Professional Documents
Culture Documents
www.elsevier.com/locate/enbuild
Abstract
Fully glazed facade that has been increasingly used in Singapore causes higher energy consumption and thermal discomfort due to higher
solar gain. The use of double glazed facade system with ventilation system is one way to solve these problems. The objective of this paper is to
investigate the effects of double glazed facade with ventilation system on the energy consumption, thermal comfort and condensation and
compare to single glazed facade system. TAS and CFD software were utilized to calculate energy consumption, thermal comfort and
condensation for single glazed facade building as well as double glazed facade building. The simulation results showed double glazed facade
with natural ventilation were able to minimize energy consumption as well as to enhance the thermal comfort. Turning the mechanical fans on
could also solve the condensation problem due to high humidity.
# 2005 Elsevier B.V. All rights reserved.
Fully glazed facade system has been increasingly used in In recent years, a number of experimental, numerical and
Singapore due to its unique advantages. It can reduce the theoretical investigations have contributed to a better
lighting energy consumption by making full use of understanding of the double facade ventilation systems.
daylighting and can provide full external view. However, Pasquay [12] has monitored three buildings with double
high energy consumption, thermal discomfort and noise facade. Three types of building have been investigated in
control problems are associated with the single glazed this study. All the air conditioning facilities of Siemens
facade system. building in Dortmund have been removed and the facade
Double glazed facade ventilation system has been undertakes ventilation task for the whole building. The
investigated to overcome the problems pertaining to single results showed that even though the temperature in facade
glazed facade system. It is believed that double glazed space rose up to 10 8C above outdoor temperature, the inside
facade with ventilation could save energy, provide thermal temperature stayed in halfway acceptable limits. Victoria
comfort and improve acoustic performance by the additional Insurance Company in Düsseldorf had cooling equipment
glass layer in down town area with high level traffic noise. without mechanical ventilation. Although the temperature in
the facade space rose up to 8 8C above outside temperature, a
temperature of 26 8C for the whole year only exceeded 46 h.
* Corresponding author. RWE Tower in Essen had both cooling equipment and
E-mail address: bdgnh@nus.edu.sg (W.N. Hien). mechanical fan. The average temperature in the facade space
0378-7788/$ – see front matter # 2005 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2004.08.004
564 W.N. Hien et al. / Energy and Buildings 37 (2005) 563–572
3. Methodology
TAS and CFD simulation have been used for this study.
TAS is a multi-zone simulation software for energy
consumption, thermal comfort issue and condensation
problems. In order to obtain the precise air change rate
for facade space, CFD simulation has been implemented to
calculate airflow field of the double facade.
Basically, three models were developed for this study.
The first model is a six-storey building with full single
glazed facade system. The simulation was run from 2nd to Fig. 2. Layout for double glazed facade model.
W.N. Hien et al. / Energy and Buildings 37 (2005) 563–572 565
Table 1 Table 3
Building data CFD simulation results
Single Double glazed Double glazed Double glazed Double glazed
glazed facade with facade with facade with facade with
facade stack effect mechanical fan stack effect mechanical fan
Floor to floor 4.5 4.5 4.5 Grids 30 100 30 100
height (m) grids were divided grids were divided
Zones/floor 5 9 9 in 1 m 30 m in 1 m 30 m
Total zones 25 45 45 domain domain
Dry bulb 23–25 23–25 23–25 Ventilation type Stack effect in Mechanical fans
temperature (8C) the facade cavity
Relative humidity (%) 75 75 75 Ventilation rate (ACH) North: 111 320 for north, east,
Infiltration of 0.2 ach 0.2 ach 0.2 ach south and west zones
air change rate each zone each zone each zone East: 131
Lighting load (W/m2) North: 16.7 North: 16.7 North: 16.7 South: 113
East: 16.3 East: 16.3 East: 16.3 West: 131
South: 16.7 South: 16.7 South: 16.7
West: 16.3 West: 16.3 West: 16.3
Internal: 3.1 Internal: 3.1 Internal: 3.1
fans. Although there is a high improvement of air change
Sources: [9,10,13].
rate for the double facade with the aid of mechanical fan, the
third model does not drastically reduce the cooling loads. It
cooling loads and solar heat gains profile along the height of seems that ventilation has not much effect on decreasing the
double facade. cooling loads.
In order to study the effectiveness of ventilation inside the
4.1.2. Annual energy demand comparison for different double facade for heat extraction, two more scenarios have
orientations been investigated for this study—one with double facade
Higher solar heat gain was found in the east–west without ventilation and the other with extremely high
orientation, which contributes to the higher cooling load. ventilation (999 ACH). It can be seen that there is about
Since double glazed facade is able to decrease the solar heat 100 MWh/year cooling load reduction if single facade has
gain, the cooling load demands are more uniform for double been convert to double facade (single facade model and DF
glazed facade with stack effect and double glazed facade with no ventilation). This could be attributed to solar gain
with mechanical fan compare to single glazed facade reduction with the aid of double facade. If natural ventilation
(Fig. 4). with stack effect has been considered, there will be further
cooling load reduction of about 23.6 MWh/year. It can be
4.1.3. Annual cooling loads among three models seen that double facade with natural ventilation has a good
It can be seen from Fig. 5 that cooling loads has been potential to reduce energy consumption. There is about
drastically reduced with the help of double facade (nearly 1.3 MWh/year and 0.6 MWh/year cooling load reduction, if
120 MWh/year). This can be attributed to two factors. One is the model has been converted from no mechanical fan to
the high reduction of solar heat gains. The other one is the 2 m/s mechanical fan and from 2 m/s mechanical fan (the
ventilation of the facade to extract heat and cool down the third model) to 6 m/s mechanical fan (full ventilation in
internal surface temperature. However, it is interesting to see double facade) respectively. It can be explained that double
that there is no much difference in energy consumption facade with purely stack effect can be effective enough to
between double glazed facade with stack effect and double extract heat inside the double facade and cool down the
facade with mechanical fan. There is very small cooling load
reduction (about 1.3 MWh/year) with the aid of mechanical
Table 2
Material specification
Single glazed Double glazed Double glazed
facade facade with facade with
stack effect mechanical fan
Glass Clear double Clear double Clear double
glazed with glazed with internal glazed with internal
internal blind blind for internal side; blind for internal side;
6 mm heat absorption 6 mm heat absorption
glass for external side glass for external side
Roof Concrete slab Concrete slab Concrete slab
(U = 0.25 (U = 0.25 (U = 0.25
Fig. 3. Cooling loads and solar heat gains profile along height of double
W/m2 8C) W/m2 8C) W/m2 8C)
facade.
566 W.N. Hien et al. / Energy and Buildings 37 (2005) 563–572
Fig. 6. External surface temperature profiles for the inner layer glazed wall.
Brager and Dear [7] noted that 20% of PPD corresponds to if double glazed facade with mechanical fan is chosen over
the limits of 0.85 PMV. PMV index less than 0.85 is double glazed facade with stack effect.
classified as unacceptably cold and more than +0.85 is From Figs. 8 and 9, PMV and PPD indexes for June are
classified as unacceptably hot. higher than December for all models due to cooler weather
Values for air temperature, RH and MRT were retrieved in December. Highest thermal comfort level is achieved in
from the results generated by TAS simulation. The northern zone second storey of double glazed facade during
metabolic rate and clothing insulation of the subjects were December. Lowest thermal comfort level is happened in
determined to be 1.2 and 0.57, respectively. Air velocity eastern and western zone sixth floor of single glazed facade
inside the air-conditioned room was taken as 0.15 m/s for the during June.
calculation.
4.2.2. PMV and PPD comparison among different storeys
4.2.1. PMV and PPD among three models Increasing trend of PPD and PMV on the higher storeys
From Table 4, PPD indexes was found to be lower for has been observed for both single and double facade systems
double glazed facade with stack effect and mechanical fan due to higher solar heat gain on higher storeys. The rate of
compare to single glazed facade. However, difference raise is quite consistent for single facade system whereas a
between double glazed facade with stack effect and double sudden raise has been observed on the upper floors for
glazed facade with mechanical fan was negligible. Single double facade system. This could be explained by increase
facade system failed to achieve thermal comfort since the of temperature in the facade cavities both as a function of
PPD value was higher than 20%. height of a building and higher solar gains.
Mean values of PPD shows that, if double glazed facade From Fig. 10, it has been observed that most
is chosen over single glazed facade, 5% more people seem to uncomfortable floor during both seasons is sixth floor. For
be satisfied. However, only 0.05% more people are satisfied double glazed facade, almost all floors for both seasons
Fig. 7. Internal surface temperature profiles for the internal layer glazed wall.
568 W.N. Hien et al. / Energy and Buildings 37 (2005) 563–572
Table 4
Mean values of PMV and PPD for three scenarios
Single facade Double facade Double facade
(NV) (MV)
June December June December June December
PMV 0.96 0.89 0.82 0.78 0.81 0.77
PPD (%) 24.5 22.0 19.6 18.0 19.5 18.0
4.3. Condensation
Fig. 9. PMV values for single and double facade. Fig. 11. PPD variations in different zones: June (single glazed facade).
W.N. Hien et al. / Energy and Buildings 37 (2005) 563–572 569
Fig. 16 shows the layouts of condensation at 10.00 p.m., surface temperature of heat absorption glass (23.7 8C) as
and the section shows the occurrence of condensation on left compared to ambient temperature in the double glazed
surface, facing west. Again, no condensation was found for cavity (24.2–25.7 8C).
single glazed facade, but it happened on 2nd and 3rd model
on the inside and outside of heat absorption glass. 4.3.4. Comparison of condensation’s rate
Operations of mechanical fans were successful in removing The rate of condensation for middle surfaces (Surface 2)
all condensation on the inside surface and partly of the is lower compared to right–left surface (Surfaces 1 and 3). It
outside surface, but still unsuccessful in removing con- happened on both outside and inside of heat absorption
densation on the left and right of outside surface of heat glass. This is again due to surface temperature differences
absorption glass, as shown in Fig. 17. between middle and left–right surface (Fig. 18).
Surface temperature plays an important role in determin-
ing the occurrence of condensation. For single glazed facade 4.3.5. Comparison of condensation between lower and
since the surface temperature is similar to ambient higher floor
temperature (24 8C), condensation does not occur. For the Middle surfaces have been chosen to investigate the
2nd and 3rd model, condensation occurred due to lower distribution of condensation on different floors. From
Fig. 17. Comparison of condensation rate among four scenarios on 6th story: west orientation, 2 January.
Figs. 19 and 20, it can be seen that 2nd storey has the lowest
condensation rate. Whereas the surface temperature of 2nd
storey has been found about 1 8C lower compare to higher
floor 23 8C.
5. Conclusions
References [8] You, L.J., et al., Heavenly Mathematics: Sun and Architecture,
National University of Singapore, 2002. Retrieved 1 April 2004 from
World Wide Web: http://www.math.nus.edu.sg/aslaksen/teaching/hm/
[1] E. Gratia, A.D. Herde, Optimal operation of a south double-skin
projects/0304-1-66.
façade, Energy and Buildings 36 (2004) 41–60.
[9] ASHRAE Handbook: 1993 Fundamentals. American Society of Heat-
[2] E. Gratia, A.D. Herde, Natural ventilation in a double-skin facade,
ing, Refrigerating and Air-Conditioning Engineers, Atlanta, GA,
Energy and Buildings 36 (2004) 137–146.
1993.
[3] C. Balcoo, A non-dimensional analysis of a ventilated double
[10] Handbook on Energy Conservation in Buildings and Building Ser-
façade for energy performance, Energy and Buildings 36 (2004)
vices, 1983. The Development and Building Control Division (PWD),
35–40.
Singapore.
[4] J.V. Grabe, A prediction tool for the temperature field of double
[11] H. Manz, Total solar energy transmittance of glass double facades with
facades, Energy and Buildings 34 (2002) 891–899.
free convection, Energy and Buildings 36 (2004) 127–136, http://
[5] Bill B.P. Lim, Control of the External Environment of Buildings,
www.personal.psu.edu/users/e/x/exj126/.
Singapore University Press, National University of Singapore, Kent
[12] T. Pasquay, Natural ventilation in high-rise building with double
Ridge, Singapore, 1998.
façade, saving or waste of energy, Energy and Buildings (2004).
[6] Thermal Environmental Conditions for Human Occupancy, ASHRAE
[13] SS CP 38, 1999. Artificial Lighting in Buildings.
STANDARD 55-81, American Society of Heating, Refrigerating, and
[14] E. Jean-Louis, D. Walker, J. Lee, H. Allen, Energy Efficient Appli-
Air-conditioning Engineers, Atlanta, GA, 1992.
ance. Retrieved 20 March, 2004 from the World Wide Web: http://
[7] G. Brager, R. Dear, A standard for natural ventilation, ASHRAE
www.personal.psu.edu/users/e/x/exj126/
Journal 42 (10) (2000) 21–28.