Professional Documents
Culture Documents
Microprocessor controlled
Constant Current Regulator
Type
MCR 2.5kVA to 30kVA
J-Bus remote control
AM 06.350e-JB Edition 4.1
1
AM 06.350e-JB Edition 4.1
Safety
Regulatory safety precautions are applicable in some countries, on some
precautions sites; in absence of such legal prescriptions, the operating and maintenance
personnel should refer to the FAA Advisory Circular AC 150/5340-26
"Maintenance of Airport Visual Aid Facilities" for instructions on safety
precautions. Personnel must observe the safety regulations at all times.
While every practicable safety precaution has been incorporated in this
equipment, the following rules must be strictly observed.
Keep away
Operating and maintenance personnel must at all time observe all safety
from live regulations. Do not change neither lamps nor components or make
circuits adjustments inside equipment with the light circuit energised.
See FAA Advisory Circular AC 150/5340-26 concerning safety precautions.
Resuscitation
Operating and maintenance personnel should familiarise and keep
themselves trained in the resuscitation techniques found in the First Aid
Instruction Manual.
Electrostatic
Modules and components susceptible to electrostatic damage
Discharge
ESD Electronic modules and components should be touched only when this is
unavoidable e.g. soldering, replacement,…
A human being must first of all eliminate electronic charges from his own
body just before touching an electronic module or component.
The easiest way of discharging a human being's body is to touch a
conductive earthed object.
Electronic modules or components must not be brought in contact with highly
insulating materials such as plastic sheets, synthetic fibre clothing,…
They must be laid down on conductive surfaces.
The tip of the soldering iron must be earthed.
Electronic modules and components must be stored and transported in
conductive packing.
2
AM 06.350e-JB Edition 4.1
Use
This Instruction Manual is the property of
restriction
notice n.v. ADB s.a.
585, Leuvensesteenweg
B-1930 Zaventem - Belgium
Tel 32 2 722 17 11 Fax 32 2 722 17 64
http://www.atd.siemens.de/airports
This manual or parts thereof may not be reproduced, stored in a retrieval
system, or transmitted, in any form or by any means, electronic, mechanical,
photocopying, recording, nor otherwise, without ADB's prior written consent.
Guarantee N.V. ADB S.A. guarantees that the performance of the inset lights described
in this manual, when sold by ADB or its licensed representatives, meets the
requirements of ICAO Annex 14 volume 1 and FAA specification AC
150/5345-46.
Any defect in design, material or workmanship, which may occur during
proper and normal use over a period of one (1) year from date of shipment,
will be repaired or replaced by ADB free of charge, ex works. Operational
failure resulting from lamp burnt out, improper maintenance or installation,
damage due to runway maintenance equipment, snow ploughs or aircraft
arresting gear hooks is not considered a result of proper use and is beyond
the scope of the warranty.
Warranty does not cover natural wear and tear nor damage arising after
delivery owing to faulty or negligent handling, excessive strain, unsuitable
materials for Operation, deficient civil engineering Work, unsuitable soil
conditions, and such chemical, electrochemical or electrical influences as
were not assumed at the time of the Contract.
All liability for consequences of any inexpert alterations or repairs carried out
by Purchaser or a third party shall be waived.
N.V. ADB S.A. shall in no event be liable to Purchaser for any further claims,
particularly claims for damages not affecting the goods themselves.
The above constitutes the limits of ADB’s liabilities in connection with the
inset lights covered by this manual.
3
AM 06.350e-JB Edition 4.1
Table of content
Section 2 Installation 43
2.1 Introduction 43
2.2 Installation 44
2.3 Electrical connection 46
2.4 Starting procedure 52
2.4.1 Tap selection 54
2.4.2 Tap wiring 59
2.5 Reparations and modifications 62
2.5.1 Replacement of modules 62
2.5.2 Replacement of EPROMs 63
Section 3 Maintenance 64
Section 4 Troubleshooting 65
Section 6 Drawings 84
4
AM 06.350e-JB Edition 4.1
5
AM 06.350e-JB Edition 4.1
6
AM 06.350e-JB Edition 4.1
Table of Pictures
FIG 1-1: POWER FACTOR AND EFFICIENCY FOR A MCR RATED 30 KVA 12
FIG 1-2: MCR STAND-ALONE UNIT 14
FIG 1-3: MCR 2.5 KVA 15
FIG 1-4: MCR 4-10 KVA 16
FIG 1-5: MCR 4 TO 10 KVA WITH EFD MODULE FRONT VIEW - OPEN 17
FIG 1-6: MCR 4 TO 10 KVA REAR VIEW - OPEN 17
FIG 1-7: MCR 12.5-30 KVA 18
FIG 1-8: MCR 12.5 TO 30KVA WITH EFD & LFD MODULES FRONT VIEW - OPEN 19
FIG 1-9: MCR 12.5 TO 30KVA REAR VIEW - OPEN 19
FIG 1-10: POWER MODULE KSR 110 A (DOUBLE EUROCARD 6U HIGH) 20
FIG 1-11: POWER MODULE KSR 43 A (DOUBLE EUROCARD 6U HIGH) 20
FIG 1-12: MODULE DE PUISSANCE KSR 43 A 21
FIG 1-13: MODULE DE PUISSANCE KSR 110 A 21
FIG 1-14: CONTROL MODULE (DOUBLE EUROCARD 6U HIGH) 22
FIG 1-15: MCR FRONT PANEL WITH MULTIPLEX REMOTE CONTROL CONNECTORS 23
FIG 1-16: MULTIPLEX REMOTE CONTROL CONNECTION ON THE REAR SIDE 30
FIG 1-17: MULTIPLEX CONNECTION BETWEEN MCR’S (CHANNEL A - 4 WIRES CONNECTION) 31
FIG 1-18: EARTH FAULT DETECTOR MODULE (MCR 12.5 TO 30 KVA) 35
FIG 1-19: LAMP FAULT DETECTOR MODULE (MCR 12.5 TO 30KVA) 37
FIG 1-20: MCR NAME PLATE 42
FIG 2-1: INSTALLATION OF MCR, MINIMUM CLEARANCE WALLS 44
FIG 2-2: DETAIL OF A TYPICAL INSTALLATION 45
FIG 2-3: CONNECTING A 2.5KVA MCR 48
FIG 2-4: CONNECTING A 4 TO 10 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR REMOTE
CONTROL CABLES) 49
FIG 2-5: CONNECTING A 4 TO 10 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR REMOTE
CONTROL CABLES) WITH CUTOUT SCO 49
FIG 2-6: CONNECTING A 12.5 TO 30 KVA MCR (SERIES CABLE, SUPPLY CABLE AND REAR
REMOTE CONTROL CABLE) - FRONT VIEW 51
FIG 2-7: CONNECTING A 12.5 TO 30 KVA MCR- REAR VIEW 51
FIG 2-8 : 2.5 KVA POWER TRANSFORMER TOP VIEW 59
FIG 2-9 : TAP ADAPTATION MCR 4 TO 10 KVA 60
FIG 2-10 : TAP ADAPTATION MCR 12.5 TO 30 KVA 60
FIG 2-11: TAP WIRING 61
7
AM 06.350e-JB Edition 4.1
Table of Tables
8
AM 06.350e-JB Edition 4.1
1 Section 1
1.1 Introduction
The MCR The ADB MCR is a microprocessor controlled Constant Current Regulator
specially designed for the supply of airport lighting series loops at various
intensity levels.
Scope This manual covers the ADB MCR microprocessor controlled Constant
Current Regulator manufactured in full compliance with:
• ICAO: Aerodrome Design Manual, Part 5 paragraphs 3.2.1.4/5/6
• FAA : AC 150/5345-10E and L829
• European: EMC EN 50081-2 and EN 50082-2 for industrial environments
• France: STNA approved.
Operation The constant current regulators are designed for use in airport series lighting
limits circuits.
They are designed to meet the requirements of the various specifications
mentioned above.
Operation outside the design limitations of these specifications may result in
degradation of performance, damage or failure of regulator components or
hazardous conditions.
All regulators are designed for indoor operation, at an ambient temperature
from -20°C (-40°C on special request) up to +55°C.
All the regulators are air cooled without fans.
Using the regulator at ambient temperatures out of the specified range could
cause damage. Good ventilation shall be provided specially when operation
near the maximum temperature limit is expected.
EMC - According to EN50081-2, para. 7.1, the MCR regulator will not be used in
conformity residential, commercial and light-industrial environment.
9
AM 06.350e-JB Edition 4.1
Rated powers 2.5/ 4/ 5/ 7.5/ 10/ 12.5/ 15/ 20/ 25/ 30 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%) (*)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: Standard 6.6 A; also 20 A for 25 and 30 kVA.
Remote control and Multiplex: industrial field bus (J-Bus)
monitoring
Rated Output Max. RMS Dielectric test Max. open Max. open
powers current output on output circuit RMS circuit peak
(A) voltage circuit - V - (1) output volt.(2) voltage (3)
10
AM 06.350e-JB Edition 4.1
Limits The current regulation is guaranteed within the limits of ± 1%, in the following
conditions.
Limitations • operation from -5% to -15% of nominal input voltage with full load can
cause too low output current at maximum brightness step.
• operation at +15% of the nominal input voltage will be restricted to
maximum 1-hour period to avoid over-heating or over-stressing of the
components.
Readjustment Although the nominal input voltage is factory-wired some re-adjustments are
possible in the ranges 220 up to 240V and 380 up to 415 (420V): consult
factory.
RV-DV If the last digit of the code number of your MCR is “1” or above, this means
that it is equipped with RV-DV terminals and, optionally, with a SCO cutout.
The interlocking of the SCO Cutout microswitch and the MCR RV-DV
terminals allows to energise the regulator after the Cutout contacts are
engaged and to de-energise the regulator before the Cutout contacts are
totally opened.
11
AM 06.350e-JB Edition 4.1
FAA The power factor and the efficiency are in accordance to or better than the
Accordance FAA specifications.
Power Factor At nominal input power, nominal resistive load and maximum brightness:
• powers up to 10 kVA: 0.90
• powers above 10 kVA: 0.95
Efficiency At nominal input voltage and resistive load and max. brightness: 90 to 92%.
Taps By means of output taps on the secondary (high voltage) side of the power
transformer (PT) the power factor can be optimised versus the actual load at
full brightness. The following taps are provided:
• actual load between 100% and 82% of nominal (8/8)
• actual load between 81% and 71% of nominal (7/8) (*)
• actual load between 70% and 46% of nominal (6/8) (*)
• actual load between 45% and 33% of nominal (4/8)
• actual load between 32% and 22% of nominal (3/8) (*)
• actual load between 21% and 0% of nominal (2/8) (*)
Example Taps
2/8 3/8 4/8 6/8 7/8 8/8
100% Efficiency
90
80 Power Factor
70
60
50
40
Load
12 25 37 50 75 87 100%
Fig 1-1: Power factor and efficiency for a MCR rated 30 kVA
12
AM 06.350e-JB Edition 4.1
Output The lightning arrestors LA1 and LA2 (fig 1.3, 1.5 and 1.8) on the output
voltage surge terminals of the series circuit protect the output of the MCR.
protection
13
AM 06.350e-JB Edition 4.1
Description Each stand-alone MCR will accept, in one enclosure, a power module
KSR43A or KSR110A (as required) fitted with the control module, a fused
input switch (in the low voltage unit), and the high voltage components (in the
high voltage unit). The stand-alone regulators have standard lifting lugs and
optional rolling castors.
1 2
Part Function
1 Power Module KSR 110 A (para. 1.3.5)
2 Control Module (para. 1.3.6)
3 Fused input switch
4 Time counter
5 High voltage compartment
14
AM 06.350e-JB Edition 4.1
Technical data
267
SELECT
ON
FAULT
FAULT
FAULT
LOCAL
RESET
REM
OFF
S1
S2
S3
S4
S5
S6
S7
S8
X
1
X
3
X
2
15
AM 06.350e-JB Edition 4.1
Technical data
Rated powers 4/ 5/ 7.5/ 10 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: 6.6 A
Remote control and Multiplex: industrial field bus (J-Bus)
monitoring
1260
100
16
AM 06.350e-JB Edition 4.1
Pictures Fig 1-5: MCR 4 to 10 kVA with EFD Module Front View - Open
Control Module
Name Plate
Choke L1
Lamp Monitor Transformer (option LFD)
Output Voltage Transformer TP1 (option LFD)
Output Current Transformer TI 1
RV-DV terminals
Interface module
Output Transformer
Ground Stud M6
17
AM 06.350e-JB Edition 4.1
Technical data
Rated powers 12.5/ 15/ 20/ 25/ 30 kVA.
Rated input voltages 220/ 230/ 240/ 380/ 400/ 415 V (±15%) (*)
Rated frequencies: 50/ 60 Hz (± 5%).
Series circuit current: Standard 6.6 A; also 20 A for 25 and 30 kVA.
Remote control and Multiplex: industrial field bus (J-Bus)
monitoring
SELECT
ON
FAULT
FAULT
FAULT
LOCAL
RESET
REM
OFF
S1
S2
S3
S4
S5
S6
S7
S8
X
1
X
3
X
2
1260
18
AM 06.350e-JB Edition 4.1
Pictures Fig 1-8: MCR 12.5 to 30kVA with EFD & LFD Modules Front View - Open
Name Plate
Lamp Monitor
Transformer TI 2 (option LFD)
Output Current
Transformer TI 1
Earth Fault Detection
Module (option EFD)
S6 through S1 Tap
adaptation to actual load
Lightning Arresters
LA1 - LA2
Output Voltage
Transformer TP1 (option LFD)
Interface module
Output transformer
Ground Studs M6
19
AM 06.350e-JB Edition 4.1
Principle The complete power range from 2.5 to 30 kVA is based on two easily
replaceable power modules, one for max. 43 A (KSR 43 A) and the other for
max. 110 A (KSR 110 A).
These modules are installed in the low voltage unit of the MCR.
Pictures Fig 1-10: Power Module KSR 110 A (Double Eurocard 6U High)
F1 F2
267 mm
x
1
x
3
x
2
244 mm
F1 F2
267 mm
x
1
x
3
x
2
122 mm
20
AM 06.350e-JB Edition 4.1
P2
P7
1 2 5 3 4 6 7
8
F1 F2
P2
MCR-110A
P7
1 2 5 3 4 6
Legend
Part Function
1 Auxiliary fuses F1 and F2
2 Dual in/out terminals
3 Thyristor pack THP1
4 Thyristor trigger and contactor on/off control PCB
5 2-pole contactor K
6 Auxiliary supply transformer T1
7 Plugs P2 and P7 for the Control Module
8 Input current transformer Tin
21
AM 06.350e-JB Edition 4.1
General The module with the on-board microprocessor controls and monitors the
operation of the regulator
167 mm
x
1
x
1
x
3
x x
2 1
45,72 mm
Additional • Piggy-back PCB for multiplex remote control, with two DB9 front
piggy-back connectors on the front panel.
PCB's • Piggy-back PCB for Lamp Fault detection (option LFD)
22
AM 06.350e-JB Edition 4.1
Front panel Fig 1-15: MCR Front Panel with multiplex remote control connectors
Display Selection
CCR-ON
I-Fault 2
Earth Fault
Lamp Fault
Local Operation
7
6
23
AM 06.350e-JB Edition 4.1
Front panel: 1. 4 digits multiple info alphanumerically display; with the “display select”
legend push button, the values that can be selected are:
• output current,
• brightness step,
• % of maximum output load (option LFD),
• output voltage (option LFD),
• number of failed lamps (option LFD),
• circuits identification,
• series circuit insulation value (option EFD),
• lamp test.
2. Led's for information about the status of the regulator:
• CCR ON,
• I-fault,
• Earth-fault (option EFD),
• Lamp fault (option LFD),
• Local operation.
3. Reset button,
4. Remote, Off, brightness step 1 to 8 drum selector,
5. DB9-male connector for connection to a PC (X1),
6. Two DB9-female multiplex remote control connectors (XA and XB)
7. DB25-male connector (X2) for feedback signals (current, LFD and EFD)
duplicated to P7 on the rear (ADB-use),
8. Fixing screws.
Drum selector During switch over from one brightness step to another it is possible that,
due to an intermediate position, the output current has a totally different
value or that the regulator switches off.
The output current will however never be higher than the maximum value.
If the drum selector is handled in a normal way this situation will not occur.
For all the local selections above the maximum step (e.g. position 4 for a 3
brightness steps regulator) the output current will equal the maximum step.
The drum selector has no end position. It can be switched, without any
danger, from position 8 to the position "remote control".
24
AM 06.350e-JB Edition 4.1
Introduction The regulator is delivered with factory programmed default brightness values.
Each brightness step can be re-adjusted between the maximum and the
minimum current value with the PC software.
Default values The table below shows the current values for each brightness step in
function of the number of steps.
Imax (A) 20
Imin (A) 5.5
Brightness step Nr of steps
Drum selector 3 4 5 6 7 8
Fig 1-15
1 14.5 10 8.5 8.2 6.7 8.5
2 16.7 13.3 10.3 10 8.5 9.4
3 20 16.7 12.4 11.8 10.3 10.3
4 “ 20 15.8 13.6 12.4 11.8
5 “ “ 20 16.4 15.8 13.9
6 “ “ “ 20 19.4 16.7
7 “ “ “ “ 20 19.4
8 “ “ “ “ “ 20
25
AM 06.350e-JB Edition 4.1
Output current The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
monitoring for display ("I<<") on the front panel) and switches off when the output current
open circuit drops below the minimum output current. The restart of the MCR is only
possible after troubleshooting and reset (reset button on the front panel).
Output current The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
monitoring for display ("I>>") on the front panel) and switches off when the output current
over current is higher than one of the two preset levels and after the corresponding time-
delay of each level. The restart of the MCR is only possible after
troubleshooting and reset (reset button on the front panel).
Mains supply Undervoltage: If the mains supply voltage drops below a certain (user-
voltage adjustable) level, the MCR switches off.
monitoring When the mains supply voltage has reached a higher (user-adjustable)
level, the MCR restarts automatically.
Overvoltage: An alarm will be generated when the mains supply voltage
reaches a (user-adjustable) level.
Capacitive With an open circuit on long screened series cables the output current, due
output current to cable capacitance, may remain above the open circuit threshold level
monitoring thus inhibiting the operation of the open circuit shut down.
The MCR creates an alarm (indicated by the led “I fault” and on the 4 digits
display ("I<<") on the front panel) and switches off during open circuit shut
down. The restart of the MCR is only possible after troubleshooting and
reset (reset button on the front panel).
Monitoring of The control module monitors the conduction angle of the thyristor.
the output If the conduction angles of both thyristors are not equal, the MCR switches
current for off (indicated by the led “I fault” and on the 4 digits display "ASY" on the
asymmetry front panel). The restart of the MCR is only possible after troubleshooting
and reset (reset button on the front panel).
Monitoring of In case of overload the output current cannot be guaranteed by the MCR,
overload the reaction of the MCR can be programmed by the user with the PC
software. The default reaction is not to switch off the MCR!
The alarm is indicated by the blinking led “I fault” on the front panel.
Monitoring of A fast response network fires back the thyristors if the peak value of the
output current output current reaches a value greater than twice the maximum peak value
surge in normal operation. The thyristors remain in the off-state for several periods
limitation and the firing angle then goes smoothly from zero back to the normal value.
26
AM 06.350e-JB Edition 4.1
1.6.1 General
J-Bus piggy The additional piggy-back PCB for J-Bus remote control is mounted onto the
back PCB basic print PCB1364 of the control module.
The use of the piggy back PCB 1432 is required (in stead of the
previous PCB1398):
• when the MCR operates with a circuit selector CSM
• with the redundant J-Bus (dual J-Bus) software version 2.00 or higher
Master/ Slave A MCR is always a “slave” on the bus. There can be a maximum of 31 MCR’s
on one bus section with one common “bus master”.
CSM circuit The circuit selector has to be considered as an extension of the MCR.
selector The control messages to and the back-indications from the CSM are
transferred through the dedicated serial link (RS485) between the CSM logic
board PCB1433 and the J-bus interface PCB1432.
The MCR and the CSM circuit selector must have the BUS remote control
system!
1.6.2 Connection
Front or rear Front: Two DB9-female connectors (XA and XB of fig 1-15) on the front panel
connection of the control module.
Rear: Four DB9 connectors on the interface module: one male(P3) and one
female(P1) for channel “A” and one male(P4) and one female(P5) for channel
“B” or two DB9-female connectors (XA and XB of fig 1-15) on the front panel of
the control module.
The channels are galvanically insulated from the MCR circuitry and from each
other.
27
AM 06.350e-JB Edition 4.1
Slave number Hex value of the switches on dip-switch SW1 “Slave address”
28
AM 06.350e-JB Edition 4.1
PCB1398 PCB1432
W1 No function
J6 W2 2 or 4 wires transmission / Channel B
If strap is placed this corresponds to 2 wire transmission,
thus transmission as well as reception messages are
passing over lines E+ / E-. ( In this case each slave
receives also the answers from the other slaves )
Without strap the transmission happens over 4 wires:
Transmission over E+/E- and reception over lines R+/R-.
J5 W3 Line termination resistor / Channel B–Transmission
If strap is placed a line termination resistor of 150 ohm is
connected to the line.
J4 W4 Line termination resistor / Channel B–Reception
If strap is placed a line termination resistor of 150 ohm is
connected to the line.
J3 W5 2 or 4 wires transmission / Channel A
If strap is placed this corresponds to 2 wire transmission,
thus transmission as well as reception messages are
passing over lines E+ / E-. ( In this case each slave
receives also the answers from the other slaves )
Without strap the transmission happens over 4 wires :
Transmission over E+/E- and reception over lines R+/R-.
J2 W6 Line termination resistor / Channel A–Transmission
If strap is placed a line termination resistor of 150 ohm is
connected to the line.
J1 W7 Line termination resistor / Channel A–Reception
If strap is placed a line termination resistor of 150 ohm is
connected to the line.
Line The line termination resistors (150 to 850 Ohm) (Straps W3, W4, W6, W7 on
termination PCB1432 or J1, J2, J4, J5 on PCB1398) are only to be placed on the
resistors PCB1432 / PCB1398 of the MCR’s, which are at the extremities of the line, to
prevent line reflections to occur.
In case of a 2 line system only the straps of the used channel are to be
placed.
- BUS A: W6 and W7 / J1 and J2
- BUS B: W3 and W4 / J4 and J5
Take care that only the line termination resistors at the end of the line are
placed. When other straps are also placed, the signals on the line are
weakened. This can cause an incorrect functioning of the MCR!
29
AM 06.350e-JB Edition 4.1
Picture Fig 1-16: Multiplex Remote Control connection on the rear side
REM. CONTR
TELECOM.
DB9 connector
INPUT
ALIM.
RV
DV
Ground The ground connections of the serial bus RS485 (DB9/3) power supply must
connection be interconnected between all the MCR’s.
30
AM 06.350e-JB Edition 4.1
Cable Fig 1-17: Multiplex connection between MCR’s (Channel A - 4 wires connection)
configuration
MCR : Previous MCR :
Interface module PCB1399 Interface module PCB1399
for rear connection for rear connection
Ea+ Ea+
1 1
Ea- Ea-
2 2
Ra- Ra-
7 7
Ea+ Ea+
1 1
Ea- Ea-
2 2
Ra- Ra-
7 7
Next MCR :
Interface module PCB1399
for rear connection
Front The wire of the previous and to the next MCR have to be soldered on the
connection same pin of connector XA for channel A and XB for channel XB.
31
AM 06.350e-JB Edition 4.1
32
AM 06.350e-JB Edition 4.1
33
AM 06.350e-JB Edition 4.1
34
AM 06.350e-JB Edition 4.1
Principle The earth fault detector module measures the insulation resistance between
the series circuit and the ground or the cable screen with the regulator
switched to the supply, even when not running. A stabilised, current limited,
500 V DC voltage is applied between the series circuit and the ground or
cable screen, irrespective of the operating voltage, via a high voltage
resistor. The insulation resistance is determined from the resulting leakage
current.
Measurement The measurement range is from 6.3 kOhm to 0.5 GOhm. The insulation
range resistance can be displayed on the front panel display.
2 levels Two alarm levels are available. Each level can be set in a range from 6,3
kOhm to 150 Mohm.
Alarm If the insulation value drops below the alarm level, the “earth-fault” led on the
front panel is activated and a back indication signal is generated towards the
remote control. If the insulation, then, increases above that level the alarm
remains latched. The reset is possible with the “RESET” button on the front
panel or via a remote control command.
Picture Fig 1-18: Earth Fault Detector module (MCR 12.5 to 30 kVA)
EFD components
(with logic print)
35
AM 06.350e-JB Edition 4.1
Theory The Lamp fault detector module (LFD) measures the reactive power required
to saturate the unloaded lamptransformers of the series loop by integrating
the series loop voltage (obtained through the voltage transformer) during a
measuring window (derived from the unloaded current transformer mounted
in the regulator enclosure).
The measured voltage with all the lamps of the series loop intact is
compensated to obtain a zero volt reading.
With a defined number of lamps in open circuit the module can be calibrated
to obtain a read-out corresponding to the number of lamps de-activated.
Tolerances If the above mentioned restrictions are fulfilled, the obtained tolerance will
be:
• for 0 to 5 burnt lamps : + 1 lamp
• for 6 to 10 burnt lamps: + 2 lamps.
36
AM 06.350e-JB Edition 4.1
Picture Fig 1-19: Lamp Fault Detector module (MCR 12.5 to 30kVA)
Lamp Monitor
Transformer T.I.2
Output Voltage
Transformer T.P.1
37
AM 06.350e-JB Edition 4.1
Cutout SCO As an option, the regulator MCR can be delivered with a cutout SCO
mounted onto the bottom part of the rear panel.
The purpose is to isolate safely the series circuit from the CCR during
maintenance or testing operations. It also allows periodical isolation
resistance measurement series circuit to ground without disconnecting the
series cable.
Refer to instruction manual AM.06.455e.
Cover
Handle horizontal turned 90° ccw. turned 90° cw. from position A
from position A
The series circuit connected to the shorted and disconnected from the CCR, shorted and
is CCR grounded connected to the measurement terminal
The CCR is delivering current shorted and shorted and grounded
to the series circuit grounded
The microswitch activated and not activated activated and allows the regulator to be
(2) is allows the CCR to and inhibits the ON
be ON CCR to be ON
The cover can be locked by can be locked can be locked by the key
the key by the key
1. The position of the cover intermediate between B and C, i.e., turned 180° from
position A, cannot be used and the cover cannot be plugged into the body.
2. An activated microswitch means that the normally open contact is closed and that
the normally closed contact is open. For interlocking with the CCR, only the
normally open contact will be used.
38
AM 06.350e-JB Edition 4.1
Time counter As an option, the regulator MCR can be delivered with a time counter “ON”
mounted on the right front panel of the low-voltage compartment (see fig
1.2).
The time counter “ON” starts counting as soon as the MCR is switched ON,
independent of the brightness step.
When the MCR operates with a CSM circuit selector, no time counters
are allowed on the MCR.
Nevertheless, the option time counter is available on the CSM!
39
AM 06.350e-JB Edition 4.1
1.11 Equipment required for installation, start-up and troubleshooting but not
supplied
Tools 1 True RMS Voltmeter (preferable: 5000V AC scale with isolating transformer).
1 Multimeter
1 Ohmmeter "Megger" 5000V insulated
1 Clamp or A-meter true RMS scale 10 and 30Amps
1 Complete set of tools for electrician and mechanic (no special tool required)
40
AM 06.350e-JB Edition 4.1
Floppy A Floppy-disc with the communication program between the MCR and the
PC can be ordered.
Section 7 shows how to install the program and explains the functions of the
software.
Take care that the software version is compatible with the version of the
basic MCR software. (see table 1.3).
compatible with
Basic MCR software version of PC version of J-Bus
version software on floppy software
disc Single Dual
1.02 1.04 --- ---
1.05 1.04 --- ---
1.08 1.08 1.00 ---
1.10 1.11 1.01 ---
1.11 1.11 1.02 ----
1.12 1.12 1.02 ----
1.21 1.21 1.21 1.21
1.22 1.21 1.21 1.21
1.23 1.24 1.21 1.21
2.00 2.00 2.03* 2.03*
*Version 2.03 replaces version 2.00 & 2.01 and is full compatible to these
latter ones.
Only version 2.03 is available as spare part.
Ordering For information about ordering codes and ADB part numbers, refer to:
codes Section 5 Parts list and spare parts.
41
AM 06.350e-JB Edition 4.1
Values
Output Power Output current Supply Voltage
c d a b e
2.5 kVA 6.6 A 220/ 230/ 240 14 378
4 kVA 6.6 A 220/ 230/ 240 22 606
5 kVA 6.6 A 220/ 230/ 240 28 757
7.5 kVA 6.6 A 220/ 230/ 240 41 1136
10 kVA 6.6 A 220/ 230/ 240 54 1515
12.5 kVA 6.6 A 220/ 230/ 240 67 1894
15 kVA 6.6 A 220/ 230/ 240 77 2272
20 kVA 6.6 A 220/ 230/ 240 103 3030
2.5 kVA 6.6 A 380/ 400/ 415 8 378
4 kVA 6.6 A 380/ 400/ 415 13 606
5 kVA 6.6 A 380/ 400/ 415 17 757
7.5 kVA 6.6 A 380/ 400/ 415 24 1136
10 kVA 6.6 A 380/ 400/ 415 31 1515
12.5 kVA 6.6 A 380/ 400/ 415 39 1894
15 kVA 6.6 A 380/ 400/ 415 45 2272
20 kVA 6.6 A 380 60 3030
20 kVA 6.6 A 400/ 415 57 3030
25 kVA 6.6 A 380/ 400/ 415 75 3788
30 kVA 6.6 A 380/ 400/ 415 88 4545
25 kVA 20 A 380/ 400/ 415 75 1250
30 kVA 20 A 380/ 400/ 415 88 1500
42
AM 06.350e-JB Edition 4.1
2 Section 2
Installation
2.1 Introduction
Introduction This section provides instructions for the installation of the MCR regulators.
Refer to the substation drawings and specifications for the specific installation
instructions.
Unpacking Unpack the crate upon receipt and examine the regulator to insure that no
damage has occurred during shipping. Note any exterior damage to the crate,
which might lead to detection of equipment damage. When handling the
regulator care should be taken to maintain the regulator in the upright position.
If damage to any equipment is noted, a claim form should be filed with the
carrier immediately. The inspection of the equipment by the carrier may be
necessary.
Installation The regulator will be installed in a well-ventilated room with sufficient clearance
criteria for personnel to inspect and maintain the regulator.
The installator should refer to the specific installation plan for implantation.
The series cut-outs and the circuit selector (if any) are generally also installed
in the same room (refer to appropriate manual).
For special models, refer also to the appropriate manuals (outside, portable,
rack-mounted version).
43
AM 06.350e-JB Edition 4.1
2.2 Installation
Regulator If the regulator is equipped with castors, it can simply be pushed to the right
with wheels location in the substation, provided the floor is flat.
Adequate precautions should be taken to avoid overbalancing the regulator if
there are obstacles on the floor such as wires or small unevenness.
Note that the 4 to 10 kVA regulators do not have a square footprint.
Regulator The regulator can be lifted by the lifting lugs on the top (see fig 1-2). Always
without use the 4 lifting lugs to lift it.
wheels
Ventilation Air outlet grids are provided at the rear and the top; air inlet grids, at the
bottom and the front of the regulator.
To avoid overheating of CCR-components, take care never to obturate these
ventilation grids.
Fig. 2-1 gives the position of the regulator with regard to the minimum
clearance necessary to have good ventilation. Side by side, the regulators
have to remain to a minimum of 5 cm from each other.
Air exhaust
Min 50 cm to the wall
Front side
Rear
side
Air intake
Air
exhaust
Air intake
44
AM 06.350e-JB Edition 4.1
Cutout SCO As an option, the regulator MCR can be delivered with a cutout SCO
mounted onto the bottom part of the rear panel.
Refer to the instruction manual AM.05.455e for more information about it.
45
AM 06.350e-JB Edition 4.1
Panels to For connecting the supply, output and remote control cables,
remove • 2,5 kVA: remove top and rear panel
• 4 to 10 kVA: remove the front and rear panels
(MCR with serial number up to ?? only rear panel)
• 12.5 to 30 kVA: remove the front and rear panels.
Refer to the previous page for the precautions to take.
Grounding Although the supply cable includes a ground wire, additional safety
grounding is required. Use the ground studs M6 on the rear/ bottom of the
regulator (see Fig 1-6 and Fig 1-9). The grounding wire will have at least 16
mm² and be as short as possible.
Main supply The minimum section of the main supply cable (see table 2.1) is valid under
cable following conditions:
46
AM 06.350e-JB Edition 4.1
Table 2-1 Table 2-1: Main supply cable sections, fuses, power module,…
47
AM 06.350e-JB Edition 4.1
48
AM 06.350e-JB Edition 4.1
MCR Fig 2-4: Connecting a 4 to 10 kVA MCR (series cable, supply cable and rear remote
4 to 10 kVA control cables)
Supply cable
Rear remote control cable
Fig 2-5: Connecting a 4 to 10 kVA MCR (series cable, supply cable and rear remote
control cables) with cutout SCO
Interlock cable
Stress relieve cable clamps
Supply cable
Rear remote control cable
Series cable
49
AM 06.350e-JB Edition 4.1
50
AM 06.350e-JB Edition 4.1
MCR Fig 2-6: Connecting a 12.5 to 30 kVA MCR (series cable, supply cable and rear remote
12.5 to 30 kVA control cable) - Front view
Series cable
Series cable
51
AM 06.350e-JB Edition 4.1
Caution Read the safety instructions and check if the installation complies with para.
2.3. Do the following preliminary checks:
• grounding
• main supply cable, routing, wiring and voltage
• series circuit cable, routing, wiring and insulation resistance to earth.
• remote control cable, routing, wiring and voltage.
Procedure The first start-up will be done in local control only (drum selector on front
panel of control module). It is advised, as far as possible, to disconnect the
remote control.
Step Action
1 Open the fused input switch (Fig 1-2) and put the drum selector (Fig 1-
15) in the OFF position.
2 Disconnect the series circuit (if already connected) and short the output
terminals. Measure the output current with an AC current clamp around
the shorting wire. Warning: High voltage!
3 Switch ON the regulator supply on the low voltage distribution board and
measure the input voltage on the main supply terminals (Fig 2-3, 2.4, 2.5
and 2-7). The measured voltage must match the input voltage indicated
on the nameplate within -5 to +10%.
4 Check if the input fuses are correctly positioned. . Notice that the fused
switch cannot be closed if the fuses are not the correct size, not present
or not correctly positioned (these last remarks in case of fuses Neozed).
5 With the drum selector still in the OFF position, close the fused input
switch. The display on the control module will indicate “0.00” (output
current) and the green “ON” led and the yellow “LOCAL” led will be lit.
If the EFD module is present the EFD-LED will flash as long as the EFD-
reading is not available (depending on the setting of the EFD, Start-up
delay)
6 Turn the drum selector to position B1 and measure the output current
with the external A-meter and compare it with the indication on the
display. Repeat the same for all each brightness step by turning the
drum selector through positions B1 to B8.
The value of the actual output current depends on the number of
programmed steps (see para. 1.4)
7 Switch OFF the regulator by turning the drum selector CCW (counter
clock wise) to the OFF position and open the fused input switch. If the
EFD module is present the EFD-LED will flash as long as the EFD-
reading is not available (depending on the setting of the EFD, Start-up
delay)
8 Remove the short circuit on the output and switch the regulator ON
(close the fused switch and turn the drum selector to position B1). The
main contactor will switch ON and after a short period OFF. The display
will indicate “I<<“ and the led “I fault” on the control module lights up,
indicating an open series circuit.
52
AM 06.350e-JB Edition 4.1
9 Switch OFF the regulator by turning the drum selector CCW (counter
clock wise) to the OFF position and open the fused input switch.
Connect the series circuit to the regulator. Switch ON the regulator and
check the output current. Check that the maximum output current is not
less than 6.6 A (or 20A).
Unless the maximum output current has been reprogrammed, failure to
reach that current indicates a too high series circuit load or a too low
main supply voltage. Switch off the MCR.
With the maximum output current, check that the main input voltage is
not less than the 95% of the nominal value.
10 Proceed with the adaptation of the output transformer secondary taps to
the actual load. (para. 2.4.1)
11 Calibration of the EFD and LFD option (if installed).(see section 7)
53
AM 06.350e-JB Edition 4.1
Target Adaptation of the regulator to the installed load by using the right tap
combination.
Preliminary For each method a preliminary visual check will be made on the series circuit.
check Switch ON the CCR at a convenient brightness and check that all the lamps of
the circuit operate. If not, take corrective actions until all lamps are OK.
Check that the mains voltage is at its nominal value.
Step Action
1 Switch ON the MCR to the maximum brightness step 6.6A or 20A
2 Measure the RMS output voltage at the output terminals after
about 10 minutes. Determine the correct tap using table 2.2 -
choose the tap with the nearest higher voltage than the measured
RMS output voltage.
Switch off the MCR and wire the chosen tap (see par 2.4.2).
Warning: High Voltage!
3 Switch ON the regulator at the maximum brightness for about 10-
min. and check that the output current is not below the maximum
value. If the output current is too low, wire to the next higher tap.
4 Close the MCR taking into account the requirements given in par.
2.2.
Table 2 - 2 Table 2-2: Maximum voltages (V RMS) for each tap, each power and output current.
PWR/ Iout Tap 8/8 7/8 6/8 4/8 2/8
2.5 kVA/ 6.6A 378 - - 190 -
4 kVA/ 6.6A 606 530 450 300 150
5 kVA/ 6.6A 757 660 565 375 185
7.5 kVA/ 6.6A 1136 990 850 565 280
10 kVA/ 6.6A 1515 1320 1130 755 375
12.5 kVA/ 6.6A 1894 1650 1410 940 465
15 kVA/ 6.6A 2272 1980 1695 1130 560
20 kVA/ 6.6A 3030 2645 2260 1505 745
25 kVA/ 6.6A 3788 3305 2825 1880 935
30 kVA/ 6.6A 4545 3965 3390 2255 1120
25 kVA/ 20A 1250 1090 930 620 310
30 kVA/ 20A 1500 1310 1120 745 370
54
AM 06.350e-JB Edition 4.1
Step Action
1 Remove the front panel of the power module (KSR43A or
KSR110A) by loosening the 5 screws.
F1 F2
5 screws to
remove
x
1
x
3
x
2
Do not lose the pin washers, they must be put in place again.
2 Switch ON the regulator to the maximum brightness step.
3 After about 10 minutes, measure the voltage on the terminals
labelled “OUT1” and “OUT2” of the power module.
4 Switch OFF the MCR. Using the table 2.3, select and wire (see
par 2.4.1 and 2.4.2) the tap to be used.
5 Once the taps had been wired, switch ON the regulator again at
the maximum brightness for about 10 minutes and check that the
output current is not below the maximum value. If the output
current is too low, wire to the next higher tap.
6 Close the MCR taking into account the requirements given in
para. 2.2.
55
AM 06.350e-JB Edition 4.1
Table 2 - 3 Table 2-3: Tap to choose, for each power, depending on the measured primary voltage.
56
AM 06.350e-JB Edition 4.1
Table 2-3 Table 2-3: Tap to choose, for each power, depending on the measured
primary voltage.
57
AM 06.350e-JB Edition 4.1
Third method You can also use the PC software (see section 7) to determine which tap to
select. Therefore, follow the next procedure.
Procedure
Step Action
1 Wire the 8/8 tap and switch ON the regulator to the maximum
brightness.
2 Connect the PC to the regulator, open the program and go to
menu F8: “power monitoring”. Select in the sub-menu “primary
parameters” the “Thyristor conduction angle” parameter.
3 Read the thyristor conduction angle and select the tap using the
table below:
58
AM 06.350e-JB Edition 4.1
Step Action
1 To gain access to the power transformer terminals (S6 to S1),
remove the top cover and disconnect the ground wire. Note the
position of the ventilation slots.
2 Wire the tap according to fig 2-11.
3 Switch ON the regulator at the maximum brightness step for about
10 minutes
4 Check that the output current is not below the maximum value.
If it is so, wire to the next higher step and check again till the
output current is below the maximum value.
5 Close the MCR taking into account the requirements given in par.
3.2.
P10
P9 S1
P8 S2
P7 S3
P6 S4
P5 S5
P4 S6
P3
P2
P1
59
AM 06.350e-JB Edition 4.1
Step Action
1 Remove the front panel and disconnect the ground wire.
2 Wire the tap according to fig 2-11.
3 Switch ON the regulator at the maximum brightness step for about
10 minutes
4 Check that the output current is not below the maximum value.
If it is so, wire to the next higher step and check again till the output
current is below the maximum value.
5 Close the MCR taking into account the requirements given in par.
3.2.
S6 through S1 tap
adaptation to actual
load
identification label
OUT
OUT
S6
S5
S4
S3
S2
S1
Spare strap
60
AM 06.350e-JB Edition 4.1
S1 wire m1 S1 wire m1
S2 S2
82 to 100 % 71 to 81 %
(8/8) (7/8)
S3 S3
S4 wire m2 S4
S5 S5 wire m2
strap B strap B
S6 S6
S1 S1 wire m1
S2 wire m1 S2
59 to 70 % 22 to 46 %
(6/8) (4/8)
S3 S3
strap A
S4 S4 wire m2
S5 wire m2 S5
strap B strap B
S6 S6
S1 wire m1
S2
8 to 22 %
(2/8)
S3
strap B
S4 wire m2
S5
S6
61
AM 06.350e-JB Edition 4.1
62
AM 06.350e-JB Edition 4.1
63
AM 06.350e-JB Edition 4.1
3 Section 3
Maintenance
Introduction The MCR regulators have been developed using new technologies and in view
of reducing the maintenance tasks to a minimum.
This section establishes the maintenance procedures required for the MCR
regulator. The maintenance tasks must be performed on a securing basis to
insure optimum performance, minimise service interruption and avoid major
breakdowns.
To check Action
Operational • the operation of the • Use eventually a PC to log the
regulation on all data
brightness steps
• all readings.
Electrical • Input voltage • If the regulator voltage is not
within -5% to +15% of rated
voltage, notify the power
company to correct the
voltage.
• Output current (RMS • Record it and adjust if out of
value) tolerance; use a RMS-reading
A-meter.
Visual • the wiring of the • Repair damaged or loose
regulator and circuit wires
• Replace damaged
components
• Housing for rust spots • Clean and repaint rust spots.
and damage. • Repair the eventual damages
• Dust inside housing • Clean by blowing dry air over
the dirty components,
PCB’s,…
64
AM 06.350e-JB Edition 4.1
4 Section 4
Troubleshooting
65
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
Guideline As a guideline for troubleshooting, use table 4-1 to table 4-3. Three different
cases are given:
Display and Together with these explanations, the next 2 tables show how to interpret the
led’s info. indications on the front panel display and the meaning of the different led’s:
Table Information
Table 4-4 How to interpret the indications on the display?
Table 4-5 Led’s information
Fuses The table 4-6 gives an overview of the fuses (main fuses, fuses on the power
module,…) in the MCR.
66
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
67
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
68
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
Table 4-3 Table 4-3: Regulator does not produce not the requested output current.
69
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
Table 4-4 Table 4-4: How to interpret the indications on the front panel.
The 4 digits display normally indicates the actual values of the chosen
parameter (see par. 1.3.6), but in some cases the display indicates a
character string:
If This means
%--- Percentage of output load not available
V--- Output voltage measurement not available
L--- Lamp fault detector, not present
L*** Lamp fault detector, present but disabled or not adjusted
---M Earth fault detector, not present
???M Earth fault detector, measurement not available
This display will also indicate how the regulator interprets an occurring failure
that causes the regulator to switch off (if the strap ST2 on the PCB1364 is in
position 2 which is a default setting on delivery):
If This means
CS? The regulator operates with a circuit selector.
No circuit is selected on the circuit selector.
I>> The regulator switched OFF for over current
I<< The regulator switched OFF because the output current was below
a minimum level (open circuit, thyristors not operational, main
contactor not closed, loose wire, output current measurement is
failing, …
Asy The regulator switched OFF for asymmetric output current
P>> The regulator switched OFF for overload.
The regulator is set to switch OFF in case of output overload with
the PC function: F5/ Alarm levels output current/ “switch off level if
overload Yes or No.
These failures will disappear after having pushed on the Reset button (Rep 3
on Fig. 1-15) on the front panel.
70
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
Several led’s are available on the front panel of the control module and
inform you about the status of the MCR.
As a general rule, a blinking led indicates that the considered function is
not available and a permanent lighted led indicates a failure.
Those led’s are installed on the front panel of the basic microcontroller board
(PCB1364). Some of them can only light up if the corresponding option is
installed.
Led Indicates
DS1 TXD, messages to the PC if the serial link is active.
DS2 RXD, messages from the PC if the serial link is active.
DS3 blinks at a rate of once per second if the program runs.
DS4 5V-power supply present.
71
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
LED Function
DS1 RXD1
RS232-link, logic level , Receive line from regulator PCB1364
DS2 TXD1
RS232-link, logic level, transmission line to regulator PCB1364
DS3 TXD0
RS485-link, transmitted signal, channel A
DS4 RXD0
RS485-link, received signal, channel A
DS5 V5A
Isolated 5V DC for RS485 , Channel A and link to circuit
selector
DS6 SOUT0
RS485-link, transmitted signal, channel B
DS7 SIN0
RS485-link, received signal, channel B
DS8 V5B
Isolated 5V DC for RS485 , Channel B
DS9 SOUT1
RS485-link, transmitted signal to circuit selector PCB1433.2
DS10 SIN1
RS485-link, received signal from circuit selector PCB1433.2
Led Indicates
DS1 5V-power supply present.
Led Indicates
DS1 LOW SCALE, lights up if the actual leakage current is below
20µAdc.
DS2 500 V DC, lights up if the 500 V DC is too low in regard to the
reference voltage.
DS3 IN RANGE, extinguishes if the output current of the module gets
limited.
DS5 OHM-TEST lights up if the relay for the ohm-test is activated.
72
AM 06.350e-JB Edition 4.1
Troubleshooting, Continued
On the boards:
73
AM 06.350e-JB Edition 4.1
5 Section 5
Parts list
Introduction This section covers the main replaceable parts for the MCR regulators.
Caution Replacement of electronic components may be done, only with original spare
parts delivered by ADB. Not doing so can result in severe damage to the unit
and be hazardous for the user or the operator.
Reference A reference code number is assigned to each part contained in the equipment.
designation When ordering, always mention the reference code number of the ordered part
but also the serial number, type, power rating, input voltage, frequency, N° of
brightness steps, output current, which are indicated on the nameplate of the
regulator.
• Other parts: Other parts should be kept in stock to cope with repair: fuses,
lightning arrestors, PCB’s, terminals & connectors, fused input switch,
circuit breaker, power module and others.
Orders All spare parts orders shall be addressed to ADB or our local representative.
n.v. ADB s.a.
585, LEUVENSESTEENWEG
B - 1930 ZAVENTEM, BELGIUM
Tel. 32/2/722.17.11
Fax : 32/2/722.17.64
74
AM 06.350e-JB Edition 4.1
Remark 1 The PCB 1441 (NC 1593.11.700) replaces the PCB 1377 (NC 1590.03.250)
in the MCR versions where the last digit of the code number is “1” or above.
Anyway, in older versions (with last digit = 0), the PCB 1441 can also be
used as spare parts. The terminals 3 and 4 of the counter-connector X5,
which is delivered with the PCB, have to be shortened.
Remark 2 To replace the old contactor on the KSR110 (NC 6148.45.530) by the new
one (NC 6148.45.600) the current transformer on the KSR110 has to be
repositioned!
75
AM 06.350e-JB Edition 4.1
(*) Dual JBUS The dual JBUS Eprom has to be ordered separately and put on the piggy-
back on the control module. (code number: see table 5.6)
76
AM 06.350e-JB Edition 4.1
Remark 1 The PCB 1432 (NC 1590.03.390) replaces the PCB 1398 (NC 1593.10.610)
in the MCR versions where the last digit of the code number is “2” or above.
Anyway, in older versions (with last digit = 0 or 1), the PCB 1432 can also be
used as spare part.
77
AM 06.350e-JB Edition 4.1
78
AM 06.350e-JB Edition 4.1
Table 5-4 Table 5-4: Spare parts for EFD option (see Fig 1-5 and 1-8).
Table 5-5 Table 5-5: Spare parts for LFD option (see Fig 1-5 and 1-8).
79
AM 06.350e-JB Edition 4.1
Table 5.-5a Table5-5a Spare parts for Time counter “TC-ON” option.
Table 5-5b Table 5-5b: Spare parts for Time counter “TC-MAX” option.
SP6195.02.020
TC-MAX 6195.02.020 Digital Hour counter 24x48 6-250VDC/AC
T20 6300.00.020 Safety transformer 230-400V/24V 40VA
K20 6169.07.010 Relay 2PNO 24VAC-coil 2940 39.1
F20 6130.27.000 Fuse M 1.25A - 50kA 500V - DIA 6x32
80
AM 06.350e-JB Edition 4.1
81
AM 06.350e-JB Edition 4.1
82
AM 06.350e-JB Edition 4.1
83
AM 06.350e-JB Edition 4.1
6 Section 6
Drawings
Introduction In the table below, you will find the list of drawings:
84
AM 06.350e-JB Edition 4.1
DS1
85
AM 06.350e-JB Edition 4.1
DS1-DS2-DS3-DS4
F1
RAM
P1 Params
EPROM
P3 Rem. control
F2-F3
ST2
P4 LFD
Serial
EPROM
P6
P8
F4
86
AM 06.350e-JB Edition 4.1
87
AM 06.350e-JB Edition 4.1
88
AM 06.350e-JB Edition 4.1
89
AM 06.350e-JB Edition 4.1
F1 - F2
90
AM 06.350e-JB Edition 4.1
91
AM 06.350e-JB Edition 4.1
92
AM 06.350e-JB Edition 4.1
93
AM 06.350e-JB Edition 4.1
94
AM 06.350e-JB Edition 4.1
7 Section 7
Use The PC with the dedicated ADB software is required to modify parameters, in
particular for the adjustment of the lamp fault detection module and for the
circuit selector CSM (see catalogue leaflet A.06.412e).
It can also be used to control the regulator.
Caution! The PC can control the regulator or change parameters only if the front
panel drum selector of the regulator is in OFF position (ref. 4 on Fig 1-
15).
When the regulator is in the REM or LOCAL position, the software can
display parameters and status but it is impossible to modify them.
Hardware The program requires at least a 386 PC with at least 4 Mb of RAM to be able
to run. At least 1 COM port is necessary for communication with the MCR.
No mouse is required.
DOS The PC software is written in PROTECTED (or 386) mode i.e. it uses
protected memory above the standard 1 Mbytes DOS limit.
mode Therefore the DOS extender program DOS4GW.EXE must either be present
in the same directory or it must be found in one of the directories specified in
the path.
Software This description is only valid for the MCR PC software version 2.00
version If the delivered software version differs from the above versions, refer to the
manual delivered with that software.
95
AM 06.350e-JB Edition 4.1
7.1.1 Overview
Introduction In this chapter you will find all the information about the connection of the PC
to the regulator and about the installation of the software on the PC.
Connection One side of the communication cable MCR – PC is connected with the DB 9-
male connector on the front plate of the Control Module and the other side
with the COM1 or COM2 serial port of the PC.
DB9 connector
Communicati The communication cable needs 4 wires and a separate ground, which can
on cable be the cable-screen.
As with all RS232 connection, the maximum length is limited to 15 meters.
The cable layout is listed in the following table.
96
AM 06.350e-JB Edition 4.1
Software Copy the files from the floppy to the hard disk.
installation The program can be installed anywhere on the hard disk and is independent
of a particular directory structure; nevertheless, it is a good practice to create
a new subdirectory for this particular application.
Before running the program, check that the used serial port, which is used on
Communicati
the PC, corresponds with the serial port set in the CONFIG.DAT file.
on port
The CONFIG.DAT file is an ASCII text file, which can be read and modified with
any simple text editor (e.g. EDIT delivered with DOS). Care must be taken to
use an editor who adds no header to the file because this header makes it
illegible to the main program (no Word, no WordPerfect...).
Procedure to follow :
- Unlock the file CONFIG.DAT by the DOS command attrib -r config.dat
- Edit the file CONFIG.DAT by the DOS command edit config.dat
- In the paragraph “Communications Port”, check the parameter
"mcr_com_num".
Change the number if it doesn't correspond with the serial port of the PC.
- Press both the keys “ALT” and “F” on the keyboard of the PC.
A menu appears in the left corner of the screen.
The edition of the CONFIG.DAT file will be left after having pressed on the
key "X" on the keyboard.
Note: When the parameter has been changed, a submenu will appear. The
key “ENTER” has to be pressed to confirm the change.
- Lock the file by the DOS command attrib +r config.dat
97
AM 06.350e-JB Edition 4.1
The other important parameter is “LANG”. It selects the language you want
Language file
to use.
By default all the text strings in the program are in English and embedded in
the code. For any other language, the parameter LANG = "xxx" must be
added in CONFIG.DAT. At the same time a language file with the name
LANG_XXX.DAT must exist in the same directory (see below).
98
AM 06.350e-JB Edition 4.1
For other languages you can create your own file by translating all the
Creation of
strings. Therefore a reference language file LANG_REF.DAT holds all the
language file
strings in English and some useful comments for the translator. Care must be
taken not to exceed the maximum length of each string as is mentioned in
the language file. The language files must have the r-attribute set too (see
above).
99
AM 06.350e-JB Edition 4.1
For a language XXX you can modify this file for corrections. Care must be
Modification
taken not to exceed the maximum length of each string as is mentioned in
of language
the language file. The language files must have the r-attribute set too (see
file XXX
above).
100
AM 06.350e-JB Edition 4.1
7.2.1 Overview
Introduction All the setting parameters of the MCR are read from the MCR EEPROM of
the control module and stored in the database of the PC. Where necessary,
they are displayed.
In this chapter you will find all the information about the running of the
program and its environment.
MCR control The MCR control module is identifiable by its unique serial number, which is
module burned in the EEPROM and which cannot be changed on site.
identification
Serial number The serial number (S/N) of an MCR control module identifies this module. It
is a 6-digit number in the format “yy-xxxx” where yy stands for the year of
production and xxxx is a 4-digit sequential number.
Config file The Config-file is a file that stores the settings of the MCR (except the S/N of
the control module and some MCR dependant parameters).
Config-file The Config-file name is yy-xxxx.CFG, where yy-xxxx is the S/N number of the
name control module.
There is an individual Config-file for each MCR control module.
101
AM 06.350e-JB Edition 4.1
Log file The Log-file is a file that stores the events occurred to the MCR when
connected to a PC.
Log-file name The Log-file name is yy-xxxx.LOG, where yy-xxxx is the S/N number.
There is an individual Log-file for each MCR control module.
Type of entry All log entries consist of the date and time of the event followed by a
message string.
If a new event occurs, a new message is added to the Log-file and replaces
the oldest message in the PC memory.
Data stored • A message each time the PC connects to or disconnects from an MCR;
• A message each time a step command was issued to the MCR from the
PC or from the control tower;
• Any error detected by the MCR (burnt lamps, isolation error, regulation
error, ...) and which generates a message on the PC screen;
• Any communication error between PC and MCR;
• Any erroneous password entry by the user;
• Each change in position of the local selector switch on the MCR control
module front panel;
• A message each time the EFD or LFD is calibrated.
To print the If you exit the program, you can print the log files by a simple DOS “copy”
Log-file command to the printer port.
102
AM 06.350e-JB Edition 4.1
Database The MCR has a double database: one in EEPROM and the other in RAM.
After a power-down, when starting up again, all-important parameters are
fetched from a local EEPROM and copied to RAM. During normal operation
only the copy in RAM is used.
When connected, the PC reads the parameters in RAM and displays them on
the screen. When you modify a parameter, only the copy in the MCR RAM
gets changed.
After changing one or more parameters, you have three alternatives:
• To keep the changes and select the "Save to EEPROM" menu;
This automatically supersedes a binary file on the PC disk with the name
"yy-xxxx.CNF", where yy-xxxx is the serial number of the control module.
• To reject the changes and select the "Restore from EEPROM" menu. This
destroys all the RAM modifications and returns to the last EEPROM
contents;
• To read a set-up from disk. This is useful if several MCRs have to receive
the same set-up. The operator only needs to do the set-up on the first
one, then save the set-up to EEPROM at the same time creating a file on
disk. For the next MCRs, all he has to do is to select the menu "Restore
from file" and then enter the serial number of the previous MCR. The
settings are then restored from file to RAM (except the S/N of course and
the calibration parameters which are MCR-dependent), after this, the
"Save to EEPROM" menu must be selected to burn the data into the
EEPROM.
Each time data is written to the EEPROM, the date and time found on the PC
are copied with it. The next time the PC connects to that MCR, this time-
stamp is read back and put on the display; you know then immediately when
the last update occurred.
103
AM 06.350e-JB Edition 4.1
Start up After a successful connection, the machine enters an infinite loop during
which 2 tasks are performed:
• a regular and automatic data exchange with the MCR (STATUS);
• a check on the keyboard to capture operator commands.
Structure of
The screen is divided in “windows” with a “menu” bar at the top.
the screen
To the left, the status window (1) is always present and shows:
• the output current (as a thermometer-like vertical bargraph and as a value)
• the mains voltage
• the currently active step
• the number of burnt lamps (if LFD option is installed)
• the insulation resistance of the series circuit (if EFD option is installed)
• the status of the circuits (if the MCR operates with a CSM circuit selector)
The right window (top - 2) can be selected by the user via the menu bar (3) on
the top of the screen. 8 different dialogue screens are provided: Help, Log, PC
control, CCR Set-up, EFD, LFD, Power Monitor and Exit.
On the bottom right (4) the “prompt” window gives information such as:
• how to go into another window
• error messages or communication error messages
104
AM 06.350e-JB Edition 4.1
Picture
In the figure below the view of the first screen is shown.
A communication error between the MCR and the CSM circuit selector is
indicated with the blinking red message "MISSING". The normal series
circuit status is not indicated.
105
AM 06.350e-JB Edition 4.1
Modification If you want to modify a parameter, you should select the correct window,
scroll into it with the UP/DOWN arrows until the cursor is on top of the
parameter and then hit <ENTER> to modify the parameter. For menus which
are larger than the window, there is an automatic window scrolling when the
cursor reaches the first (respective last) line.
Parameters are always organised in blocks with a header on top. To scroll
faster, use the PgUp and PgDw keys: they position the window on the
previous (respective next) header.
The cursor positions itself only on the lines that hold a parameter, never on a
header.
Parameters can only be selected and modified in the top right window.
Conditions to Access is only allowed if the drum selector on the MCR control module is in
modify the OFF position.
parameters
106
AM 06.350e-JB Edition 4.1
Passwords The purpose of the passwords is to protect the MCRs against any accidental
erroneous operations.
Depending on its importance, the parameter is protected by a USER- or by
an INSTALLATION-password.
By default the passwords are:
• user password: "ADB user"
• installation password: consult ADB
Note the upper and lower case characters!
There is a hierarchy between passwords: entering a correct installation
password also opens the user-password, but the reverse is not true.
It is almost impossible to provide an absolute tamper-proof barrier against
any intended sabotage. Nevertheless, it is our aim that you do not know the
installation password. This avoids the possibility that you could erroneously
reconfigure certain parameters with an eventual fatal result for the lamps or
the MCR.
It is then the responsibility of the installation engineer to set-up the MCR’s,
then to modify the INSTALLATION-password and to note it for future
interventions.
It is possible to change these passwords via the menu but of course only
after the correct corresponding password has been entered.
How long does a password allow access to the parameters? You can choose
between 3 alternatives via a menu:
• Re-entry of the password is required prior to each operation; this is
tedious but very safe.
• The password remains "open" during 10 minutes after the entry of the
correct password. During that 10-min interval the operator can continue
changing parameters without having to enter the password each time.
• The password remains open during 24 hours. This is useful when a
complete set-up of the MCR is necessary and the operator remains within
sight of the PC.
In any case, you can inhibit access to the MCR by an immediate recall of the
password via menu. If e.g. the password was opened for a 24-hour period,
but you have to leave the MCR unsupervised for an extended period, access
can be recalled. At the next attempt to modify a parameter, the password
must then be re-entered.
107
AM 06.350e-JB Edition 4.1
Type of Depending on the type of parameter which you want to modify, the program
parameters can react in different ways:
• Some parameters are READ-ONLY (e.g. the mains frequency) and cannot
be modified. When selected, they generate an overlay, which tells the
user that his demand cannot be complied with.
• Other parameters can only accept certain predefined values (E.g. the
output current can only be 4.15, 6.6, 8.33, 9.2, 12 or 20 A and nothing in-
between).
To select another value, just hit the <SPACE> bar until the correct value
appears in the overlay and then hit <ENTER> to validate the new value.
This erases the overlay, puts the new value in the correct window and
transmits the new value to the MCR.
This message is interleaved with the normal STATUS messages.
If you do not want to change the value, just hit <ESC> instead of <ENTER>;
the overlay disappears, but the value remains unchanged and there is no
message to the MCR.
For example, all "flag" parameters are of this type. They accept 2 values e.g.
on/off or enabled/disabled.
• Other parameters accept any value. You must enter the new value via the
keyboard. Hitting <ENTER> performs a value check and if it is outside
one of the predefined bounds, it is rejected and you receive an error
message in the bottom-right window. If it is accepted, the window is
updated and a message is sent to the MCR.
To exit an overlay without changing anything, just hit <ESC>.
Invalid If the program requires the entry of a value, the input routines will reject any
characters invalid characters and lock all keyboard entries until a <BACKSPACE> is
entered which clears the erroneous character.
Example: a parameter expects a number, but you enter an alphabetic
character by mistake.
Instead of seeing the normal underscore indicating the cursor position, you
will see a white square. The only way-out is to hit a <BACKSPACE> to
remove the last character. The square then disappears and the normal
cursor appears again. You can then proceed to enter the correct value.
In this way, the user is guaranteed that when he hits the final <RETURN> at
the end of his input, the string passed for analysis to the program contains
only valid characters.
108
AM 06.350e-JB Edition 4.1
To leave the To leave the program, go to the EXIT menu and enter the character
program displayed in the window (For English this is 'y' or 'Y');
To avoid losing data, you are warned when you try to leave the program and
some parameters were changed but not saved to EEPROM. You can then
force an exit and accept the consequences if there is a power down on the
MCR, or remain in the program and do a "save to EEPROM".
Trying to leave the program with Ctrl-C generates an error, but does not
interrupt the program. <Alt-Ctrl-Del> however is active and reboots the
machine.
109
AM 06.350e-JB Edition 4.1
7.4.1 Overview
Introduction In this chapter you will find all the information about the parameters and the
menus to use and modify them.
110
AM 06.350e-JB Edition 4.1
7.4.2 F1 Help
Description This menu displays a short help describing the different menus.
Description This menu display the last 50 events stored in the log-file. All the events are
numbered with the most recent on top.
2 operations are allowed: scrolling and deleting. The delete function only
removes the 50 lines in the program log.
The true log file on disk remains untouched, but that too can be deleted
using the normal DOS delete function.
111
AM 06.350e-JB Edition 4.1
7.4.4 F3 PC Control
Introduction The purpose of this menu is to allow you to take over control of the MCR with
the PC.
PC Control
1. If the number of brightness steps is set to 255 (stepless mode), the range
is 69 to 255; If the parameter “Separate ON/ OFF” is set to “YES”, the
value “0” is also possible.
2. This simulates the shutdown i.e. the action, which switches off the
thyristors without opening the power contactor. Under normal operation
the shut-down is used in conjunction with a circuit selector.
When the MCR operates with a circuit selector, the shutdown can only be
activated by the circuit selector.
3. Only possible if MCR operates with a CSM circuit selector.
The indication “Inhibit” means that the circuit is disabled on the logic
board of the CSM (dip-switch SW1).
Save/ Restore
112
AM 06.350e-JB Edition 4.1
Software version
113
AM 06.350e-JB Edition 4.1
MCR identification
Output current
114
AM 06.350e-JB Edition 4.1
Hardware
115
AM 06.350e-JB Edition 4.1
Submenu J-Bus
(1) In the stopbar mode, as soon as power is applied, the MCR switches to
the default current. When the bus becomes operational, the MCR follows the
bus. If the bus breaks down, the MCR maintains the current output until the
bus time-out expires and then, the MCR goes to the default current even if
the last command from the tower was to switch off the MCR.
In normal mode, the MCR stays OFF at power-up until the bus comes on-
line; it then follows the bus. If the bus breaks down, the MCR maintains the
current output until the bus time-out expires. Then, if the last command
received from the tower was “OFF”, the MCR remains OFF; but, if a current
was selected, the MCR reacts as defined by the bus failure mode (see
there).
(2) If set to NO, the selector on the front panel of the control module is
always operational and allows any local operator to take over the control of
the MCR at any moment.
If set to YES, the bus has the highest priority and the selector position is
ignored. Only if the bus is defective, can you take over the control by pushing
the reset button and turning the selector to the desired position.
116
AM 06.350e-JB Edition 4.1
Submenu J-Bus
(3) There are 2 softwares available for the JBUS interface:
• Single Bus: the bus arbitration parameter will only accept the values
“Disabled” and “A only”; if set to “Disabled”, all requests (read and write)
received from the bus are ignored. To avoid a time-out or a break-down in
the bus master, all bus messages are acknowledge with the “Bus
Disabled” code.
• Dual Bus: All 5 values are accepted.
If set to “Disabled”, “A only” or “B only”, all requests (read and write) from
the bus which is disabled are ignored and a “Bus Disabled”
acknowledgment is returned. The read and write request from the bus
which is enabled are accepted and executed.
If it is set to “A then B”, read commands from both busses will be accepted
and the correct data returned. If the bus A sends a write request, it will be
accepted and executed. All write requests from the bus B will be ignored
and acknowledged with the “access rejected” code. If there is a
break-down on the bus A, after the “bus time-out”, control transfers to the
bus B which can then transmit a write request to the MCR.
If this parameter is set to “B then A”, the above description is reversed.
(4) If the MCR is in stopbar mode, this parameter is not operational. In
normal mode, if "default" is chosen, the user can enter a default output
current.
If “actual” is selected, the output current of the MCR remains unchanged.
(5) This is the default current to which the MCR switches after the bus time-
out to expires and if the MCR is in stopbar mode. In normal mode, this value
is used only if the bus failure mode is set to “default”. It is the responsibility of
the user to give this parameter a meaningful value.
(6) If the MCR switches off because of an error, the control tower can reset
the MCR if this flag is set to YES. If it is set to NO, there must be a local
operator to push the reset button on the control module front panel.
117
AM 06.350e-JB Edition 4.1
Submenu J-Bus
(1) This number is read from the DIP-switches on the JBUS piggy-back and
cannot be modified by the program. If the slave number is set to "0" (invalid
value), this will be displayed in flashing to draw your attention.
(2) If there is no parity, there are 2 stop bits.
If the parity is set to ODD or EVEN, there is only a single stop bit
(3) These parameters are only visible if the “dual bus” software is installed.
Submenu J-Bus
BUS presets
The output current of the MCR can be controlled by selecting a specific step
(max 8 steps) either locally or in remote. But if there is a central control desk,
the MCRs are almost never controlled individually but in group.
With the presets it is possible to define for each MCR a specific intensity for
different meteorological conditions e.g. "preset1 = sunshine", "preset2 = day
+ rain", "preset3 = day + mist", "preset4 = night",...
The values need not be one of the pre-programmed steps, but are true
currents and can have any value between the minimum and maximum
allowed current or OFF. Each step is individually programmed for each MCR
and need not have the same value for all the MCRs in a group.
It is then possible to set an MCR individually to a certain preset or to send a
broadcast message from the BUS-master to all MCRs to switch them all
together to the same preset.
118
AM 06.350e-JB Edition 4.1
Submenu J-Bus: time counters Only if MCR operates with a circuit selector CSM.
119
AM 06.350e-JB Edition 4.1
120
AM 06.350e-JB Edition 4.1
(1) Controls the level at which an overcurrent alarm will be given if the error
persists for the time defined by delay 1.
(2) This level must be higher than the preceding one but with a shorter delay.
(3) If an overload occurs, the MCR cannot guarantee the level of the output
current. It will in any case generate a regulation error; moreover with this flag
the MCR can be forced to switch-off under those conditions.
(4) If the positive and negative half-waves of the output current do not have
the same value during the time specified by the delay parameter, an error is
generated. An asymmetry error is a sign for the existence of a DC
component on the output current, which is harmful to the power transformer
of the MCR.
(5) If the MCR cannot maintain the programmed output current, an alarm
appears after this delay
121
AM 06.350e-JB Edition 4.1
Mode of operation
Step settling Custom 0/ 0.5/ 1 / When you switch from one step 0
speed 1.5/ 2 / 2.5 to another, the MCR can either
sec react instantaneously or move to
the new step in the time defined
here (for a current variation from
0 to the maximum value).
Back indication Custom YES / NO When this flag is set, the control YES
in local mode tower receives all back indication
signals. If this parameter is set to
NO there will be no back
indication signals to the tower
when the MCR operates in Local
control.
ON-OFF-ON Custom 0/ 0.2/ 0.4/ When the MCR is rapidly 0
delay 0.6/ 0.8/ switched OFF and ON again, this
1 sec parameter defines the minimum
delay during which the MCR will
remain OFF regardless of the
switching speed.
Local display
122
AM 06.350e-JB Edition 4.1
123
AM 06.350e-JB Edition 4.1
Calibration First, read carefully the WARNINGS in the paragraph “Calibration” (par
7.5.4). Calibration of the output current directly influences the output current
at Bmax.
The other calibrations act on the values displayed in the F8 Power Monitor
menu and the back indication values with the multiplexed remote control.
Change passwords
Error simulation
Only possible if the MCR is operational and delivers current into the
series circuit.
124
AM 06.350e-JB Edition 4.1
Control commands
Alarms If either of the next two parameters is exceeded, a message on the CRT is
generated and also logged on disk
125
AM 06.350e-JB Edition 4.1
Setup
Calibration
126
AM 06.350e-JB Edition 4.1
Error simulation
127
AM 06.350e-JB Edition 4.1
Status
Control commands
Alarms For both “Number of lamps” and “VA-drop”, 2 levels can be defined. The
second level must be larger than the first one.
The delay is a time-out which retards the generation of an alarm to filter-out
spurious errors and which allows the series circuit to warm-up.
128
AM 06.350e-JB Edition 4.1
Hardware
129
AM 06.350e-JB Edition 4.1
Error simulation
If one of these errors is simulated, the MCR responds with the corresponding
back-indication. The Led Lamp fault on the front panel will light up.
130
AM 06.350e-JB Edition 4.1
Introduction None of the parameters displayed in this window are modifiable. All are
updated in real time from data read by the PC in the MCR database. If the
LFD module is not present, the output voltage and power measurements and
their derived parameters are not available and will not be shown.
Primary parameters
Power parameters
To exit the For the English language, enter 'y' to exit. For other languages it is always
program the first letter of the equivalent "YES" string. If you changed some
parameters and did not save the data to EEPROM, a supplementary warning
is generated. You can then select the "PC Control" menu, do a "Save to
EEPROM" and then come back to the EXIT menu and leave the program.
It is also possible to disregard this warning and exit without saving. You must
then be aware that the modified parameters exist only in the MCR RAM and
that they will be overwritten by the EEPROM data at the next power-down,
power-up sequence.
131
AM 06.350e-JB Edition 4.1
7.5 Calibration
7.5.1 Overview
Calibration A calibration requires instruments, which have a high precision class (0.5%),
instruments and which have been calibrated recently. Since most of the measured values
are phase-controlled sine waves, all instruments must be of the TRUE-RMS
type and certainly not of the moving coil and rectifier type.
The use of amperemeter clamps, although easy to use, is not advisable for
calibration for the following reasons:
• they are sensitive to magnetic fields in the environment. Due to the
proximity of the MCR, outside influence cannot be avoided;
• measurements are dependent on the position of the cable in the clamp;
• because clamps are mechanical devices, the closure of the magnetic
circuit can change for each measurement;
• clamps must be calibrated before use because of remanent magnetism;
• their precision is generally less than that of a good Ammeter.
We advise the use of a measuring transformer. Although it requires the
circuit to be opened, it guarantees a consistently high quality measurement.
Warning You must be aware that the following operations are potentially dangerous
and must be executed with the utmost care for the safety of the personnel.
132
AM 06.350e-JB Edition 4.1
Preliminary Before starting an LFD calibration, check the hardware settings, the series
circuit and the output power transformer tap setting.
Warming-up In order to perform exact measurements of the output voltage, the series
loop must warm up to a stable temperature. This temperature depends on
the ambient temperature.
You can verify the warming-up by monitoring the output voltage on the MCR
or the PC display. If the loop is cold, its resistance is low and the output
voltage for a given current is low. When the loop warms-up, its resistance will
increase and hence the output voltage will rise (for the same current). After a
time, the output voltage will level out when the final temperature is reached.
You must enter the required warm-up time as a parameter in the LFD menu.
"reference" The reference calibration is a series of measurements while all lamps are
calibration functional.
Erase the previous LFD calibration before starting the calibration!
Before doing this calibration, you must visually check that all lamps are
indeed working, that the correct output tap is wired and that the correct
selection is made in the LFD-menu for the primary voltage of the voltage
measuring transformer and the total loop length.
When you select the reference calibration, a secondary menu, in which you
can see the status of the measurements, appears.
By pushing button “D” on the keyboard you can toggle on or off the VDLV-
factor which, in case of a correct reference calibration, should stay lower
than 5, 10 or 15 (depending on the precision selected by the LFD during the
calibration).
During the warm-up phase, the output current is forced to the nominal output
current and the warm-up time is down-counted in this display.
During the measurements, the output current slowly decreases while the
measurements are made. At the end of this calibration you are prompted to
save the results in EEPROM. Answering “NO” gives the same result as
pushing the <ESC> key. The measurements will not be saved.
133
AM 06.350e-JB Edition 4.1
"lamps
This calibration is only possible after execution and saving of the reference
removed" calibration.
calibration
For the "lamps removed" calibration, you must remove a known number of
lamps and start the calibration. You are then prompted to enter this number
into the system. The MCR then measures again a series of parameters.
During the calibration, by pushing button “D” on the keyboard, you can toggle
on or off the VDLV-factor which, in case of a correct “lamps removed”
calibration should stay 128, 64, 32 or 16 (depending on the reactive power,
due to the unloaded transformers, in regards to the total loop power during
this calibration).
At the end you are prompted to save the results to EEPROM.
Answering “NO” gives the same result as pushing <ESC> key. The
measurements will not be saved.
When at a later date one or more lamps blow, the system can compute the
exact number of defective lamps by interpolating between both sets of
values.
Minimum Nr
To obtain an accurate calibration measurements, there are a minimum
of lamps to number of lamps, which must be removed depending on the system
remove configuration. In most cases 4 lamps will be sufficiently to perform the
calibration, otherwise some more lamps have to be removed.
(If the detected VDLV-factor does not reach the minimum value of 16, it will
be necessary to increase the number of unloaded transformers or to
increase the loop length (Menu F7) to perform the calibration.
134
AM 06.350e-JB Edition 4.1
EFD mode EFD calibration is only allowed if the module is in “continuous” mode.
EFD To calibrate the EFD module completely, activate in the F6 menu the
calibration calibration parameter “Full calibration”.
Proceed as follow :
- open the fused input switch of the MCR.
- earth the series circuit.
- disconnect the EFD module from the series circuit by disconnecting the
HV-wire between PCB1381 and PCB1384.
- close the fused input switch.
- follow the instructions written on the screen
It is a fully automatic operation and terminates with a message if an error
occurs
- save this parameterisation in the EEprom.
- open the fused input switch of the MCR
- reconnect the EFD to the series circuit. (HV-wire between PCB1381 and
PCB1384).
- close the fused input switch
135
AM 06.350e-JB Edition 4.1
Introduction
When the MCR leaves the factory, it is fully calibrated. Moreover there are no
potentiometers, which can change their value because of ageing.
Still, if on site some components have to be exchanged, it may become
necessary to recalibrate the MCR.
Parameters to
There are 6 parameters to be calibrated:
be calibrated
• Output voltage,
• Output current,
• Output power,
• Input voltage,
• Input current,
• Input power.
MCR load All of the above parameters except the mains voltage can only be calibrated
if the MCR is sufficiently loaded. Indeed it is worse than useless to try and
calibrate e.g. the output voltage with only a small load connected.
Warning When you select a calibration parameter a Warning message appears onto
message the display to caution you. You can then abort the operation by hitting ESC or
continue by hitting any other key.
MCR Except for the output current, the normal sequence of events is that the PC
calibration forces the MCR to the maximum step, waits a bit, then prompts you to read
the value displayed on whatever instrument connected and then type this
value on the PC keyboard.
When the <ENTER> key is hit, all necessary correction factors are computed
and transmitted to the MCR. The MCR then returns to the step that was
previously selected.
136
AM 06.350e-JB Edition 4.1
8 Section 8
J-Bus - Software
8.1 Introduction
JBUS The JBUS is a subset of the MODBUS which was one of the first industrial
protocol fieldbusses ever developed.
Master - Slave In the MODBUS/JBUS configuration, only one device can initiate
transactions. The other devices can only respond by giving the requested
data or by taking the requested action.
The device that initiates the communication is called “Master” and the others
are called “Slave”.
The master distinguishes between slaves by using a number, which must be
unique in the range 1 to 255. In the case of a broadcast message, a
message addressed to all the slaves, the slave number is 0.
Hardware Uses standard RS485 drivers and receivers in either 2-wire or 4-wire mode.
Message From the viewpoint of the master, the slaves can be considered as RAM-at-
structure a-distance.
This RAM is organized in words. It is the task of the developer of the slave to
define this RAM and to declare the significance and the use of the contents.
For more information, refer to “MODICON MODBUS reference guide”.
Transmission This application uses the RTU transmission mode in which each 8-bit byte in
mode a message contains two 4-bit hexadecimal characters. The message is
transmitted in a continuous stream.
The allowed baudrates are: 150, 300, 600, 1200, 2400, 4800, 9600, 19200
and 38400 baud (ex factory, the MCR is set for 38400 baud).
If there is no parity, there are 2 stop bits and for even or odd parity, there is
only 1 stop bit. (ex factory, the MCR is set with even parity).
137
AM 06.350e-JB Edition 4.1
Foreword
Although the general structure of the data base will remain unchanged,
details such as type, number and position of individual parameters are
subject to modifications. The programmer of the MASTER software must
then construct his soft in such a way that it remains flexible and can easily
be adapted to subsequent data base changes. He must also pay attention to
the execution time of the message generation, the acknowledgment analysis
and the computation of the slave time-out.
138
AM 06.350e-JB Edition 4.1
8.2.1 Overview
Introduction In this chapter you will find information about the JBUS protocol and an
introduction to its application to the remote control of the MCR.
Topic
Structure of a message
Functions
Exception Message
139
AM 06.350e-JB Edition 4.1
Introduction To be understood by the slave (here a MCR), the message sent by the
transmitting device has to follow a well defined structure.
Structure The general structure begins with a start, follows with the address, the
requested function, the data, a check field and stops with an end.
Start/ End The message starts with a silent interval and, following the last character
transmitted, another silent interval marks the end of the message.
Address The address field identifies the slave, which should response to the message
from the master. It contains 8 bits and must be in the range of 1 to 255
decimal.
When the slave sends its response, it places its own address in the address
field of the response to tell the master which slave is responding.
The address “0” is used to transmit messages simultaneously to all slaves
and, in this case, no response will be sent.
Function The function field tells the addressed slave what action to perform.
When a slave receives a message without any error and if the message is
destined for that slave, it will execute the command and send back an
acknowledgment to the master (except if it is a broadcast message - slave 0
- or if the slave is in listen-only mode).
Data The data field contains additional information, which the slave must use to
take the action requested by the function code. If no errors occur, the data
field of the response contains the data requested.
Error check The error checking field contains a 16-bit value implemented as two 8-bit
field bytes. The error check value is a result of a Cyclical Redundancy Check
(CRC) calculation performed on the message content.
The transmitting device calculates the CRC value and appends it to the
message transmitted. During receipt of the message, the slave computes the
CRC over the complete message including the CRC. The result must be
zero.
140
AM 06.350e-JB Edition 4.1
8.2.3 Functions
Function The function field tells the addressed slave what action to perform.
Not all functions allowed by the MODBUS specifications are implemented; for
the MCR communication, the following will be used:
• Read N words: 03hex or 04hex
• Write N words: 10hex
• Write 1 word: 06hex
• Read status word: 07hex
• Diagnostics: 08hex (see below).
Nevertheless, if an unrecognized function is received by the slave, this may
not perturb its normal operation and the slave must return an exception
response (see page 142).
Diagnostics The function 08hex provides a series of tests for checking the
communication system between the master and the slave or for checking
various internal error conditions within the slave.
Each slave holds a certain number of diagnostic counters and registers. With
the function 08hex it is possible to read or clear these registers.
All the counters are 16 bit (1 word) wide and they are reset at power-up.
They can overflow from FFFF to 0000. This overflow is not signaled and
therefore, if the master wants to use the diagnostic counters to provide a
statistical analysis of the quality of the communication, the counters must be
read and cleared before any overrun has occurred.
If the bus is in 2-wire mode, all slaves also receive the messages returned by
the other slaves. This means that the message counter increments twice for
each dialogue.
141
AM 06.350e-JB Edition 4.1
Response When the master sends a message to a slave, it expects a normal response
Message (except for a broadcast message). Three different events can then occur:
1. if there is no communication error and the slave can handle the message
normally, it returns a normal response
2. If there is a communication or a CRC error, the message is invalidated
and will not be analyzed; moreover, the slave cannot even be certain that
the message was destined for him. Therefore, there is no
acknowledgment. This must lead to a time-out in the master who can then
either retry the same dialogue or proceed with another slave.
3. If the slave receives a message without any errors at all, but is not able to
handle the function (e.g. unknown parameter address), then an exception
message is returned. This message consists of 5 bytes:
• the slave number (1 byte)
• the function word received from the master + 80hex (1 byte)
• an exception code (1 byte)
• the standard CRC (2 bytes).
142
AM 06.350e-JB Edition 4.1
8.3.1 Overview
Introduction This chapter presents a proposal about the use of the JBUS in the MCR
environment. It forms an entity with the structure of the database in order to
guarantee a high throughput in both directions between master and slaves.
Topic
The piggyback board
Database
Master Software (proposal)
143
AM 06.350e-JB Edition 4.1
Introduction The BUS interface (hardware and software) resides on a piggyback board,
which is plugged onto the MCR control module and communicates with it
using a private serial communication.
Slave number The slave number (1 to 255) must be set by means of 8 dip-switches on the
piggyback board.
The sum of the Hex-value of all dip-switches in off position corresponds with
the value of the slave number.
For the dip-switches and their corresponding Hex-values see para 1.6.3.
Example : Slave number 5 is given with dip-switch 1 and 3 in “OFF” position
and the dip-switches 2, 4, 5, 6, 7 and 8 in “ON” position.
When a new slave number is set, the power supply has to be switched
OFF. Only after having switched “ON” the power supply again the new
slave number is active!
Piggyback At start up the piggyback CPU connects to the MCR and downloads a
data base complete copy from the MCR database.
The local copy is kept up-to-date by continuous refresh exchanges with the
MCR. This is especially true for the MCR status parameters which reflect the
actual state of the MCR (output current, mains voltage,...).
144
AM 06.350e-JB Edition 4.1
Exception If the db_valid bit in the mcr_status parameter is cleared, any read or write
code 41hex command received from the bus master and attempting to access the local
data base returns the exception code 41hex "piggyback data base invalid".
If this bit is set, any read command received from the BUS master returns
data from the local data base and any write commands are acknowledged
and passed on to the MCR except for those parameters which are not
present in the MCR (e.g. diagnostic counters) or do not accept write
commands (e.g. serial number). These are skipped.
Flags and All piggyback <--> MCR communication errors are counted.
counters The bus master has free access to these parameters and can thus analyze
statistically the quality of the internal communication. All the counters are
cleared at power up of the MCR but can also be cleared later on by the bus
master.
145
AM 06.350e-JB Edition 4.1
8.3.3 Database
Introduction The database as seen from the JBUS is derived from the database
exchanged with the PC.
Added to this are the JBUS diagnostic parameters and the parameters used
by the dialogue between the piggyback board holding the JBUS interface
and the MCR control module.
Database The database is a single word array. In this array the parameters are
structure grouped in blocks by logical function e.g. BUS diagnostics, status
parameters,...
The parameters to exchange via the BUS are most of the time bytes and not
words. Where 2 byte parameters can be logically joined, they were put in the
same word. If that was not possible, an empty filler byte is used. At a later
date it is possible that the filler byte will be replaced by a useful parameter.
Dummy data To allow for future expansion and yet avoid having to rewrite the master
application software, dummy data are reserved in the data base and each
block always begins at an offset which is a multiple of 16 words.
Attribute code In the piggyback all parameters have an attribute code which defines if it is a
rd_only, wr_only or rd/ wr parameter. Attempts by the BUS to write to a
read-only parameter does not generate an exception: the data is simply
ignored. When reading a parameter which is wr_only a 0 is returned
irrespective of the true value of the parameter. Again, there is no exception.
Writing to a dummy parameter is ignored; reading from it always returns 0.
146
AM 06.350e-JB Edition 4.1
Access to the Although the parameters are grouped in logical blocks, it is not required from
parameters the master software to access parameters block-by-block. The block system
is a logical structure to enable the master to access all data relevant to a
specific module in one operation, but it remains possible to access data
which exceeds block boundaries and read e.g. 2 blocks in one access
(including of course the intervening "dummy" parameters).
The only limits on the number of parameters accessed in one exchange are
those imposed by the MODBUS protocol:
• Write N words: the data length expressed in bytes is passed to the
slave in a single byte. Therefore the data length is limited to 255 bytes or
127 words.
• Read N words: the data length in bytes in the acknowledge message
from the slave is also passed in a single byte. The same length limit
applies here: 255 bytes or 127 words.
For the moment the size of this array is 160h or 352 words.
147
AM 06.350e-JB Edition 4.1
Scan loop At start up, the master reads in a configuration file the list of the slave
numbers present on the BUS.
The master executes then a "read status word" on each of the slaves in
sequence. For each slave the db_valid bit is checked in the returned value.
If this bit is set, the complete database of that slave is read either block-by-
block or in groups of any appropriate length.
Once the master has acquired all the slave parameters, an infinite scan loop
is entered during which the STATUS block of each MCR slave is read in
sequence.
This data is used to display or track the true output current and any other
parameter(s) the customer may want to check regularly.
Configuration The master must have a list of the slave numbers present on the bus. By
File preference this list is not embedded in the code, but is read at start up from a
configuration file. The same configuration file can be used to define the bus
parameters: baudrate, parity and time-out in case of communication
breakdown.
If the master does not have a list, he can attempt to read all possible 255
slaves in sequence and note those who acknowledge. This procedure does
not allow the master to detect missing slaves who have a (temporary)
breakdown or who are not powered-up.
Scan loop The scan loop can be interrupted by events and commands.
interruption
Events If the MCR detects an event such as e.g. burnt-out lamps, grounding of the
high voltage loop, etc., one of the error bits in the err_100 to err_600
parameters will be set. At the same time, the mcr_event bit is set in the
mcr_status parameter. The BUS master receives the mcr_status
parameter in each status block and the setting of this bit is a signal for the
master software to read the error block immediately and to analyze its
content.
After the master has read the error codes, these are not cleared in the
piggyback data base nor is the mcr_event bit. At each subsequent pass the
master will have to read the error codes again and compare them to the
preceding values in order to find any new errors.
148
AM 06.350e-JB Edition 4.1
Commands When you issue a command such as MCR ON/OFF, the selection of an MCR
step or the read of a parameter, this must generate a special message which
must pass with the highest priority. The sequence is:
• the master waits for the acknowledgment to the current message;
• it stops the STATUS READ sequence;
• it sends the special command message to the slave;
• it waits for the acknowledgment;
• the normal scan is resumed.
Should the STATUS READ sequence not be interrupted, this would have
consequences on the reaction time of the MCR to user commands.
Slave If a slave breaks down, it will not respond to any of the master messages. If
breakdown this happens for a number of consecutive messages defined in the master
software, the master should signal to the operator a slave breakdown.
The master should continue to scan the slave in the hope that it will come
back on-line. When that happens, the master must read the complete data
base again.
Caution Reading the complete data base can take several seconds (depending on
the baudrate). This could interfere with the messages to other slaves. It is
proposed to read only part of the data base once every STATUS scan cycle.
Failing to do this could generate a time-out error on a slave with a sudden
jump to the default output current as a consequence.
149
AM 06.350e-JB Edition 4.1
8.4.1 Overview
Introduction According to the use which is made of an MCR, the latter has to react in a
well defined way at start-up or if there is a loss of control following a BUS
breakdown. The control arbitration defines how an MCR reacts in each case.
Safety In the following pages, you will see that there are several ways to activate the
Precautions MCR (locally or remote). You will learn that it is possible to disable the
control busses, but also that the local control can be overridden by the bus.
Considering the complexity of the controls:
If you want to access the interior of the cabinet, access the outside
wiring or work on the series circuit, you must remove the main fuses
from the MCR.
Topic
Control sources and parameters
Dual Bus Control Arbitration
Control arbitration in Stopbar mode
Control arbitration in Normal mode
150
AM 06.350e-JB Edition 4.1
Setup Control The setup of the MCR can only be controlled by:
• the PC (for all parameters);
• BUS A or B (for non-critical parameters).
Bus Arbiter The operation mode of the Bus Arbiter is completely different for Single Bus
and for Dual Bus modes.
The Bus Arbiter is a data base parameter which can be read by both bus
masters. They cannot modify it directly but only via a write to the Bus
Control parameter.
151
AM 06.350e-JB Edition 4.1
Bus Arbiter The Bus Arbiter parameter can only have the values "Disabled" or "A Only".
Single Bus If set to "A only", all requests will be accepted, provided the local selector is
in the Remote position or the local_kill parameter is set.
If set to "disabled", all requests (read and write) issued by the bus master
will be rejected, but still be acknowledged with a "Bus disabled" exception
code (43hex). In this way, no time-out will occur in the master.
In the hardware it is always the BUS A connector which is used.
Bus Arbiter
The Bus Arbiter parameter can have the values "Disabled", "A only", "B only",
Dual Bus "A then B" and "B then A".
Value Comment
Disabled operates in the same way as described above except that all
messages on both busses will be ignored but are
acknowledged by the Bus Disabled exception code (43 hex).
“A only” or allow all accesses on the selected bus if the conditions
“B only” described above are met (selector on Remote or local_kill
on). The bus which is disabled (i.e. B if "A only" and A if "B
only") will receive the Bus Disabled acknowledgement.
“A then B” or In "A then B" only BUS A has write access, provided the
“B then A” selector is in the Remote position or the local_kill parameter
is set.
BUS A is called the Primary Bus and BUS B the Redundant
Bus. In "B then A", the roles are reversed: B is the Primary
Bus and A the Redundant Bus.
If the redundant bus attempts to issue a write command, it
will receive an Access denied exception code (44 hex) and
the command will be ignored.
Both busses have full Read access rights at all times.
All write requests from a master which does not have the rights to do so are
ignored and are acknowledged with an Access Denied exception code,
except for a single word write to the bus control parameter which is allowed
at all times and under all conditions.
152
AM 06.350e-JB Edition 4.1
If part of the The bus arbiter is a software device which resides in each MCR. The access
bus breaks rights are then determined for each MCR separately. The consequence is
down that if only part of the primary bus breaks down, due to e.g. a bad contact,
some of the MCRs will still be controlled by the primary bus, the others by the
redundant bus.
To solve this ambiguous situation, the redundant bus can take over the
complete bus by sending the value AA55 hex to the bus control parameter.
This message can be addressed to each slave in sequence, but can also be
sent as a broadcast message to all slaves.
Data If the primary bus changes a parameter, the copy of the data base in the
Synchronisati redundant bus master has become obsolete. To force an update, the
on redundant master will receive an mcr_status parameter with the db_valid
bit cleared. It should wait until the db_valid bit is set again and then down
load the complete data base.
Bf_mode Defines the operational mode (stopbar or normal) which determines how
parameter the MCR starts at power-up and reacts when the bus breaks down. This
parameter can only be modified during setup by the PC.
The fundamental difference between an MCR in stopbar and in normal
mode is determined by our fail-safe philosophy.
A stopbar is essentially a traffic light denying access to a part of the airfield
(e.g. the runway). As such, its normal state is switched ON and it requires an
express command to be switched OFF and allow an airplane to proceed.
Therefore, in case of BUS breakdown, the MCR will immediately switch ON
to the default output current pre-programmed by the customer. It is the
responsibility of the user to set this default to a meaningful value (e.g. 100%).
A MCR used in normal mode is e.g. for an approach. In this case, it must be
avoided to switch it ON by mistake as this might cause planes to select the
wrong runway to land on. For this reason, a MCR in normal mode which
received as last valid command to switch OFF will remain OFF if the BUS
breakdowns. IF, on the other hand, the last command was the selection of a
non-zero output current, it will either keep this output current or switch to the
default current, depending on the bf_brkdown parameter (see below).
153
AM 06.350e-JB Edition 4.1
local_kill ON or OFF; it controls the access by the local selector to the MCR.
parameter If it is set to OFF, the MCR will react immediately when the position of the
selector is changed. I.e. local personnel in front of the MCR can always take
over the control.
If it is set to ON, the BUS remains the master of the MCR and the position of
the selector is ignored. Access by local personnel is denied. Only if the BUS
is in time-out can the local operator push the reset button and turn the
selector to regain control.
Note that if the bus is operational, pushing the reset button has no effect.
In case of two busses, if both are enabled (“A then B” or “B then A” mode), both must be down
before this take over is possible. If only one is enabled (“A only” or “B only”), the take over is
possible if the bus which was enabled is down.
Access to • With an operational BUS, the BUS master can clear the local_kill
“local_kill” by parameter. The local operator can then turn the selector and take over
the BUS local control without pushing the RESET button first. This allows
maintenance on an MCR while the other MCR’s remain operational and
under control of the BUS.
• The BUS master retains the capability to read the data base, but all write
commands are rejected and an exception code 42hex is returned. To
regain control, the local selector must be put back in the remote position
and then the BUS master can set the local_kill parameter back to 1.
Alternatively, the PC can set the "BUS overrides selector" flag to
relinquish mastership back to the BUS.
• If the BUS master issues a command to save the MCR parameters to
EEPROM, the local_kill parameter is not saved, but remains at the value
it received during setup. The consequence is that if there is a power-out
on the MCR, this parameter will be restored at the next power-up to the
value as defined during the setup.
154
AM 06.350e-JB Edition 4.1
Additional • Bf_brkdown defines how the MCR will react in case of BUS time-out
parameters (only used in normal mode).
If set to present, the output current present before the failure is
conserved.
If set to default, it switches to the default output current defined by
bf_def.
• Bf_def defines the default output current to which the MCR switches when
the BUS breakdowns.
• Bf_time defines the slave time-out.
If there are two busses, there is a time-out for each one (bf_time_a and
bf_time_b) and they can be set to different values.
Normally, the piggyback board expects to receive from the master error-
free requests addressed to itself at regular intervals. The normal interval
time before the MCR knows that the BUS is down is a function of the
selected baudrate, the number of slaves, the length of the exchanged
messages and the slave and master reaction times.
The programmer of the master software should do a worst case estimate
on the total number of bytes to exchange taking into account the
interleaving of the STATUS messages with occasional command and data
base read messages and arrive at a result which is expressed in BYTES.
Knowing the baudrate, the minimum time can be computed. To this must
be added the master and slave reaction time.
This is the minimum time-out, but if we allow 3 repeats of the same
message, which we should consider as the worst case error, the interval
should also be multiplied by 3.
This time should be programmed in the MCR bus time-out parameter by
the PC during the initial setup. The value can be read by the bus as bf-
time.
Each time the slave receives an error free message, a countdown timer is
preset with the bf_time value. If the timer becomes 0, the piggyback
sends a BUS-down flag to the MCR. The way the MCR reacts to this
depends on the bf_mode parameter (see page 158 and page 159).
155
AM 06.350e-JB Edition 4.1
Breakdown 1. If the primary bus breaks down, it will lose its access rights which will pass
Procedure to the redundant bus. This allows the redundant bus to take the control of
the MCR instead of the primary bus.
2. If the redundant bus breaks-down also, the MCR output is determined by
other parameters: bf_mode, bf_brkdwn and bf_def (see there).
3. If the redundant bus is re-established, control passes back to that bus
immediately.
4. If the primary bus comes back on line, the access rights remain with the
redundant bus. This avoids a toggle effect which could occur if there is a
bad connection in the primary bus wiring or if there is some cyclic
disturbance from a foreign origin on the bus.
5. The primary bus can take back control by writing the value AA55 hex to
the Bus Control parameter in the "command parameters" block.
Forcing If the primary bus is operational and has full access rights, the redundant bus
access rights can take away these rights forcibly by writing the value AA55 hex to the Bus
Control parameter. In that case, the value of the Bus Arbiter is switched so
that the bus which was till now the redundant bus now becomes the primary
bus. From this it is clear that the Master software must protect the
sending of this command in a suitable way e.g. by a password.
Each master can be aware of the true state of the system if it analyses the 3
MSBits of the MCR_STATUS parameter.
The value which both busses receive will be different:
• The bus which sees the MSBit (bit 15) set is the PRIMARY bus
• The next lesser bit (14) signifies that the PRIMARY bus has lost its rights
• The next bit (13) means that the other bus is down.
156
AM 06.350e-JB Edition 4.1
157
AM 06.350e-JB Edition 4.1
ON the local selector is ignored and the MCR outputs directly the pre-
programmed default output current pending the first BUS
command; then, the MCR follows the BUS.
With an operational BUS, the local operator cannot take over
control via the selector. Only if the BUS breaks down, can the
local operator push the RESET button on the MCR and turn the
selector to go to local mode. When the BUS comes back on-line,
the MCR will follow the BUS immediately even if the local operator
has taken over control.
OFF the local selector is used to determine the output.
At BUS
If the BUS breaks down, the MCR switches to the default output current
Breakdown irrespective of the last command received from the BUS. E.g., if the last valid
command from the BUS was to switch the stopbar OFF, it will be switched
ON again automatically.
If the local_kill parameter is: see “At Power up”
158
AM 06.350e-JB Edition 4.1
Parameters The situation is controlled by 2 major parameters: local_kill (at power up) and
bf_brkdwn (at BUS break down).
ON The local selector is ignored and the MCR selects the last valid
current selected via the bus before the power was lost.
With an operational BUS, the local operator cannot take over
control via the selector. Only if the BUS breaks down, can the
local operator push the RESET button on the MCR and turn the
selector to go to local mode. When the BUS comes back on-line,
the MCR will follow the BUS immediately even if the local operator
has taken over control.
If the bus does not come back on line before 5 seconds have
elapsed, the MCR reacts in the same way as if a bus breakdown
occurred (see there). The programmed bus time-out is ignored.
OFF the local selector is used to determine the output.
At BUS
The MCR reacts depending on the bf_brkdwn parameter.
Breakdown
(Note that this parameter does not exist in Stopbar mode)
If the bf_brkdwn parameter is:
Present the MCR stays on the present step until a power-out occurs or
until the BUS returns.
Default if the last step command received via the BUS was OFF, the
MCR remains OFF (e.g. if the MCR controls an approach array
which is currently not in use, we don’t want it to suddenly light
up).
But, if the BUS selected a step, the MCR switches to the
preprogrammed default output current defined by bf_def.
159
AM 06.350e-JB Edition 4.1
8.5 Parameters
8.5.1 Overview
Introduction In this chapter you will find all the information about the parameters .
Topic
BUS A Diagnostic counters
BUS B Diagnostic counters
Diagnostic subfunctions
8.5.4 Diagnostic subfunctions, Continued
MCR status
Error codes
Control parameters.
Preset parameters
Command parameters
Output Current parameters
Mains parameters
CCR Identification
EFD parameters
LFD parameters
BUS A and piggyback parameters
MCR display parameters
Calibration parameters
BUS B parameters
Circuit Selector parameters
160
AM 06.350e-JB Edition 4.1
Table A-2-1a The table below lists the parameters related to the BUS A diagnostic
counters. All counters can be read, but not written to. They can be cleared,
individually or in group, but only using Diagnostic subfunctions (see page
163).
161
AM 06.350e-JB Edition 4.1
Table A-2-1b The table below lists the parameters related to the BUS B diagnostic
counters. All counters can be read, but not written to. They can be cleared,
individually or in group, but only using Diagnostic subfunctions (see page
163).
162
AM 06.350e-JB Edition 4.1
163
AM 06.350e-JB Edition 4.1
Table A-2-2 The table below lists the parameters related to the communication between
the basic print and the Jbus piggyback.
All counters can be individually or in group modified.
164
AM 06.350e-JB Edition 4.1
Table A-2-3 The table below lists the parameters related to the MCR status.
165
AM 06.350e-JB Edition 4.1
166
AM 06.350e-JB Edition 4.1
167
AM 06.350e-JB Edition 4.1
Table A-2-4 The table below lists the parameters related to the error codes.
If either of these parameters is non-zero, then bit 0 will be set in the
mcr_status parameter in the status block.
Unspecified bits are unused and remain 0.
168
AM 06.350e-JB Edition 4.1
Table A-2-5 The table below lists the parameters related to the control parameters.
169
AM 06.350e-JB Edition 4.1
Table A-2-6 The table below lists the parameters related to the preset parameters.
For a description of the use of the presets, see the Section 7: PC control and
monitoring.
The values stored here determine a current as defined by the formula:
preset value * I_max/ FFhex.
All values between 45hex and FFhex are valid and also 0 to switch OFF the
MCR.
Once the presets are programmed, they can be used by writing to the preset
parameter defined in the command parameter block (see further).
170
AM 06.350e-JB Edition 4.1
Table A-2-7 The table below lists the parameters related to the command parameters.
All the parameters in this block must be used one at a time and should not
be transmitted as a block, but as single parameters.
In the MCR, it is the fact of receiving a write command of a non-zero value
which will activate the command. The transmitted value is irrelevant and is
not even stored in the MCR. After reception and execution of this command,
this parameter should be cleared in the master data base to avoid accidental
transmission of non-zero values.
page 169).
92 2 dummy D
93 3 Save to EEPROM After the master has modified parameters in the MCR W
data base, they are stored in its RAM only. To keep
them permanently, they must be saved to the
EEPROM of the MCR.
Before issuing this command, you must first write the
current date/ time stamp in offset 6, 7 and 8 of this
block; afterwards, set the save parameter to 1 and
send it to the MCR.
The date/ time of the last save to EEPROM can be
read back in the mcr_id block.
94 4 Restore from If the MCR data base was erroneously modified by W
EEPROM the master, or if there was some remote testing going
on, the master can restore the last known good
configuration which was stored in the EEPROM of
the MCR by putting a non-zero value in this
parameter and transmitting it to the MCR.
171
AM 06.350e-JB Edition 4.1
172
AM 06.350e-JB Edition 4.1
Table A-2-8 The table below lists the parameters related to the output current
parameters.
173
AM 06.350e-JB Edition 4.1
174
AM 06.350e-JB Edition 4.1
Table A-2-9 The table below lists the parameters related to the mains parameters.
175
AM 06.350e-JB Edition 4.1
Table A-2-10 The table below lists the parameters related to the CCR identification.
176
AM 06.350e-JB Edition 4.1
Table A-2-11 The table below lists the parameters related to the EFD parameters.
177
AM 06.350e-JB Edition 4.1
FBÆFF dummy D
178
AM 06.350e-JB Edition 4.1
Table A-2-12 The table below lists the parameters related to the LFD parameters.
179
AM 06.350e-JB Edition 4.1
Table A-2-13 The table below lists the parameters related to the BUS A and piggyback
parameters.
180
AM 06.350e-JB Edition 4.1
Table A-2-14 The table below lists the parameters related to the MCR display parameters.
181
AM 06.350e-JB Edition 4.1
Table A-2-15 The table below lists the parameters related to the calibration parameters.
These parameters are read only and used to compute the true input/ output
values.
182
AM 06.350e-JB Edition 4.1
Table A-2-16 The table below lists the parameters related to the BUS B and piggyback
parameters.
183
AM 06.350e-JB Edition 4.1
Table A-2-17 The table below lists the parameters related to the Circuit Selector
parameters.
184
AM 06.350e-JB Edition 4.1
185
AM 06.350e-JB Edition 4.1
Table A-2-18 The table below lists the parameters related to the Circuit Selector
parameters, hour counters.
Table A-2-19 The table below lists the parameters related to the Circuit Selector
parameters, hour counters.
186
AM 06.350e-JB Edition 4.1
Table A-2-20 The table below lists the parameters related to the Circuit Selector
parameters, communication link MCR-CSM.
187
N.V. ADB S.A.
Leuvensesteenweg, 585 – B 1930 Zaventem – Belgium
Tel. : 32/2/722.17.11 – Fax : 32/2/722.17.64
Companies in France, U.K. and U.S.A. – Agents all over the world