customer nor
should the manufacturer be required to state an approximate
kVA kVA value since even the latter condition may cramp the design of
[per unit) (per unit)
the machine.
Stable from full load 0-8 2-9 0-40 0-35 0-90
to zero lagging 0-9 2-5 0-45 0-40 0-80 (5.5) Effect of Specifying Transient Reactance X'd
power factor only 10 2-2 0-50 0-50 0-60
To a certain extent all the above considerations are overridden
Stable from no load 0-8 11 100 0-80 0-75 by the choice of the value* of the transient reactance X'd of the
to full active-power 0-9 0-95 110 0-90 0-65
output 10 0-85 1-25 100 0-30 machine.
A normal large low-speed water-wheel alternator has a natural
transient reactance X'd of 30-35 %, and the values of the second
(5.2.2) Stability at No Load. set of synchronous reactances given in Table 1 correspond to
Consider the condition in a large power station with an this value of Xd. However, if a system analysis shows that the
alternator connected to the busbars but not supplying load. If machine must have a transient reactance less than the natural
now conditions require the active-power load of the alternator value, the purchaser should not assume that the machine will
to be rapidly increased to full load, then if for any reason the have a correspondingly reduced value of Xd. In the absence
voltage regulator is under hand-control or, owing to an absence of any special requirements relative to operation at leading
of terminal-voltage change (see Section 4.1), does not operate, power factors, the extent to which Xd is reduced with X'd is
and the field current is thus not increased, the machine may again a matter for the machine designer alone.
fall out of step if the value of synchronous reactance is too high.
Suitable maximum values of Xd, together with the corresponding (6) POWER CHARTS FOR SYNCHRONOUS MOTORS
short-circuit ratios to avoid this condition, are given in Table 1; The characteristics of synchronous motors are given, as in the
it may be a coincidence, but it is nevertheless interesting to note case of alternators, by the fundamental diagram of Fig. 8; the
that the values thus obtained are those which many customers curves applicable to motors are below the horizontal axis and
specify or manufacturers recommend for large alternators to are mirror images of those above the axis.
satisfy average operating conditions; i.e. those not requiring The procedure for developing power charts for synchronous
large amounts of kVA at low leading power factors. motors is thus exactly the same as that for alternators, although
The values of Xd and short-circuit ratio given in Table 1 for the manner of arranging motor charts will differ from that for
this condition and that of Section 5.2.1 are only to be regarded generators.
as examples of the manner in which these machine quantities In the first place the power loading on the motor is determined
may be specified. These quantities could if required be specified, entirely by the requirements of the apparatus being driven, and
for example, to ensure that the machine operated stably on in the second place the majority of motors operate with a fixed
rated output from rated power factor, say 0-8 lagging, to 0-5 field current, so that the amount of leading or lagging power
leading power factor; this condition would require a value of supplied to or drawn from the line is determined, for a given field
Xd differing from either of those given in Table 1. current, entirely by the power load.
The importance of selecting the correct value of Xd for a given Under these conditions a normal motor runs more or less
set of conditions must be emphasized. On the one hand, the unattended, and there is little point in providing a combined
cost of an alternator will, in general, vary inversely with about watt- and VAr-meter with a power chart as previously described.
the fourth root of the synchronous reactance, so that a decrease Nevertheless a chart of the form shown in Fig. 14 can be of
of Xd from 200% to 100% (i.e. doubling the short-circuit ratio) considerable value in determining, in conjunction with the
will increase the cost by about 20%. On the other hand, for a characteristics of other parallel electrical loads, such as induction
given rated load and power factor, the value ofXd exactly defines motors, the optimum rating of the motor, the active-power
the stability limit of the machine under steady-state conditions. rating being determined, of course, by the shaft load on the
It therefore follows that it is preferable for a customer to synchronous motor.
specify in detail only the operating conditions and not the
synchronous reactance or the short-circuit ratio of an alternator. (7) OPERATION OF A SYNCHRONOUS CONDENSER
The choice of the best values for these constants should be left The main purpose of synchronous condensers on large power
to the design engineer. systems is to maintain constant voltage by supplying varying
amounts of lagging or leading power to the line in accordance
(5.3) Parallel Operation of Alternators driven by Internal with the conditions ruling at the moment.
Combustion Engines The only active-power loading on the machine is represented
It has been common practice in the past to select those com- • Here again the value of this parameter should not be settled capriciously, but
should be determined by a proper analysis of the system. As shown by Ross, 8 an
bined values of the synchronous reactance of the alternator and unduly low value of X'$ requires a relatively expensive machine.
WALKER: OPERATING CHARACTERISTICS O F SALIENT-POLE MACHINES 21

•» Lagging kVAr in the negative direction, it is possible for the machine to


Leading — •
1-2 1-0 0-8 0-6 0-4 0-2 0 supply 90% of its rated output at zero lagging power factor
0-2 . 0-4 0-6
without any change in the dimensions or characteristics of the
condenser. It is not possible to exceed this figure of 90% since
otherwise the losses in the machine itself will lead to unstable
operation as shown by the armature-current locus corresponding
to IfIXd~ — 0-33. The vector diagram for this condition of
operation at maximum stable output is shown in Fig. 15(6).
Conditions are not usually as clear cut as the above discussion
would imply since in many cases the transient stability of the
system to which the condenser is connected may set a maximum
limit to the transient reactance of the machine. It is impossible
to lay down a hard and fast rule for the relationship of transient
and synchronous reactances in a given machine; for this reason
it is essential, in order to obtain the most economical arrange-
ment, that the purchaser of a condenser should specify only the
transient reactance (preferably obtained from a network analysis
of the system) of the machine and the fraction of the rating at
Fig. 14.—Power chart for salient-pole synchronous motor. zero leading power factor that it is required to supply at zero
Xd = 1 -28 per unit, Xq =- 1 08 per unit. lagging power factor.
Rated power factor -••- 1 -0.
It is undesirable for either the purchaser or his consultant to
by its losses which are supplied from the line. The condenser specify the value of the synchronous reactance (or the short-
is thus a special case of the synchronous motor, but, since the circuit ratio) since the values of these parameters which give the
losses are practically constant and represent only 2-3% of the most economic condenser for the given operating conditions can
rating of the machine, the power charts already described have usually be best determined by the machine designer.
little practical application. Nevertheless, a power chart in a
restricted form is of interest in investigating the performance of (8) OPERATION AS A SYNCHRONOUS RELUCTANCE
synchronous condensers when operating at zero lagging power MACHINE
factor, since on zero leading power factor the internal voltage It can be seen from Fig. 8 that one locus for the armature
and thus thefieldcurrent are given by the arithmetic sum of the current vector is the circle drawn with centre on the .v-axis and
short-circuit current E\Xd per unit and the per-unit armature touching the two ordinates at E/Xd and E/X^ that corresponds
current. The synchronous-condenser operating characteristics to zero field current. It thus follows that a salient-pole machine
on zero lagging power factor are given by the curves in the left- will operate as a motor or generator with no field excitation
hand quadrant of Fig. 8 below the horizontal axis, and this although with a substantial reduction in power output. Advan-
area has been considerably magnified in Fig. 15(o), which has tage has been taken of this phenomenon in the development of
the well-known synchronous reluctance motor; this machine is
Constant power line , kW (machine loss)
usually manufactured by simply milling a number of longitudinal
slots in the rotor of a standard squirrel-cage induction motor.
The number of these slots corresponds to the number of poles
of the stator winding, and the width of the slots is arranged to
give the maximum ratio of XJXq consistent with an acceptable
value of magnetizing current. The combined power chart and
008 vector diagram of such a motor is shown below the horizontal
•v-O-33 / axis in Fig. 16, and it can be seen that it operates inherently at
\ Theoretical
stability limit Generator
•+0-48'

Per-unit KVAr
(lead) R
Fig. 15. -Characteristics for synchronous condenser operating Per-unit k W
on zero lagging power factor.
(a) Condenser supplying lagging output.
Xd ~ 1-7 per unit, Xa = 1 -0 per unit.
Machine loss -=2% of rated output.
(b) Current vector diagram at maximum stable power.
95% full load power.

been drawn for values of Xd = 1-7 per unit and Xq = 1-0 per unit
appropriate to a typical synchronous condenser. It can be seen
that in order to operate with a small positive field current it is Motor
necessary to restrict the lagging power to 50% of the rating at Fig. 16.—Combined power chart and vector diagram for a
zero leading power factor. However, if the excitation system is synchronous reluctance motor.
designed to reduce the field current to zero and then increase Xd 2-22 per unit, Xq -••= 0-78 per unit.
22 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES
a low lagging power factor. A high power factor could be and the values of all three variables on the right-hand side of
obtained only by an impermissibly small radial air-gap to give a this equation are now known.
low value of magnetizing current. If it is required to calculate only the curves of Fig. 8 but
For this reason the reluctance motor is used only in those not those of Fig. 9, then eqns. (1) to (4) can be simplified to a
applications requiring less than about 10 h.p. single equation, which involves much less labour, as follows:
These machines are occasionally used as reluctance generators,
and Fig. 16 shows that in this case the machine can generate only ~ ~\ cos 8 (6)
at a low leading power factor. This may introduce difficulties
in practical operation because in industrial installations none of in which r is the length of a ray, drawn in Fig. 8, from the
the loads connected to the infinite busbar may have the charac- value of E\Xq on the horizontal axis, to the required locus.
teristics required by the reluctance generator. The curve traced out by this equation for varying values of 8
is, of course, the limacon of Pascal.
(9) ALGEBRAIC ANALYSIS The theoretical stability-limit curve is plotted from the follow-
(9.1) The Excited-Rotor Machine ing equation:
From the geometry of Fig. 1 it can be seen that the pole angle 8 E
is given by ^=1--^-
1- \ . . (7)
S-arctan (1)* x. xj • '
,E//^-sin in which d and y are co-ordinates of the stability curve. The
derivation and method of applying this equation are given in
and from similar considerations the internal voltage Eo, and Appendix 13.1.
thus t h e field current If, for t h e given values of E, / , a n d <f> is
It is interesting to note the types of limacons which are obtained
obtained from
for various values of E^Xd. If EJXd > (E/Xg - E/Xd) then,
Eo = IXdsin (8 - <f>) + E c o s 8 . . . (2) for example, the smooth outer curve of Fig. 8 is obtained; as
EfJXd -> (E/Xg — EIXd) the curve exhibits an increasingly
T h e value of <f> for a n y required value of 8 is easily derived marked depression at the left side on the horizontal axis. When
from eqn. (2) a n d Fig. 1 a n d is given by E0/Xd - m\IXq - UXd), eqn. (6) becomes
f;
0 — 8 — arc tan \
E sin 8
' VI . .
tan8/J
(3) . . . . (8)

Correspondingly, by derivation from eqn. (1), the value of / which is the equation to the cardioid, and the depression now
for the same value of 8 is given by becomes a cusp with its point at the origin of r.
With Eo/Xd < E{\IXq — l/Xd) the limacon develops a loop,
1
. • (4) as can be seen in Fig. 8, this loop being the armature-current
XAcos <£/tan 8 + sin <f>. ) • locus for negative values of field current.
These are, in essence, for steady-state operation, the four When EJXd = 0, i.e. zero field current, eqn. (6) simplifies to
fundamental equations of the salient-pole machine from which
all steady-state operating characteristics can be derived. COS (9)
These equations can be applied to the calculation of, for
example, the curves of Fig. 8. The values of Xd and Xq being which is, of course, the equation to the circle in Fig. 8. It is
known, a required locus, say that for the field current corre- also the equation for the current locus of the reluctance machine
sponding to rated terminal voltage load and power factor, is (see Fig. 16).
calculated as follows. It can be seen from eqn. (6) and Fig. 7 that the equation for
The value of 8 at rated load is calculated from eqn. (1) and per-unit active power is
from this the value of internal voltage and thus the field current
on rated load are obtained from eqn. (2). To facilitate further P = rE sin 8
calculation a number of suitable values are assumed for 8 and
the corresponding values of <f> and / are calculated from = HT S i n 28 . (10)
eqns. (3) and (4), the previously calculated value of EJXd at
rated load being treated as a constant. The outer curve of To find the value of 8 at this maximum power and thus the
Fig. 8 can then be plotted from these results. A similar procedure maximum power, eqn. (10) is differentiated with respect to 8 and
is adopted for the remaining loci in Fig. 8, in each case the equated to zero, thus obtaining
starting point being the calculation of E0/Xd for a given value
of / at the rated power factor.
If, as previously suggested, E and / are expressed as per-unit
values, then, at rated voltage and load, E and / are unity. To By substituting these values of 8 in eqn. (10) the value of maxi-
calculate the above set of curves for a different value of E, say mum power is readily obtained.
at 90% of terminal voltage, it is only necessary to re-evaluate Reference was made in Section 3.4, in connection with
eqns. (l)-(3) using E—- 0-9 per unit instead of E = 1 per unit. Figs. 8 and 9, to the fact that the power curves represent a
The curves of Fig. 9 can now easily be obtained from the fundamental torque with a second-harmonic torque superimposed
previous calculations, since on it. This is also shown, in algebraic form, by eqn. (10).
Per-unit active power = El cos <f> (5)
(9.2) The Reluctance Machine
* A counter-clockwise rotation is assumed to be positive. The zero position (see
Fig. 8) for the armature current vector is along the active-power axis above the apparent- For the excited salient-pole machine the armature current
power axis. The zero position for the internal voltage vector is along the apparent-
power axis and to the right of the ordinate at EIXq. and power factor are specified at the outset, but with the
WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES 23
reluctance machine it is necessary to determine these quantities (11) ACKNOWLEDGMENTS
for a specified active-power loading. In order to retain the The author is indebted to the Directors of the British Thomson-
simplicity of the per-unit system it is necessary to assume Houston Co., Ltd., for permission to publish this paper. He also
an approximate full-load current in amperes and use this in wishes to thank Mr. L. D. Anscombe, M.A., Member, of the
calculating the per-unit values of Xd and Xq. It is important same Company, and a number of colleagues for advice and
to note that the extent to which the assumed value differs from criticism, and to acknowledge his debt to another colleague,
the value obtained from the following equation has no effect Mr. N. Kerruish, M.A., for assistance in the mathematical
whatever on the accuracy of the per-unit value of current analysis. Messrs. Nalder Bros, and Thompson Ltd., London,
calculated from, for example, eqn. (14). The assumed value of kindly supplied the meter details of Fig. 12.
per-unit current should, of course, lie within the theoretical
current range of the machine, i.e. E\Xd to E/Xq.
The power output is given by eqn. (10) after omitting the left- (12) REFERENCES
hand term since the machine has no rotor excitation and (1) MORTLOCK, J. R., and DAVIES, M. W. H.: "Power System
is zero. Thus Analysis" (Chapman and Hall, 1952), p. 179.
(2) GIBBS, W. J.: "Algebra of Electric Machine Analysis"
(Technical Monographs—The British Thomson-Houston
Co., Ltd.).
By differentiating with respect to 8 and equating to zero, the (3) DAVID, H., and FAVERAN, J.: "Stability of Alternators with
value of 8 for maximum power is found to be 45°, which is Series Excitation connected by a Long Line to a High
obvious from Fig. 16. Power System," C.I.G.R.6., 12th Session 1948, Vol. 3,
The equation for maximum power thus becomes Paper No. 305.
E 1 (4) ANGELINI, A. M.: "General Topogram for Synchronous
p (l-XA Machines," ibid., Vol. 2, Paper No. 114.
*'"»* 2\Xq X d) • • • • (5) CRARY, S. B.: "Power System Stability, Vol. 1" (Chapman
The current and power factor at any given active-power loading and Hall, 1945), pp. 114-150.
are given by (6) SZWANDER, W.: "Fundamental Characteristics of Syn-
E [~1 + chronous Turbo-Generators," Journal I.E.E., 1944, 91,
Part II, p. 185.
x (7) British Patent No. 568166.
British Patent Application No. 11295, 1952.
<f> —• arc cos f - British Patent Application No. 13137, 1952.
± vci - (8) Ross, P. G.: "Some Notes on the Transient Reactance of
. . . . (15)* Water-wheel Alternators" (Proceedings—B.T.H. Summer
in which p is the per-unit rated load referred to the maximum School, 1952).
output [eqn. (13)].
Since the losses in this type of machine are high they must (13) APPENDICES
be added to the active-power output to give the per-unit rated (13.1) Derivation of the Equation for the Pull-Out Point of
load. a Salient-Pole Machine
At maximum output, i.e. p = 1, eqn. (14) reduces to
For simplicity assume terminal voltage E = 1.
Then sin 8 = IqXq and Eo — cos 8 - IdXd
and eqn. (15) to where Id — / sin (8 — </>) and Iq --- I cos (8 — <f>)

Let / cos <f> -- y and / sin (f> - - x

At zero output, i.e. p — 0, eqn. (14) reduces to therefore sin 8 = Xq(y cos 8 + y sin 8 tan <f>) . . . (20)

Eo — cos 8 = Xd(y sin 8 — y cos 8 tan <j>) . . (21)


7=--or — (18)
A A
d q The pull-out point is where /cos (f>, i.e. y, is a maximum and it
and eqn. (15) to <^ arccosO = 90° (19) is required to find the maximum value of y for a given £ 0 .
For maximum y, dy\d<^> = 0.
(10) CONCLUSIONS Differentiating eqns. (20) and (21) with respect to <f> and
The paper has shown that a simple vector diagram, based on putting dy/d<f> — 0
the 2-axis theory, can be developed for a salient-pole machine. d8 „ / . r,d8 ,dS
,ao . ~ i i\
e
This diagram can form the basis of a power chart that, used in cos -jy = Xqy(~
s
,, + cos o t a n <pJ± -\- sin o sec 2 «p J
sm odcf>
conjunction with a combined watt- and VAr-meter, gives an
operator a ready means of maintaining the load on an alternator (22)
within the machine operating limits, particularly those relating and
to stable working. It is shown that in order to obtain the
cheapest and most economical machine it is preferable that the 2
sin 8 -j-. --= XHy(cos 8 -,-. + sin 8 tan d>
T n — cos 8 sec <f>) . (23)
purchaser should specify the operating conditions only, and that dcp \ d<p d(p J
the choice of appropriate machine constants such as synchronous Eliminating dS/dcf) from eqns. (22) and (23) and simplifying:
reactance should be left to the machine designer.
* For the derivation of these equations see Appendix 13.2. Xd cos2 8 + Xq sin2 8 = XdXqy tan (24)
24 WALKER: OPERATING CHARACTERISTICS OF SALIENT-POLE MACHINES

By using the relationship of eqn. (20) it follows that For per-unit values of E other than 1 0 this equation is
written
* s yxQ
tan o = -— j r y— i J v ~v
1 — xXq

Divide eqn. (24) throughout by cos2 8 so that Since for any values of E, Xd and Xg, d always lies between
1 and 0, the values of y' from the equation

(28)

This reduces to can be calculated, once and for all, as in Table 2, so that for a
. • • (25) given machine the values of y in eqn. (27) can be obtained by
multiplying the values of y' by (E/Xq — EIXd).
The co-ordinates of any point on the theoretical stability
curve of, for example, Fig. 8 are thus given by x and y in (13.2) Derivation of Current and Power-Factor Equations of
eqn. (25), since this stability curve, in effect, passes through Reluctance Machine
all the points of maximum active-power output for the various In Fig. 16 the diameter of the circle is given by E(l/Xq— 1/Xd).
limacons shown in this Figure. Let this be replaced by 2k. The vertical NQ is a measure of
A more convenient form for calculation is obtained by the power output; let this output as a fraction of the maximum
replacing the x-co-ordinate by d: output [eqn. (13)] be represented by p. From eqn. (6), RN in
Fig. 16 equals 2k cos 8. Let OM in Fig. 16 equal i.
Then from the triangle NQO
(29)
and from triangle RNQ
Eqn. (25) then reduces to (2k S^ 8)2 - 4fc2 COS2 8 . . (30)

This gives cos2 8 =


• • • « >
Substituting this in eqn. (29) gives
Table 2

d
Replacing / and k by their actual values and simplifying, gives
E
005 4 4-140 T f1 ±
010 2-700 7 J •
0-20
0-30
1-600
1070
LFig. 16
Again from
0-40 0-735 pk
0-50 0-500
0-60 0-327 I
0-70 0196
0-80 0100
0-90 0033
100 0 ± vo -
. . . . (32)

You might also like