You are on page 1of 16

Automatic Transfer Switch (ATS)

Generator Transfer Switch (GTS)

ATS GTS

Installation Manual
020-161-B0 Rev. –  01 / 07

Alpha Technologies
Power
Alpha Technologies ®
Installation Manual
Automatic Transfer Switch (ATS)
Generator Transfer Switch (GTS)

From Alpha Technologies (www.alpha.com)


020-161-B0  Rev. – 01 / 07
Save This Manual: It contains important installation and operating instructions. Keep it in a safe place.

Table of Contents
The emergency shutdown procedure is on the inside rear cover

1 Safety Checklists......................................... 1
2 Overview...................................................... 2
3 Mounting the ATS/GTS................................ 3
4 Wiring the ATS/GTS to the UPS.................. 5
Specifications................................................. 8

DANGER
Risk of Electrical Shock
To reduce the risk of electrical shock and to ensure the safe operation of the ATS/GTS, the symbols
below are used throughout this manual. Where they appear, only qualified personnel should carry out
these instructions.

A dangerous voltage exists in this area. Use extreme caution at all times.

Attention: Important operating instructions. Follow them exactly.


1 Safety Checklists

PRELIMINARY: For Information Only


The ATS and/or GTS are to be installed by people trained in the safe use of high-energy
power supplies and their batteries. Also assumed is knowledge of the local electrical
code(s) and their safe application.

DANGER: NEVER let water from rain, a hose, tap or a sprinkler’s output, road splash or
other water sources enter the enclosure of the ATS/GTS to prevent accidental shorts,
shocks or electrocutions.

DANGER: This unit does NOT have an on/off switch. Whenever it is connected to line or
battery power, power is present at the output. Use extreme caution at all times.

 Do not work alone under hazardous conditions.


 Read this manual. If you have any questions about safe installation, operation or
maintenance, contact Alpha Technologies’s customer service department.
 Use this manual together with the Operator’s Manual of the UPS.
 Carefully unpack the components. Report any shipping or other damage at once.
 Always assume electrical connections or conductors are live. Turn off all circuit breakers
and double-check with a voltmeter before performing installation or maintenance.
 Before installation, verify the input voltage and current requirements of the load are met by
the UPS’s output (See specifications). Verify the line voltage and current meet the UPS’s
input requirements.
 The ATS/GTS have more than one live circuit. AC power may be present at their outputs
even if the UPS is disconnected from line or battery power.
 The ATS/GTS can be operated to a maximum operating temperature of 55°C. Also see the
specifications section for temperature ratings.
 At high ambient temperature conditions, the enclosure’s surface can be very hot to the
touch.

Doc# 020-161-B0 Rev. – 01 / 07 


ATS/GTS Installation Manual

2 Overview

The Automatic Transfer Switch (ATS) (Figure 2.1) and the Generator Transfer Switch (GTS)
PRELIMINARY: For Information Only

(Figure 2.2) are optional add-on switching units specifically designed for (but not limited to) the
FXM family (FXM 650, 1100, 1500 and 2000) and the Novus Micro family (Micro 300/600/1000,
Standard, XL and XL3) of UPS. These switching units provide power and/or bypass capacity
(automatic or manual) so that the operator may safely disconnect the UPS from line or genera-
tor power for easy removal and servicing. In bypass mode, the loads are directly connected to
the line or generator power without any conditioning. The ATS and/or GTS allow the use of 3
different back-up sources (line, batteries and/or generator).

CB2

120 VAC Output


option (NEMA 5-15R)

SW1

CB1
Figure 2.1
Automatic Transfer Switch (ATS)

SW1

Figure 2.2
Generator Transfer Switch (GTS)

 Doc# 020-161-B0 Rev. – 01 / 07


3 Mounting the ATS/GTS

The ATS and GTS can be mounted as stand alone, chassis (e.g. on the external bottom enclo-

PRELIMINARY: For Information Only


sure of the Novus Micro family UPS) or rack (e.g. inside the end system enclosure of the FXM
family UPS). The following diagrams illustrate some of the possible configurations.

Top

Front Side

Figure 3.1 – ATS mounting views (stand alone)


MOUNTINGEAR - TOPMOUNTED

MOUNTINGEAR - REARMOUNTED

Figure 3.2 – ATS mounting view (chassis mounted)

Figure 3.3 – ATS mounting view (rack mounted)


Doc# 020-161-B0 Rev. – 01 / 07 
ATS/GTS Installation Manual
PRELIMINARY: For Information Only

Figure 3.4 – GTS mounting view (rack mounted)

Figure 3.5 – ATS & GTS mounting view (rack mounted)

 Doc# 020-161-B0 Rev. – 01 / 07


4 Wiring the ATS/GTS to the UPS

The ATS/GTS should be wired to the UPS as shown in Figure 4.1 below.

PRELIMINARY: For Information Only


The ATS/GTS/UPS end system must be correctly grounded for proper operation.
Older facilities may have inadequate electrical grounding. Inspection must be performed
by a qualified electrician before installation to ensure that grounding meets the local
electrical code.

To provide branch circuit protection, the utility line attached to the ATS/GTS/UPS’s
input MUST be protected by a circuit breaker certified for this use as per the local
or national electrical code.
The breaker’s minimum size is calculated by the following formula:
Minimum Breaker Size= UPS’s maximum input current / 0.8
The unit’s maximum input current is read off of the UPS’s nameplate. For example, if the
nameplate gives the maximum input current as 25A, the circuit breaker should be rated
at least 30A.

The input and output lines to and from the ATS/GTS/UPS system MUST have
1 2 3 4 5 6

disconnect devices attached.WIRING DIAGRAM

A
FXM FAMILY A

UPS L

N GEN
INPUT OUTPUT L

L N G L N G G GTS LINE OUT N


L
G
L N G L N G LINE IN
N
TO UPS FROM UPS SCREW LUG
LOAD G
B
L L B

SCREW LUG
N
LINE IN ATS LINE OUT N

G
G
FXM FAMILY
SCREW LUG
SCREW LUG
UPS
INPUT OUTPUT

L N G L N G
Fig 1. ATS & UPS TO UPS FROM UPS
LOAD
C L L C

LOAD/UPS INPUT
L
FXM FAMILY
N LINE OUT
ATS LINE IN
N
N GEN
L G G
G LINE
TOOUT
GTS
UPS
N SCREW LUG SCREW LUG

L G
LINE IN
N
SCREW LUG
G

D
Fig 3. ATS & GTS D
SCREW LUG
Fig 2. GTS

If stranded wires are used, ferrules or equivalent crimping terminals must be used.
1 2 3 4 5 6

Figure 4.1 – ATS/GTS to UPS Wiring Diagram

Doc# 020-161-B0 Rev. – 01 / 07 


ATS/GTS Installation Manual

ATS
PRELIMINARY: For Information Only

• With SW1 & CB1 On – Unit is in UPS


Mode

• With SW1 Off, CB1 On – Unit is in


Bypass Mode

• With SW1 On, CB1 Off – UPS Inverter is


supplying power (Not recommended)

• With SW1 & CB1 Off – Unit is in Bypass


– Service Mode

Figure 4.2 – ATS schematic diagram

GTS
• With SW1 On – Automatic Generator
Transfer is Enabled
• With SW1 Off – Generator Transfer is
Disabled

Figure 4.3 – GTS schematic diagram

 Doc# 020-161-B0 Rev. – 01 / 07


PRELIMINARY: For Information Only
Figure 4.4 – ATS & GTS Schematic diagram

Servicing the UPS

• ATS: Turn off CB1, SW1 and battery CB of the UPS.


• GTS (UPS connected to Line Out): The main source branch CB protection coming either
from Generator or Line has to be turn-off. Likewise, battery CB of the UPS has to be turn-
off.
• ATS and GTS combine: Turn off CB1, SW1 and battery CB of the UPS.

Other Note:
• Simplex 5-15R receptacle is for 120V (rated 5A) only.
• 2 position mate and lock connector is for 230V only.

Doc# 020-161-B0 Rev. – 01 / 07 


Due to ongoing product improvements, specifications are subject to change without notice
ATS/GTS Installation Manual

ATS/GTS – Mechanical Specifications


PRELIMINARY: For Information Only

Dimensions, in (mm) 3.25 x 5.3 x 4.5


H x W x D (82 x 135 x 114)
Weight, lb (kg) 3 (1.36)
(stand alone)
Material sheet metal, 1.2 mm thick
Color Black
Mounting options Stand alone, chassis or rack mounted
Connections
• Line In 2 position TB Weco #327-HDS-02 or equivalent.
• Line Out 2 position TB Weco #327-HDS-02 or equivalent.
• From UPS or Gen 3 position TB Weco #324-HDS-03 or equivalent.
• To UPS 3 position TB Weco #324-HDS-03 or equivalent.
Recommended Wire Size
• Line In AWG #14 – #6 AWG
• Line Out AWG #14 – #6 AWG
• From UPS or Gen AWG #22 – #10 AWG
• To UPS AWG #22 – #10 AWG
Note: Terminate all stranded wires with ferrules or
equivalent crimp terminals.

Humidity
Up to 95% (RH)
• Operating (non-condensing)
• Storage
Up to 95% (RH)
Temperature Range, °C
• Operating –20 to 55*
• Storage (non-operating) –40 to 75
* capable of operating up to 75°C for 8 hours
Altitude, ft (m)
• Operating Up to 12,000* (3658)
Up to 15,000 (4572)
* de-rate 2°C per 1000 ft above 4500 ft.
• Storage (non-operating) >15000 ft

ATS/GTS – Electrical Specifications


Input
Voltage (nominal), VAC 120 or 230
Frequency, Hz, ±5% 50/60
Current, Amps
30/16 @120/230VAC
(@ nominal Vin)
Power, VA 3600
Power Factor 0.8 to 1.0
Output
Voltage (nominal), VAC per UPS, Line or Generator
Frequency, Hz, ±5% 50/60
Power, W/VA 3600
Regulatory
Electrical Safety CSA 107.3–05
Immunity CE (for 230V version)

 Doc# 020-161-B0 Rev. – 01 / 07


This page is intentionally left blank.
This page is intentionally left blank.
Emergency Shutdown Procedure
The ATS/GTS does not have an on/off switch. Whenever it senses battery or line
power, there is power present at the outputs and the unit is active.
1. Turn off the circuit breaker providing line power to the unit.
2. Disconnect the batteries from the UPS.
3. Turn OFF the attached generator (if connected).

For emergency technical support 7 days a week/24 hours a day, call:


USA: 1 800 863 3364 Canada: 1 800 667 8743
www.alpha.com
Complete the following for your records
Serial # _________________________________________
Options_________________________________________
Purchase Date ___________________________________

This Novus Micro Secure 100 was purchased from


Dealer__________________________________________
City_ ___________________________________________
State/Province____________________________________
Zip/Postal Code___________________________________
Country _________________________________________
Telephone # _____________________________________
Fax # _ _________________________________________
E Mail Address ___________________________________
Power
Alpha Technologies ®

Alpha Technologies
3767 Alpha Way
Bellingham, WA 98226
USA
Tel: +1 360 647 2360
Fax: +1 360 671 4936
Web: www.alpha.com

Alpha Technologies Ltd.


4084 McConnell Court
Burnaby, BC, V5A 3N7
CANADA
Tel: +1 604 430 1476
Fax: +1 604 430 8908

Alpha Technologies
Europe Ltd.
Twyford House
Thorley
Bishop's Stortford
Hertfordshire
CM22 7PA
UNITED KINGDOM
Tel: +44 0 1279 501110
Fax: +44 0 1279 659870

Alpha Technologies GmbH


Hansastrasse 8
D 91126 Schwabach
GERMANY
Tel: +49 9122 79889 0
Fax: +49 9122 79889 21

Alphatec, Ltd
P.O. Box 56468
Limassol, Cyprus
CYPRUS
Tel: +357 25 375675
Fax: +357 25 359595

AlphaTEK ooo
Khokhlovskiy Pereulok 16
Stroenie 1, office 403
109028 Moscow
RUSSIA
Tel: +7 495 916 1854
Fax: +7 495 916 1349

Alphatec Baltics
S. Konarskio G. 49
Vilnius 2009
LITHUANIA
Tel: +350 5 210 5291
Fax: +350 5 210 5292

Alpha Technologies
5 Avenue Victor Hugo
F 92140 Calmart France
FRANCE
Tel: +33 3 41 90 07 07
Fax: +33 1 41 90 93 12

Due to continuing product improvements, Alpha reserves the right to change specifications without notice.
Copyright © 2007 Alpha Technologies, Inc. All rights reserved. Alpha is a registered trademark of Alpha Technologies. 020-161-B0  Rev. –  01/07.
    

You might also like