Range Compact
Range of product NS630b...1600
Product or component type Circuit breaker
Device short name Compact NS800N
Device application Distribution
Poles description 4P
Protected poles description 4t
Neutral position Left
Network type AC
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name Micrologic 6.0
Trip unit technology Electronic
Trip unit rating 800 A ( 50 °C )
Complementary
Network frequency 50/60 Hz
Control type Rotary handle
Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
(In) rated current up to 65 °C 800 A ( 50 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 800 A
Breaking capacity 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Environment
Standards IEC 60947-2
Product certifications ASEFA
ASTA
Power losses 15 W
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
2
Pollution degree 3 conforming to IEC 60947
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -50...85 °C