COMMENTS:

1) Coordination with other services mandatory with approval from


relevant authorities prior to installation & erection of the system.
2) Balancing of the system necessary for approval.
3) Air terminal devices (diffusers/grilles) to be approved by
Architectural/Interior Design discipline for aesthetic appeal (shape,
finish, color, texture).
4) The review does not hold true for cooling load estimation/calculation.

- UNIT/EQUIPMENT TO BE DETAILED IN SCHEDULE WITH ON-COIL &


OFF-COIL TEMPERATURE, CAPACITY, AIR FLOW RATE, AMBIENT USED FOR
SELECTION, ETC.
EVEN FOR EXISTING UNITS/EQUIPMENTS.
- UNIT SELECTION MUST BE FOR ACTUAL OUTPUT @ AMBIENT CONDITIONS.
THE UNITS BY MOST OF THE BRANDS ARE RATED AT 35 DEG. C (95 DEG. F);
WHICH SHOULD BE DERRATED FOR AMBIENT AS IN DESIGN.
- FLEXIBLE DUCT TO BE LIMITED TO 1.2 MT. LENGTH AS PER ADC STANDARD.
- AIR TERMINAL OUTLETS TO BE SELECTED FOR MIN. NOISE CRITERIA.
- ESTIMATED ESP TO BE FURSNISHED TO THE SUPPLIER FOR EQPT. SELECTION. 28 July 2018 SALMAN SARANG
- REFRIGERANT PIPING TO BE STRICTLY AS PER MANUFACTURER'S
RECOMMENDED FOR TOTAL LENGTH WITHING MAXIMUM RUN LIMIT.
- CONDENSATE DRAIN MUST BE VENTED APPROPRIATELY TO AVOID FOUL
ODOR THROUGH THE EQUIPMENT.

5 TON
REVISE THE UNIT SELECTION FOR 3 TR SIZE

Flood

Flood

Flood
Flood

Flood
Flood

Flood

Flood

Flood
(ACTUAL OUTPUT) & DUCTING WITH AIRFLOW
RATE CLEARLY MENTIONED ACCORDINGLY

600 x 300
400 x 300

PLENUM BOX SHOULD BE USED INSTEAD OF DIRECT DUCT


CONNECTION; TO AVOID ACOUSTICAL PROBLEM.
Flood

Flood

Flood

Flood

Flood

Flood
Flood

Flood
Flood

AVOID RETURN DUCT ROUTING BENEATH THE EQPT. FOR


HASSLE FREE MAINTENANCE.

Scale :- 1 : 50 Format :- A4
Date :- 18 - 07 - 2018
LAYOUT NOT ELIGIBLE FOR REVIEW.
RESUBMIT FF SYSTEM COMPRISING
PIPING, VALVE, SIZES INDICATED, ETC.

28 July 2018 SALMAN SARANG

- CHECK FOR THE REQUIREMENT OF UPRIGHT SPRINKLER AS


PER NFPA & LOCAL CODES IN CAVITY/VOID SPACE ABOVE

Flood

Flood

Flood
Flood

Flood
Flood

Flood

Flood

Flood
FALSE CEILING.
- NFPA-13 REQUIRES VOID AREA WITH DEPTH EXCEEDING 900
MM TO BE PROTECTED WITH UPRIGHT SPRINKLER.

Flood

Flood

Flood

Flood

Flood

Flood
Flood

Flood
Flood

Scale :- 1 : 50 Format :- A4
Date :- 18 - 07 - 2018

RETURN BEND CONNECTION FOR PIPE SIZING NORMALLY COMPLYING TO ORDINARY


PENDANT SPRINKLER MANDATORY. HAZARD CLASSIFICATION AS PER NFPA-13; MANDATORY.
CHECK IF REQUIRED TO CLASSIFY UNDER MORE ADVANCE
CATEGORY SUITABLE TO GOODS' STORAGE.