Professional Documents
Culture Documents
RP 174 PDF
RP 174 PDF
OISD-RP-174
Second Edition
July 2008
For Restricted Circulation
WELL CONTROL
OISD – RP – 174
Prepared by
II
NOTE
OISD (Oil Industry Safety Directorate) publications are prepared for use in the Oil
and Gas Industry under Ministry of Petroleum & Natural Gas. These are the property of
Ministry of Petroleum & Natural Gas and shall not be reproduced or copied and loaned or
exhibited to others without written consent from OISD.
Though every effort has been made to assure the accuracy and reliability of the data
contained in the document, OISD hereby expressly disclaims any liability or responsibility
for loss or damage resulting from their use.
The document is intended to supplement rather than replace the prevailing statutory
requirements.
III
FOREWORD
The Oil Industry in India is 100 years old. Because of various collaboration
agreements, a variety of international codes, standards and practices have been in
vogue. Standardisation in design philosophies and operating and maintenance
practices at a national level was hardly in existence. This coupled with feed back
from some serious accidents that occurred in the recent past in India and abroad,
emphasised the need for the industry to review the existing state of art in designing,
operating and maintaining oil and gas installations.
With this in view, the Ministry of Petroleum and Natural Gas in 1986 constituted a
Safety Council assisted by the Oil Industry Safety Directorate (OISD) staffed from
within the industry in formulating and implementing a series of self regulatory
measures aimed at removing obsolescence, standardising and upgrading the
existing standards to ensure safe operations. Accordingly, OISD constituted a
number of functional committees of experts nominated from the industry to draw up
standards and guidelines on various subjects.
The recommended practices for "Well Control" have been prepared by the
Functional Committee for revision of “Well Control". This document is based on the
accumulated knowledge and experience of industry members and the various
national / international codes and practices.
Suggestions are invited from the users after it is put into practice to improve the
document further. Suggestions for amendments to this document should be
addressed
The Coordinator
Functional Committee on
“Well Control”,
Oil Industry Safety Directorate,
7thFloor, New Delhi House,
27, Barakhamba Road,
New Delhi -110 001.
Email: oisd@vsnl.com
IV
COMMITTEE FOR PREPARING STANDARD ON
"WELL CONTROL"
1998
-----------------------------------------------------------------------------------------------------------------------------
Name Designation & Position in
Organisation Committee
----------------------------------------------------------------------------------------------------------------------------
----------------------------------------------------------------------------------------------------------------------------
V
Functional Committee for Complete Review of OISD-STD-174,
2008
LEADER
MEMBERS
Shri V.P. Mahawar Oil and Natural Gas Corporation Ltd., Ahmedabad.
Shri R.K. Rajkhowa Oil India Ltd., Duliajan, Assam.
Shri S.K. Ahuja Oil and Natural Gas Corporation Ltd., Mumbai.
Shri B.S. Saini Oil and Natural Gas Corporation Ltd., Sibsagar, Assam.
Shri A.J. Phukan Oil India Ltd., Duliajan, Assam.
MEMBER COORDINATOR
VI
Contents
1
Pulling pipe out of hole 3.14 Kill Rate
BHP = Hydrostatic pressure - swab Reduced circulating rate (kill rate) is
pressure. required when circulating kicks so that
additional pressure to prevent
3.7 Choke manifold formation flow can be added without
The assembly of valves, chokes, exceeding pump liner rating. Kill rate
gauges, and piping to control flow is normally half of the normal
from the annulus and regulate circulating rate. For subsea stacks in
pressures in the drill string / annulus deep water, kill rates less than half of
flow, when the BOPs are closed. the normal circulating rate may be
required to avoid excessive back
3.8 Degasser pressure in the choke flow line.
A vessel, which utilizes pressure
reduction and/or inertia to separate 3.15 Kill Rate Pressure
entrained gases from the liquid The circulating pressure measured at
phases. the drill pipe gauge when the mud
pumps are operating at the kill rate.
3.9 Diverter
A device attached to the wellhead or 3.16 Marine riser system
marine riser to close the vertical The extension of the wellbore from the
access and direct flow into a line away subsea BOP stack to the floating
from the rig. drilling vessel which provides for fluid
returns to the drilling vessel, supports
3.10 Fracture Pressure the choke, kill, and control lines,
The pressure required to initiate a guides tools into the well, and serves
fracture in a sub surface formation as a running string for the BOP stack.
(geologic strata). Fracture pressure
can be determined by Geo-physical 3.17 Maximum Allowable Annular
methods; during drilling fracture Surface Pressure (MAASP)
pressure can be determined by It is maximum allowable annular
conducting a leak off test. surface pressure during well control;
any pressure above this may damage
3.11 Hydrostatic Pressure formation / casing / surface
Pressure exerted by the fluid column equipment.
at the depth of interest is termed as
hydrostatic pressure. The magnitude 3.18 Mud Gas Separator
of hydrostatic pressure depends upon A device that removes gas from the
the density and the vertical height of drilling fluid returns, when a kick is
liquid column. Hydrostatic pressure being circulated out. Mud gas
can be calculated by the following separator is also known as gas buster
formula. or poor-boy degasser.
Hyd. pressure (psi) = 0.052 x mud
wt.(ppg) x TVD (feet) 3.19 Pipe-light
Hyd. pressure (kg/cm2) = Mud ‘Pipe-light’ occurs at the point where
wt.( gm/cc) x TVD (mtrs)/10 the formation pressure across the pipe
where TVD = True vertical depth. cross-section creates an upward force
sufficient to overcome the downward
3.12 Influx force created by the pipe’s weight- a
The flow of fluids from the formation potentially disastrous scenario.
into the wellbore.
3.20 Pore Pressure
3.13 Kick Pressure at which formation fluid is
A kick is intrusion of unwanted trapped in the pore (void) spaces of
formation fluids into wellbore, when the rock is termed as formation
hydrostatic head of drilling fluid pressure or pore pressure. It can be
column is / becomes less than the expressed in various ways like:
2
formation pressure. Kick can lead to In term of pressure - psi or kg/cm
blowout, if timely corrective measures In term of pressure gradient - psi /ft or
2
are not taken. kg/cm /meter.
2
In term of equivalent mud wt. - ppg or II. For effective well control the
gm/cc. following elements of well planning
should be considered:
3.21 Shall
The word ‘shall’ is used to indicate a. Casing design and kick
that the provision is mandatory. tolerance
b. Cementing
3.22 Should c. Drilling fluid density
The word ‘should’ is used to indicate d. Drilling fluid monitoring
that the provision is recommendatory equipment
as per sound engineering practice. e. Blowout prevention equipment
selection
3.23 Underbalanced Drilling (UBD) f. Contingency plans with
Drilling operation, when the actions to be taken if the
hydrostatic head of a drilling fluid is maximum allowable casing
intentionally (naturally or induced by pressure is reached
adding natural gas, nitrogen, or air to g. Hydrogen sulphide
the drilling fluid) kept lower than the environment, if expected.
pressure of the formation being drilled
with the intention of bringing formation
fluids to the surface. III. During well planning shallow gas
hazard should also be considered.
Well plan should include mitigating
measures considering the following:
4.0 Planning for well control
a. Pilot hole drilling,
b. Use of diverter.
4.1 Cause of Kick c. Riserless drilling (with
floater)
Kick may be caused due to:
i. Encountering higher than
anticipated pore pressure.
5.0 Diverter Equipment and Control
ii. Reduction in hydrostatic System
pressure in the wellbore.
A diverter system is used during top-
hole drilling; it allows routing of the flow
4.2 Cause of Reduction in Hydrostatic away from the rig to protect persons
Head and equipment. Components of diverter
system include – annular sealing
I. Failure to keep the hole full of device, vent outlet(s), vent line(s),
drilling fluid valve(s), control system.
II. Swabbing,
III. Loss of circulation Recommended practices for diverter
IV. Insufficient drilling fluid system:
density.
V. Gas cut drilling fluid I. The friction loss should not exceed the
VI. Loss of riser drilling fluid diverter system rated working pressure,
column. place undue pressure on the wellbore
and /or exceed other equipment’s
4.3 Well Planning design pressure, etc., e.g. marine riser.
The diverter system should be
I. Well planning should include accordingly designed.
conditions anticipated to be
encountered during drilling / II. To minimise back pressure (as much as
working over of the well, the well practical) on the wellbore while diverting
control equipment to be used, and well fluids, diverter piping should be
the well control procedures to be adequately sized.
followed.
3
III. Vent lines should be 10” or above for I. Stop drilling
offshore and 8” or above for onshore.
II. Pick up Kelly until tool joint is above
IV. Diverter lines should be straight as far rotary.
as possible, properly anchored and
sloping down to avoid blockage of the III. Open vent line towards downward
lines with cuttings etc. wind direction, close diverter packer
and close shale shaker inlet valve.
V. The diverter and mud return (flow line)
lines should be separate lines. IV. Stop pump and check for flow through
open vent line.
VI. Diverter valves should be full opening
type either pneumatic or hydraulic with V. If flow is positive, pump water or
automatic sequencing / manual drilling fluid as required moderating
sequencing. the flow.
VII. The diverter control system may be self VI. Monitor and adjust packer pressure as
contained or an integral part of the and when required.
blowout preventer control system. It
should be located in safe area. VII. Alert the personnel on the rig.
VIII. The diverter control system should be VIII. Take all precautions to prevent fire by
capable of operating the diverter system putting off all naked flames and
from two or more locations - one to be unnecessary electrical systems.
located near the driller's console.
Additionally following are applicable in
IX. When a surface diverter system and a case of subsea wells:
sub-sea BOP stack are used, two
separate control / accumulator systems I. Monitor and adjust slip joint packer
are required. This will allow the BOPs pressure as and when required.
to be operated and the riser
disconnected in case the diverter II. Watch for gas bubbles in the vicinity of
control system gets damaged. drilling vessel.
4
V. Size of choke line and choke manifold inspection should include the seal area
should be same. of the connectors (Choke and kill lines)
for any damage.
VI. Closing systems of surface BOPs
should be capable of closing each ram IV. Major inspection: after every 5 years of
preventer and annular preventer up to service or as per OEM’s
18¾” size within 30 seconds and recommendation. The BOP stack,
annular preventer above 18¾” size choke manifold, and diverter assembly
within 45 seconds. should be disassembled, and inspected
in accordance with the OEM’s
VII. Closing systems of sub-sea BOPs guidelines.
should be capable of closing each ram
preventer within 45 seconds and V. Spare parts requirement as per OEM
annular preventer within 60 seconds. should be considered. However,
minimum spare parts as listed below
VIII. Ram type subsea preventers should be should be readily available:
equipped with an integral or remotely
operated locking system. Surface ram i) A complete set of ram seals for
preventer should be equipped with each size and type of ram BOP in
mechanical / hydraulic ram locks. use.
ii) A complete set of bonnet or door
seals for each size and type of
6.2 Periodic Inspection and Maintenance ram BOP in use.
iii) Ring gaskets to fit end
I. The organisation should establish connections.
inspection and maintenance procedures iv) A spare annular BOP packing
for well control equipment. Inspections element and a complete set of
and maintenance procedures should seals.
take into consideration the OEM’s
recommendations. VI. During storage of BOP metal parts and
related equipment, they should be
II. Inspection recommendations, where coated with a protective coating to
applicable, may include: prevent rust. Storage of elastomer parts
should be in accordance with
a. Verification of instrument manufacturer’s recommendations.
accuracy
b. Relief valve settings VII. System should be in place to control
c. Pressure control switch use of rubber / elastomer parts, having
settings limited shelf life.
d. Nitrogen precharge pressure
in accumulators VIII. Separate maintenance history / log
e. Pump systems book of all the BOPs, Choke manifold
f. Fluid Levels and Control unit should be maintained.
g. Lubrication Points
h. General condition of IX. All pressure gauges on the BOP control
i) Piping systems system should be calibrated at least
ii) Hoses every three years.
iii) Electrical conduit/cords
iv) Mechanical components
v) Structural components 6.3 Surface Blow out Prevention
vi) Filters/strainers Equipment
vii) Safety covers/devices
viii) Control system adequacy Surface blow out prevention
ix) Battery condition equipment is used on land operations
and offshore operations where the
III. Inspections between wells: after each wellhead is above the water level.
well, the well control equipment should
be cleaned, visually inspected, I. Well control equipment can be classified
preventive maintenance performed under the following categories based on
before installation at the next well. The pressure rating:
5
I. Control systems are typically simple
a) 2000 psi WP closed hydraulic control systems
b) 3000 psi WP consisting of a reservoir for storing
c) 5000 psi WP hydraulic fluid, pump equipment for
d) 10000 psi WP pressurizing the hydraulic fluid,
e) 15000 psi WP, and accumulator banks for storing power
f) 20,000 psi WP fluid, manifolding, piping and control
valves for transmission of control fluid
for the BOP stack functions.
II. Refer Annexure-I for recommended
2000 psi BOP stack. One double, or two II. A suitable control fluid should be
single ram type preventers - one of selected as the system operating
which be equipped with correct size medium based on the control system
pipe rams the other with blind or blind- operating requirements, environmental
shear rams. requirements and user preference.
III. Refer Annexure-II for recommended III. Two (primary and secondary) or more
3000/5000 psi BOP stack. The stack pump systems should be used having
comprises of, besides annular BOP, independent power sources. Electrical
one double, or two single ram type and / or air (pneumatic) supply for
preventers - one of which should be powering pumps should be available at
equipped with correct size pipe rams all times such that the pumps will
and the other with blind or blind-shear automatically start when the system
rams. pressure has decreased to
approximately ninety percent of the
IV. Refer Annexure-III for recommended system working pressure and
10000 / 15000 / 20000 psi BOP stack. automatically stop within plus zero or
The stack comprises of, besides minus 100 psi of the system design
annular BOP, three single, or one working pressure.
double and one single ram type
preventers: one of which be should be IV. With the accumulators isolated, the
equipped with blind or blind-shear rams pump system should be capable of
and the other two with correct size pipe closing annular BOP on the drill string
rams. being used, open HCR valve on choke
line and achieve the operating pressure
V. When the bottom ram preventer is level of annular BOP to effect a seal on
equipped with proper size side outlets, the annular space within 2 minutes.
the kill and choke lines may be
connected to the side outlets of the V. Each pump system should be protected
bottom preventer. In that case the from over pressurisation by a minimum
drilling spool may be dispensed with. of two devices designed to limit the
pump discharge pressure. One device
VI. Inspite of the above, a drilling spool use should limit the pump discharge
may be considered for the following two pressure so that it will not exceed the
advantages: design working pressure of a BOP
Control System. The second device
a. Stack outlets at drilling spool normally a relief valve, should be sized
localizes possible erosion in to relieve at a flow rate of at least equal
less expensive drilling spool. to the design flow rate of the pump
systems, and should be set to relieve at
b. It allows additional space not more than ten percent over the
between preventers to design pressure.
facilitate stripping, hang off,
and / or shear operations. VI. The combined output of all pumps
should be capable of charging the entire
accumulator system from precharge
6.3.1 Control System for Surface BOP pressure to the maximum rated control
Stacks (Onshore and Bottom- system working pressure within 15
supported Offshore Installations) minutes.
6
VII. The hydraulic fluid reservoir should office for BOP stack functions, besides
have a capacity equal to at least twice the one near the driller.
the useable hydraulic fluid capacity of
the accumulator system. XIII. Remote control panels should have
light indicators to show open/close/block
VIII. In the field, the precharge pressure position of each BOPS and
should be checked and adjusted to Hydraulically operated choke and kill
within 100 psi of the recommended valves. For onshore it is optional and for
precharge pressure during installation of offshore unit it is must.
the control system and at the start of
drilling each well (interval not to exceed XIV. For offshore units emergency backup
sixty days). BOP control system should be
available. A backup system consists of
IX. The BOP control system should have a a number of high pressure gaseous
minimum stored hydraulic fluid volume, nitrogen bottles manifolded together to
with pumps inoperative, to satisfy the provide emergency auxiliary energy to
greater of the following two the control manifold. The nitrogen
requirements: backup system is connected to the
control manifold through an isolation
a) Close from a full open position at valve and a check valve. If the
zero wellbore pressure, all of the accumulator pump unit is not able to
BOPs in the BOP stack, plus 50 supply power fluid to the control
% reserve. manifold, the nitrogen back-up system
may be activated to supply high
b) The pressure of the remaining pressure gas to the manifold to close
stored accumulator volume after the BOPs.
closing all of the BOPs should
exceed the minimum calculated
(using the BOP closing ratio)
operating pressure required to 6.4 Subsea Blow out Prevention
close any ram BOP (excluding the Equipment
shear rams) at the maximum
rated wellbore pressure of the Subsea BOP stack arrangements
stack. should provide means to:
X. All rigid or flexible lines between the I. Close in on the drill string and on the
control system and BOP stack should casing or liner and allow circulation.
be fire resistant including end
connections, and should have a working II. Close and seal on open hole and allow
pressure equal to the design working volumetric well control operations.
pressure of the BOP control system. All
control system interconnect piping, III. Strip the drill string using the annular
tubing hose, linkages etc. should be BOP(s).
protected from damage from drilling
operations, drilling equipment IV. Hang off the drill pipe on a ram BOP
movement and day to day personnel and control the wellbore.
operations.
V. Shear logging cable or the drill pipe and
XI. The control unit should be installed in a seal the wellbore.
location away from the drill floor and
easily accessible to the persons during VI. Disconnect the riser from the BOP
an emergency. stack.
XII. A minimum of one remote control panel VII. Circulate the well after drill pipe
accessible to the driller to operate all disconnect.
system functions during drilling
operations should be installed at VIII. Circulate across the BOP stack to
onshore rigs. In offshore, one control remove trapped gas.
panel shall be available at a non
hazardous area preferably tool pusher
7
d. Ram preventers should be
6.4.1 Subsea BOP Stack equipped with an integral or
remotely operated locking system.
Subsea blow out prevention
equipment is used on subsea
wellhead. 6.4.2 Control System for Subsea BOP
Stack
I. Well control equipment can be classified
in following categories based on For subsea operations, BOP operating
pressure rating. and control equipment should include:
8
VI. Two full function remote control panels XIII. If diverter control system is not self
to operate BOP stack functions should contained, hydraulic power may be
be available, out of which one should be supplied from BOP control system.
accessible to driller on the rig floor. A
flow meter for indicating control fluid XIV. The diverter control system should be
flow should be located on each remote designed to prohibit closing the diverter
control panel. packer unless diverting lines have been
opened.
VII. The remote panels should be
connected to the control manifold in XV. Air storage backup system should be
such a way that all functions can be provided with capability to operate all
operated independently from each the pneumatic functions at least twice in
panel. the event of loss of rig air pressure.
VIII. Two independent control pods with all XVI. The drilling BOP shall have two
necessary valves and regulators to annular preventers. One or both of the
operate all BOP stack functions should annular preventers shall be part of the
be available. Two separate and LMRP. It should be possible to bleed off
independent sets of surface and subsea gas trapped between the preventers in
umbilicals should be used, one a controlled way.
dedicated to each control pod. Main
hydraulic fluid line should be of
minimum 1” size.
6.4.3 Deep Water Drilling Operations
IX. An emergency control system, either For Deep water drilling operations
acoustic system or remotely operated following additional requirements should
vehicle (ROV) operated control system be met:
should be used in the event that the
BOP functions are inoperative due to a I. If two or more different size strings are
failure of the primary control system. run, blind-shear ram should be able to
Emergency control system should shear all sizes of string.
charge and discharge stack mounted
accumulator, close at least one ram II. Use of two blind-shear rams is preferred
type preventer, blind shear ram and for ensuring the backup seal in case of
open Lower Marine Riser Package unplanned disconnect.
(LMRP) hydraulic connector.
III. In addition to choke and kill lines, a
X. The BOP control system should be dedicated boost line shall be provided
capable of closing each ram BOPs and for riser cleaning with necessary boost
opening or closing fail-safe-close valves line valves above the BOP stack.
within 45 seconds. For annular
preventer, closing time should not IV. In the event of full or partial evacuation
exceed 60 seconds. Time to unlatch the of mud from the riser, to combat riser
LMRP should be less than 45 seconds. collapse, an anti-collapse valve should
be provided in the riser system allowing
XI. Precharge pressure of accumulator automatic entry of seawater.
bottle in case of 3000 psi WP unit
should be 1000 +/- 100 psi and in case V. ROV should be able to perform
5000 psi WP unit should be 1500+/- 100 following functions:
psi. Only Nitrogen should be used for
precharge. i. LMRP and wellhead connector
unlatch.
XII. Separate diverter control panel should ii. LMRP and wellhead ring gasket
be available at rig floor to operate all release.
diverter control functions. Second iii. Methanol / Glycol injection.
control panel should be provided in the iv. Opening and closing of pipe
safe and approachable area away from rams and blind-shear rams.
rig floor. v. LMRP and Accumulator Dump.
9
VI. The need to utilize a multiplex BOP XVI. During drilling operations, to avoid any
control system to meet the closing time damage to drilling equipment in the
requirements should be evaluated for event of station keeping failure, there
application, if required. should be prescribed emergency
disconnect procedures, clearly
VII. The kill-/choke line ID should be verified indicating the point at which disconnect
vis-à-vis acceptable pressure loss, to action is to be started.
allow killing of the well at predefined kill
rates. The kill-/choke line should not be XVII. In general, preparation for disconnect
less than 88.9 mm (3½ inches). should begin at a distance with
reference to well mouth, when it is 2.5
VIII. It should be possible to monitor the % of water depth and disconnect should
shut-in casing pressure through the kill be initiated at 5.5 % of water depth.
line when circulating out an influx by
means of the work string / test tubing / XVIII. Emergency disconnect should include
tubing. the following:
IX. It should be possible to monitor BOP i. Hang up of the drill pipes on pipe
pressure and temperature at surface, rams.
through appropriate means. ii. Shearing the drill pipe.
iii. Effect seal on the wellbore.
X. It should be possible to flush wellhead iv. Disconnect the LMRP.
connector with antifreeze liquid solution v. Clear the BOP with LMRP.
by using the BOP accumulator bottles vi. Safely capture the riser.
or with a ROV system or other methods.
XIX. For monitoring riser angles, flex joint
XI. Detailed riser verification analysis angle reading should be available at the
should be performed with actual driller console on a real time basis and
environment and well data (i.e. weather connected to an alarm on derrick floor.
data, current profiles, rig characteristics
rd
etc.) and should be verified by a 3 XX. In variance to 0.5 ppg kick margin
party. normally considered, for deep water a
variance of upto 0 .2 ppg for conductor
XII. A simulated riser disconnect test should casing interval and 0.3 ppg for surface
be conducted considering manageable casing interval can be considered.
emergency weather / operational
scenarios. XXI. When using tapered drill pipe string
there should be pipe rams to fit each
XIII. The riser should have the following: pipe size. Variable bore rams should
§ current meter; have sufficient hang off load capacity.
§ riser inclination measurement
devices along the riser; XXII. Bending loads on the BOP flanges
§ riser tensioning system with an and connector shall be verified to
anti-recoil system to prevent withstand maximum bending loads (e.g.
riser damage during highest allowable riser angle and
disconnection; highest expected drilling fluid density.)
§ flex joint wear bushing to reduce
excessive flex joint wear.
§ riser fill-up valve. 6.5 Choke and Kill Lines
XIV. Parameters that affect the stress 6.5.1 Choke Lines and Choke Manifold
situation of the riser should be Installation with Surface BOP
systematically and frequently collected
and assessed to provide an optimum rig I. The choke manifold consists of high
position that minimizes the effects of pressure pipe, fittings, flanges, valves,
static and dynamic loads. and manual and/or hydraulic operated
adjustable chokes. This manifold may
XV. Wellhead and riser connector should be bleed off wellbore pressure at a
equipped with hydrate seal. controlled rate or may stop fluid flow
10
from the wellbore completely, as XII. Preventive maintenance of the choke
required. assembly and controls should be
performed regularly, checking
II. For working pressure of 3000 psi and particularly for corrosion, wear and
above, flanged, welded or clamped plugged or damaged lines.
connections should be used on the
component subjected to well pressure. XIII. Spare parts requirement as per OEM
should be considered. However,
III. Choke line from BOP to choke minimum spare parts as listed below
manifold and bleeding line should be should be readily available:
of minimum 3 inches nominal
diameter. i. One complete valve for each
size installed.
IV. In down stream of choke line alternate ii. Two repair kits for each valve
flow and flare routes should be size installed.
provided so that eroded / plugged or iii. Parts for manually adjustable
malfunctioning parts can be isolated chokes, such as flow tips, seat
for repair without interrupting flow and gate, inserts, packing,
control. gaskets, O-rings, disc
assemblies, and wear sleeves.
V. When buffer tanks are employed in iv. Parts for remotely controlled
down stream of chokes, provision choke(s).
should be made to isolate a failure or v. Miscellaneous items such as
malfunctioning without interrupting hose, flexible tubing, electrical
flow. cable, pressure gauges, small
control line valves, fittings and
VI. The choke manifold should be placed electrical components.
in a readily accessible location,
preferably outside of the rig structure. XIV. The following are the
recommendations for choke
VII. All the choke manifold valves should installation upto 5000 psi WP rating:
be full opening and designed to
operate in high pressure gas and i. Use two manually operated
drilling fluid service. adjustable chokes (out of two
chokes, use of one remotely
VIII. All the connections and valves in the operated choke is optional).
upstream of choke should have a ii. At least one valve should be
working pressure at least equal to the installed in upstream of each
rated working pressure of ram choke in the manifold.
preventer in use.
XV. The following are the
IX. Choke manifold should be pressure recommendations for choke
tested as per the schedule as fixed for installation of 10000 psi WP and
blowout preventer stack in use. above rating:
11
for use in the event rig air permit pumping or flowing through
becomes unavailable. either line.
6.5.2 Kill Lines and Kill Manifold II. Choke and kill line should be of
Installation with Surface BOP minimum three inches nominal
diameter.
I. The kill line system provides a means
of pumping into the wellbore when the III. One kill / choke line should be
normal method of circulating down connected to lower most side outlet of
through the Kelly or drill pipe cannot BOP.
be employed. The kill line connects
the drilling fluid pumps to a side outlet IV. There should be minimum one choke
on the BOP stack. line and one kill line connection above
lower ram BOP.
II. All lines valves, check valves and flow
fittings should have a working V. The ram BOP outlet connected to
pressure at least equal to the rated choke or kill line should have two full
working pressure of the ram BOPs in opening hydraulically operated fail-
use. The equipment should be tested safe-close valves adjacent to
on installation and periodic operation, preventer.
inspection; testing and maintenance
should be performed as per the VI. Connector pressure sealing elements
schedule fixed for the BOP stack in should be inspected, changed as
use, unless OEM’s recommendations required, and tested before being
dictate otherwise. placed in service. Periodic pressure
testing is recommended during
III. Line size should be minimum 2 inches installation. Pressure rating of all lines
nominal diameter. and sealing elements should be at
least equal to the rating of ram BOP.
IV. Two full bore valves (manual / HCR)
should be installed for up to 3000 psi VII. Periodic flushing of choke and kill line
manifold. Use of check valve is should be carried out to avoid
optional. plugging since they are normally
closed.
V. Two full bore manual valves and a
check valve or one full bore manual VIII. Flexible connections required for
and one HCR valve should be used in choke and kill lines should have
kill line in 5000 psi and above pressure rating at least equal to the
pressure rating manifold. rated working pressure of ram BOP.
VI. Spare parts requirement as per OEM IX. Spare parts requirement as per OEM
should be considered. However, should be considered. However,
minimum spare parts as listed below minimum spare parts as listed below
should be readily available: should be readily available:
12
XIV. All control valves of BOP control unit
II. Prior to drilling out the casing shoe, be either in the fully close or open
the casing should be pressure tested. position as required and should not be
Pressure test of all casing strings left in block or neutral position during
including production casing / liner operations.
should be done to ensure integrity of
casing. XV. Control valve of blind / blind–shear
ram should be protected to avoid
III. When the well head and BOP stack unintentional operation from the
used are of higher working pressure remote panel.
than the required as per design of the
specific well, the equipment may not XVI. Recommended oil level should be
be tested to its rated pressure. maintained in the control unit reservoir.
IV. When ram type preventers are XVII. Outlets of all sections of well head
installed the side outlets should be should have at least one gate valve.
below the rams.
V. All connections, valves, fittings, piping 6.7 Blow out Preventer Testing
etc. exposed to well pressure, should
be flanged or clamped or welded and
must have a minimum working 6.7.1 Function Test
pressure equal to the rated working
pressure of the preventers. I. All operational components of the BOP
equipment systems and diverter (if in
VI. Always install new and clean API ring use) should be function tested at least
gaskets. Check for any damage in the once a week to verify the components’
ring as well as grooves before use. intended operations.
VII. Correct size bolts/nuts and fittings II. The test should be preferably conducted
should be used and tightened to the when the drill string is inside casing.
recommended torque. All connections
should be pressure tested before III. Both pneumatic and electric pump of
drilling is resumed. accumulator unit should be turned off
after recording initial accumulator
VIII. All manually operated valves should pressure.
be equipped with hand wheels, and
always be kept ready for use. IV. All the blow out preventers and
hydraulically operated remote valve
IX. Ram type preventers should have (HCR) in choke / kill line should be
locking arrangement manual or auto function tested. Closing time of rams
lock. and opening time of HCR should be
recorded.
X. Wellhead side-outlets should not be
used for killing purpose, except in V. For surface BOP stack closing time
case of emergencies. should not exceed 30 seconds for each
ram preventers and annular preventers
XI. Kill lines should not be used for smaller than 18¾" and 45 seconds for
routine fill up operations. annular preventer of 18¾" and larger
size. For sub-sea BOP stack closing
XII. All sharp bends in high pressure time should not exceed 45 seconds for
lines should be of targeted type. all ram preventers and 60 seconds for
annular preventers.
XIII. All choke and kill lines should be as
straight as practicable and firmly VI. Operating response time for choke and
anchored to prevent excessive whip or kill valves (either open or close) should
vibration. Choke and Kill manifolds not exceed the minimum observed ram
should also be anchored. BOP close response time.
13
VII. Function test should be carried out c. Following repairs that require
alternately from main control unit / rig breaking a pressure connection.
floor panel / auxiliary panel. d. But not less than once every 21
days.
VIII. Record final accumulator pressures
after all the functions. It should not be VIII. Low pressure test should be carried out
less than 200 psi above the at 200-300 psi.
recommended precharge pressure of
accumulator bottles. IX. Once the equipment passes the low
pressure test, it should be tested to high
IX. All the gate valves and blow out pressure.
preventers should be returned to their
original position before resuming X. Initial pressure test of blowout preventer
operations. stack, manifold, valves etc., should be
carried out at the rated working
X. All the results should be recorded in the pressure of the preventer stack or well-
prescribed format (Annexure-VII). head whichever is lower. Initial pressure
test is defined as those tests that should
be performed on location before the well
6.7.2 Pressure Test is spudded or before the equipment is
put into operational service.
I. All blowout prevention components that
may be exposed to well pressure should XI. Subsequent high pressure tests should
be tested first to a low pressure and be carried out at a pressure greater
then to a high pressure. These include than maximum anticipated surface
blowout preventer stack, all choke pressure. Exception is the annular
manifold components, upstream of preventer which should be tested to
chokes, kill manifold / valves, kelly 70% of its rated pressure or maximum
valves, drill pipe and tubing safety anticipated surface pressure whichever
valves and drilling spools (if in use). is lower.
Pressure test (both low and high) on
each component should be of minimum XII. The pipe used for testing should be of
5 minutes duration, each. All the results sufficient weight and grade to safely
should be recorded in the format. withstand tensile, yield, collapse, or
(Annexure - VIII) internal pressures.
II. Test BOP using cup tester or test plug. XIII. Precaution should be taken not to
expose the casing to pressures in
III. Before pressure testing of BOP stack, excess of its rated strength. A means
choke and kill manifold should be should be provided to prevent pressure
flushed with clean water. build up on the casing in the event the
test tool leaks (wellhead valve should
IV. Clean water should be used as test be kept open when pressure testing
fluid. However for high pressure gas with test plug).
wells, use of inert gas such as N2
(nitrogen) as test fluid is desirable. XIV. Pressure should be applied from the
direction in which all the BOPs, choke
V. High pressure testing unit with pressure and kill manifold, FOSV / Kelly cock etc.
chart recorder be used for pressure would experience pressure during kick.
testing.
VI. Use test stump for sub-sea BOP stack 6.8 Minimum Requirements for Well
pressure testing. Control Equipment for Workover
operations (on land)
VII. Well control equipment should be
pressure tested: For workover operations:
14
equipped with correct size pipe/tubing 7.0 Procedures and Techniques for
rams and the other with blind or blind- Well Control (Prevention and
shear ram. Working pressure rating of Control of Kick)
BOP stack should exceed anticipated
surface pressure.
7.1 Kick Indications
II. Kill line should be of minimum 2 inch
size. Indications of kick can be:
III. One independent automatic I. Increase in drilling fluid return
accumulator unit with a control manifold, rate
clearly showing open and closed II. Pit gain or loss
positions, for preventer(s) to be III. Changes in flowline temperature
provided. The accumulator capacity IV. Drilling breaks
should be adequate for closing all the V. Pump pressure decease and
preventers without recharging pump stroke increase
accumulators. Unit should be located at VI. Drilling fluid density reduction
safe easily accessible place. VII. Oil show
VIII. Gas show
IV. The BOP stack should have remote
control panel clearly showing open and
closed positions for each preventer. 7.2 Prevention and Control of Kick
This Control Panel should be located
near to the driller’s position. In case of overbalance drilling:
V. Trip tank should be installed on I. The planned drilling safety margin is
workover rig deployed for servicing of difference between planned drilling
high pressure/ gas wells for continuous fluid weight and estimated pore
fill up and monitoring the hole during pressure.
round trips. Indicator to monitor tank
level can be either mechanical or digital II. To maintain primary well control,
and clearly visible to driller. drilling personnel should ensure that
the hydrostatic pressure in the
VI. Full opening safety valve of drill string / wellbore is always greater than the
tubing size and matching thread formation pressure by safety margin.
connection should always be available
at derrick floor during well servicing. It III. The use of trip margin (which is in
should be kept ready in 'open' position addition to safety margin) is
for use with operating wrench. encouraged to offset the effects of
Operating wrench(s) should be kept at a swabbing and equivalent circulating
designated place. density (ECD). The additional
hydrostatic pressure will permit some
VII. Sufficient volume of the workover fluid degree of swabbing without losing
should be available in reserve during primary well control.
workover operations.
IV. Successful well control (Blowout
VIII. During conventional production testing, prevention programme) includes
well should be perforated with adequate following elements:
overbalance.
a. Training of personnel and
IX. After release of the packer the string drills.
should be reciprocated, to ensure b. Monitoring and maintaining
complete retraction of packer elements, drilling fluid system.
prior to pull out of string. It should be c. Selection of appropriate well
ensured that there is no swabbing control equipment.
action. d. Installation, maintenance and
testing of well control
equipment.
e. Adoption of established well
control procedures.
15
7.2.1 Precautions before Tripping Out suitable well control method. If no self
flow is observed, run back to the
I. Conditioning of drilling fluid prior to bottom and circulate and condition the
tripping out should be ensured. This drilling fluid.
should include:
IV. Flow checks should be carried out:
a. No indication of influx of
formation fluids. i. Prior to all trips out of the
b. The drilling fluid density in and out hole.
should not differ more than 0.024 ii. During first 10 stands.
gm/cc (0.2 ppg.) in open hole. In iii. At the casing shoes.
cased hole there should not be iv. Prior to tripping out of drill
any difference. collars through BOP stack.
II. A trip tank shall be lined up and V. Any time a trip is interrupted, safety
function tested. Trip sheet shall be valve should be installed on the drill
ready to be filled during tripping out string.
(Annexure-VI).
III. Full opening safety valve(s) with 7.2.3 Precautions During Tripping In
suitable working pressure and with
proper connections and size, to fit all I. Regular flow checks and monitoring of
drill string connections, must be level in annulus should be done.
available on the rig floor. They should Where situation requires trip tank may
be kept ready in 'open' position for use be used to monitor drilling fluid
with operating wrench. Operating loss/gain.
wrench(s) should be kept at a
designated place. II. Circulation should be given to break
gelation of mud as per requirements
IV. An inside BOP, drill pipe float valve or especially in deep wells and where
drop in check valve should be heavy mud is used.
available for use whenever stripping is
required to be done. III. With a float valve in the string, drill
pipe should be filled up intermittently.
V. As far as possible tripping out should
be dry. If tripping out is wet, proper
mud bucket should be used enabling 7.2.4 Precautions During Casing
mud to flow back to the return Lowering
channel.
I. Regular flow checks and monitoring of
level in annulus should be done and
7.2.2 Precautions During Tripping Out fill up schedule of casing pipe / liner
should be followed as per the plan and
I. Well should be checked for swabbing use clean mud for casing/liner filling.
during pulling out. If positive, suitable
corrective measures such as change II. Running in speed of casing/liner
in tripping speed, tripping out with should be maintained considering
pump on, change in drilling fluid allowable surge pressure.
properties etc should be taken.
16
II. This should also include roles VII. Based on the risk assessment of the
responsibilities of the personnel during well and depending upon the situation,
kick. well control method to be used should
be selected. Plan and procedures for
III. The following information should be special situations such as casing
pre-recorded for use in kill sheet pressure reaching maximum allowable
preparation: casing data (properties), annular surface pressure (MAASP)
safe working pressure limit for surface should be available at the installation
blowout preventer equipment, (contingency plan).
wellhead, casing string, approved
maximum allowable casing pressure VIII. Shut in method to be used should also
(MAASP) and contingency plan, pump be pre-selected in the kill sheet.
rate for killing operation (SCR),
system pressure losses, capacities- IX. Sufficient quantity of drilling fluid
displacement, mud pump data, drilling weighting materials and chemicals
fluid mixing capability, trip margin, must be stored to meet any kick
water depth (offshore), well profile and situation.
shut-in method to be used (soft / hard
shut in).
7.3 Kick Control Procedures
IV. Record slow circulating rates at 1/3
and 1/2 the pump speed of drilling Following are recommended well
SPM at: control procedures for surface stack
and sub-sea.
a. the beginning of every shift
b. any time the mud weight is 7.3.1 Surface Stack
changed
c. after drilling 500 feet/150 mtrs. of For onshore and bottom-supported
new hole offshore installations:
d. after bit change
e. after pump repairs A. During Drilling
f. after each trip due to change in
BHA, bit nozzle. I. Stop drilling
II. Pick up Kelly to position tool joint
V. LOT / PIT after each casing should be III. Stop mud pump.
known. Whenever LOT / PIT is to be IV. Check for self-flow.
carried out, 2-3 meters of fresh V. If positive, proceed further to
formation should be drilled. close the well by any one of the
following procedures (Refer Table-
VI. Distance from rotary table to blowout 1).
preventer (s) be noted and sketch v Soft shut in
displayed in dog house and v Hard shut in
Toolpusher's office.
TABLE - 1
17
VI. Monitor the casing pressure. If the II. Record shut in pressure.
casing pressure is about to exceed
MAASP, follow the contingency plan. III. Monitor the casing pressure. If the
casing pressure is about to exceed
VII. Calculate the drilling fluid density maximum allowed (MAASP), follow
required to kill the kick. the contingency plan.
VIII. Initiate the approved / selected well IV. Calculate the drilling fluid density to kill
kill method. the kick.
IX. Check rig crew duties and stations. V. Initiate the approved /selected well kill
method.
X. Review and update the well control
worksheet. VI. Check rig crew duties and stations.
XI. Check pressures of all annuli of the VII. Review and update the well control
well. worksheet.
I. Position tool joint above rotary table 7.3.2 Floating Installations (Sub Sea)
and set pipe on slips.
A. During Drilling
II. Install Full Opening Safety Valve
(FOSV) in open position on the drill I. Stop drilling
pipe and close it.
II. Position the tool joint for the BOP’s
III. Close the well following any one of the operation.
procedures as per above table. (table
- 1) III. Shut down the drilling fluid pump(s).
IV. Monitor the casing pressure. If the IV. Check the well for flow – if it is flowing,
casing pressure is about to exceed follow shut in procedure.
MAASP, follow the contingency plan.
V. If the soft shut-in procedure has been
V. Calculate the drilling fluid density selected: open the choke line, close
required to kill the kick. Annular BOP and close the choke.
VI. Initiate the approved / selected well kill VI. If the hard shut-in procedure has been
method. selected: close Annular BOP and
open the choke line with the choke in
VII. Check rig crew duties and stations. closed position.
VIII. Review and update the well control VII. Observe the casing pressure, if it
worksheet. exceeds MAASP, follow the
contingency plan.
IX. Check pressures of all annuli of the
well. VIII. Check for trapped gas pressure.
i. Position a tool joint above the viii. Connect the circulating head to
hang-off rams leaving the lower the standpipe, open the safety
Kelly cock high enough above the valve.
floor to be accessible during the
maximum expected heave and XII. Allow the shut-in pressure to stabilise
tide when the selected tool joint and record pressures.
rests on the hang-off rams.
XIII. Determine the volume of the kick.
ii. Close the hang-off rams.
XIV. Calculate the drilling fluid density
iii. Carefully lower the drill string until required to kill the kick.
the tool joint rests on the hang-off
rams. XV. Select a kill method.
iv. Reduce support pressure on the XVI. Check rig crew duties and stations.
motion compensator to support
about half of the weight of drill XVII. Review and update well control
string above the BOPs plus some worksheet.
overpull to provide drill string
tension to assist shearing, if XVIII. Inspect the BOP stack with television,
required. if feasible.
b. Without a motion
compensator: B. During Tripping
i. Set the slips on the top joint of drill I. Install safety valve.
pipe.
II. Position the tool joint for the BOP’s
ii. Close the lower Kelly cock. operation.
iii. Break the Kelly/top drive III. Check the well for flow – if it is flowing,
connection above the lower Kelly follow shut in procedure.
cock and put it in the rat hole.
IV. If the soft shut-in procedure has been
iv. Pick up the assembled space-out selected: open the choke line, close
joint, safety valve, and circulating Annular BOP and close the choke.
head with the safety valve closed.
Make up the space-out joint on the V. If the hard shut-in procedure has been
closed lower Kelly cock. selected: close Annular BOP and
open the choke line with the choke in
v. Open the lower Kelly cock, closed position.
remove the slips, and position tool
joint above the hang-off rams VI. Observe the casing pressure, if it
leaving the safety valve high exceeds MAASP, follow the
enough above the floor to be contingency plan.
accessible during the maximum
expected heave and tide when the VII. Check for trapped gas pressure.
19
VIII. For release of trapped gas, close the tension on the circulating head
uppermost rams below the choke line with a tension device.
and close the diverter, open the
annular preventer to allow trapped gas v. Connect the circulating head to
to rise, displace riser with kill fluid and the standpipe, open the safety
close the annular preventer, reopen valve.
the ram preventer.
XI. Allow the shut-in pressure to
IX. Adjust the closing pressure on the stablise and record pressures.
annular preventer to allow stripping of
tool joints. XII. Determine the volume of the kick.
X. Hang off the drill pipe as follows: XIII. Calculate the drilling fluid density
required to kill the kick.
a. With a motion compensator:
XIV. Select a kill method.
i. Position a tool joint above the
hang-off rams leaving the safety XV. Check rig crew duties and stations.
valve high enough above the floor
to be accessible during the XVI. Review and update well control
maximum expected heave and worksheet.
tide when the selected tool joint
rests on the hang-off rams. XVII. Inspect the BOP stack with
television, if feasible.
ii. Close the hang-off rams.
iii. Carefully lower the drill string until C. When String is Out of
the tool joint rests on the hang-off Hole
rams.
I. At the first indication of the well
iv. Reduce support pressure on the flowing, close the blind / blind-shear
motion compensator to support rams.
about half of the weight of drill
string above the BOPs plus some II. Open the gate valve on the subsea
overpull to provide drill string BOP stack to open the choke line,
tension to assist shearing, if close the choke line at the surface.
required.
III. Record shut-in pressures. Wt.
b. Without a motion compensator: (specific gravity) of fluid in the choke
line should be considered for
i. Pick up the assembled space-out calculating shut-in casing pressure.
joint, safety valve, and circulating
head with the safety valve closed. IV. Record the kick volume.
Make up the space-out joint on the
string. V. Run the drill string in the hole to the
ii. Open the safety valve, remove the top of the BOPs with NRV.
slips, and position tool joint above
the hang-off rams leaving the VI. Add the hydrostatic pressure of the
safety valve high enough above fluid in the choke line to the surface
the floor to be accessible during pressure to determine the pressure
the maximum expected heave and below the blind rams.
tide when the selected joint rests
on the hang-off rams. VII. Determine if the pressure below the
blind rams can be overbalanced by
iii. Close the hang-off rams. hydrostatic pressure of the drilling fluid
that can be safely contained by the
iv. Carefully lower the drill string until riser. If so, adjust the riser tensioners
the tool joint lands on the closed to support the additional drilling fluid
hang-off rams. Slack off the entire weight and displace the drilling fluid in
weight of drill string while holding
20
the riser with drilling fluid of the c. The reaction time from float
required density. raising to the designated crew
member's readiness to start
VIII. Close the diverter. Open the BOPs the closing procedure should
and watch for flow. If the well does not be recorded and response
flow, open the diverter and trip in the time should not be more than
hole. 60 seconds.
IX. If the well starts to flow, close the blind d. Total time taken to complete
ram preventer, displace the choke and the drill should be recorded
kill lines with heavy drilling fluid, and and it should not be more than
circulate until the riser contains drilling 2 minutes.
fluid of the desired density.
e. Drill should be initiated without
X. Continue going in the hole. Stop prior warning during routine
periodically, close the pipe rams, and operation.
circulate the riser by pumping down
the kill line to maintain the required f. Drill should be conducted
drilling fluid density in the riser. once a week with each crew.
I. The competence with which drilling I. Raise alarm by raising mud tank float -
personnel respond to well control automatic or oral.
situations and follow correct procedures
can be improved by carrying out II. Stop drilling / other operation in
emergency drills. progress.
II. While drilling in H2S / sour gas prone III. Position tool joint for BOPs’ ram closing.
area, detectors shall be installed and
breathing apparatus in sufficient IV. Stop mud pump
quantity and cascade system shall be
made available. Crew shall be trained V. Secure brake
to handle situations in this environment.
VI. During / after the above steps, as
III. Organisation should assign specific applicable, designated crew should
responsibilities to the identified / move to assigned positions
designated persons, for actions required
during an emergency related to well VII. Check for self flow
control, which would be part of rig ERP.
VIII. Record the response time.
a. Following drills should be
performed:
i. Pit drill Trip Drill (Drill Pipe in BOP)
ii. Trip drill
21
IV. Close FOSV after installation
II. Close blind/ blind-shear ram.
V. Designated crew members should move
to assigned position, during / after the III. Record response time.
above steps, as applicable.
VII. Record response time. Asstt. Shift Incharge / Asstt. Driller and above
supervisory personnel should have valid
Note: Trip drill should be carried out preferably accredited well control certificate (of the
when bit is inside the casing. A full opening appropriate level).
safety valve for each size and type of
connection in the string shall be available on At least one trained person should always be
derrick floor, in open position. Safety valves present on derrick floor to observe well for any
may be clearly marked for size and activity even during shutdown period
connection.
VII. Record response time. III. Mud / pit volume totaliser should be
installed for all the reserve and active
Note: Under actual kick conditions (other mud tanks to detect mud tank level's
than drills) if only one stand of drill deviation with an accuracy of + one
collar remains in the hole it would be barrel. Mud volume totaliser should
probably faster to simply pull the last have high / low alarm (visual or audible
stand and close the blind ram. If setting).
numbers of drill collar stands are more
and well condition does not permit IV. Gas detector should always be
step III than install FOSV with change available. Gas measurement should be
over sub on drill collar, close it and carried out near the point where the
close annular preventer. mud from the well mouth surfaces
Preparation for step III above should (Shale shaker and rig sub structure).
be done in advance prior to starting
pull out of drill collar - make one single
/ stand of drill pipe with drill collar 9.2 Trip Tank System
change over sub.
iii. Leaking connection below XX. Adequate provision should be made for
drilling BOP. the safe storage and / or disposal of
produced fluids and drill cuttings.
iv. Leaking rotating control device Reservoir liquids should not be stored in
or flowline before ESDV, seal an earthen pit. Refer to MOEF
elements, connection to flowline, guidelines for handling of drilling fluids
drilling BOP or high pressure and drill cuttings (OISD-RP-201)
riser.
XXI. Explosive potential monitoring should
v. Erosion or wash out of choke. be conducted at all the points where
Consider the case where there is a potential of release of
isolation for repair of the choke combustible vapours to atmosphere.
cannot be achieved.
XXII. For wells which contain H2S, drill
vi. Failure of surface equipment cuttings should be held in tanks
after RCD. This can be leaks or equipped with vapour control. Vapour
plugged equipment and lines. shall either be vented to a flare stack or
through an H2S scrubbing system.
vii. Work string failure.
Another related technique of UBD is Managed
viii. Emergency shut-in. Pressure Drilling (MPD). While UBD is mostly
25
focused on maximizing the performance of the
reservoir, MPD is more focused on
successfully drilling the well, while minimizing
the time and money spent on non-productive
time (NPT), in addition to not damaging the
formation in the process.
a. A fail-safe-open, remotely
operated valve in the overboard
line.
b. A cement line pressure gauge in
the choke panel, a remote camera
in the shaker house, with display
in the driller's house.
c. A choke / kill line glycol injection
system.
d. High pressure and / or high
temperature resistant seals should
be installed in choke and kill lines,
including flexible line hoses and
the choke and kill manifold,
packing in the kelly cock / internal
BOP, packing / seal in the marine
riser.
26
12.0 References
2. API-RP 16E: Recommended Practices for Design of Control Systems for Drilling
Well Control Equipment
7. API-SPEC 16D: Specifications for Control Systems for Drilling Well Control Equipment
9. HSE-OTH 512: HPHT Wells: Perspective on Drilling and Completion from the Field
27
Abbreviations
28
Annexure-I
29
Annexure-II
Arrangements for 3000 psi and 5000 psi Surface BOP Stack
30
31
32
33
Annexure-VI
TRIP SHEET
Note –
· Column 5 - Actual vol. of drilling fluid taken by hole (diff. of trip tank reading )
· Column 6 – Diff. of column 3 and 5
34
Annexure-VII
RIG : DATE :
WELL :
BOP STACK DETAIL (as applicable):
1. Annular BOP -
2. Single / Double / Triple ram type BOP -
3. Upper pipe ram size -
4. Lower pipe ram size -
SIGNATURE : SIGNATURE :
NAME : NAME :
SHIFT INCHARGE/ : DIC/TOOL PUSHER :
DRILLER
35
<< Back Home Next >>