FI002K0021v1100UK – THS/21E and THS/21 Programming Manual

Industrial Metal Detectors


THS/21E & THS/21
Programming Manual

Document code Date Software version


FI002K0021v1100UK 20/12/2011 THSV5401 – ALMV5400

Read this Manual carefully before installing, operating or carrying out maintenance on the device. Keep the Manual in a safe
place for future reference, and in perfect condition. This Manual must accompany the device described therein in the
case of change of ownership, and until the device is broken up.

1
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual

SYMBOLS
The equipment is marked with this symbol wherever the user should refer to this Manual in order to avoid possible
damage. The same symbol appears in the Manual at points where warnings or particularly important instructions,
essential for safe, correct operation of the device, are given.
The equipment is marked with this symbol in the areas where there is dangerous voltage. Only trained maintenance
personnel should carry out work in these areas. The same symbol appears in the Manual at points where warnings
essential for safe, are given.
This symbol appears in the Manual at points where suggestions, additional information or other relevant notes are given.

REVISION RECORD
Revision Date Author Reference Description
1000 09/11/2010 TP2 – SP - First Emission – Upgrading FI025GB2K8v6
1001 06/04/2011 TP2 – SP - Web server, Bin lock, USB management
1100 07/10/2011 TP2 – SP - Upgrade to THSV5401

2
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual

CONTENTS
1  SAFETY INSTRUCTIONS – WARNINGS ....... 5 
3  PROGRAMMING PARAMETERS ................. 15 
1.1  General warnings ...................................... 5 
3.1  Administrator .......................................... 15 
1.2  Correct use of the device .......................... 5 
3.1.1  Remote passwords .................................. 16 
2  PROGRAMMING ............................................. 6  3.2  Reset ...................................................... 17 
2.1  Access to Programming ............................ 6  3.3  Product selection .................................... 17 
2.1.1  Factory preset configuration ....................... 6  3.4  Products.................................................. 18 
2.1.1.1  Access levels ..................................... 6  3.4.1  Save prod.to USB .................................... 20 
2.1.1.2  Remote Communication..................... 7 
3.4.2  Load prd. from USB ................................. 22 
2.2  Administrator functions ............................. 7 
3.5  Autolearn ................................................ 24 
2.3  Configuration of the system by the
Administrator ............................................. 7  3.6  Autolearn-advanc ................................... 25 
2.3.1  Programming .............................................. 7  3.7  Detection................................................. 26 
2.3.2  Users .......................................................... 7  3.8  Ejection ................................................... 28 
2.4  General points on programming ............... 8  3.9  Counters ................................................. 32 
2.4.1  Keypad functions ........................................ 8  3.10  Configuration .......................................... 33 
2.4.2  Entering the username ............................... 9  3.10.1  Compatibility chk ...................................... 33 
2.4.3  Entering the password .............................. 10  3.11  Configuration-adv ................................... 37 
2.4.4  Restricted login ......................................... 10  3.11.1  Network config. ........................................ 40 
2.5  Exit from programming ........................... 11  3.11.2  Motor config ............................................. 50 
2.5.1  Exit from programming ............................. 11  3.12  Barcode reader ....................................... 53 
2.5.2  Time out ................................................... 11  3.13  I/O Status ................................................ 55 
2.6  Defining a new user ................................ 11  3.13.1  Outputs .................................................... 55 
2.7  Quick Access menu programming 3.13.2  Inputs ....................................................... 55 
procedure ................................................ 12  3.13.3  Measures ................................................. 56 
2.8  Programming the Metal Detector 3.13.4  Variables .................................................. 56 
according to the kind of product.............. 13 
3.14  Diagnosis managem. .............................. 57 
2.8.1  Procedure for minimizing the "product
effect" ....................................................... 13  3.15  MD Test .................................................. 63 
2.8.2  Procedure for automatic product 3.16  Fail-safe test ........................................... 63 
acquisition ................................................ 13  3.17  Print ........................................................ 64 
3.17.1  With no IXC card installed ........................ 64 
3.17.2  With IXC card installed ............................. 65 
3.17.2.1  Save events ..................................... 66 
3.18  Q-C setup (Quality Control) .................... 68 
3.19  Test samples .......................................... 70 
3.20  Unlock bin ............................................... 70 
3.21  Commands accessible only in Remote
Programming .......................................... 71 
3.22  Remote programming ............................. 76 
3.22.1  Communication parameter settings ......... 76 
3.22.1.1  RS232 or RS232 Aux ...................... 76 
3.22.1.2  Bluetooth ......................................... 76 
3.22.1.3  Ethernet / WiFi connections (only
with IXC card) .................................. 76 
3.22.2  Entering remote programming ................. 77 
3.22.2.1  Connecting to a Metal Detector ....... 77 
3.22.2.2  Displaying a parameter setting ........ 77 
3.22.2.3  Changing a parameter setting ......... 77 
3.22.2.4  Executing a function ........................ 77 
3
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual

3.23  Access via Web Server ........................... 78 


4  APPENDIX ..................................................... 89 
3.23.1  Network configuration .............................. 78 
4.1  Parameters list – Alphabetical order....... 89 
3.23.2  Functions available .................................. 78 
3.23.2.1  Status .............................................. 79  4.2  Parameters list – Menu order ................. 90 
3.23.2.2  Products .......................................... 79 
3.23.2.3  Products Counters ........................... 80 
3.23.2.4  Test Diameters ................................ 80 
3.23.2.5  Products Export ............................... 81 
3.23.2.6  Products Import ............................... 81 
3.23.2.7  Products Delete ............................... 82 
3.23.2.8  Buffers Export .................................. 82 
3.23.2.9  Configuration Backup/Restore ......... 83 
3.23.2.10  Configuration Export/Import ............. 84 
3.23.2.11  Network ........................................... 85 
3.23.2.12  System upgrade (Web Server) ........ 86 
3.23.2.13  Maintenance .................................... 86 
3.23.2.14  System Info ...................................... 87 
3.23.2.15  Logout.............................................. 87 

4
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
SAFETY INSTRUCTIONS - WARNINGS 1
Read this Manual carefully before installing or operating the device and before carrying out maintenance operations.

1 SAFETY INSTRUCTIONS – WARNINGS


1.1 General warnings
- All personnel operating on the device must have an adequate preparation and shall know the
procedures described in this Manual.
- Observe current regulations regarding electrical and personal safety for both the operator
and the installer when installing the device.
- Any modification to the system is forbidden and void all warranties and certifications.
- Follow the instructions contained in this Manual for all operations relating to installation, use
and maintenance of the device.
CEIA cannot be held responsible for any damage resulting from procedures which are not
expressly indicated in this Manual, or from any lack of attention, either partial or total, of the
procedures described therein.
- This Manual must accompany the device described therein in the case of change of
ownership, and until the device is broken up.

1.2 Correct use of the device


- The Metal Detectors from the THS/21E and THS/21 series are electronic devices for the
detection of metal masses transiting inside the detection antenna.
- The final user is responsible for selecting the appropriate sensitivity for their application.
After this selection has been made, and programming has been adjusted accordingly, it is
also the final user's responsibility to verify calibration using the test object(s) appropriate to
the level of security selected. Additionally, this test should be carried out periodically to
insure no changes have occurred in the equipment.

5
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
2 PROGRAMMING

2 PROGRAMMING
The list of parameters and menus, accessible by each users, together with the system behaviors, can change in respect
of this Manual description, depending on the settings modifications. Contact the System Administrator for any
information.

2.1 Access to Programming


Upon access to Programming a user name and a password are requested.
Each type of operator can access a specific set of parameters, consisting of one or more menus.

2.1.1 Factory preset configuration


When first switched on, the Metal Detector is configured with predefined users with access parameters as described in
the following table:

2.1.1.1 Access levels


Predefined operators
Quality Control Head of
Operator Supervisor Technician Administrator
Operator Quality Control
Username 000001 000002 000003 000004 000005 ADMINI
Password 000001 000002 000003 000004 000005 000000
Administrator •
Reset • • •
Product Selection • • •
Products • • •
Autolearn • • •
Autolearn-advanc • •
Detection • • •
Ejection • • •
Counters • •
MENU

Configuration • •
Configuration-adv •
Barcode reader1 • • •
I/O Status • •
Diagnosis managem. • •
MD Test • • •
Fail-Safe test 2

Print • •
Q-C setup • •
Test samples • •
Unlock bin •
1 – The Barcode reader menu is available only upon request
2 – The Fail-safe Test menu is available only with an Ejection confirmation sensor installed

6
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING 2
2.1.1.2 Remote Communication
For the Remote Communication, two access type are provided:
- Only the password (predefined password is 000006). This access type is selected by default.
- User and Password exactly as a local access (see table above).
To select which access type to use, see parameters RM and AURM.

Only the Administrator operator can manage all the users.


It is Administrator responsibility to redefine all predefined access data in order to avoid unauthorized access to
programming.

2.2 Administrator functions


The Administrator has total control over the configuration of the Metal Detector and can define the
roles of the staff that will be working with it. The Administrator's prerogatives, therefore, are the
following:
- Modifying or deleting existing operators and/or setting new passwords.
- Defining new operators and their passwords.
- Authorization for operators to access operational parameters, grouped into menus.
- Total access to all operating parameters.

2.3 Configuration of the system by the Administrator


2.3.1 Programming
The Administrator can program the detector independently to define its operational configuration, or
can delegate one or more functions to the operators.

2.3.2 Users
The Administrator defines the users that work with the detector according to their respective
responsibilities. The Administrator therefore gives the user:
- an user name and a password for access to Programming
- the indication of the operational parameters that the user can modify or display.

The Administrator can define up to 40 users (including the Administrator).

It is imperative that the Administrator responsible for the device redefines the users and passwords pre-set in the factory
in order to block access to Programming on the part of unauthorized personnel.
It is not possible to modify the username ADMINI.

THS/21 is the first system on the market that allows complete personalization of product names and of the users that work
with them (name and surname, user name, password, …).

7
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
2 PROGRAMMING

2.4 General points on programming


2.4.1 Keypad functions
The control of the Metal Detector and the setting of the device parameters are performed through
the control panel keyboard, as shown below:

On THS/xx21 and THS/xx21E


Key Function
Access and exit from the programming phase
Return back from the submenus to the previous menu
Exit from the Metal Detector Status visualization
Scroll through the sequence of instructions
Choice of the parameters to be changed

Metal Detector Status visualization

Selection of the selected submenu from the main menu


Confirmation of the data entered
Reset of some kinds of fault

Only on THS/xx21
Key Function

Cancel the last character entered

Quick access to predefined functions, with programming method complying with


CFR21 (see User Manual)

Modification of the parameter values

8
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING 2
2.4.2 Entering the username
In the following example, the way to digit the username “STEVEN” is shown.

THS/21E
THS/21
Display Keys pressed Meaning

User
Press P to enter Programming. The cursor
#_____ • • blinks in the position of the first character
Press four times the key “7” to cycle through
• the letters and to set the “S” as the first
character. The cursor moves automatically on.
User

S#____
… Press 8 times the DOWN arrow to cycle back
• the alphabet and select the letter “S” as the
first character. Press E to confirm.

Press twice the key “8” to set the “T” as the


• second character.
User
The cursor moves on and starts suggesting
ST#___
again the last character entered. Press once
• the UP arrow to select the letter “T” and press
E to confirm.
Press three times the key “3” to set the “E” as
• the third character.
User

STE#__ … Using the DOWN arrow key, cycle back the


• alphabet until the letter “E” is shown. E to
confirm.

Press four times the key “4” to cycle through


• the letters and to set the “V” as the fourth
character.
User

STEV#_

Using the UP arrow key, cycle up the alphabet
• until the letter “V” is shown. E to confirm.

Again three times the key “3” to set the “E” as


• the fifth character.
User

STEVE# … Using the DOWN arrow key, cycle back the


• alphabet until the letter “E” is shown. E to
confirm.

Press three times the “6” to set the “N” as the


User • last character.
STEVEN
Using the UP arrow key, cycle up the alphabet
… • until the letter “N” is shown.

• •
User

STEVEN
Press “Enter” to confirm the username

9
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
2 PROGRAMMING

2.4.3 Entering the password

THS/21E
THS/21
Display Keys pressed Meaning

After the user name, the password is


• •
Password

#_____
required. As an example we will digit
“000004”.
Push “0” to get for the letter “0” as the first
Password • character. The cursor moves on.
*#____
Push the UP arrow key to select the “0” as
• the first character. E to confirm.
Continue to push “0” until the cursor reach
• the last character position.
Password
The cursor moves on and starts suggesting
*****#
again the last character entered. Continue
• to push E until the cursor reach the last
character position.
Press once the key “4” to set the number
Password • “4” as the last character
******
Press four times the UP arrow key to set
• the number “4” as the last character

• •
Password

******
Press “Enter” to confirm the password

The display will show an asterisk in the place of each character entered.

2.4.4 Restricted login


LOGIN RESTRICTED
This fault message appears if three consecutive attempts to access
with the wrong password or user name have been made (see
parameter FLR).
Due to this event, the detector is NOT operative and set itself on fault
status.

To reset from this fault, enter Programming at Administrator level and exit. In case the
Administrator lost the password to login, contact CEIA.

10
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING 2

2.5 Exit from programming


2.5.1 Exit from programming

Press the P key to exit from the current menu (or submenu), until the main screenshot is
shown on the display.

2.5.2 Time out


The programming session will be terminated automatically if no commands are entered for a period
of 5 minutes.

2.6 Defining a new user


Example: John Smith, product operator, password OPER01, enabled for Product selection menu.

Before creating a new user, or assigning a new operator to a pre-defined one, print the event list and erase the event
buffer.

THS/xx21E THS/xx21
Administrator § Administrator~~~~~~~§
Reset
Reset Product selection
Products
Product selection Autolearn Select menu Administrator, pressing .
Autolearn-advanc
Products Detection
Ejection
Create user @ Create~user~~~~~~~~~§
Modify user
Modify user Erase user
Set BlueTooth PIN
Erase user Remote passwords Select command Create user, pressing .
Remote passwords

==== Create user === [\\\ Create user \\\]

#_____ Enter name of new user (6 alphanumeric characters) and press to


#_____
{|||||||||||||||||||} confirm.
--------------------

User OPER01@ User~~~~~~~~~~OPER01@


Name USER01
Name USER01 Surname USER01
Descrip. USER01
Surname USER01 Password The properties list will appear, followed by the menu list.
Reset N
Descrip. USER01 Product selection N
Products N
Name JOHN
User OPER01

Surname
Name
SMITH
Surname
JOHN
SMITH
Enter the name, surname, a brief description and the desired
Descrip
Descrip. OP PROD
OP PROD Password~~~~~~OP0001@
password, by scrolling using the arrows and selecting by
Reset N
Password OP0001@ Product selection N pressing .
Products N
Password User OPER01
Name JOHN
Reset N Surname SMITH
Descrip. OP PROD Enable the Product selection menu only by changing the menu status
Product selection Y@ Password OP0001
Reset N from N (disabled) to Y (enabled).
Products N Product~selection~~Y@
Products N
Create user @ Create~user~~~~~~~~~§
Modify user
Modify user Erase user
Set BlueTooth PIN
Erase user Remote passwords Exit the menu with to confirm the newly-defined user.
Remote passwords

11
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
2 PROGRAMMING

2.7 Quick Access menu programming procedure


This function is not available on THS/21E models.

The system Administrator can program up to 10 shortcuts to menus or single parameters, in order
to quickly activate them through the Quick Access and the correspondent numeric key (0-9).
Here below, as an example, we will program the Autolearn menu to the position 6 of the Quick
Access list.

Display Keys pressed Meaning


Administrator~~~~~~~~§
Reset
Product selection
Products
Autolearn Access to the parameters list.
Autolearn-advance
Detection
Ejection
Administrator
Reset
Product selection
Products Select command or parameter to be added in
Autolearn~~~~~~~~~~~~§
Autolearn-advance the Quick Access function list.
Detection
Ejection
Create~link~to~~~~~~~@
Erase link Press the Quick Access key and hold it
Erase all links pressed until the display will change as
shown.
Autolearn~~~~~~~~~~~~@
Erase link The first line will alternatively show the
Erase all links message Create link to and the name of the
selecterd function/parameter.
[\\\ QUICK ACCESS \\\]
0) Products Press E to accept. The display will show the
1) Quick Access list, in order to assign the right
2) Sensitivy
3) number.
4) Reset In the example beside, the number 1 and 3
& Scroll down
{||||||||||||||||||||} are free to be used.
[\\\ QUICK ACCESS \\\]
$ Scroll up
5)+MD Test
6) Press the down arrow to scroll the Quick
7)+Print
8)+I/O Status Access list to the second page.
9)+Counters
{||||||||||||||||||||}
[\\\ CREATE LINK \\\\]
[\\\\\\\\\\\\\\\\\\\\]
Link 6
created Press 6 to choose that position in the list.
{||||||||||||||||||||}
{||||||||||||||||||||}

CEIA THS/PH21N
ALM V5.xxx THS V5.xxx
Press three times P to exito from
Programming
Product:PROD01
[\\\ QUICK ACCESS \\\]
$ Scroll up
5)+MD Test
6)+Autolearn Now the Quick Access + 6 will call for the
7)+Print or
8)+I/O Status Autolearn menu (a menu is indicated, in the
9)+Counters list, with a + in front of the name)
{||||||||||||||||||||}

The parameter/menu called with Quick Access will request the insertion of an username and/or a password, if needed.

12
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING 2

2.8 Programming the Metal Detector according to the kind of product


The operating mode of the Metal Detector is to be determined according to the kind of product to
be inspected, in order to obtain:

- the minimization of the ”product effect” (see below);


- the determination of the detectable metallic Test Samples (see below);
- a correct ejection mode configuration according to the product (see also Installation Manual);

The factory settings (product DEFAULT) are suitable for dry products.

It is always advisable to optimise installation in line with the criteria described in the installation Manual in order to obtain
maximum sensitivity and maximum rejection of environmental interference.

2.8.1 Procedure for minimizing the "product effect"


The goal of this procedure is to obtain the following operating mode:
a) the detector does not set off an alarm when some of the pure product, without any metallic
contamination, passes through the probe.
b) the detector sets off an alarm when some of the product containing a metallic sample passes
through the probe

2.8.2 Procedure for automatic product acquisition


This procedure comprises the automatic acquisition of non-contaminated product characteristics in
order to identify the contribution to the received signal due to the metal mass to be detected. The
characteristics are acquired progressively by making the product pass through the Metal Detector
several times.

The procedure must be completed once started. Do not change any parameter setting during the procedure.

# Display THS/xx21E Display THS/xx21 Step


=== New product === Prod. SUGAR01
Rename product
[\\ New product \\\]
Select a product or create a new one (see User Manual, par.
1 BISC#________ BISC#_______
3.6.1).
{||||||||||||||||||}
-------------------

Autolearn OFF Autolearn OFF


Aut.det.mode~sel~~ON@ On THS/xx21 set Autolearn > Aut.det.mode sel to ON to
Multi-band ON@ Min.trans.number 1
perform an autolearn for all detection modes. Set it to OFF to
Min.trans.number 1
perform it only on the current detection mode. Set it to ON if
not sure about the correct detection mode of the product.
2 On THS/21E-3F set Autolearn > Multi-band to ON to
perform an autolearn for all bands. Set it to OFF to perform it
only on the current band. Set it to ON if not sure about the
correct band of the product.
Autolearn OFF Autolearn OFF
Aut.det.mode sel ON
Multi-band ON Min.trans.number~~~1@ Set the parameter Autolearn > Min.trans.number to a
Min.trans.number 1@ suitable value for the product composition. The value of 1 is
3 suggested for products that have regular shape and
composition, higher the product non-uniformity, higher should
be the minimum transits to perform a correct autolearn
Autolearn ON@ Autolearn~~~~~~~~~ON@
Aut.det.mode sel ON
Multi-band ON Min.trans.number 1
Set Autolearn > Autolearn to ON and exit from the
4 Min.trans.number 1
programming phase (push P button).

13
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
2 PROGRAMMING

# Display THS/xx21E Display THS/xx21 Step


PASS PRODUCT
PASS PRODUCT Pass the non-contaminated product through the Metal
Prod. PROD1
Detector each time is requested. The message PASS
5 PRODUCT appears on the display, and the buzzer (if
^
Product:PROD01 enabled) is activated.
PROCESS WAIT
process ...... 65%
^^^^^^^^^^---65% At the end of each transit, the Metal Detector will ask to wait
6 for a few seconds, in order to process the signal. In this
^ phase, the alarm led is blinking.
Product:PROD01
THS/21E V5.3xx CEIA THS/21
ALM V5.xxx THS V5.xxx
Prod. PROD1 At the end of the Autolearn procedure, the Metal Detector
7 exits from the autolearn phase and the standard message
^ appears on the display.
Product:PROD01

Pass some pure product through the detector: the device should not set off any alarm. If the detector gives an alarm
whenever some of the pure product passes through the probe, repeat the procedure, increasing the number of transits (see
8 point 3.). At the end of this second procedure, the pure product is still giving alarm, decrease the “Sensitivity” parameter
until the detector does not give an alarm (this is probably due to non-uniformity of the product).
Pass some of the product with the metallic sample: the detector should give an alarm. If any alarm is given,
increase the size of the metallic sample gradually, until locating its minimum dimension that will be detected with at least 5 dB,
in order to ensure the detection of the sample in every transit position.

In the case that the size of the metallic samples has been modified, communicate them
9 immediately to the Head of Quality Control or to the Administrator, so as to let them to change
their values in the relative menu.

If the signal given by the sample is higher than 12 dB, the Metal Detector Tests can fail. See SAC parameter.
It is responsibility of the customer to determine the diameter values of the test samples to be used in the Quality Control
Procedure. It is responsibility of the Quality Control Head to set this values on the MD Test Samples menu.
[\\\\\ STATUS \\\\\\]
Sensitivity 265
Not available
Detection mode
FE perform.
4
0.80
At the end of the procedure, on the Metal Detector Status
on TH/21E NFE perform. 1.00 screen, will be indicated the minimum detectable diameters.
- SS perform
Prd. alarms
1.20
10 This indication is purely indicative and it is responsibility of
{|| & Scroll down ||}
the customer to verify their effective detection.

The minimum detected diameters can be different from the indication on Status screen.

14
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

3 PROGRAMMING PARAMETERS
Administrator
After user logging, the list of available Local Programming Menus is Reset
Product selection
shown. The list changes according to the permission levels of the Products
Autolearn
user logged. The list beside is the example of the programming tree Autolearn-advanc
for the Administrator level. Detection
Ejection
Counters
Configuration
Each parameter or command is described in detail, together with Configuration-adv
Barcode reader
corresponding Remote Programming code (if available); moreover, I/O Status
Diagnosis managem.
the type (global or related to the current Product) and the Models that MD Test
Fail-safe test
include it in the Programming, are reported. Print
Q-C setup
Test samples
Unlock bin

Some parameters require the use of Input Devices and/or Relays. Therefore, the settings of these parameters have
effect only on Metal Detectors that have Input lines and Relays involved (See Installation Manual).
The parameter standard settings can change according to the Metal Detector System. For each Metal Detector unit, they
are reported on the Factory Acceptance Test Sheet attached to the Installation and Maintenance Manual.

3.1 Administrator
Create user
List of commands available under the Administrator menu Modify user
Erase user
Set Bluetooth PIN
Remote passwords

Remote Possible settings Standard setting Parameter


Create User
- 6 alphanumeric chars. - Global
Description Models
Creation of a new user
All models
Enter the name of a new user: a list of the user's properties will appear.

THS/xx21E THS/xx21
User OPER01 User OPER01
- Name from 1 to 12 alphanumeric char. Name JOHN
JOHN Surname SMITH
- Surname from 1 to 12 alphanumeric char, Name
Descrip. OP PROD
- Description from 1 to 12 alphanumeric char, Surname SMITH Password
Reset
OP0001
N
- Password 6 alphanumeric characters Descrip. OP PROD Product~selection~~Y@
Products N
- List of menus that can be enabled

If the user name already exists, the command aborts.


If the user name is 000000, the access to Programming will be achieved simply by pressing P, without any username or
password request. When an username 000000 is set, to access to Programming at different levels, hold the P key
pressed for at least 3 seconds.
If the password field is left empty, the password will not be requested for this username.
It is possible to create up to 40 users (Administrator included).
If the unit is equipped with the IXC card, an additional property named “Web access” will be listed for each user.
If the property is set to “ON”, this user will be able to access the Metal Detector also from web server.

Remote Possible settings Standard setting Parameter


Modify User
- 6 alphanumeric chars. - Global
Description Models
Modify an user
All models
Select an existing user by pressing the arrows keys: the list of the user's properties will appear:

15
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Erase User
- 6 alphanumeric chars. - Global
Description Models
Delete an user All models

THS/xx21E THS/xx21
===================== [\\\\\\\\\\\\\\\\\\\]
Scroll the users list through the arrow keys. Press E to
select the user to be erased, then press UP to confirm or erase erase
USER01?
E to cancel. UTENTE1?
($)=YES |||||| NO=(E)
(SU)=YES ----- NO=(E)

Remote Possible settings Standard setting Parameter


Set Bluetooth PIN Up to 8 alphanum.
BPIN 00000000 Global
chars.
Description Models
Set the Bluetooth PIN
All models
Needed for the remote connection with a personal computer, via Bluetooth.

3.1.1 Remote passwords


RS232password
List of commands available under the Remote passwords submenu auxRS232passw

Remote Possible settings Standard setting Parameter


RS232password
RM 6 alphanum. chars. 000006 Global
Description Models
Password for the Remote Programming access via RS232
This parameter select the remote access authentication way:
- Alphanumeric value: only the password RM is required All models
- Empty (RM = ‘NULL’ in remote programming): username & password valid for the local access are
required.

Remote Possible settings Standard setting Parameter


auxRS232passw
AURM 6 alphanum. chars. 000006 Global
Description Models
Password for the Remote Programming access via Auxiliary RS232
This parameter select the remote access authentication way:
- Alphanumeric value: only the password AURM is required All models
- Empty (AURM = ‘NULL’ in remote programming): username & password valid for the local access
are required.

16
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.2 Reset
Remote Possible settings Standard setting Parameter
Reset
RS - - Global
Description Models
Alarm and fault Reset
This command restore the system from alarms and faults that require a Reset operation. All models
RS command does not reset the Emergency condition: in this case, the Emergency button need to
be released and the R button, if present, needs to be pressed (see Installation Manual).

3.3 Product selection


Product DEFAULT
List of commands available under the Product selection menu.

Remote Possible settings Standard setting Parameter


Product
PI 12 alphanumeric chars. - Global
Description Models
Type of product selected
All models
Selection of a product previously entered and saved.

Local programming THS/xx21E THS/xx21


====== Product ====== [\\\\\ Product \\\\\]
The various defined products are shown on the display. @DEFAULT
Scroll them with the arrow keys and choose the desired *DEFAULT PROD01
PROD02
product by pressing the E key. On THS/21 models, PROD01 POW003
BRWNSUGAR
typing letters in the search field results in a product list PROD02 {|||||||||||||||||||}
Search: #___________
restricted to the names that match that string.

Remote programming Remote display


This command displays the list of products: the current
product is shown by the “>” cursor. #PI<ENTER>
To change the current product, assign the corresponding Default
ProdA
value to the PI setting. > ProdB
ProdC
#PI ProdA<ENTER>
#PI<ENTER>
Default
> ProdA
ProdB
ProdC
#

On product DEFAULT are saved all factory settings for the detection of the reference test samples, as indicated on the
Factory Acceptance Test (FAT) of the Metal Detector, included with the Installation Manual.
It is not possible to erase or to modify the DEFAULT product.
The standard configuration includes also the product P1, as a copy of DEFAULT but modifiable (and erasable).

17
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.4 Products
Product
List of commands available under the Products menu Rename product
New product
Erase product
Prod. Barcode
Save prod.to USB
Load prd from USB

Remote Possible settings Standard setting Parameter


Product
PI 12 alphanumeric chars. - Global
Description Models
Type of product selected
All models
Selection of a product previously entered and saved.

Local programming THS/xx21E THS/xx21


====== Product ====== [\\\\\ Product \\\\\]
The various defined products are shown on the display. @DEFAULT
Scroll them with the arrow keys and choose the desired *DEFAULT PROD01
PROD02
product by pressing the E key. On THS/21 models, PROD01 POW003
BRWNSUGAR
typing letters in the search field results in a product list PROD02 {|||||||||||||||||||}
Search: #___________
restricted to the names that match that string.

Remote programming Remote display


This command displays the list of products: the current
product is shown by the “>” cursor. #PI<ENTER>
To change the current product, assign the corresponding Default
ProdA
value to the PI setting. > ProdB
ProdC

#PI ProdA<ENTER>
#PI<ENTER>
Default
> ProdA
ProdB
ProdC
#

On product DEFAULT are saved all factory settings for the detection of the reference test samples, as indicated on the
Factory Acceptance Test (FAT) of the Metal Detector, included with the Installation Manual.
It is not possible to erase or to modify the DEFAULT product.
The standard configuration includes also the product P1, as a copy of DEFAULT but modifiable (and erasable).

Remote Possible settings Standard setting Parameter


Rename product Related to the
PN 12 alphanumeric chars. -
current product
Description Models
Product SUCAR01
Rename~product~~~~~~@
Rename the product All models

THS/xx21E THS/xx21
== Rename product == [\ Rename product \\]
Changes the name of the current product.
It is not possible to rename the product DEFAULT. SUGA#_______ SUGA#_______

-------------------- {|||||||||||||||||||}

18
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


New product
NW 12 alphanumeric chars. - Global
Description Models
Creation of a new product
Product SUGAR01
Create a new product. The maximum number of products is 500 for Rename product
All models
the THS/21 series and 250 for the THS/21E series. [\\\ New product \\\]

BISC#_______
{|||||||||||||||||||}

THS/xx21E THS/xx21
=== New product ==== [\\ New product \\\\]
The initial parameters of the new product will be the
same of the product selected when the new product is BISC#_______ BISC#_______

created. Copying the DEFAULT product, parameters FD, -------------------- {|||||||||||||||||||}

SD and ND will not be copied.

Remote Possible settings Standard setting Parameter


Erase product
EP 12 alphanumeric chars. - Global
Description Models
Elimination of a product
Product SUGAR01 All models
Rename product

THS/xx21E THS/xx21
=== Erase product === [\\ Erase product \\]
Scroll the product list using the arrow keys, and select DEFAULT
the product to be erased pressing the E key. DEFAULT PROD01
@PROD02
PROD01 SUGAR01

*PROD02 {|||||||||||||||||||}
Search: #_________

===================== [\\\\\\\\\\\\\\\\\\\]
A confirmation is needed to complete the operation.
erase erase
PROD02?
It is not possible to erase the product DEFAULT. PROD02?
{|| $=YES || E=NO ||}
(UP)=YES ----- NO=(E)

Remote Possible settings Standard setting Parameter


Prod. barcode Related to the
BARC - -
current product
Description Models
Product barcode
This function show the barcode related to the current product. If a barcode has not been yet All models
assigned, the result is “NULL”.
This function is visible only if the barcode reader menu has been activated (see BE parameter).

19
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.4.1 Save prod.to USB


Select product(s)
List of commands available under the Save prod.to USB submenu. Save all products
This menu is available only on models with IXC card installed.

Remote Possible settings Standard setting Parameter


Select product(s)
- - - Global
Description Models
Selection of Products to save to USB All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
= Select product(s) = [ Select product (s) ]
Press E and select each Product to be saved. ¼PROD01
A full circle icon identifies all selected products. -PROD01 @¼PROD03
½PROD05
At the end, keep E key pressed for 3 seconds. *-PROD03 ¼PROD09
{||||||||||||||||||||}
+PROD09 Search :#___________

=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

Overwrite [\\\\\\\\\\\\\\\\\\\\]
In case one or more Products already exist in USB
memory, press & to overwrite all selected Products (or PROD05? Overwrite
PROD05?
P to null the saving ), otherwise decide one by one, (UP)=YES NO=(E)
$=YES NO=E
pressing $ to overwrite or E to not overwrite. (DW)=ALL NONE=(P) { &=ALL |||||| NONE=P}

===================== [\\\\\\\\\\\\\\\\\\\]
Each selected Product is saved as:
Done Done

:/Ceia/Products/SNxxxxxxxxxxx/ ---------------------
{|||||||||||||||||||}
ProductName.tpr

where xxxxxxxxxxx is the Metal Detector serial number.

20
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Save all products
- - - Global
Description Models
Save all Products to USB memory All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
All products are automatically saved to USB memory.
WAIT WAIT
CAN TAKE MINUTES
CAN TAKE MINUTES
{|||||||||||||||||||}
---------------------

Overwrite [\\\\\\\\\\\\\\\\\\\\]
In case one or more Products already exist in USB
memory, press & to overwrite all selected Products (or PROD05? Overwrite
PROD05?
P to null the saving ), otherwise decide one by one, (UP)=YES NO=(E)
$=YES NO=E
pressing $ to overwrite or E to not overwrite. (DW)=ALL NONE=(P) { &=ALL |||||| NONE=P}

===================== [\\\\\\\\\\\\\\\\\\\]
Each selected Product is saved as:
Done Done

:/Ceia/Products/SNxxxxxxxxxxx/ ---------------------
{|||||||||||||||||||}
ProductName.tpr

where xxxxxxxxxxx is the Metal Detector serial number.

21
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.4.2 Load prd. from USB


This menu is available only on models with IXC card installed.

THS/xx21E THS/xx21
== Select directory = [\ Select directory \]
Enter in this Menu and select the Metal Detector to copy @+SN2110021111
the Products from. Press E to select. *+SN2110021111 +SN2110021112
+SN2110021115
+SN2110021112 +SN2110021116
+SN2110021117
+SN2110021115
{||||||||||||||||||||}

Select product(s)
List of commands available under the Load prd. from USB Load all
submenu.

Remote Possible settings Standard setting Parameter


Select product(s)
- - - Global
Description Models
Load Products settings from USB memory All models

This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

= Select product(s) = [ Select product(s) ]


In case one or more Products already exist in USB ¼PROD01
memory, press & to overwrite all selected Products (or -PROD01 @¼PROD03
½PROD05
P to null the saving ), otherwise decide one by one, *-PROD03 ¼PROD09
{|||||||||||||||||||}
pressing $ to overwrite or E to not overwrite. +PROD09 Search:#___________

Overwrite [\\\\\\\\\\\\\\\\\\\\]
In case one or more Products already exist into the
Metal Detector, press & to overwrite all selected PROD05? Overwrite
PROD05?
Products (or P to null the saving ), otherwise decide one (UP)=YES NO=(E)
$=YES NO=E
by one, pressing $ to overwrite or E to not overwrite. (DW)=ALL NONE=(P) { &=ALL |||||| NONE=P}

Size is different [\\\\\\\\\\\\\\\\\\\\]


It is possible to import products created on other Metal
Detectors (of the same model), but with different probe Load PROD05? Size is different
Load PROD05?
dimensions.
In this case, for this products, can be necessary to (UP)=YES NO=(E) { $=YES ||||||| NO=E }

perform a new Autolearn procedure.


===================== [\\\\\\\\\\\\\\\\\\\]
It is not possible to import products created on different
Metal Detector models. PROD05 PROD05
Not compatible
Not compatible
{ P=EXIT || CONT.=E }
(P)=EXIT CONT.=(E)

===================== [\\\\\\\\\\\\\\\\\\\]
The product DEFAULT and the current product cannot
be overwritten. Product in use Product in use

(P)=EXIT CONT.=(E)
{ P=EXIT || CONT.=E }
---------------------

22
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Load all
- - - Global
Description Models
Load all Products settings from USB memory All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
A confirmation is needed.
Do you confirm? Do you confirm?

(UP)=YES NO=(E)
{|| $=YES || NO=E ||}
---------------------
{|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
All products are automatically loaded from USB memory.
WAIT WAIT
CAN TAKE MINUTES
CAN TAKE MINUTES
{|||||||||||||||||||}
---------------------

Overwrite [\\\\\\\\\\\\\\\\\\\\]
In case one or more Products already exist into Metal
Detector, press & to overwrite all selected Products (or PROD05? Overwrite
PROD05?
P to null the saving ), otherwise decide one by one, (UP)=YES NO=(E)
$=YES NO=E
pressing $ to overwrite or E to not overwrite. (DW)=ALL NONE=(P) { &=ALL |||||| NONE=P}

Size is different [\\\\\\\\\\\\\\\\\\\\]


It is possible to import products created on other Metal
Detectors (of the same model), but with different probe Load PROD05? Size is different
Load PROD05?
dimensions.
In this case, for this products, can be necessary to (UP)=YES NO=(E) { $=YES ||||||| NO=E }

perform a new Autolearn procedure.


===================== [\\\\\\\\\\\\\\\\\\\]
It is not possible to import products created on different
Metal Detector models. PROD05 PROD05
Not compatible
Not compatible
{ P=EXIT || CONT.=E }
(P)=EXIT CONT.=(E)

===================== [\\\\\\\\\\\\\\\\\\\]
The product DEFAULT and the current product cannot
be overwritten. Product in use Product in use

(P)=EXIT CONT.=(E)
{ P=EXIT || CONT.=E }
---------------------

23
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.5 Autolearn
Autolearn
List of commands available under the Autolearn menu. Aut.det.mode sel
Multi-band
Min.transits numb

Remote Possible settings Standard setting Parameter


Autolearn
LE ON / OFF OFF Global
Description Models
Product autolearn
This command activates the Autolearn procedure, in which the Metal Detector set automatically the
best Product settings for the “product effect” compensation.
To start the Autolearn, select ON and exit from programming. The request for the product transit will All models
be shown on the display. See also TN parameter.
The parameter returns to OFF automatically at the end of procedure. See paragraph “Programming
the metal detector according to the kind of product”.

Remote Possible settings Standard setting Parameter


Aut.det.mode sel
ADMS ON / OFF ON Global
Description Models
Autolearn detection mode selection
If ADMS is set to ON the Autolearn procedure will automatically determine the best Detection mode Only on
for the product in transit. THS/xxMS21
If set to OFF the Autolearn procedure will be performed only on current Detection mode.

Remote Possible settings Standard setting Parameter


Multi-band
MB ON / OFF ON Global
Description Models
Autolearn band selection
If MB is set to ON the Autolearn procedure will automatically determine the best band for the product Only on
in transit. THS/xx21E-3F
If set to OFF the Autolearn procedure will be performed only on current band.

Remote Possible settings Standard setting Parameter


Min.transits numb
TN 1 – 10 1 Global
Description Models
Minimum number of product transits for Autolearn
TN=1 is enough for uniform products. In the case of non-uniform products, increase TN in order to All models
have a more accurate product autolearn.
With ADMS=ON (or MB=ON) more transits could be required, depending on the product type.

24
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

3.6 Autolearn-advanc
Metal optimiz.
List of commands available under the Autolearn-advanc menu Autolearn sens.
Sens. margin
Max learn sens
Vibr.immunity
Ej.during autlr

Remote Possible settings Standard setting Parameter


Metal optimiz. AVRG / BFE
MOPT AVRG Global
BNFE / BSS
Description Models
Selection of the operating band criteria during autolearn
During the autolearn procedure, the Metal Detector choose automatically the best detection mode, Only for
according to MOPT value. THS/xxMS21
- AVRG: Optimization for Ferrous metals, non Ferrous metals and Stainless Steel detection and
- BFE: Optimization for ferrous metals detection THS/xx21E-3F
- BNFE: Optimization for non-ferrous metals detection
- BSS: Optimization for stainless steel detection

Remote Possible settings Standard setting Parameter


Autolearn sens.
ASE ON / OFF ON Global
Description Models
Automatic Sensitivity adjustment during Autolearn
All models
ASE =ON: the Metal Detector, during the Autolearn procedure, adjust also the sensitivity value except
according to SA and MASE parameters. THS/MN21
ASE=OFF: during the Autolearn procedure, the current sensitivity value is not changed.

Remote Possible settings Standard setting Parameter


Sens. margin
SA 10 – 50 25 Global
Description Models
Margin of sensitivity
The application of this parameter has effect only if ASE=ON and after the Autolearn.
After the Autolearn, the Sensitivity value is automatically set in order to guarantee a margin (defined
by SA parameter) for the corresponding Alarm threshold level, in order to avoid that signal
variations, due to non-uniformity in product characteristics, could cause false Alarms. All models
The higher are signal variations, the greater should be SA value, the lower will be the Sensitivity
value. Set SA higher than 25 just in case of product with very strong signal variation (for example:
bulk and wet product). The value of 25 corresponds to a ratio of about 2.5 between the alarm
threshold and the product signal.

Remote Possible settings Standard setting Parameter


Max learn sens
MASE 100 – 299 290 Global
Description Models
Maximum sensitivity value adjustment during Autolearn
Maximum sensitivity value that can be set by the Autolearn procedure. All models
The application of this parameter has effect only if ASE=ON and after the Autolearn.

25
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Vibr.immunity
VI 0 – 250 0 Global
Description Models
Vibration immunity
This parameter has effect only after the Autolearn execution. All models
Setting VI between 1 and 250, the Autolearn procedure optimizes the Product settings both for the except
best detection sensitivity and against possible mechanical vibrations. Increasing this value will result THS/MN21
in a higher vibrations immunity of the Metal Detector, but the detection sensitivity could result lower and
respect with VI=0. THS/xx21E
If VI is set to 0, during the Autolearn procedure the Metal Detector will optimize only the detection
sensitivity. Set VI≠0 only if strictly necessary.

Remote Possible settings Standard setting Parameter


Ej.during autlr
EDA ON/OFF OFF Global
Description Models
Ejection during Autolearn
Set EDA=ON to activate the ejection during the Autolearn in order to rejected the product passed. All model
See also EM parameter.
Available only with EM=F

3.7 Detection
Sensitivity
List of commands available under the Detection menu Detection mode
TX program
Band

Remote Possible settings Standard setting Parameter


Sensitivity Related to the
SE 0 - 299 -
current product
Description Models
Alarm trigger threshold level
The higher is SE value, the lower is the Alarm trigger threshold level for the signal received from the
Metal Detector, to be set depending on the product signal.
The SE value concurs, with the other Product settings (set by Autolearn), to the detection
performance. For dry and non magnetic product, the higher is the SE value, the lower is the metal All models
mass that can be detected.
If ASE=ON, after the product Autolearn, the Metal Detector set automatically the highest possible SE
value for the current product, according to SA and MASE parameters.
If set manually, choose the right value not to have false Alarms (depending on the product
characteristics and on the environment) or bad detection performance.

Remote Possible settings Standard setting Parameter


Detection mode Related to the
DM 0-9 0
current product
Description Models
Detection mode
The Detection Mode must be selected according to the kind of product to be inspected.
If ADMS=ON, the Metal Detector performs the Autolearn selecting also automatically the best DM
Only on
value suitable for the product. THS/xxMS21
The manual selection of DM always requires to perform successively the Autolearn procedure.
The default value of 0 is suitable for dry products.
It is recommended to set ADMS=ON to permit the automatic best Detection Mode selection. Selecting
manually DM value does not guarantee the best possible Detection performance.

26
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


TX program Related to the
TP 0 - 17999 0
current product
Description Models
Transmission Program
Only on
This parameter setting determines the best minimization for the product effect and it is automatically THS/xx21E
set by the Autolearn procedure. The default value of 0 is suitable for dry product.
Changing manually the value of TP can cause an incorrect detection operation of the Metal Detector!
In this case, repeat the Autolearn procedure.

Remote Possible settings Standard setting Parameter


Band Related to the
BA LOW / MEDIUM / HIGH HIGH
current product
Description Models
Band
The Band must be selected according to the kind of product to be inspected. Only on
If MB=ON, its value is determined automatically by the system during the Autolearn procedure. THS/21E-3F
The manual selection of BA always requires to perform successively the Autolearn procedure.
The default value of HIGH is suitable for dry products.
It is recommended to set MB=ON to permit the automatic best Band selection. Selecting manually BA value
does not guarantee the best possible Detection performance.

27
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.8 Ejection
Ejection mode
List of commands available under the Ejection menu Ej. distance
Ejection time
Pack length
Ej.st.sync.area
Ej.en.sync.area

Remote Possible settings Standard setting Parameter


Ejection mode B / F / S / SB / R Related to the
EM FS / H / HA / HB
-
current product
Description Models
Ejection mode
see table below
Selection of ejection mode for contaminated material. See Installation Manual.

Ejection
Description Models
mode
Used for bulk product
No photocell required -
with manual removal
After an Alarm:
- With Conveyor Control System or using an encoder, the belt stops after a time set
by ED parameter; otherwise the EJECT Relay is activated after ED/BS time (if
Following Conveyor Input is used, the time ED/BS is counted only during the input All models
activation). A manual reset is requested.
- the contaminated product must be manually removed.
B - the Alarm must be reset manually (by Detector Reset button on Conveyor Control
System or using E key or by RESET input activation).
- the belt transport must be restarted.
See ED, BS, FC.
The Metal Detector does not check if there are any subsequent fragments in the material
immediately following to that causes alarm: all material between the probe entrance and ejection position
shall be eliminate. To minimize waste of material it is advisable to select a low setting for the ED
parameter.
Ideal for air blow ejector,
Used for bulk product
No photocell required retractable belt and
with automatic ejection
flap deviator
After an Alarm:
F - EJECT Relay and the Ejector are activated after ED/BS time, for ET time. (if All models
Following Conveyor Input is used, the time ED/BS is counted only during the input
activation).
- the contaminated product is automatically ejected
See ED, ET, ERT, BS, FC.
Used for packed product
(properly aligned and
Photocell required Ideal for piston ejector
spaced) and automatic
S ejection All models

After an Alarm with Synchronization Photocell activation, the operation mode is like
for EM=F. See ED, ET, ERT, BS, FC, PH, PD.

Used for packed product


Photocell required -
with manual removal

SB All models
After an Alarm with Synchronization Photocell activation, the operation mode is like
for EM=B. See ED, BS, FC, PH, PD.

28
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Ejection
Description Models
mode
Usable only with flat
Reversed belts.
No photocell required belts, capable of
Used for bulk product
reversed running
R In case of Alarm, the conveyor belt direction is reversed for a distance ED. All models
Available only with Conveyor Control System.
Do not select with modular belt systems.

Used for packed


(aligned, poorly spaced) Ideal for air blow ejector
Photocells required
or bulk product, and or retractable belt
automatic ejection
Includes automatic set-aside of contaminated material with Synchronization and
Ejection Check photocells.
FS - EJECT Relay and the Ejector are activated after ED/BS time, for the belt area All models
equal to Antenna Width + 2PLEN + eventually (EE+ES), symmetrically respect to
Antenna center.
- the contaminated product is automatically ejected
See ECPD, ECK, ECKA, ED, EE, ERT, ERF, ES, BS, FC, PD, PH, PL, PLEN, EE, ES
See Installation Manual.

Used for bulk product


Ideal for Only for
from filling machine to -
THS/PLVM21 series THS/Gxx
clipping machine
HA THS/PLxx
Includes automatic ejection with automatic filling cycle restart. THS/PLVxx
THS/FFVxx
See Installation Manual.

Used for bulk product


Ideal for Only for
from filling machine to -
THS/PLVM21 series THS/Gxx
clipping machine
H THS/PLxx
Includes automatic ejection with filling cycle restart from clipper machine THS/PLVxx
THS/FFVxx
See Installation Manual.

Used for bulk product


Ideal for
from filling machine to - Only for
THS/PLVM21 series
clipping machine THS/Gxx
HB Includes automatic ejection with filling cycle restart from clipper machine after Metal THS/PLxx
Detector Reset by external button THS/PLVxx
THS/FFVxx
See Installation Manual.

29
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Ej. distance Related to the
ED 0 – 6000 mm -
current product
Description Models
Distance of ejection system from probe or photocell
This parameter indicates the position of the ejection system and it should be set according to the
Ejection mode (EM parameter) as shown below.
For the correct setting of ED, see also the Installation Manual.
Ejection
Meaning
mode
Approx. distance between the Antenna center and the point where the contaminated
B
product should stop
F, FS Approx. distance between the Antenna center and the ejector position
Distance between the Synchronization Photocell and the point where the All models
SB
contaminated product should stop
S Distance between the Synchronization Photocell and the ejector position
R Approx. distance ran reversed by the conveyor belt, after the alarm
The time ED/BS is the delay, from the Alarm, after which the belt stops or the ejector is activated.
With Conveyor Control System or using an encoder, the delay is counted only during the belt
movement.
For systems using FOLLOWING CONVEYOR input, it is counted only during its own activation (see
FC parameter).
Not available with EM=H, HA, HB

Remote Possible settings Standard setting Parameter


Ejection time Related to the
ET 0,01 – 30,00 s -
current product
Description Models
Ejector activation time
Set ET to the minimum time the ejector (and the EJECT Relay) remain activated after an Alarm,
allowing the correct ejection of the contaminated product.
Depending on EM, the real time the ejector will be activated is: All models
- if EM=S : ET
- If EM=F : ET + Alarm time (approx. the transit time of the metal mass through the probe)

Not available with EM=B, SB, FS

Remote Possible settings Standard setting Parameter


Pack length Related to the
PLEN 20 – 250 mm -
current product
Description Models
Nominal length of the pack
Nominal length of the product pack (in millimetres).
Setting PLEN value, the minimum belt area to be cleared from contaminated product is equal to:
All models
PLEN + Antenna Width + PLEN

The effective cleared area is taking in count also parameters EE and ES.
Available only with EM = FS.

30
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Ej.st.sync.area Related to the
ES 0 – 250 mm -
current product
Description Models
Ejection start synchronization area
Set ES (typically equal to PLEN) in order to synchronize the ejection start with the beginning of the All models
pack in transit.
Available only with EM = FS.

Remote Possible settings Standard setting Parameter


Ej.en.sync.area Related to the
EE 0 – 250 mm -
current product
Description Models
Ejection end synchronization area
Set EE (typically equal to PLEN) in order to synchronize the ejection end with the ending of the pack All models
in transit.
Available only with EM = FS.

31
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.9 Counters
Prd alarms
List of commands available under the Counters menu. Prd packs
Tot.alarms
Tot. packs
Work time

Remote Possible settings Standard setting Parameter


Prd alarms Related to the
CA 0 – 999999999 -
current product
Description Models
Number of alarms with current product (since last counter reset)
For systems with Conveyor Control System or encoder, the Alarms are counted only during the belt
movement. For systems using FOLLOWING CONVEYOR input, the Alarms are counted only during All models
the input activation. For all other systems, the alarms are always counted.
To reset this counter select the parameter, press the UP key and confirm by pressing the E key.
In remote programming execute the CR command.

Remote Possible settings Standard setting Parameter


Prd packs Related to the
CO 0 – 999999999 -
current product
Description Models
Number of transits of packs of current product (since last counter reset)
This count is performed through the Synchronization PHOTOCELL input.
For systems with Conveyor Control System or encoder, the packs are counted only during the belt
movement. For systems using Following Conveyor input, the packs are counted only during the All models
Input activation. For all other systems, the packs are always counted.
To reset this counter select the parameter, press the UP key and confirm by pressing the E key.
In remote programming execute the CR command.

Remote Possible settings Standard setting Parameter


Tot.alarms
AC 0 – 999999999 - Global
Description Models
Number of total alarms (since last counter reset)
This counter represents the total number of alarms, since last counter reset. The remarks done for
CA are still valid. All models
To reset this counter select the parameter, press the UP key and confirm by pressing the E key.
In remote programming execute the AR command.

When CA counters increase, AC also increase, but when CA counters reset, AC is not modified.

Remote Possible settings Standard setting Parameter


Tot. packs
OC 0 – 999999999 - Global
Description Models
Number of total packs (since last counter reset)
This count is performed through the PHOTOCELL input. This counter increases with all products.
The remarks done for CO are still valid. All models
To reset this counter select the parameter, press the UP key and confirm by pressing the E key.
In remote programming execute the OR command.
When CO counters increase, OC also increase, but when CO counters reset, OC is not modified.

32
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Work time
WT - - Global
Description Models
Working time
This parameter returns the number of operative hours of the Metal Detector. All models
It is not possible to reset this counter.

3.10 Configuration
Compatibility chk
List of commands available under the Configuration menu Buzzer
Ext.buzzer
Language
Transmission
TX Channel
Keyb alarm reset
Keyb fault reset
Time
Date setting
Alarm time
Ejection
UP/DOWN enable
Manual motion
Stop on fault

3.10.1 Compatibility chk


Gener.comp.check
List of commands available under the Compatibility chk submenu Elec.comp.check
Belt comtam.check
Belt length

Remote Possible settings Standard setting Parameter


Gener.comp.check
- - - Global
Description Models
General compatibility check
This command perform a complete set of automatic checks to verify the general compatibility of the All models
Metal Detector system with the installation environment. Follow the requests shown on display until
the outcome is carried out. See also Installation and Maintenance Manual.

Remote Possible settings Standard setting Parameter


Elec.comp.check
- - - Global
Description Models
Electrical compatibility check
This command perform an automatic check to verify the electrical compatibility of the Metal Detector All models
system with the installation environment. Follow the requests shown on display until the outcome is
carried out. See also Installation and Maintenance Manual.

Remote Possible settings Standard setting Parameter


Belt contam.check
- - - Global
Description Models
Belt contamination check
This command perform an automatic belt contamination check. Follow the display message All models
requests. This command will not be visible if BLEN=0. See also Installation and Maintenance
Manual.

33
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Belt length
BLEN 0 – 20000 mm - Global
Description Models
Length of the conveyor belt
All models
Set BLEN value to the belt total length (development). Set BLEN=0 in systems without belt.

Remote Possible settings Standard setting Parameter


Buzzer
SO ON / OFF ON Global
Description Models
Activation of the built-in buzzer
All models
Activation of the buzzer included in the ALM board.

Remote Possible settings Standard setting Parameter


Ext.buzzer
ESO OFF / ON1 / ON2 OFF Global
Description Models
Activation of the external buzzer
Activation of the external buzzer (HORN Output, see Installation Manual) connectable to the Metal
Detector. The external buzzer is activated with the following criteria: All models
- ESO=OFF: the external buzzer is never activated
- ESO=ON1: the external buzzer will be activated only for fault conditions.
- ESO=ON2: the external buzzer will be activated for metal alarms and fault conditions.
In THS/FBB and other configurations with single external lamp, set ESO=ON2, because the lamp is
connected to HORN output.

Remote Possible settings Standard setting Parameter


GB / F / D / S / NL
Language JP / P / E / H / PL
LG SRB / RO / CZ
- Global
RUS / TR / I
Description Models
Language for messages
All models
The International Codes are used to identify each language.

Remote Possible settings Standard setting Parameter


Transmission
TX ON / OFF ON Global
Description Models
Disabling of the Metal Detector transmitter
All models,
If set to OFF, the Metal Detector transmitter is disabled, and it is not possible to detect metals. except
A message on the display advises about this condition. THS/MN21
The parameter is automatically set to ON if the Detector is switched off and on again.

Remote Possible settings Standard setting Parameter


TX channel
CH 1-4 1 Global
Description Models
Transmission channel All models,
Selection of a specific transmission channel, in order to allow the automatic synchronization except
between adjacent Metal Detectors. THS/MN21

34
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Keyb alarm reset
KAR ON / OFF ON Global
Description Models
Enabling of the keyboard for direct alarm reset
This parameter set the Reset mode when manual Alarm Reset is required (i.e. after an Alarm with
EM=B). If KAR=OFF, it is possible to reset the Alarm only by Reset command (in the Programming
Menu) or pressing Reset button (Detector Reset Button on Conveyor Control System). All models
If KAR=ON, it is possible to reset the Alarm also pressing the E key.
Independently from KAR value, alarms can be always manually reset through the activation of
RESET input.

Remote Possible settings Standard setting Parameter


Keyb fault reset
KFR ON / OFF / RBO ON Global
Description Models
Enabling of the keyboard for direct fault reset
This parameter set the Reset mode for not self-recovering Faults.
It is always possible to reset Faults activating the Reset command (in the Programming Menu).
- KFR=OFF: it is possible to reset Faults only by Reset command.
- KFR=RBO: it is possible to reset Faults also pressing Reset button (Detector Reset Button on All models
Conveyor Control System).
- KFR=ON: it is possible to reset Faults also pressing the Detector Reset button on Conveyor
Control System or the E button on the keypad.
Independently from KFR value, alarms can be always manually reset through the activation of
RESET input.

Remote Possible settings Standard setting Parameter


Time
TM HH:MM - Global
Description Models
Current time
All models
HH = Hours; MM = Minutes. In remote programming, digit: TM=HH:MM

Remote Possible settings Standard setting Parameter


Date
DA DD/MM/YY - Global
Description Models
Current date
DD = Day; MM = Month; YY: Last two figures of the year. All models
In remote programming, digit: DA=DD/MM/YY

Remote Possible settings Standard setting Parameter


Alarm time
AT 0 – 20 s / A / R A Global
Description Models
Activation time of detector alarm relay
In case of alarm, the Alarm relay (ALARM RELAY) and the external alarm signal lamp (YELLOW
LAMP output) are activated depending of AT value:
- AT=0, the Alarm Relay and the Alarm signal lamp are not activated.
- AT>0: the Alarm Relay and the Alarm signal lamp are activated only for the alarm duration plus All models
the AT value (in seconds). When EM=B, the Alarm relay and the signal lamp are activated for AT
seconds after Alarm Reset.
- AT=A: the Alarm Relay and the Alarm signal lamp are activated only for the Alarm duration.
- AT=R: the Alarm Relay and the Alarm signal lamp remain active after the Alarm until manual
Alarm Reset.

35
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Ejection
EJ ON / OFF ON Global
Description Models
Ejection disabling/enabling
Enabling/disabling of the ejection system according to the Ejection Mode (see EM parameter). All models
If disabled, shall be enabled during Metal Detector tests: a message will be shown on the display.
This parameter is automatically restored to ON at start-up.

Remote Possible settings Standard setting Parameter


UP/DOWN enable
UD ON / OFF ON Global
Description Models
Disabling/enabling for the belt speed adjustment
Enabling/disabling the use of arrow keys on Conveyor Control System, for the belt speed All models
adjustment. with Conveyor
If UD=ON, it is possible to adjust the belt speed with belt stopped or in movement. The belt speed is Control System
shown on the display during the changes.
If MM=ON, it is possible to change the belt speed only entering in programming.

Remote Possible settings Standard setting Parameter


Manual motion
MM ON / OFF OFF Global
Description Models
Disabling/enabling of the conveyor belt manual movement
Enabling/disabling the use of arrow keys on Conveyor Control System, for the manual belt All models
movement. with Conveyor
If MM=ON, it is possible to move manually the belt keeping pressed the arrow key (Up arrow for the Control System
product transit direction, Down arrow for the reverse direction).
WARNING.
With modular conveyors, set MM=OFF to avoid damages to the conveyor transmission system.

Remote Possible settings Standard setting Parameter


Stop on fault
SF ON / OFF ON Global
Description Models
Disabling/enabling for the belt stop, in case of fault All models
If SF=ON, the belt stops immediately in case of Fault during the belt movement. With SF=OFF, in with Conveyor
case of Fault, the belt continues to run. Control System

36
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.11 Configuration-adv
IXC presence
List of parameters available under the Configuration-adv menu. Backup conf.to USB
Restor.cfg.from USB
Export conf.to USB
Import cfg.from USB
Network config.
Product tracking
Inhib. time
Barcode enable
Minimum speed
Speed
Maximum speed
Filter adj
Phcell position
Phcell-MD dist.
Check phot.dist
EjON resp.time
EjOFFresp.time
K transmis.
K encoder
Diameter
TA
TA1
TA2
TA autolearn
Autotest phase
Autotest module
Autotest diagnos
Display mode
Display contrast
Dimming delay
Input logic
BIN FULL input
BIN ABSENT input
EJECT.CONF.input
PHOTOCELL input
FOLLW.CONV.input
LOW PRESSURE inp
Analysis mode
Eject.queue reset
Reverse detect
Ejec.act.if stop
EJECT RELAY logic
PREC.CONV enable
FOLL.CONV enable
Autom. Restart
Test relay mode
Aux relay mode
Stop time
Motor config.
RS232 BaudRate
auxRS232B.Rate
DTR protocol
Bounce time
Bounce t. slow
Centre belt time

Remote Possible settings Standard setting Parameter


IXC presence
IXC ON / OFF - Global
Description Models
Enabling of the IXC board
All models
Setting IXC=OFF, all functions relative to the network connection and USB interface are disabled.
Anyway all events will be stored on the SCD board internal memory.
In case of IXC card, use an USB memory device exclusively dedicated to this.

37
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Backup conf.to USB
- - - Global
Description Models
Metal Detector Configuration Backup All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
In case the Metal Detector configuration already exist in
USB memory, press $ to overwrite or E to not already exists already exists
Overwrite?
overwrite. Overwrite?
{| $=YES |||| NO=E |}
(UP)=YES ----- NO=(E)

===================== [\\\\\\\\\\\\\\\\\\\]
The Configuration file is saved as:
Done Done

:/Ceia/Configuration/ ---------------------
{|||||||||||||||||||}
xxxxxxxxxxx.tcb

where xxxxxxxxxxx is the Metal Detector serial number.

Restor.cfg.from Remote Possible settings Standard setting Parameter


USB - - - Global
Description Models
Metal Detector Configuration recovery All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

==== Select file ==== [\\\ Select file \\\]


Select the Metal Detector serial number. It is not @+SN2110021111
possible to load the configuration file of a different Metal *+SN2110021111 +SN2110021112
+SN2110021115
Detector. +SN2110021112 +SN2110021116
+SN2110021117
+SN2110021115
{|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
A confirmation is needed: press $ to overwrite or E to
not overwrite. Do you confirm? Do you confirm?

(UP)=YES NO=(E)
{|| $=YES || NO=E ||}
---------------------
{|||||||||||||||||||}

38
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Remote Possible settings Standard setting Parameter
Export conf.to USB
- - - Global
Description Models
Export the Metal Detector Configuration for a similar Metal Detector system All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
In case the Metal Detector configuration already exist in
USB memory, press $ to overwrite or E to not already exists already exists
Overwrite?
overwrite. Overwrite?
{| $=YES |||| NO=E |}
(UP)=YES ----- NO=(E)

===================== [\\\\\\\\\\\\\\\\\\\]
The Configuration file is saved as:
Done Done

:/Ceia/Configuration/ ---------------------
{|||||||||||||||||||}
xxxxxxxxxxx.tce

where xxxxxxxxxxx is the Metal Detector serial number.

Import cfg.from Remote Possible settings Standard setting Parameter


USB - - - Global
Description Models
Import Metal Detector Configuration from a similar Metal Detector system All models
This command is available only if IXC=ON

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

==== Select file ==== [\\\ Select file \\\]


Select the Metal Detector serial number to copy the @+SN2110021111
configuration from and press E. *+SN2110021111 +SN2110021112
+SN2110021115
+SN2110021112 +SN2110021116
+SN2110021117
+SN2110021115
{|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
A confirmation is needed: press $ to overwrite or E to
not overwrite. Do you confirm? Do you confirm?

(UP)=YES NO=(E)
{|| $=YES || NO=E ||}
---------------------

Size is different [\\\\\\\\\\\\\\\\\\\\]


It is possible to import configuration from Metal
Detectors of the same model, installed on identical Load Size is different
Load
systems, but with different probe dimensions. 2110021111? 2110021111?

The correct functioning of the systems is however to be (UP)=YES NO=(E) { $=YES ||||||| NO=E }

verified.
===================== [\\\\\\\\\\\\\\\\\\\\]
It is not possible to import configurations of different
Metal Detector models. 2110021111 2110021111
Not compatible
Not compatible
{||||||||||||||||||||}
---------------------

39
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.11.1 Network config.


HN~~~~~THS2110021111@
List of commands available under the Network config. submenu. Host protocol STAT
IP 192. 9.201. 96
NM 255.255.255. 0
GW 192. 9.201.100
This menu is available only on models with IXC card installed DNS 192.168. 0.100
(IXC=ON). MAC 000A26:99:18:0C
Web server ON

Remote Possible settings Standard setting Parameter


HN 14 characters THSXXXXXXXXXX
HN alphanumeric string (XXXXXXXXXX=S/N)
Global
Description Models
Host name All models

Remote Possible settings Standard setting Parameter


Host protocol
HPR STAT / DHCP - Global
Description Models
Host protocol
All models
STAT: Static. DHCP: Dynamic Host Configuration Protocol

Remote Possible settings Standard setting Parameter


IP from 000.000.000.000
IPA to 255.255.255.255
192.168.127.200 Global
Description Models
IP address
All models
Not available with HPR=DHCP.

Remote Possible settings Standard setting Parameter


NM from 000.000.000.000
NM to 255.255.255.255
255.255.255.0 Global
Description Models
Net mask
All models
Not available with HPR=DHCP.

Remote Possible settings Standard setting Parameter


GW from 000.000.000.000
GW to 255.255.255.255
- Global
Description Models
Gateway All models
Not available with HPR=DHCP.

Remote Possible settings Standard setting Parameter


DNS from 000.000.000.000
DNS to 255.255.255.255
- Global
Description Models
Domain Name System All models
Not available with HPR=DHCP.

Remote Possible settings Standard setting Parameter


MAC
MAC - - Global
Description Models
MAC address All models

40
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Web server
WEBS ON / OFF ON Global
Description Models
Web server activation All models

Remote Possible settings Standard setting Parameter


Product tracking Related to the
FO OFF / 1 – 5 OFF
current product
Description Models
Automatic adjustment to product characteristics drifts
All models,
Set FO≠OFF only in case of chemical-physical characteristics drift over time, enough to determine except
variations on the received signal; the Metal Detector will automatically optimize the product THS/MN21
compensation, at a speed proportional to the value of FO.
Set FO≠OFF only if strictly necessary and at a value as low as possible, depending on the product
characteristics.

Remote Possible settings Standard setting Parameter


Inhib. time
IN 0,00 – 30,00 s 0 Global
Description Models
Inhibition time
In every model, if IN≠0, the Metal Detection capability is inhibited when INHIBITION Input is
activated. The Metal Detection capability is enabled back after IN time from Input deactivation. For All models
Conveyor Control System, the Metal Detection capability is also inhibited for IN time after belt start.
Set IN=0 to disable this function.
A message is shown on the display when the Metal Detector is inhibited.

Remote Possible settings Standard setting Parameter


Barcode enable
BE 6 alphanum. chars - Global
Description Models
Enabling code for operation with bar-code reader
6-character code supplied by CEIA and specific for each Unit.
This code enables the Metal Detector to work with a Bar-Code reader. All models
Settings BE with the right code enable the visualization of the Barcode Menu with all the
corresponding parameters.

Remote Possible settings Standard setting Parameter


Minimum speed
BL See below - Global
Description Models
Minimum product transit speed
Set this parameter value [m/min] to the minimum product transit speed.
The value range of this parameter depends on the system configuration: All models
- With Conveyor Control System: 10  KT  BL  BM (see parameter KT and BL)
- With Control Power Box: 2  BL  BM

Set this value as closest as possible to BS, according to the needed settings, in order to increase the Metal
Detector immunity to interferences.

41
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Speed Related to the
BS 2 – 250 m/min. -
current product
Description Models
Product transit speed
This parameter set the nominal value for the product transit speed [m/min].
The product transit speed is adjustable according to system configuration:
- With Conveyor Control System: set BS to the desired belt speed, in the range BL ÷ BM. All models
- With Control Power Box and without an encoder (KE=0): set BS as close as possible to the
nominal product transit speed, in the range BL ÷ BM.
- With Control Power Box and with an encoder (KE>0): the BS parameter is not available.

Remote Possible settings Standard setting Parameter


Maximum speed
BM See below - Global
Description Models
Maximum product transit speed
Set this parameter to the maximum product transit speed [m/min].
The range of this parameter depends on the system configuration: All models
- With Conveyor Control System: BL  BM  MI  KT (see parameters MI and KT)
- With Control Power Box: BL  BM  250
Set this value as closest as possible to BS, according to the needed settings, in order to increase the Metal
Detector immunity to interferences.

Remote Possible settings Standard setting Parameter


Filter adj
ADS -3 / +3 0 Global
Description Models
Filter adjustment
Setting ADS on values higher than zero, the detection and ejection capabilities are increased with All models
high speed products; consequently the immunity is decreased.
Set ADS on negative values only in case an increased immunity to environmental noises is needed.
Always check the correct functioning of the system, after every modification of ADS parameter.

Remote Possible settings Standard setting Parameter


Phcell position
PH IN / OUT - Global
Description Models
Position of the synchronization photocell relative to the probe
IN: photocell located at entrance to the probe (respect to the transit direction); All models
OUT: photocell located at exit from the probe (respect to the transit direction).
Available only with EM=S or SB

Remote Possible settings Standard setting Parameter


Phcell-MD dist.
PD 0 – 2000 mm - Global
Description Models
Distance between Metal Detector and Synchronization photocell
Set PD to the distance between the center of the Synchronization Photocell and the nearest side of All models
the Probe.
Available only with EM=S, SB or FS

42
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Check phot.dist
ECPD 0 – 6000 mm - Global
Description Models
Distance between Metal Detector and Ejection Check photocell
Set ECPD to the distance between the center of the Ejection Check Photocell and the exit side of All models
the Probe.
Available only with EM=S or FS

Remote Possible settings Standard setting Parameter


EjON resp.time
ERT 0.000 – 2.000 s - Global
Description Models
Ejector ON response time
Set ERT to the energizing response time of the ejection system electrovalve. All models
Available only with EM=F, S or FS

Remote Possible settings Standard setting Parameter


EjOFFresp.time
ERF 0.000 – 2.000 s - Global
Description Models
Ejector OFF response time
Set ERF to the de-energizing response time of the ejection system electrovalve. All models
Available only with EM=FS

Remote Possible settings Standard setting Parameter


K transmis.
KT 0.000 – 9.999 - Global
Description Models
Transmission constant of the motor reducer unit
Set KT > 0 only with Conveyor Control System, as
indicated in the Installation Manual. transit _ speed All models
KT 
transit_speed is in m/min motor _ frequency
motor_frequency is in Hz
When the value of KT is altered, parameters BL and BM are automatically set to nominal values 30 x KT
and 60 x KT respectively. BL and BM can nevertheless be altered manually as well (see parameters BL
and BM).

Remote Possible settings Standard setting Parameter


K encoder
KE 0 – 1000 ppr 0 Global
Description Models
Encoder constant
Set KE to the encoder ppr (pulse per revolution). If the encoder is not used, set KE=0. All models
After having KE and DI set, verify the correct speed measure, in I/O Status > Measures > Speed.

Remote Possible settings Standard setting Parameter


Diameter
DI 10 – 250 mm - Global
Description Models
Diameter of encoder measurement wheel
Set DI to encoder measurement wheel diameter (or to the belt cylinder, with the encoder applied on All models
it). After having KE and DI set, verify the correct speed measure, in I/O Status > Measures.

43
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


TP adjustment
TA 0 – 35999 - Global
Description Models
Correction of the received analysis signal
Only on
This parameter is specific for each device and automatically set during TA Autolearn. THS/xx21E
See also TL parameter.
Changing manually this value can cause an incorrect operation of the Metal Detector! In this case, execute
TA Autolearn.

Remote Possible settings Standard setting Parameter


TA1
TA1 0 – 35999 - Global
Description Models
Correction of the received analysis signal
Only on
This parameter is specific for each device and automatically set during TA Autolearn. THS/xx21
See also TL parameter.
Changing manually this value can cause an incorrect operation of the Metal Detector! In this case, execute
TA Autolearn.

Remote Possible settings Standard setting Parameter


TA2
TA2 0 – 35999 - Global
Description Models
Correction of the received signal analysis parameter
Only on
This parameter is specific to each device. This parameter must be automatically set up using the TL THS/xx21
command in case the SCD card is replaced.
Changing manually this value can cause an incorrect operation of the Metal Detector! In this case, execute
TA Autolearn.

Remote Possible settings Standard setting Parameter


TA autolearn
TL ON / OFF OFF Global
Description Models
TA or TA1/TA2 Autolearn
All models,
The TL command starts TA Autolearn procedure to set automatically TA value (or TA1 and TA2 except
values). Follow the procedure as reported in the Installation Manual. THS/MN21
TL is automatically set to OFF at the end of procedure.
Perform TL command only if strictly needed (for example in case of SCD replacement): a wrong execution
cause an incorrect operation of the Metal Detector. In that case, repeat correctly the procedure.
In case of environmental noises during the execution of TA Autolearn, it is possible that it will be aborted
(message “AUTOLEARN ABORTED”).

Remote Possible settings Standard setting Parameter


Autotest phase
ATTP ON / OFF ON Global
Description Models
All models,
Autotest signal Phase tracking
except
Automatic control, continuously performed, to guarantee the maximum Metal Detector operative THS/MN21 and
stability in every condition. THS/xx21E

44
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Autotest module
ATTM ON / OFF ON Global
Description Models
All models,
Autotest signal Magnitude tracking
except
Automatic control, continuously performed, to guarantee the maximum Metal Detector operative THS/MN21 and
stability in every condition. THS/xx21E

Remote Possible settings Standard setting Parameter


Autotest diagnos
ATD ON / OFF ON Global
Description Models
All models,
Activation of Autotest diagnosis
except
Activation of Autotest diagnosis in order to signal Antenna faulty conditions. THS/MN21 and
THS/xx21E

Remote Possible settings Standard setting Parameter


Display mode
DMD GRAPH / ALPHA GRAPH Global
Description Models
Not available for
Selection of the display mode
THS/xx21E
If set to ALPHA, the display will shows 4 lines of 20 characters, without any graphic. models
For applications with Programming interface emulation, set DMD=ALPHA. See also DL and DLU
parameters.

Remote Possible settings Standard setting Parameter


Display contrast
DC 2 – 115 100 Global
Description Models
Display contrast adjustment All models

Remote Possible settings Standard setting Parameter


Dimming delay
DDD 10 – 900 s 60 Global
Description Models
Selection of the dimming delay
All models
Time (in seconds) elapsing from the last display update, to the automatic contrast lowering.

Remote Possible settings Standard setting Parameter


Input logic
LO P/N P Global
Description Models
Inputs logic
Applies to all inputs. Set this parameter (P=PNP logic, N=NPN logic) according to all input devices
logic.
If LO=P, each input line is pulled to +Vin (by pull-down resistor on ALM card) when the All models
corresponding connected device is activated.
If LO=N, each input line is pulled to 0V (by pull-up resistor on ALM card) when the corresponding
connected device is activated.
Refer to the Installation Manual for the electrical connections

45
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


BIN FULL input
IL NC / NO - Global
Description Models
Function type of the device connected to the “BIN FULL” input
NC: Normally Closed; NO: Normally Open All models
Set NC or NO according to the functioning type of the connected sensor, in normal working
condition. Refer to the Installation manual for the electrical connection.

Remote Possible settings Standard setting Parameter


BIN ABSENT input
IA NC / NO - Global
Description Models
Function type of the device connected to the “BIN ABSENT” input
NC: Normally Closed; NO: Normally Open. All models
Set NC or NO according to the functioning type of the connected sensor, in normal working
condition. Refer to the Installation manual for the electrical connection.

Remote Possible settings Standard setting Parameter


EJECT.CONF.input
IE NC / NO - Global
Description Models
Function type of the device connected to the “EJECT.CONFIRMATION” input
NC: Normally Closed; NO: Normally Open
Set NC or NO according to the functioning type of the connected sensor, in normal working All models
condition. If EJECTIOR POSITION CHECK input is used, its function type is complementary to IE.
Refer to the Installation manual for the electrical connection.

Remote Possible settings Standard setting Parameter


PHOTOCELL input
IP NC / NO - Global
Description Models
Function type of the device connected to the “PHOTOCELL” input
NC: Normally Closed; NO: Normally Open
Set NC or NO according to the output type of the connected sensor, in normal working condition. All models
If EJECTION CHECK input is used, its function type is equal to IP.
Refer to the Installation manual for the electrical connection.

Remote Possible settings Standard setting Parameter


FOLLW.CONV.input
IW NC / NO - Global
Description Models
Function type of the device connected to the "FOLLOWING CONVEYOR" input
NC: Normally Closed; NO: Normally Open All models
Set NC or NO according to the output type of the connected sensor, in normal working condition.
Refer to the Installation manual for the electrical connection.

46
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


LOW PRESSURE inp
IAP NC / NO - Global
Description Models
Function type of the device connected to the "LOW PRESSURE" input
NC: Normally Closed; NO: Normally Open All models
Set NC or NO according to the output type of the connected sensor, in normal working condition.
Refer to the Installation manual for the electrical connection.

Remote Possible settings Standard setting Parameter


Analysis Mode Related to the
AM STD / HSE / HVI STD
current product
Description Models
Analysis mode of the received signal
HVI: Vibration immunity optimized for not dry product, detection sensitivity lower than STD All model except
HSE: Sensitivity optimized for dry product, vibrations immunity lower than STD (not available on THS/MN21
THS/xx21E models).
Available only for some Detection modes. If not available, AM=STD.

Remote Possible settings Standard setting Parameter


Ejec.queue reset
QR ON / OFF OFF Global
Description Models
Reset of ejection queue in case of belt stop
QR=OFF: in case of belt stop during a product alarm, all the product between the probe entrance
(for EM=F) or photocell (for EM=S) and the ejector will be rejected when the belt is
started again. All models
QR=ON: in case of belt stop during a product alarm, the ejection queue is reset in case of belt
stop.
Available only with EM=S or F

Remote Possible settings Standard setting Parameter


Reverse detect Related to the
RD ON / OFF OFF
current product
Description Models
Reverse detection
Detection of lack of metal parts, with inverted
operation of both output relays (alarm and ejection).
This function requires a photocell (EM=S or SB) to be
mounted before or after the probe. All models
This function is normally used, for example, to detect
packages without closing clip.

Example with photocell at exit:


To reset the standard Metal Detection operation, set RD=OFF.

47
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Eject.act.if stop
EIS ON / OFF - Global
Description Models
Ejector activation when belt stops
With EIS=ON the system has different behaviours, according to its configuration:
- With Conveyor Control System or encoder: in case of a belt stop during an ejection, the ejector will
continue to be activated until the belt restart and then it will finish the ejection.
- With FOLLOWING CONVEYOR Input used: in case of input deactivation during an ejection, the All models
ejector will continue to be activated until the input is activated again and then it will finish the
ejection.
With EIS=OFF the ejector is deactivated after 2 seconds from the belt stop during an ejection, or
from the FOLLOWING CONVEYOR.input deactivation.
Not available with EM=B or SB

Remote Possible settings Standard setting Parameter


EJECT RELAY logic
ERL NO / NC NO Global
Description Models
Ejection relay logic
NC: In case of ejection, the relay switch to pin NC; All models
NO: In case of ejection, the relay switch to pin NO.

Remote Possible settings Standard setting Parameter


PREC CONV enable
PC ON / OFF OFF Global
Description Models
Enable “preceding conveyor” relay
Through the PREC_CONV relay (Preceding conveyor relay) the Metal Detector can control a device
connected in-line with it (for example a preceding conveyor system). All models
- With Conveyor Control System or encoder, if PC=ON the PREC_CONV relay is activated only
during the belt movement. If PC=OFF: the relay is always deactivated.
- With other systems, the application of this parameter has no effect.

Remote Possible settings Standard setting Parameter


FOLLW.CONV.enab
FC ON / OFF OFF Global
Description Models
Enable “following conveyor” input
Through the FOLLOWING CONVEYOR input (Following Conveyor) is possible to control the Metal
Detector from a device connected in-line with it (for example a following conveyor system).
If FC=ON the input status generates different behaviors for the Metal Detector, according to the
system configuration:
- with Conveyor Control System: the Metal Detector belt is enabled to run only if the FOLLOWING
CONVEYOR input is active. The belt stops immediately in case of FOLLOWING CONVEYOR
input deactivation. See also RE. All models
- with Control Power Box and without encoder: the Metal Detector stops incrementing the delay
counter for ejection activation in case the “following conveyor” input is not active. This functionality
can be used for example on a pipeline to stop the ejection activation delay in case the pump that
runs the liquid is stopped.
- with Control Power Box and with encoder: the application of the parameter enable the belt speed
control (see also EA) only with the FOLLOWING CONVEYOR input enabled.
If FC=OFF: the system behavior is independent from the input status.

48
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Autom. restart
RE ON / OFF OFF Global
Description Models
Belt restart if there is “FOLLOWING CONVEYOR” input activation
If FC= OFF, the parameter has no effect;
If FC=ON:
- RE=OFF: if the belt is stopped by the “FOLLOWING CONVEYOR” input deactivation, when the
input is reactivated, the conveyor belt must be restarted manually. All models
- RE=ON: if the belt is stopped by the “FOLLOWING CONVEYOR” input deactivation, when the
input is reactivated, the conveyor belt restarts automatically unless the STOP key has been
pressed in the meantime. When the belt is stopped because of the following conveyor input, the
green light ( ) flashes.
Available only with Conveyor Control System

Remote Possible settings Standard setting Parameter


Test relay mode
TRM TREQ / TACT TREQ Global
Description Models
Test Request Relay functioning mode
It is possible to set the functioning mode for the TEST REQUEST relay: All models
- TREQ: the Relay is activated at the scheduled Test request, until the start of the Test execution;
- TACT: the Relay is activated only during the test execution.

Remote Possible settings Standard setting Parameter


Aux relay mode
ARM from 0 to N 0 Global
Description Models
AUX Relay functioning mode
- ARM=0: AUX relay is used for the Quick Test; See parameter QCKT. All models
- ARM=N: AUX relay is activated when SC status include the value set on ARM.
See SC parameter for the possible values of N.

Remote Possible settings Standard setting Parameter


Stop Time
ST 0 – 99 min 0 Global
Description Models
Belt auto-stop time
The use of a Synchronization Photocell is requested: if no passage is detected for a time ST, with All models
the belt running, the conveyor belt stops automatically (N.B. No message is given).
Available only with Conveyor Control System

49
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.11.2 Motor config


Nom.MotorVolt.
List of parameters available under the Motor config submenu. Nom.MotorCurr.
Nom.MotorPower
Nom.MotorCosPhi
This menu is available only on models with Conveyor Control System. Nom.MotorEffic
Nom.MotorFreq.
Nom.Motor.Speed
Max inv. freq.
Acceler. Time
Deceler. Time
Flying start
Inv.PulseFreq.
Inv.BaseFreq.
ResetInv.ToDefault

All the following parameters refers to motor and inverter provided by CEIA.
In case of customer motor, read the motor label for the correct values

Remote Possible settings Standard setting Parameter


Nom.MotorVolt.
NMV 70 – 230 V 230 Global
Description Models
Nominal motor voltage, from rating plate
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Nom.MotorCurr.
NMC 0.00 – 9.00 A - Global
Description Models
Nominal motor current, from rating plate
If set to 0.00, the motor overload protection is disabled. All models
This parameter is adjustable only with the motor stopped.
Available only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Nom.MotorPower
NMP 0.00 – 10.00 kW - Global
Description Models
Nominal motor power, from rating plate
This parameter is adjustable only with the motor stopped. All models
Available only on some versions and only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Nom.MotorCosPhi
NMCP 0.000 - 1.000 - Global
Description Models
Nominal motor power factor (cos), from rating plate
All models
This parameter is adjustable only with the motor stopped.
Available only on some versions and only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Nom.MotorEffic
NME 0.00 – 0.99 - Global
Description Models
Nominal motor efficiency, from rating plate
This parameter is adjustable only with the motor stopped. All models
Available only on some versions and only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself
50
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Nom.MotorFreq.
NMF 12 – 99,00 Hz - Global
Description Models
Nominal motor frequency, from rating plate
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Nom.Motor.Speed
NMS 0 – 40000 rpm - Global
Description Models
Nominal motor speed, from rating plate
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Max inv. freq.
MI 60 – 100 Hz - Global
Description Models
Maximum output frequency of the inverter
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System
On CEIA integrated systems the value is already set to ensure the correct functioning of the system itself

Remote Possible settings Standard setting Parameter


Acceler. Time
ACCT 0.00 – 99.00 s - Global
Description Models
Motor acceleration time
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System

Remote Possible settings Standard setting Parameter


Deceler. Time
DECT 0.00 – 99.00 s - Global
Description Models
Motor deceleration time
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System

Remote Possible settings Standard setting Parameter


Flying start
IFLY OFF / ON - Global
Description Models
Flying start
Set to ON only in case of motor interferences to the THS/MN21 probe. All models
This parameter is adjustable only with the motor stopped.
Available only with Conveyor Control System

51
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Inv.PulseFreq. 2, 4, 6, 8, 10,
IPF 12, 14, 16 kHz
- Global
Description Models
PWM frequency
This parameter is adjustable only with the motor stopped. All models
Available only with Conveyor Control System

Remote Possible settings Standard setting Parameter


Inv.BaseFreq.
IBF 50 / 60 Hz - Global
Description Models
Motor frequency [Hz]
This parameter is adjustable only with the motor stopped. All models
Available only on some versions and only with Conveyor Control System

Remote Possible settings Standard setting Parameter


ResetInv.ToDefault
IRST - - Global
Description Models
Reset inverter parameters to default
This command reset all inverter internal parameters (not listed here) to the default values, optimized All models
for THS. A confirmation will be requested. This command is selectable only with the motor stopped.
Available only with Conveyor Control System

Remote Possible settings Standard setting Parameter


RS232 BaudRate
BR 9600 / 57600 bps 57600 Global
Description Models
Setting of the RS232 BaudRate All models

Remote Possible settings Standard setting Parameter


auxRS232B.Rate
AUBR 9600 / 57600 bps - Global
Description Models
Setting of the auxiliary RS232 BaudRate All models

Remote Possible settings Standard setting Parameter


DTR protocol
DT N/H N Global
Description Models
DTR protocol
Use of DTR (Data Terminal Ready) line to communicate with a serial printer.
DT=N: line not used; All models
DT=H: line used, in handshake mode, as active if high. The Metal Detector stops sending data to
the serial port, in case the line is not pulled up.

Remote Possible settings Standard setting Parameter


Bounce time
BT 0,001 – 0,200 s 0,005 Global
Description Models
Setting of the minimum activation time for fast inputs
All models
Minimum activation time for a “fast” input (all inputs and the photocells), to be considered active.

52
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Remote Possible settings Standard setting Parameter
Bounce t. slow
BTS 0,001 – 0,200 s 0,05 Global
Description Models
Setting of the minimum activation time for slow inputs
Minimum activation time for a “slow” input (control keys and emergency buttons), to be considered All models
active.

Remote Possible settings Standard setting Parameter


Centre belt time
CBT 0 – 60 s 0 Global
Description Models
Retractable flat belt centering time delay
Used on some models of retractable conveyors with flat belt, equipped with centering pistons and
photocells; in this systems:
- the activation of a centering photocell, activates the relative centering piston All models
- the deactivation of a centering photocell, deactivates the relative centering piston with a delay of
CBT (the delay count will be reset in case of re-activation of the photocell within CBT time).
Set CBT=0 to deactivate the centering.

3.12 Barcode reader


Window start
List of parameters available under the Barcode reader menu. Window end
Learn code
This menu is available only if the use of a barcode reader has been Barc-MD dist.
enabled (contact CEIA). No code ejection

Remote Possible settings Standard setting Parameter


Window start
WS 1 - 48 - Global
Description Models
First of product identification characters
First character of series used to identify the product within the code.
Example: If on an EAN13 code (code length 13 digits) we want to ignore the first 3 digits, we must All models
set WS=4 and WE=13. In this case code 8004040090011 is considered the same of code
9114040090011.
Available only with barcode reader enabled

Remote Possible settings Standard setting Parameter


Window end
WE 1 - 48 - Global
Description Models
Last of product identification characters
Last character of series used to identify the product within the code.
Example: If on an EAN13 code (code length 13 digits) we want to ignore the last 2 digits, we must All models
set WS=1 and WE=11. In this case code 8004040090011 is considered the same of code
8004040090022.
Available only with barcode reader enabled

53
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Learn code
LC ON / OFF OFF Global
Description Models
Activation of code/product association phase
Command which allows a code to be associated with a product. When activated (LC=ON), the
message “Pass Code” appears on the display. After the barcode is passed in front of the reader, the
message “ENTER to confirm” and the code read both appear on the display. Press ENTER to All models
associate the code read with the current product, press PROG key to cancel the operation. if one of
the arrow keys is pressed, a new request to pass the barcode in front of the reader is made.
Available only with barcode reader enabled

Remote Possible settings Standard setting Parameter


Barc-MD dist.
BD 300 – 5000 mm - Global
Description Models
Distance between reading point and antenna
The reader is mounted upstream of the probe in order to read a code stamped on the package. If the
code is recognised, the reader sends a command to the Metal Detector to select the relevant
product type. The time required by the THS to process the barcode is usually insignificant, but
becomes important if the band or the detection mode is changed due to a modification in the type of
product. When the Metal Detector receives the signal to change product type, an internal adjustment
procedure is activated the length of which determines the minimum distance between two packages
with different codes, that is to say containing different products.

Dp Dp

S S
BR
BR

N N

Dsbr L Dsbr L

THS/xxMS21 THS/21E-3F THS/xx21 or THS/21E or


with change of with change of THS/xxMS21 THS/21E-3F
detection mode band (BA) without change of without change of
Model / (DM) between one between one detection mode band (BA
Event product and the product and the (DM) between one parameter) All models
other other product and the between one
other product and the
other
Distance
between the Dp  L + 3000 mm Dp  L + 300 mm
packs
Distance
between the
barcode
Dsbr  3000 mm Dsbr  300 mm
reader and
the THS/21
probe

S Metal Detector probe L Length of probe


N Conveyor belt Dsbr Distance THS probe-barcode rea er
BR Barcode Reader Dp Distance between packs of different products

Available only with barcode reader enabled and EM=S or SB

54
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


No code ejection
NE ON / OFF OFF Global
Description Models
Ejection of packs with wrong code
When activated, the packages without barcodes or with invalid barcodes are ejected. If deactivated, All models
there is no action.
Available only with barcode reader enabled and EM=S or SB
In order to function, a photocell for synchronization of the packs must be installed. This photocell can be
installed before or after the THS probe; HOWEVER, IT MUST BE INSTALLED AFTER THE BARCODE
READER.

3.13 I/O Status


Outputs
This menu shows, in real time, the list of input and output lines with Inputs
Measures
indication of their status, together with the value of the measures Variables
performed by and variables set on the Metal Detector.
The status display is subdivided into practical submenus.

3.13.1 Outputs
Alarm relay L
This submenu shows, in real time, the list of output lines with Eject relay L
Eject NO L
indication of their status. (L: not active, H: Active). Eject NC L
PREC CONV relay L
TEST REQ.relay L
Selecting an output and pressing the E key, it is possible to manually READY relay H
AUX relay L
change each state pressing arrow keys. Pressing again the E key, the INVERTER relay L
MOTOR FAULT light L
output is deselect and return to the previous state. RUNNING light
RED lamp
L
L
YELLOW lamp L
BLUE lamp L
The list of shown output lines may vary depending on the Metal Detector model. Ext.buzzer L

3.13.2 Inputs
PHOTOCELL input H
This submenu shows, in real time, the list of input lines with indication EJECT.CONF.input L
EJECT CHECK in H
of their logic level. (L: not active, H: Active). RESET in L
INHIBITION in L
FOLLW.CONV.input L
BIN FULL input L
BIN ABSENT input L
LOW PRESSURE inp L
AUX1 input L
EJ.POSIT.CHK.in L
START button in L
STOP button in L
UP button in L
DOWN button in L
RESET button in L
ENCODER in -
MOTOR FAULT in L
EMGCY sec1 H
EMGCY sec2 H
EMGCY sec3 H
J16.3-4 H
EMGCY RELAY H
DTR in L
Vout CHECK H
Vin CHECK H
DIP 1 H
DIP 2 H
DIP 3 H
The list of shown input lines may vary depending on the Metal Detector model. Show Barcode Rdr In H

55
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.13.3 Measures
Speed
This submenu shows a list of measures performed in real time by the Motor curr.
Motor volt V11
Metal Detector. This can be useful during Technical Assistance. ALM supply V1 24.0
ALM supply V2 +15.7
ALM supply V3 -15.9
SCD supply V4 1.6
Vtx+ V5 13.5
Vtx- V6 13.3
V71 0.0
V72 0.0
V81 3.5
V82 0.2
Vprobe V9 15.4
ALMsupply V12 5.8
Itx+ I5 0.283
Itx- I6 0.270
Internal temp. +45
The list of shown measures may vary depending on the Metal Detector model. Ej.op.time 0.000

3.13.4 Variables
This menu is not available on THS/xx21E models.

Z1 0
This submenu shows a list of variables related to the current product. Z2 0
Z3 0
These variables are set automatically during the Autolearn
procedure.
The list of shown variables may vary depending on the
Metal Detector model and settings.

Changing manually these values can cause an incorrect operation of the Metal Detector! In this case, repeat the
Autolearn for the current product.

56
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.14 Diagnosis managem.
Photocell fault
List of parameters available under the Diagnosis managem. menu. Sync.max.activ
Chck.max.activ
Phot.fau.thres
Bin full
Bin full delay
Bin absent
Bin absent delay
Bin with lock
Unlock bin time
Air pressure low
Low press. delay
Eject confirmat.
Confirm time
Eject.check
Ej.check accur.
Pho.diag.if stop
Ejector pos.chk
Ej.pos.chk delay
Encoder check
Test time out
Test failed
Event buf. full
Login restrict.
Al.rate period
Al.rate threshold
Ej. max extent
Ejec.on fault
Probe fault reset

Remote Possible settings Standard setting Parameter


Photocell fault
PA ON / OFF OFF Global
Description Models
Enabling of Synchronization and Ejection Check photocells diagnosis
Enabling / disabling of the diagnosis for the Synchronization and Ejection Check photocells. All models
See SPMA, CPMA and PAT parameters.

Remote Possible settings Standard setting Parameter


Sync.max.activ
SPMA 0 – 60000 mm 0 Global
Description Models
Maximum continuous activation of the Synchronization photocell
Set SPMA to a maximum allowed distance (in millimetres) ran from the belt with continuous All models
Synchronization photocell activation: if exceeded, the “Sync Photocell” Fault is activated.
Set SPMA=0 to disable this diagnosis. Anyway, this diagnosis is anyway disabled with PA=OFF.

Remote Possible settings Standard setting Parameter


Chck.max.activ
CPMA 0 – 60000 mm 0 Global
Description Models
Maximum continuous activation of the Ejection Check photocell
Set CPMA to a maximum allowed distance (in millimetres) ran from the belt with continuous Ejection All models
Check photocell activation: if exceeded, the “Ejection Check Photocell” Fault is activated.
Set CPMA=0 to disable this diagnosis. Anyway, this diagnosis is anyway disabled with PA=OFF.

Remote Possible settings Standard setting Parameter


Phot.fau.thres
PAT 0 – 10000 - Global
Description Models
Photocell fault activation threshold
If PAT > 0, the Synchronization and Ejection Check photocells activations are counted during the
belt movement (or with FOLLOWING CONVEYOR Input activated, if used) without ejection in
progress. All models
If the difference between photocells activations reaches PAT value, the Metal Detector activates the
Fault status related to the photocell with less activations.
Set PAT=0 to disable this diagnosis. Anyway, this diagnosis is anyway disabled if PA=OFF.
PAT=1 is equivalent to PAT=2.

57
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Bin full
LF ON / OFF / CEON - Global
Description Models
Bin Full fault activation
Set LF = ON to enable the “Bin Full” Fault activation in case of BIN FULL Input activated for a time
longer than LFD delay. The system is automatically reset by removing the fault cause. All models
See also IL and LFD parameters.
With LF=CEON, the “Bin full” fault is activated when the EJECT.CONFIRMATION input is activated
(used when the ejection confirmation sensor is used to check the bin full condition too)

Remote Possible settings Standard setting Parameter


Bin full delay 00:00 – 59:59
LFD - Global
mm:ss
Description Models
Bin Full fault delay
All models
If the BIN FULL input is activated continuously for LFD time, the relative Fault status is activated.

Remote Possible settings Standard setting Parameter


Bin absent
LA ON / OFF - Global
Description Models
Bin Absent fault activation
Set LA = ON to enable the “Bin Absent” Fault activation in case of BIN ABSENT input activated for a All models
time longer than LAD delay. The system is automatically reset by removing the fault cause.
See also IA and LAD parameters.

Remote Possible settings Standard setting Parameter


Bin absent delay 00:00 – 59:59
LAD mm:ss
- Global
Description Models
Bin Absent fault delay
If the BIN ABSENT input is activated continuously for LAD time, the relative Fault status is activated. All models
In case of a bin fitted with electro-mechanical locking device, set LAD to a value that allows a correct
emptying procedure.

Remote Possible settings Standard setting Parameter


Bin with lock
BWL ON / OFF OFF Global
Description Models
Bin control by electro-mechanical locking device
With this parameter set to ON, opening the bin with electric lock is allowed only by entering the
Programming phase and using the command Unlock bin. The electro-mechanical locking device All models
will be then open for UBT time.
Every bin unlocking is registered in the events log.

Remote Possible settings Standard setting Parameter


Unlock bin time
UBT 0 – 30 s 0 Global
Description Models
Unlock bin time All models

58
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Air pressure low
AP ON / OFF - Global
Description Models
Low Pressure fault activation
Set AP = ON to enable the “Low Pressure” Fault activation in case of LOW PRESSURE Input
activated for a time longer than APDL delay. The system is automatically reset by removing the fault All models
cause.
See also IAP and APDL parameters.

Remote Possible settings Standard setting Parameter


Low press. delay
APDL 0 – 60 s - Global
Description Models
Low Pressure fault delay
If the LOW PRESSURE input is activated continuously for APDL time, the relative Fault status is All models
activated.

Remote Possible settings Standard setting Parameter


Eject confirmat.
CE ON / OFF - Global
Description Models
Enabling of the ejection confirmation
Set CE = ON to enable the control of the ejection confirmation. After the ejector activation, if the
EJECT CONFIRM Input is not activated within CT time, the Fault “Ejection not confirmed” is
activated (for example, in case of a contaminated pack not rejected correctly into the storage bin, or
with the ejector not correctly activated). Check the cause and reset the Fault.
If Ejection Position Check sensor is not used (EPC=OFF), this control enable also the activation of
the Fault “Ejection system jam” in case of Ejection Confirmation Input activation without ejection All models
before (for example, in case of a pack blocked, during the transit, in front of the Ejection
Confirmation sensor, or with the ejector stuck in ejection position). Removing the cause, the Metal
Detector reset automatically the Fault.
If EPC=ON, this control enables also the activation of the fault “Eject.out of order”, in case the
ejector is not correctly positioned.
Available only with EM=F,S or FS.

Remote Possible settings Standard setting Parameter


Confirm time
CT 0,01 – 60,00 s - Global
Description Models
Confirm ejection time
With the Ejection Confirmation activated (CE=ON), CT represents the maximum allowed delay time All models
for the Ejection Confirmation Input to be activated, from the Ejection activation. See also CE
parameter.
If CE=ON, it is possible to view the last opening time, elapsed from opening command and Ejection
Confirmation input activation, directly on I/O Status > Measures > Ej.op.time.
Set CT at a value not lower than the real opening time.

Remote Possible settings Standard setting Parameter


Eject.check
ECK ON – OFF - Global
Description Models
Ejection check functionality
With ECK=ON, the Ejection Check Photocell (EJECT CHECK Input) checks that, during an ejection,
the belt area cleared by the ejector is completely empty, to avoid possible contaminated pack All models
transits without ejection.
Set ECK=OFF to disable the control. See also ECKA parameter.
Available only with EM=S or FS

59
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Ej.check accur.
ECKA 2 – 250 mm - Global
Description Models
Accuracy of the ejection check functionality
Setting ECKA:
EM=FS: the area to be checked is equal to the area cleared by the ejector, reduced of ECKA value All models
on both sides.
EM=S: the area to be checked is equal to the pack length, reduced of ECKA value on both sides.
Available only with EM=S or FS

Remote Possible settings Standard setting Parameter


Pho.diag.if stop
PDIS ON / OFF - Global
Description Models
Photocell diagnosis with belt stop
If PDIS is set to ON, the diagnosis for the Bin Full, Bin Absent and Low Pressure inputs are All models
performed also when the conveyor belt is stop (or with Following Conveyor Input not active, if used).

Remote Possible settings Standard setting Parameter


Ejector pos.chk
EPC ON – OFF - Global
Description Models
Activation of the Ejector Position Check
This control, together with CE=ON, enables the activation of the fault “Ejector out of order”, in case All models
the ejector is not correctly positioned or not correctly re-positioned within EPCD time from the ejector
activation.

Remote Possible settings Standard setting Parameter


Ej.pos.chk delay
EPCD 1,00 – 60,00 s - Global
Description Models
Setting of the ejector position verification delay
Set EPCD to the maximum time allowed (from the activation command) for the ejector to return All models
correctly in the rest position. See also EPC parameter.
Set EPCD to a value not lower than the real ejector opening and closing time.
If EPC=ON, it is possible to view the last activation and deactivation time (Ej.op.time, elapsed from
activation command to EJECT.CONFIRMATION input activation; Ej.cl.time, elapsed from deactivation
command to EJECTOR POSITION CHECK input activation), in I/O Status > Measures.

Remote Possible settings Standard setting Parameter


Encoder check
EA ON – OFF - Global
Description Models
Activation of the encoder check functionality
If an encoder is used (KE > 0), set EA=ON to enable the encoder belt speed check. This control
depends on the system configuration:
- With Conveyor Control System: After 10 seconds from the conveyor belt starting, if the speed read
by the encoder is lower than 0.7 BL or higher than 1.3 BM, the Fault “Encoder Frequency too low” All models
or the Fault “Encoder Frequency too high” is activated respectively. Remove the cause and reset
the Fault.
- With Control Power Box: After 10 seconds from the conveyor belt starting, if the speed read by the
encoder is lower than BL or higher than BM, the Fault “Encoder Frequency too low” or the Fault
“Encoder Frequency too high” is activated respectively. Remove the cause and reset the Fault.
Con Control Power Box, è richiesta la connessione dell’ingresso FOLLOWING CONVEYOR e l’attivazione
del parametro FC, altrimenti il controllo della velocità viene comunque sempre effettuato indipendentemente
dallo stato del nastro.

60
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Test time out
FT ON / OFF ON Global
Description Models
Activation of fault status if maximum time for Test expires
Set FT=ON to enable the Fault ”Test Timeout” activation in case of a scheduled Test not started
within the maximum time (TD or FTD). All models
In case of Test timeout, it is required to reset the Fault and to execute the Test.
See also STM parameter.

Remote Possible settings Standard setting Parameter


Test failed
FF ON / OFF ON Global
Description Models
Activation of fault status if a Test fails
Set FF=ON to enable the Fault “Test Failed” activation in case of Test failure.
In case of Test failure, it is possible to reset the Fault (if STM=OFF) or it is required to perform also All models
again and successfully the Test (if STM=ON).
See also STM parameter.

Remote Possible settings Standard setting Parameter


Event buf. full
FB ON / OFF OFF Global
Description Models
Fault activation in case of memory buffer full
The Events buffer memory contains always the last 1000 (21E series) or 10000 (21 series) or
100000 (with IXC card) occurred events. When the events buffer is 100%, the new events overwrite
the oldest ones.
Set FB=ON to avoid possible overwriting of event not yet printed: when the events buffer memory,
not printed, is at 90% (equivalent to 900 events on 21E series, 9000 on 21 series or 90000 with IXC All models
card), the Fault “Event Buffer Full” is activated. In this case it is required to print last events (PL) and
erase the print events (EV). Events are not immediately erased, but simply they are available to be
overwritten by future events.
With IXC card, save the last events with the command “Save last events”, then erase them with the
command “Empty last events”.
Set FB=OFF to disable this control. See also PL and EV parameters.

Remote Possible settings Standard setting Parameter


Login restrict.
FLR ON / OFF ON Global
Description Models
Activation of restricted login after three failed attempts
Set FLR=ON to enable the control about possible programming unauthorized access attempts: if All models
enabled, in case of three consecutive failed attempts the “Login restricted” Fault is activated.
Refer to paragraph 2.4.4 to reset this fault.

Remote Possible settings Standard setting Parameter


Al.rate period
ARP 0 – 60 min 0 Global
Description Models
Setting of alarm rate period
All models
See parameter ART.

61
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


Al.rate threshold
ART 0 – 250 0 Global
Description Models
Setting of alarm rate threshold
Set ART > 0 to enable the control of the Alarms number, according to ARP parameter:
ARP=0: if the number of current product Alarms (CA) reaches ART value, the Fault “Too many
Alarms” is activated. Reset the Product Alarm counter to Reset the Fault. All models
ARP>0: in case of ART Alarms during ARP time, the Fault “Too many Alarms” is activated. Reset
the Fault.
Set ART=0 to disable this control. See also CA parameter.

Remote Possible settings Standard setting Parameter


Ej. max extent
EMEX 0 – 60000 mm 0 Global
Description Models
Maximum continuous ejection extension
With Conveyor Control System, set EMEX to the maximum acceptable covered distance with the
ejector activated continuously due to long Alarm.
With Control Power Box, set EMEX to the maximum acceptable time with ejector activated
continuously due to long Alarm (as 0.06 EMEX/BS seconds). All models
If the ejection is activated for an extension higher than this limit, the Fault “Too many alarms” is
activated. Reset the Fault for system recovery.
Set EMEX=0 to disable this control.
Available only with EM=F or FS

Remote Possible settings Standard setting Parameter


Ejec.on fault
EF ON / OFF ON Global
Description Models
Ejection on fault
Set EF=ON to activate the ejection in case of Faults (except “Bin Full”, ”Bin Absent”, ”Low pressure”) All models
with moving belt. Reset the fault to deactivate the ejector.
With Conveyor Control System and SF=ON, the parameter has no effect.

Remote Possible settings Standard setting Parameter


Probe fault reset
PFR MAN / AUT AUT Global
Description Models
Automatic probe fault reset
If set to MAN, the system needs to be manually reset for each probe fault, even when the fault is All models
automatically solved by the system itself.

62
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.15 MD Test
FExtestx
List of commands available under the MD Test menu. NFExtest
SSxtestx

Remote Possible settings Standard setting Parameter


FE test Related to the
- - -
current product
Description Models
Activation of the test with Ferrous metal Test Sample
Select the test and press E key to start it. If FD>0, the diameter of the Ferrous Test Sample sphere
to be used is shown on display. Pass the sample within 1 minute. All models
For the test procedure and outcomes, see Functionality tests section of the Instructions manual.
See also FD,STM,SAC and FF parameters.

Remote Possible settings Standard setting Parameter


NFE test
- - - Global
Description Models
Activation of the test with Not Magnetic metal Test Sample
Select the test and press E key to start it. If ND>0, the diameter of the Not Magnetic Test Sample
sphere to be used is shown on display. Pass the sample within 1 minute. All models
For the test procedure and outcomes, see Functionality tests section of the Instructions manual.
See also ND,STM,SAC and FF parameters.

Remote Possible settings Standard setting Parameter


SS test
- - - Global
Description Models
Activation of the test with Stainless Steel Test Sample
Select the test and press E key to start it. If SD>0, the diameter of the Stainless Steel Test Sample
sphere to be used is shown on display. Pass the sample within 1 minute. All models
For the test procedure and outcomes, see Functionality tests section of the Instructions manual.
See also SD,STM,SAC and FF parameters.

3.16 Fail-safe test


Fail-safe test
List of commands available under the Fail-safe test menu.

Remote Possible settings Standard setting Parameter


Fail-safe test
- - - Global
Description Models
Activation of the Fail-Safe test
An Ejection Confirmation photocell is requested. This test disables the ejector during its execution, in
order to check if in case of ejector malfunctions the system allows to recover correctly a
contaminated pack not rejected.
Press E to execute the Fail Safe Test and pass a pack causing Alarm (e.g. a pack with a Test All models
sample); after CT time, the “Eject not confirm” Fault is activated and the Fail Safe Test finishes.
Verify the possibility to recover the contaminated pack, otherwise adjust the current settings (for
example: CT, PC, SF)
Available only with CE=ON

63
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.17 Print
The list of commands available under the Print menu changes accordingly with the presence of an
IXC card.

3.17.1 With no IXC card installed


Print last events
List of commands available under the Print menu, when no IXC card Print all events
Erase printed ev
is installed.

Remote Possible settings Standard setting Parameter


Print last events
PL - - Global
Description Models
Print last events list
This command allows to physically print (using a serial printer, see DTR) or view (using remote All models
programming software, e.g. Ceia MDScope or Hyperterminal®) all the events occurred since the last
“erasing” operation (by EV command). See also EV and DTR.

The events buffer stores until 10000 (THS 21 series) or 1000 (THS 21E series) events occurred, ordered by date and
time. It is not possible to empty its content. When it is full, the new following events will overwrite the oldest ones.
Set FB=ON (see FB parameter) to avoid any possible overwriting of not yet printed events.

Here below an example of a report:


[000] 11/07/03 - 9:01:27 Metal Detector Off
-024027-
A Event code
[001] 11/07/03 - 9:01:32 Metal Detector On
-185128-

[005] 11/07/03 - 9:02:01 LogIn (LOCAL)

B
Name: JOHN Surname: SMITH Descrip.: ADMINISTR
-138062- Date and Time
[009] 11/07/03 - 9:02:10 Product Modified: PROD01
Sensitivity 280 -> 278
Name: JOHN Surname: SMITH Descrip.: ADMINISTR
-185191-

[006] 11/07/03 - 9:02:11 LogOut (LOCAL) C Event description


Name: JOHN Surname: SMITH Descrip.: ADMINISTR
-212118-
[005] 11/07/03 - 9:02:49 LogIn (LOCAL)
Name: ALAN Surname: BLACK Descrip.: SUPERVISR
-143028- D User data
[012] 11/07/03 - 9:02:53 Alarm
Sensitivity: 278 Amplitude: 23.9 dB
-051038-

E
[015] 11/07/03 - 9:02:59 Test Passed
Prod.: PROD01 Fe diameter: 1.00 Parameter change
Name: ALAN Surname: BLACK Descrip.: SUPERVISR
-177205-

[013] 11/07/03 - 9:03:00 Ejection: PROD01


-076195-

[006] 11/07/03 - 9:03:02 LogOut (LOCAL) F Alarm data


Name: ALAN Surname: BLACK Descrip.: SUPERVISR
-096201-

+169130+
Test performed using a
# G ferrous sample

64
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Erase printed ev
EV - - Global
Description Models
Erasing of printed events
This command confirm the events printed with PL, from the last EV command and consequently
make available the corresponding memory space for next events recordings. All models
It is a good practice to use EV command only in case the events printed by PL command have been
opportunely saved (physically printed or saved in a file).
This command does not physically erase the Events buffer.

Remote Possible settings Standard setting Parameter


Print all events
PB - - Global
Description Models
Print all events
All models
This command prints all the events stored in the buffer.

3.17.2 With IXC card installed


Save last events
List of commands available under the Print submenu, when an IXC Empty last events
Save events
card is installed (IXC=ON).

Remote Possible settings Standard setting Parameter


Save last events
- - - Global
Description Models
Data saving of events occurred since the previous “Empty last events” All models

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal [\\\\\\\\\\\\\\\\\\\]
Detector USB plug, a message will be shown at the Insert USB memory
Insert USB memory
operation start. Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

The Metal Detector events are saved as:

:/Ceia/SNxxxxxxxxxxx/Log/xxxxxxxxxxx_LAST_EVENTS_YYYYMMDD_HHMM.LOG

where xxxxxxxxxxx is the Metal Detector serial number, YYYYMMDD_HHMM is the datestamp.

Remote Possible settings Standard setting Parameter


Empty last events
- - - Global
Description Models
Data empty of events, already saved with the previous “Save last events”
All models

THS/xx21E THS/xx21
===================== [\\\\\\\\\\\\\\\\\\\]
At the end of the operation, the message “Done” is
shown. Done Done

---------------------
{|||||||||||||||||||}

65
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.17.2.1 Save events


Save from-to
List of commands available under the Save events submenu. Save all events

Remote Possible settings Standard setting Parameter


Save from-to
- - - Global
Description Models
Data saving of events occurred in a time period All models

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal Detector [\\\\\\\\\\\\\\\\\\\]
USB plug, a message will be shown at the operation start. Insert USB memory
Insert USB memory
Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

From 14:17 06/04/11 From 14:17 06/04/11


Select the time interval, then select Save and press E to to 17:30 06/04/11
save the data of events occurred in that period. to 17:30 06/04/11 Save~~~~~~~~~~~~~~~~@

Save *

===================== [\\\\\\\\\\\\\\\\\\\]
In presence of several events, a message will ask to wait.
WAIT WAIT
CAN TAKE MINUTES
CAN TAKE MINUTES
{|||||||||||||||||||}
---------------------

The Metal Detector events are saved as:

:/Ceia/SNxxxxxxxxxxx/Log/xxxxxxxxxxx_YYYYMMDD_HHMM-yyyymmdd_hhmm.LOG

where xxxxxxxxxxx is the Metal Detector serial number, YYYYMMDD_HHMM is the datestamp from, yyyymmdd_hhmm is
the datestamp to.
===================== [\\\\\\\\\\\\\\\\\\\]
At the end of the operation, the message “Done” is shown.
Done Done

---------------------
{|||||||||||||||||||}

66
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


Save all events
- - - Global
Description Models
Data saving of all events All models

THS/xx21E THS/xx21
=====================
If an USB key is not already inserted on the Metal Detector [\\\\\\\\\\\\\\\\\\\]
USB plug, a message will be shown at the operation start. Insert USB memory
Insert USB memory
Press P to exit Press P to exit

--------------------- {|||||||||||||||||||}

===================== [\\\\\\\\\\\\\\\\\\\]
In presence of several events, a message will ask to wait.
WAIT WAIT
CAN TAKE MINUTES
CAN TAKE MINUTES
{|||||||||||||||||||}
---------------------

The Metal Detector events are saved as:

:/Ceia/SNxxxxxxxxxxx/Log/xxxxxxxxxxx_YYYYMMDD_HHMM.LOG

where xxxxxxxxxxx is the Metal Detector serial number, YYYYMMDD_HHMM is the datestamp.
===================== [\\\\\\\\\\\\\\\\\\\]
At the end of the operation, the message “Done” is shown.
Done Done

---------------------
{|||||||||||||||||||}

67
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.18 Q-C setup (Quality Control)


1st test delay
List of parameters available under the Q-C setup menu. Test period
Test max delay
Test mode
Sample ampl.check
Quick test
Succ.test mandat

Remote Possible settings Standard setting Parameter


1st test delay
FTD 00:00 – 23:59 00:05 Global
Description Models
Time delay for the first automatic Test Request
The periodical test request enabled (TE > 0) is requested. The first scheduled Test will be requested All models
after FTD delay from each Metal Detector start-up.
See also TE parameter.

Remote Possible settings Standard setting Parameter


Test period
TE 00:00 – 23:59 00:00 Global
Description Models
Time interval between automatic Test Requests
TE parameter allows to enable the Tests Requests scheduling, as explained below:
TE=00:00: the automatic Test Requests are disabled
TE>00:00: the Tests are requested every TE interval (from the First Test, see FTD), through the
display message “Test”, the activation of an external lamp signal (BLUE LAMP Output) All models
and eventually the TEST Relay activation (according to TRM parameter). At the Test
Request, enter in the programming and perform the test according to set criteria (see TD
and TMD parameters).
In every moment, through the Status Screen, it is possible to see when the next Test request is
scheduled.

Remote Possible settings Standard setting Parameter


Test max delay
TD 00:00 – 23:59 00:00 Global
Description Models
Maximum allowed time for the Test execution start
Maximum time delay (since the Test Request) within the Test should be started. If this time expires, All models
the Fault “Test timeout” is activated. See also FT parameter.
It is not possible to set TD>TE.

Remote Possible settings Standard setting Parameter


SINGLE, TRIPLE,
Test mode
TMD FE/SS, NFE/SS, SINGLE Global
FE/NFE
Description Models
Test execution method
This parameter sets the Metal Detector Test execution mode, as explained below:
SINGLE: it is requested to perform one of the three Tests (FE, NFE or SS Test) All models
TRIPLE: it is requested to perform all the 3 Tests (Fe, NFe and SS Test), consecutively.
FE/SS, NFE/SS, FE/NFE: it is requested to perform the 2 indicated Tests, consecutively.
The Metal Detector Test is considered Passed if all the requested Tests are passed. The Metal Detector
Test is considered Failed at the first Test Failed occurred.

68
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Remote Possible settings Standard setting Parameter
OFF, X2, X3, X4,
Sample ampl. check
SAC X6, X8, X12, X16, X4 Global
X24, X32
Description Models
Sample Amplitude Check
If SAC = “Xv” value, during each test the Metal Detector checks that the Test sample signal level will
not be “v” times higher than the alarm threshold set by the SE value. Otherwise, the corresponding All models
Test Failed Fault is activated, the message “TEST FAILED, SAMPLE TOO BIG” is shown and the
Test is recorded as NO (not passed). The value of X4 Is equivalent to a 12 dB signal.
Set SAC=OFF to disable this control.

Remote Possible settings Standard setting Parameter


Quick test
QCKT OFF / FE / NFE / SS - Global
Description Models
Quick test
If QCKT is set to a value different from OFF, in case of IN_AUX1 Input activation the corresponding
Test request is immediately activated, without the need to enter in Programming. Pass the Test
sample within 1 minute. In case ARM=0, the activation of IN_AUX1 input will activate also AUX relay All models
for 3 seconds (see also parameter ARM).
Set QCKT=OFF to disable the Quick Test functionality.
See also the Electrical Diagram in Installation Manual.

Remote Possible settings Standard setting Parameter


Succ.test mandat
STM ON / OFF OFF Global
Description Models
Successful test mandatory
STM = OFF: in case of a failed test, it is possible to reset the system All models
STM = ON: in case of a failed test, it is mandatory to reset the system, to repeat the test and to
pass it.

69
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.19 Test samples


FE diameter
List of parameters available under the Test samples menu. NFE diameter
SS diameter

Remote Possible settings Standard setting Parameter


FE diameter Related to the
FD 0.0 – 25.0 mm -
current product
Description Models
Diameter of Ferrous sample sphere used to perform the test
Setting FD > 0, this diameter value will be associated with the corresponding Test and consequently All models
shown at the moment of the corresponding Test execution.
This value is only recorded in the events buffer (for Quality Control Report using) but it does not affect the
Detection sensitivity. If set to 0, no value will be recorded with the relative test.

Remote Possible settings Standard setting Parameter


NFE diameter Related to the
ND 0.0 – 25.0 mm -
current product
Description Models
Diameter of Non-Magnetic metal sample sphere used to perform the test
Setting ND > 0, this diameter value will be associated with the corresponding Test and consequently All models
shown at the moment of the corresponding Test execution.
This value is only recorded in the events buffer (for Quality Control Report using) but it does not affect the
Detection sensitivity. If set to 0, no value will be recorded with the relative test.

Remote Possible settings Standard setting Parameter


SS diameter Related to the
SD 0.0 – 25.0 mm -
current product
Description Models
Diameter of Stainless Steel sample sphere used to perform the test
Setting SD > 0, this diameter value will be associated with the corresponding Test and consequently All models
shown at the moment of the corresponding Test execution.
This value is only recorded in the events buffer (for Quality Control Report using) but it does not affect the
Detection sensitivity. If set to 0, no value will be recorded with the relative test.

3.20 Unlock bin


Remote Possible settings Standard setting Parameter
Unlock bin
- - - Global
Description Models
Opening of the electric lock of the bin
Activating this command, the electric lock of the bin is unlocked for a time specified by parameter All models
UBT.
This command is available only if BWL=ON.

70
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

3.21 Commands accessible only in Remote Programming


Remote Possible settings Standard setting Parameter
-
PE - - Global
Description Models
Exit from remote programming
Type this command to exit from the Remote Programming. All models
If RPTO=ON, the Metal Detector exit automatically from the Remote Programming in case of 5
minutes of programming inactivity.

Remote Possible settings Standard setting Parameter


-
PV - - Global
Description Models
Software version
Provides the software version loaded on the #PV <ENTER> All models
Metal Detector. THS/21 V5.330 - ALM V5.260

Remote Possible settings Standard setting Parameter


-
HE - - Global
Description Models
Help
All models
Provides the list of all available parameters, their meanings and their current settings

Remote Possible settings Standard setting Parameter


-
DA DD/MM/YY - Global
Description Models
Current date insertion
DD = Day, MM = Month #DA 04/03/11 <ENTER> All models
YY = last two figures of the year #

Remote Possible settings Standard setting Parameter


-
AR - - Global
Description Models
Reset total alarm counter
All models
AR command resets the total alarms counter (AC).

Remote Possible settings Standard setting Parameter


- Related to the
CR - -
current product
Description Models
Reset of the current product counters
CR command resets both Alarms and Objects counter related to the current product (CA and CO All models
respectively).

Remote Possible settings Standard setting Parameter


-
OR - - Global
Description Models
Reset total pack transit counter
All models
OR command resets the total objects counter (OC).

71
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


- Related to
PS - - current product
Description Models
List of all current product parameters and their value
All models
List of parameters related to the current Product, together with their actual value.

Remote Possible settings Standard setting Parameter


- Related to
PT - - current product
Description Models
List of the current parameters settings
All models
List of all parameters, both global and related to the current product, with their current settings.
Other data about the Metal Detector Status and current configuration are included too.

Remote Possible settings Standard setting Parameter


-
EPT - - Global
Description Models
Complete list of parameters settings
All models
List of all parameters, both global and related to each product, with their current settings.
Other data about the Metal Detector Status, current configuration and users list are included too.

Remote Possible settings Standard setting Parameter


-
SN - - Global
Description Models
Serial number of the Metal Detector All models

Remote Possible settings Standard setting Parameter


-
RPTO ON / OFF ON Global
Description Models
Remote programming timeout
RPTO = ON: The remote programming session will be terminated automatically if no commands All models
are entered for a period of 5 minutes.
RPTO = OFF: The remote programming session will be terminated only through PE command.

Remote Possible settings Standard setting Parameter


-
RO - - Global
Description Models
Read out of the signal level
When the system connected to the detector sends the command “RO(CR)” the metal detector All models
(MD) will answer with “RO xxx(CR)(CR)#” where “xxx” are ASCII characters from 0 to 100. The
threshold for metal alarm is at 20. The resolution is 1.
(SP) stands for Space and (CR) stands for Carriage Return.

72
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Remote Possible settings Standard setting Parameter
-
DL - - Global
Description Models
Display and Alarm Led status
The MD replies to this command with “DL(SP)” followed by a 81-character string, (CR), (CR) and ‘#’. All models
The firsts 80 characters of the string are the image of the THS display. The last character is the
Alarm Led Status (‘0’ = Off, ‘1’ = On).
The command is available only if DMD=ALPHA.
(SP) stands for Space and (CR) stands for Carriage Return.

Remote Possible settings Standard setting Parameter


-
DLU - - Global
Description Models
Display and Alarm Led status (as UNICODE)
The MD replies to this command with “DLU(SP)” followed by a 161-character string, (CR), (CR) and All models
‘#’. The firsts 160 characters of the string are the image of the THS display in UNICODE. The last
character is the Alarm Led Status (‘0’ = Off, ‘1’ = On).
The command is available only if DMD=ALPHA.
(SP) stands for Space and (CR) stands for Carriage Return.

Remote Possible settings Standard setting Parameter


-
KS - - Global
Description Models
UP, DOWN, PROG and ENTER keys status
This command is used to set the , , and keys status of the MD. The command
sequence is:
KS(SP)abcd(CR) All models

where “abcd” is the key sequence UP (a), DOWN (b), PROG (c), ENTER (d) and it can be
represented by the ASCII character ‘0’ (key pressed) or ‘1’ (key not pressed). For example, when the
key PROG is pressed, abcd = 0010.
Digit KS(SP)0000(CR) to release all the keys.

Remote Possible settings Standard setting Parameter


-
FQ - - Global
Description Models
Ferrous Quality Test
When the system connected to the THS sends the command “FQ 1(CR)” the Metal Detector starts
the Ferrous Quality Test procedure. Checking FQ (which returns an ASCII character from 0 to 5)
allows the checkweigher to know the status of the test. This is a list of the statuses of the test:

0 Test not running 3 Test passed All models


1 Test initialisation / signal measurement 4 Test not passed
2 Wait for a product with a ferrous sample 5 Sample too big

The ‘Stainless-steel’ and ‘Non-ferrous’ tests works as the ‘Ferrous’ test.


The samples that have to be used to perform the production test are indicated by the value of the
parameters ‘FD’, ‘SD’ and ‘ND’ of the product under test.

73
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Remote Possible settings Standard setting Parameter


-
SC - - Global
Description
Self-Check
This command returns a list of all the Metal Detector status flag which are active.
The Metal Detector will reply to this command with “SC xx,xx,…..,xx(CR)(CR)#” where “xx” are ASCII strings with the
following meanings:

00 WORKING PROPERLY - 20 LOGIN RESTRICTED F 40 RESET EMERGENCY F


01 NO COMMUNICATION F 21 EVENT BUFFER FULL F 41 EJEC.CHECK FAULT F
02 EMERGENCY F 22 EJECT.SYSTEM JAM F 42 SYNC.PHOTOC.FAULT F
03 NO EJECT.CONFIRM F 23 EJECT. DISCONNEC. F 43 CHECK PHOTC.FAULT F
04 BIN FULL F 24 Reserved - 44 ENCOD.FRQ.TOO LOW F
05 LOW AIR PRESSURE F 25 Reserved - 45 ENCD.FRQ TOO HIGH F
06 POW. SUPPLY FAULT F 26 Reserved - 46 INVERTER NOT RESP F
07 MOTOR ALARM F 27 Reserved - 47 MOTOR FAULT (AUX) F
08 PROBE FAULT (0) F 28 Reserved - 48 EJECT.OUT OF ORDER F
09 PROBE FAULT (1) F 29 TEST FAILED F 49 ALR RATE TOO HIGH F
FAIL-SAFE TEST
10 PROBE FAULT (2) F 30 F 50 UPDATING CONFIG F
FAILED
PASS PRODUCT
11 R 31 Reserved - 51 LOGIN RESTRIC(1) F
during Autolearn
12 TEST R 32 BIN ABSENT F 52 LOGIN RESTRIC(2) F
13 TEST TIME OUT F 33 PROBE FAULT (4) F 53 Vin FAULT F
14 Autolearn in progress S 34 PROBE FAULT (5) F 54 Vout FAULT F
15 Reserved - 35 PROBE FAULT (3/1) F 55 PROBE FAULT (0/1) F
16 Reserved - 36 PROBE FAULT (3/2) F 56 PROBE FAULT (0/2) F
SELF BALANCING(x) IN
17 SPM NOT DETECTED F 37 S 57 SCD CARD FAULT (x) F
PROGRESS
18 COMPATIBIL.ERROR F 38 EXTERN.EMERGENCY F 58 WARN: IXC timeout W
POWER SUPPLY
19 F 39 EMERG.CIRC.FAULT F 59 !! Detect.inhibited!! S
TOO HIGH
F: Fault – R: Request – S: Status – W: Warning

Some fault messages are not applicable to all models

Remote Possible settings Standard setting Parameter


-
SQ - - Global
Description Models
Stainless Steel Quality Test
All models
See FQ command.

Remote Possible settings Standard setting Parameter


-
NQ - - Global
Description Models
Non-Ferrous Quality Test
All models
See FQ command.

74
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

Remote Possible settings Standard setting Parameter


-
EX - - Global
Description Models
Exit from programming
When you send this command to the THS Metal Detector, the screen will jump directly to TOP
screen from anywhere in the programming tree. There is only an exception to take into All models
consideration: it is not possible to leave programming phase when a MD test is in progress, so if you
issue an EX command during a MD test you receive the message "Unable to exit".

75
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.22 Remote programming


Programming can be carried out through a remote computer fitted with an RS232 interface, a
Bluetooth connection, or an Ethernet/WiFi connection, depending on their availability on the
Metal Detector, using a standard communications program (e.g. Windows HyperTerminal) or the
CEIA MDScope program, available on request.

3.22.1 Communication parameter settings


3.22.1.1 RS232 or RS232 Aux
Select the COM port used (with USB/RS232 adapter, check the COM port assigned).
Set the port as follows:

- Baud rate as set in parameters - 1 stop bit


BR (for RS232) or - no communication protocol
AUBR (for RS232Aux). - CR -> CR+LF
Default value: 57600 bit/s
- Local echo = OFF
(9600 is also selectable).
- Terminal: VT 100 (ANSI)
- 8 data bits
- NO parity

3.22.1.2 Bluetooth
- Open the Bluetooth software present in your computer.
- Create a new connection. The software will scan the area for available Bluetooth devices.
In the list will appear a device named with the THS model and Serial Number.
For example: CDSN 99999999 THS/XX
- Selecting this unit, a PIN code will be requested. The device PIN is stored on the parameter
BPIN, under Administrator menu (the default value is 00000000).
- The Bluetooth connection software will connect now to the unit, showing a message that will
indicate which virtual COM port has been created for the device. For example: COM42.
- Set the assigned COM port and Baud Rate (57600bps) in the communication parameter
settings.

3.22.1.3 Ethernet / WiFi connections (with IXC card)


- Set all connection parameters as indicated in paragraph 3.23.1.
- Set TCP port to a value of 2101.

76
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.22.2 Entering remote programming
3.22.2.1 Connecting to a Metal Detector
Via RS232 or Bluetooth
- Run the serial communication program (MD Scope) or another serial communication
software
- Perform the access by typing the password
(or login and password) as stated by
parameter RM (for RS232 and Bluetooth) or (password) <ENTER>
AURM (for RS232Aux) and confirming with #
ENTER
Default password: 000006

When typing the password, nothing is displayed on the screen.


The # prompt will be shown only after a correct password authentication

Via Ethernet or WiFi (with IXC board)


Perform the access by typing login and password, and confirming with ENTER.
During the typing, an asterisk (*) will be shown in place of each character.
Default administrator login: user: ADMINI; password: 000000.

3.22.2.2 Displaying a parameter setting


Type the code of the parameter and press ENTER: #SE<ENTER>
the parameter setting will appear next to it. #SE 30

For further details on the MD Scope program, please refer to the manual supplied with the
software.

3.22.2.3 Changing a parameter setting


Type the code of the parameter followed by a #SE 35<ENTER>
space, the new value and ENTER. #

3.22.2.4 Executing a function


Key in the parameter code and press ENTER. #PL<ENTER>
#

77
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.23 Access via Web Server


This paragraph applies only if a IXC card is fitted.

3.23.1 Network configuration


To configure the THS system on a network, use the following procedure:
- Enter the programming phase as Administrator;
- Enter the Configuration-adv menu and the Network config. submenu;
- Correctly set all parameters to connect the THS system with your network;
- Set Web server to ON.

3.23.2 Functions available


When the THS system is connected through Ethernet to the network, it is possible to perform some
operations by means of a simple browser.
The operator needs only to know the IP address (or the Network Hostname) of the device.

- Open your browser and enter the THS IP in the URL field (to know the default IP address,
see IPA parameter). Be sure that no Proxy is active.

- The THS will ask for a login name and


a password. Access with your account.

The operation is not case sensitive.

- The screen will be divided in two areas, the menu column on the left and the content area on
the right.

78
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.23.2.1 Status
This page replicates every message the THS shows on the display. The page is updated each 5 s.

3.23.2.2 Products
This page shows the list of product saved into the THS memory, showing the selected product in
green. To select a new one, press on the corresponding Select button.

79
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.23.2.3 Products Counters


This page shows, in real time, the alarm counters status.

3.23.2.4 Test Diameters


This page shows the diameter values of all the test samples.

80
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.23.2.5 Products Export
From this page it is possible to select all or some of the products stored in the THS memory, to
export them.
Each selected product will be saved in a ProductName.TPR file and all of them will be saved into
a Exported_Products.zip file.

3.23.2.6 Products Import


From this page will be possible to import back all or some of the
products exported, selecting a .tpr or a .zip file and selecting from
the list.

It is possible to import products created on other Metal


Detectors (of the same model), but with different probe
dimensions.
In this case, for this products, can be necessary to
perform a new Autolearn procedure.

It is not possible to import products created on


different Metal Detector models.

The product DEFAULT and the current product cannot


be overwritten.

81
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.23.2.7 Products Delete


If needed, from this page it is possible to delete products.

3.23.2.8 Buffers Export


Inside this page it is possible to export events data that occurred in from the Starting Date / Time to
the Ending Date / Time requested. Once the two dates are set and the Send button has been
pressed, a link to download the file appears.
The log file is saved as serialnumber_Startingdate-Endingdate.zip that contains the file
serialnumber_Startingdate-Endingdate.LOG requested.

82
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.23.2.9 Configuration Backup/Restore
From this page it is possible to backup or to restore the configuration for the connected system.

Configuration Backup
To perform a configuration backup, simply press on Click here to Backup current configuration.
The file will be saved as SerialNumber.TCB.

Configuration Restore
To perform a configuration restore, choose a TCB file
from your computer and upload it to the THS system.

A confirmation is needed.

The TCB configuration files are restorable ONLY on the same machine from where they were saved.

83
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.23.2.10 Configuration Export/Import


From this page it is possible to export the configuration to or to import it from other Metal Detectors
of the same model, installed on identical systems.

It is possible to import configuration from Metal Detectors of the same model, installed on identical systems, but with
different probe dimensions. The correct functioning of the systems is however to be verified.

It is not possible to import configurations of different Metal Detector models.

Configuration Export
To perform a configuration export, simply press on Click here to Export current configuration.
The file will be saved as SerialNumber.TCE.

The exported configuration does not include all parameters relative exclusively to each system (for example IP address,
motor configuration parameters, barcode reader activation code etc..).

Configuration Import
To perform a configuration import, choose a TCE file from
your computer and upload it to the THS system.

A confirmation is needed.

84
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.23.2.11 Network
This function allows to set all network data of the THS system.
When using DHCP protocol, the IP address will be assigned automatically by the network system.
Otherwise, using a static addressing, the network data must be entered manually.
The changes take place by pressing the Save button.

Network data as IP, Subnet Mask, Gateway, are related both for the Ethernet and the WiFi connections.

In case the network connection needs the insertion of a


password, this will be requested in a proper pop-up
window.

85
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

3.23.2.12 System upgrade (Web Server)


This function allows upgrading the Web Server installed on the IXC board, using a .rar file provided
by CEIA service department.

3.23.2.13 Maintenance
This function allows performing some maintenance operations.

System Info
This function allows saving a file containing the IXC board Information.
This file must be sent to CEIA service department.

System Reboot
This function allows performing a Reboot of the IXC System.

86
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
3.23.2.14 System Info
This function displays some relevant information about the Web
Server.

3.23.2.15 Logout
This function allows logging out the session.
Simply click on the menu “Logout”: the dialog
box for the login of a new user appears.

87
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
3 PROGRAMMING PARAMETERS

Page left intentionally blank

88
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3

4 APPENDIX
4.1 Parameters list – Alphabetical order
AC .............................................. 32 EPC ........................................... 60 NMP ........................................... 50
ACCT ......................................... 51 EPCD ......................................... 60 NMS ........................................... 51
ADMS ......................................... 24 EPT ............................................ 72 NMV ........................................... 50
ADS ............................................ 42 ERF ........................................... 43 NQ .............................................. 74
AM .............................................. 47 ERL ............................................ 48 NW ............................................. 19
AP .............................................. 59 ERT ........................................... 43 OC .............................................. 32
APDL .......................................... 59 ES .............................................. 31 OR .............................................. 71
AR .............................................. 71 ESO ........................................... 34 PA............................................... 57
ARM ........................................... 49 ET .............................................. 30 PAT ............................................ 57
ARP ............................................ 61 EV .............................................. 65 PB............................................... 65
ART ............................................ 62 EX .............................................. 75 PC .............................................. 48
ASE ............................................ 25 FB .............................................. 61 PD .............................................. 42
AT .............................................. 35 FC .............................................. 48 PDIS ........................................... 60
ATD ............................................ 45 FD .............................................. 70 PE............................................... 71
ATTM ......................................... 45 FF .............................................. 61 PFR ............................................ 62
ATTP .......................................... 44 FLR ............................................ 61 PH .............................................. 42
AUBR ......................................... 52 FO .............................................. 41 PI .......................................... 17; 18
AURM ........................................ 16 FQ .............................................. 73 PL ............................................... 64
BA .............................................. 27 FT .............................................. 61 PLEN .......................................... 30
BARC ......................................... 19 FTD ............................................ 68 PN .............................................. 18
BD .............................................. 54 GW ............................................ 40 PS............................................... 72
BE .............................................. 41 HE .............................................. 71 PT ............................................... 72
BL ............................................... 41 HN ............................................. 40 PV............................................... 71
BLEN .......................................... 34 HPR ........................................... 40 QCKT ......................................... 69
BM .............................................. 42 IA ............................................... 46 QR .............................................. 47
BPIN ........................................... 16 IAP ............................................. 47 RD .............................................. 47
BR .............................................. 52 IBF ............................................. 52 RE .............................................. 49
BS .............................................. 42 IE ............................................... 46 RM .............................................. 16
BT .............................................. 52 IFLY ........................................... 51 RO .............................................. 72
BTS ............................................ 53 IL ................................................ 46 RPTO ......................................... 72
BWL ........................................... 58 IN ............................................... 41 RS .............................................. 17
CA .............................................. 32 IP ............................................... 46 SA............................................... 25
CBT ............................................ 53 IPA ............................................. 40 SAC ............................................ 69
CE .............................................. 59 IPF ............................................. 52 SC .............................................. 74
CH .............................................. 34 IRST .......................................... 52 SD .............................................. 70
CO .............................................. 32 IW .............................................. 46 SE............................................... 26
CPMA ......................................... 57 IXC ............................................. 37 SF ............................................... 36
CR .............................................. 71 KAR ........................................... 35 SN .............................................. 72
CT .............................................. 59 KE .............................................. 43 SO .............................................. 34
DA ........................................ 35; 71 KFR ........................................... 35 SPMA ......................................... 57
DC .............................................. 45 KS .............................................. 73 SQ .............................................. 74
DDD ........................................... 45 KT .............................................. 43 ST ............................................... 49
DECT ......................................... 51 LA .............................................. 58 STM ............................................ 69
DI ............................................... 43 LAD ............................................ 58 TA ............................................... 44
DL .............................................. 73 LC .............................................. 54 TA1 ............................................. 44
DLU ............................................ 73 LE .............................................. 24 TA2 ............................................. 44
DM ............................................. 26 LF .............................................. 58 TD............................................... 68
DMD ........................................... 45 LFD ............................................ 58 TE ............................................... 68
DNS ........................................... 40 LG .............................................. 34 TL ............................................... 44
DT .............................................. 52 LO .............................................. 45 TM .............................................. 35
EA .............................................. 60 MAC ........................................... 40 TMD............................................ 68
ECK ............................................ 59 MASE......................................... 25 TN............................................... 24
ECKA ......................................... 60 MB ............................................. 24 TP ............................................... 27
ECPD ......................................... 43 MI ............................................... 51 TRM............................................ 49
ED .............................................. 30 MM ............................................. 36 TX ............................................... 34
EDA ............................................ 26 MOPT ........................................ 25 UBT ............................................ 58
EE .............................................. 31 ND ............................................. 70 UD .............................................. 36
EF .............................................. 62 NE .............................................. 55 VI ................................................ 26
EIS ............................................. 48 NM ............................................. 40 WE.............................................. 53
EJ ............................................... 36 NMC .......................................... 50 WEBS ......................................... 41
EM .............................................. 28 NMCP ........................................ 50 WS.............................................. 53
EMEX ......................................... 62 NME ........................................... 50 WT .............................................. 33
EP .............................................. 19 NMF ........................................... 51

89
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
4 APPENDIX

4.2 Parameters list – Menu order


Administrator .................................. .................. 15 Ejection ............................................ .................. 28
Create user..................................... .................... 15 Ejection mode ........................... EM ............... 28/29
Modify user ..................................... .................... 15 Ej. distance ................................ED .................... 30
Erase user ...................................... .................... 16 Ejection time .............................. ET .................... 30
Set Bluetooth PIN ................... BPIN .................... 16 Pack length ........................... PLEN .................... 30
Remote passwords ......................... .................... 16 Ej.st.sync.area ........................... ES .................... 31
RS232password................RM .................... 16 Ej.en.sync.area .......................... EE .................... 31
auxRS232passw ..........AURM .................... 16
Counters .......................................... .................. 32
Reset ........................................... RS .................. 17 Prd alarms .................................CA .................... 32
Prd packs .................................. CO .................... 32
Product selection ............................ .................. 17 Tot.alarms ..................................AC .................... 32
Product ........................................ PI .................... 17 Tot. packs ................................. OC .................... 32
Work time .................................. WT .................... 33
Products .......................................... .................. 18
Product ........................................ PI .................... 18 Configuration .................................. .................. 33
Rename product ........................ PN .................... 18 Compatibility chk ............................. .................... 33
New product ............................. NW .................... 19 Gener.comp.check ................. .................... 33
Erase product ............................ EP .................... 19 Elec.comp.check .................... .................... 33
Prod. barcode ....................... BARC .................... 19 Belt contam.check .................. .................... 33
Save prod.to USB........................... .................... 20 Belt length .................... BLEN .................... 34
Select product(s) .................... .................... 20 Buzzer ....................................... SO .................... 34
Save all products ................... .................... 21 Ext. buzzer .............................. ESO .................... 34
Load prd from USB ......................... .................... 22 Language ................................... LG .................... 34
Select product(s) .................... .................... 22 Transmission ............................. TX .................... 34
Load all .................................. .................... 23 TX Channel ............................... CH .................... 34
Keyb alarm reset ..................... KAR .................... 35
Autolearn ......................................... .................. 24 Keyb fault reset ....................... KFR .................... 35
Time .......................................... TM .................... 35
Autolearn .................................... LE .................... 24
Date ...........................................DA .................... 35
Aut.det.,mode sel ................. ADMS .................... 24
Alarm time .................................. AT .................... 35
Multi-band.................................. MB .................... 24
Ejection ...................................... EJ .................... 36
Min.trans.numb.......................... TN .................... 24
UP/DOWN enable ..................... UD .................... 36
Manual motion ..........................MM .................... 36
Autolearn-advanc ........................... .................. 25 Stop on fault ............................... SF .................... 36
Metal optimiz. ....................... MOPT .................... 25
Autolearn sens. ....................... ASE .................... 25
Sens. margin ............................. SA .................... 25
>>
Max learn sens ..................... MASE .................... 25
Vibr.immunity............................... VI .................... 26
Ej.during autlr .......................... EDA .................... 26

Detection.......................................... .................. 26
Sensitivity .................................. SE .................... 26
Detection mode .........................DM .................... 26
TX program ................................TP .................... 27
Band .......................................... BA .................... 27

90
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
PROGRAMMING PARAMETERS 3
Configuration-adv ........................... .................. 37 Motor config ................................... .................... 49
IXC presence ............................ IXC .................... 37 Nom.MotorVolt. .............. NMV .................... 49
Backup conf.to USB........................ .................... 38 Nom.MotorCurr. ............. NMC .................... 50
Restor.cfg.from USB ....................... .................... 38 Nom.MotorPower ........... NMP .................... 50
Export conf.to USB ......................... .................... 39 Nom.MotorCosPhi ....... NMCP .................... 50
Import cfg.from USB ....................... .................... 39 Nom.MotorEffic .............. NME .................... 50
Network config. ............................... .................... 40 Nom.MotorFreq .............. NMF .................... 50
HN .....................................HN .................... 40 Nom.Motor.Speed .......... NMS .................... 50
Host protocol .................. HPR .................... 40 Max inv. freq. ..................... MI .................... 51
IP ...................................... IPA .................... 40 Acceler. Time ............... ACCT .................... 51
NM.................................... NM .................... 40 Deceler. Time .............. DECT .................... 51
GW ...................................GW .................... 40 Flying start ...................... IFLY .................... 51
DNS................................ DNS .................... 40 Inv.PulseFreq. ................... IPF .................... 51
MAC ............................... MAC .................... 40 Inv.BaseFreq. ................... IBF .................... 51
Web server .................. WEBS .................... 41 ResetInv.ToDefault ........ IRST .................... 52
Product tracking ......................... FO .................... 41 RS232 BaudRate ...................... BR .................... 52
Inhib. Time .................................. IN .................... 41 auxRS232B.rate ................... AUBR .................... 52
Barcode enable.......................... BE .................... 41 DTR protocol ............................. DT .................... 52
Minimum speed ......................... BL .................... 41 Bounce time ...............................BT .................... 52
Speed ........................................ BS .................... 42 Bounce t. slow ......................... BTS .................... 52
Maximum speed ....................... BM .................... 42 Centre belt time ....................... CBT .................... 53
Phcell position............................ PH .................... 42
Phcell-MD dist............................ PD .................... 42 Barcode reader ............................... .................. 53
Check phot.dist ..................... ECPD .................... 42 Window start ............................ WS .................... 53
EjON resp.time ........................ERT .................... 43 Window end ............................. WE .................... 53
EjOFFresp.time........................ERF .................... 43 Learn code .................................LC .................... 53
K transmis. ................................. KT .................... 43 Barc-MD dist. ............................ BD .................... 54
K encoder .................................. KE .................... 43 No code eject ............................ NE .................... 54
Diameter ..................................... DI .................... 43
TA .............................................. TA .................... 44 I/O Status ......................................... .................. 55
TA1 .......................................... TA1 .................... 44 Outputs........................................... .................... 55
TA2 .......................................... TA2 .................... 44 Inputs ............................................. .................... 55
TA autolearn ...............................TL .................... 44 Measures ....................................... .................... 55
Autotest phase ....................... ATTP .................... 44 Variables ........................................ .................... 56
Autotest module .................... ATTM .................... 45
Autotest diagnos ......................ATD .................... 45
>>
Display mode ..........................DMD .................... 45
Display contrast .........................DC .................... 45
Dimming delay ........................ DDD .................... 45
Input logic .................................. LO .................... 45
BIN FULL input ............................ IL .................... 46
BIN ABSENT input...................... IA .................... 46
EJECT.CONF.input .................... IE .................... 46
PHOTOCELL input ..................... IP .................... 46
FOLLW.CONV.input .................. IW .................... 46
LOW PRESSURE inp ............... IAP .................... 46
Analysys mode ......................... AM .................... 47
Ejec.queue reset ....................... QR .................... 47
Reverse detect...........................RD .................... 47
Eject.act.if stop ......................... EIS .................... 47
EJECT RELAY logic ................ ERL .................... 48
PREC CONV enable.................. PC .................... 48
FOLLW.CONV.enab .................. FC .................... 48
Autom. Restart ........................... RE .................... 48
Mode test relay ....................... TRM .................... 49
Aux relay mode ....................... ARM .................... 49
Stop time ................................... ST .................... 49

91
FI002K0021v1100UK – THS/21E and THS/21 Programming Manual
4 APPENDIX

Diagnosis managem. ...................... .................. 56 MD Test ............................................ .................. 63


Photocell fault ............................ PA .................... 56 FE test ............................................ .................... 63
Sync.max.activ ..................... SPMA .................... 56 NFE test .......................................... .................... 63
Chck.max.activ ..................... CPMA .................... 56 SS test ............................................ .................... 63
Phot.fau.thres .......................... PAT .................... 57
Bin full ........................................ LF .................... 57 Fail-safe test .................................... .................. 63
Bin full delay ............................ LFD .................... 57 Fail-safe test ................................... .................... 63
Bin absent .................................. LA .................... 57
Bin absent delay ...................... LAD .................... 57 Print.................................................. .................. 64
Bin with lock ........................... BWL .................... 58
Print events ................................ PL .................... 64
Unlock bin time ........................ UBT .................... 58
Erase printed ev. ........................ EV .................... 65
Air pressure low......................... AP .................... 58
Print all events ........................... PB .................... 65
Low press. delay ................... APDL .................... 58
Save last events.............................. .................... 65
Eject confirmat........................... CE .................... 58
Empty last events............................ .................... 65
Confirm time .............................. CT .................... 59
Save events .................................... .................... 66
Eject.check .............................. ECK .................... 59
Save from-to ........................... .................... 66
Ej.check accur. ..................... ECKA .................... 59
Save all products .................... .................... 67
Pho.diag.if stop....................... PDIS .................... 59
Ejector pos. chk ....................... EPC .................... 59
Ej.pos.chk delay ................... EPCD .................... 60
Q-C setup......................................... .................. 68
Encoder check........................... EA .................... 60 1st test delay ............................FTD .................... 68
Test period ................................. TE .................... 68
Test time out............................... FT .................... 60
Test failed ................................... FF .................... 60 Test max delay........................... TD .................... 68
Event buf. full..............................FB .................... 61 Test mode ............................... TMD .................... 68
Login restrict. ........................... FLR .................... 61 Sample ampl. Check ............... SAC .................... 69
Al.rate period ........................... ARP .................... 61 Quick test .............................. QCKT .................... 69
Al.rate threshold ...................... ART .................... 61 Succ.test mandat .................... STM .................... 69
Ej. max extent....................... EMEX .................... 61
Ejec.on fault................................EF .................... 62 Test samples ................................... .................. 70
Probe fault reset ...................... PFR .................... 62 FE diameter ............................... FD .................... 70
NFE diameter ............................ ND .................... 70
SS diameter ...............................SD .................... 70

Unlock bin ....................................... .................. 70