Professional Documents
Culture Documents
SWITCHING, PROTECTION,
AND CONTROL SOLUTIONS
TABLE OF CONTENTS
5 Introduction
AUTOMATION
6 IntelliRupter ® PulseCloser ® Fault Interrupter
SOFTWARE
34 IntelliTeam ® SG Automatic Restoration System
COMMUNICATIONS
40 SpeedNet™ Radios &
SpeedNet™ Cell Edge Gateway
SERVICES
42 Analysis & Design
44 Project Execution
46 Post-Installation Support
47 Applications
MEDIUM-VOLTAGE
48 PMH and PME Pad-Mounted Gear
HIGH-VOLTAGE
94 SMD-1A, -2B, -2C, -3, and -50 Power Fuses
96 Circuit-Switchers
4
INTRODUCTION
IMAGINE you have a time machine and It’s difficult to keep ahead of the curve
you brought Alexander Graham Bell and and address these changes.
Thomas Edison into the year 2019. If you
S&C IS HERE TO HELP. We are applying
showed Mr. Bell your smart phone, he
our century-long heritage of innovation
wouldn’t understand what he was looking
to address the challenges facing today’s
at. But if you took Mr. Edison outside and
power grid. Our distribution automation
showed him an electrical distribution
systems are pushing the boundaries of
system, he would have a pretty good idea
reliability and reducing the duration of
what he was seeing. That, however, is
outages from hours to seconds—or to no
quickly changing.
outage at all.
In the past decade, we have seen a
Our solutions are designed to withstand
tremendous shift in the way the electric
the impacts of time and nature to help
grid works, how it operates, and how
keep the lights on for your customers. We
consumers use electricity.
understand the important role energy
Reliability of power has seen an storage plays on the grid, having in excess
increased focus as our day-to- of 49 projects totaling more than 189
day lives rely on electricity being MWh installed around the world. Our
available at all times. The costs of award-winning microgrids are providing
outages have been estimated at breakthroughs in how distributed
more than $150 billion a year in generation resources, including energy
the United States alone. storage, are managed by customers and
the utility.
Major weather events are
increasing in frequency and To help you solve the challenges of today
severity, requiring new ways to and tomorrow’s grid, our solutions are
harden our electric grid and new backed by our S&C experts. These are
methods to restore service as the men and women with the skills and
quickly and safely as possible. know-how to help you plan and execute
the solutions you need—from concept
More than 1.8 GW of operational
through completion.
battery energy storage is tied
to the grid today. Use of stored We have designed this catalog to help
energy is playing an important you, too. It is designed to help you quickly
role as utilities and others build reference the wide range of solutions
microgrids backed by distributed S&C offers in our specialty of electric
generation to improve power power switching, protection, and control.
reliability. Keep this catalog as a reference when you
are researching the solutions you need.
Indeed, distributed generation and
microgrids are creating unique Should you need more detail than is
challenges for protecting and provided here, please visit sandc.com,
controlling the power grid as loads or contact your local S&C
and generation sources fall outside sales representative.
of traditional operations.
5
INTELLIRUPTER ® PULSECLOSER®
FAULT INTERRUPTER
The IntelliRupter ® fault interrupter is a breakthrough in overhead and underground distribution system protection. It features
revolutionary PulseClosing ® Technology— a unique means for verifying the line is clear of faults before initiating a closing
operation. PulseClosing Technology is superior to conventional reclosing. It greatly reduces stress on system components as
well as voltage sags experienced by customers upstream of the fault.
CONVENTIONAL RECLOSING
PulseClosing Technology
drastically reduces overcurrent
stress on your system, as
shown here for a phase-wire to PULSECLOSING TECHNOLOGY
grounded-neutral fault.
HANDLES ALL YOUR APPLICATION NEEDS FULLY COMPATIBLE WITH S&C'S INTELLITEAM® SG
The IntelliRupter fault interrupter offers outstanding AUTOMATIC RESTORATION SYSTEM
protection for systems through 38 kV. It features a The IntelliRupter fault interrupter can be readily integrated
generous continuous-current capability of up to 800 into an S&C IntelliTeam ® SG Automatic Restoration System
amperes and a fault-interrupting rating of up to 16,000 (see page 34). After an IntelliRupter fault interrupter has
amperes symmetrical. Models are available with or without isolated a fault, the IntelliTeam SG system makes full use
an integrated, interlocked disconnect for visible air-gap of multiple sources to restore unfaulted line segments.
isolation. All switching is performed internally for reliable The IntelliTeam SG system minimizes the number of
all-weather operation. customers experiencing an extended power interruption,
tremendously improving your System Average Interruption
In standalone fault-interrupting applications, PulseClosing
Duration Index. The IntelliTeam SG system can handle
Technology enhances power quality by minimizing
multiple contingencies, too.
momentary interruptions. For example, on a radial circuit,
the IntelliRupter fault interrupter can be configured so that The IntelliRupter fault interrupter is fully compatible with
after one IntelliRupter fault interrupter opens to isolate a IntelliTeam SG Automatic Restoration System-equipped
fault, those downstream of it open on loss of power and S&C Scada-Mate ® Switching Systems, Scada-Mate CX™
send SCADA exception reports indicating the status and Switching Systems, Remote Supervisory PMH and PME
reason for opening. When power returns, each IntelliRupter Pad-Mounted Gear, and Remote Supervisory Vista ®
fault interrupter uses PulseClosing Technology to verify Underground Distribution Switchgear.
its line segment is unfaulted and then recloses to restore
EASY UP – EASY ON
service. It will never close into a fault. Cold-load inrush is
mitigated because only one line segment is energized with IntelliRupter fault interrupters are totally self-contained. All
each closing. No communication system is required to take major components—including current and voltage sensors
advantage of inrush mitigation. and the control group, surge arresters, control power,
and disconnect, if furnished—go up in one easy lift. The
embedded high-accuracy sensors eliminate the cost, clutter,
and complexity of separately mounted sensors. There’s no
control enclosure or control cable to install, either.
6
AUTOMATION
38 - kV Disconnect Style IntelliRupter PulseCloser Fault Interrupter in Upright-Crossarm Mounting Configuration
Disconnect OPEN/
CLOSE lever
Interrupter
OPEN/
CLOSE/ Control group—features hookstick-
READY removable protection and control Stainless steel Interrupter OPEN/CLOSE indicator
lever—for module and communication module; base—provides on each phase—large and uses
manually a multi-function status light indicates outstanding reflective materials for easy viewing,
opening the control group is operating corrosion resistance, day or night; it’s attached directly to
and closing normally, and a hot-line tag light even in the harshest the operating rod—no complicated
Hot-line tag lever—
interrupters indicates “set” tag environments linkages to break
for setting and
releasing tags for
energized line work
① 800 amperes with a minimum wind velocity of 2 feet (610 mm) per second.
For more information on IntelliRupter PulseCloser Fault Interrupters, see publications 766-30, 766-31, and 766A-31 at sandc.com. 7
INTELLIRUPTER® PULSECLOSER® FAULT INTERRUPTER
A NEW CONCEPT IN CONTROLS
The IntelliRupter fault interrupter is available with several
types of control groups. Each offers easy configuration
and operation—plus examination of waveforms and
events—using secure wireless communication to a
nearby laptop computer.
uu Synchronization check
8
AUTOMATION
For IntelliTeam SG system, automatic source-transfer, or Detailed logs, oscillography data, and other operational
SCADA applications, an S&C SpeedNet™ Radio or other information can be readily accessed and transferred over
approved communication device must be furnished. Such the wireless link, as can software upgrades. If a wide-
devices permit configuration, operation, interrogation, and area network radio has been furnished—and it supports
software maintenance of IntelliRupter fault interrupters from configuration through its serial port—it can be configured
any location having access to the communication system through the wireless link as well.
using optional IntelliLink® Setup Software.
When an IntelliRupter fault interrupter is set for remote
The IntelliRupter fault interrupter is also available with a operation, your dispatcher can test its electrical operation as
Standard Control Group with Battery Backup, which well as the entire SCADA control path, including communication.
supports operation for hours after loss of ac line voltage on
If a personal computer isn’t available, IntelliRupter fault
both sides of IntelliRupter fault interrupters, thus permitting
interrupters can be opened and closed and hot-line tags set
extended dead-line switching. The Universal Control Group
using a hookstick from the ground or a bucket truck.
also includes a battery and is suitable for basic closed-loop
applications, IntelliTeam® II Automatic Restoration System Should module replacement ever become necessary,
applications, and applications on systems with three or it’s easily performed, too. No need to reconfigure
more sources. IntelliRupter fault interrupters—a memory module in the
base remembers all the settings.
EASY OPERATION
The control group is easy to configure before installation.
If desired, S&C can determine the appropriate settings for IntelliRupter Fault Interrupter Operation Screen
the control group and/or perform secondary injection
testing to verify the settings, functions, and logic (see
Analysis & Design on page 42).
The IntelliRupter fault interrupter control group is configured and operated using a secure Wi-Fi communication link.
9
TRIPSAVER® II CUTOUT-MOUNTED RECLOSER
With With
System
Nom. Max BIL Cont. Interr., Sym. Porcelain Polymer
Class
Insulator Insulator
10
AUTOMATION
15-kV Overhead Pole-Top Style TripSaver II Recloser
Parallel-groove connector—tin-plated
cast red brass; for ease of connection, Bumper and retainer—spring-loaded
accommodates two conductors, even of retainer plus a bumper dampen impact on
unlike size closing, reducing possibility of bounce-back
TripSaver II recloser in
dropped-open position—
drops open at the end of its
operating sequence if the
fault is permanent
For more information on the TripSaver II Cutout-Mounted Recloser, see publications 461-32 and 461-33 at sandc.com. 11
VACUFUSE™ SELF-RESETTING INTERRUPTER
Every utility can relate to sending crews out to replace blown If the fault is permanent, the self-resetting interrupter will
fuses above overhead distribution transformers without interrupt the fault current wait a user-designated number
being able to find the cause of the fault. In fact, industry of seconds, reclose, and then interrupt the fault current and
sources reveal that 70% of overhead distribution transformer deenergize the transformer. (Unlike TripSaver® II Cutout-
fuse operations are classified as nuisance outages, where no Mounted Reclosers, VacuFuse Self-Resetting Interrupters do
other repair work is needed. not drop open on permanent outages and will remain in the
cutout mounting.) After the fault has been cleared by the
‘EVEN AT THE EDGE OF THE GRID’
line crew, the self-resetting interrupter can be closed using
The VacuFuse Self-Resetting Interrupter solves both these the manual operating lever on the side of the self-resetting
unnecessary sustained outages and subsequent maintenance interrupter.
expenses, bringing fault-testing technology closer to the
edge of the grid than had previously been possible.
HOW IT WORKS
VacuFuse Self-Resetting Interrupters solve the nuisance
outages that occur on overhead distribution transformers. As A VacuFuse
a single-phase self-resetting interrupter intended for use on Self-Resetting
5-kV, 15-kV or 25-kV distribution systems, it replaces fuses in Interrupter
responds to a
these locations. When the self-resetting interrupter detects permanent fault.
a fault, its vacuum interrupter will open to interrupt the fault
current.
If the fault is temporary, the self-resetting interrupter will This self-resetting interrupter comes factory-configured
restore power. This saves temporary faults from becoming with a user-designated time-current characteristic (TCC)
permanent outages—and the maintenance costs otherwise curve. With the ability to be placed in several manufacturers’
associated with refusing and restoration. approved cutouts, a VacuFuse Self-Resetting Interrupter
can easily be placed above 5-kV overhead distribution
transformers up to 25 kVA, 15-kV transformers up to 75 kVA,
and 25-kV transformers up to 150 kVA when mounted in a
125- or 150-kV BIL cutout mounting.
A VacuFuse
Self-Resetting
Interrupter
responds to a
temporary fault.
12
AUTOMATION
VacuFuse Self-Resetting Interrupters come ready to install, Available Fuse Link Curves
streamlining the commissioning process and lessening the
K Speed Curves KS Speed Curves T Speed Curves
amount of training for line crews. Utilities can choose from
any of the following fuse-link TCC curves: K, KS, T. Only 1K, 2K, 3K, 5K, 6K, 1KS, 2KS, 3KS, 5K,S 1T, 2T, 3T, 5T, 6T,
one curve can be chosen per device, and the settings are 8K, 10K 6KS, 7KS, 10KS 8T, 10T
permanently configured at the factory.
kV Amperes, RMS
Leakage Distance to Ground Minimum, Leakage Distance to Ground Minimum,
System Interr., Inches (mm) ② Inches (mm) ②
Nom. Max BIL Cont.
Class① Sym.
For more information on the VacuFuse™ Self-Resetting Interrupter, see S&C publications 465-30 and 465-31, available on our website sandc.com. 13
VACUFUSE™ SELF-RESETTING INTERRUPTER
Construction–Side View
14
AUTOMATION
Construction–Bottom View
15
SCADA-MATE® SWITCHING SYSTEM
S&C’s Scada-Mate Switching System is ideal for automating overhead distribution feeders. All necessary functions—sensing,
control, and communications—are provided in one economical, self-contained package. The performance capabilities,
operating features, and integration of functions provided by the Scada-Mate Switching System make remote supervisory
control of distribution feeders a practical, economical reality.
FEATURING THE SCADA-MATE SWITCH After the Scada-Mate Switch has isolated a fault, the
Scada-Mate Switching Systems are integer-style three-pole, IntelliTeam SG system makes full use of multiple sources
group-operated load interrupter switches available in voltage to restore unfaulted line segments. The IntelliTeam SG
ratings of 14.4-kV through 34.5-kV. They’re factory-assembled system minimizes the number of customers experiencing
on a one-piece base and include an integral stored-energy an extended power outage, and it handles multiple
operating mechanism. contingencies, too.
uu The control includes a high-output battery charger
Circuit making and breaking are accomplished within sealed
with a unique battery-management system, as well as
interrupters in a controlled SF6 environment. The high-
rechargeable sealed-lead starved-electrolyte battery
speed linkages used to effect operation are housed within
packs, powered from a user-supplied 120-Vac control
the base. With no external moving parts, full live-switching
source or three voltage sensors. The control additionally
performance is ensured under any and all ice conditions.
features a liquid-crystal display for viewing real-time
Visible air-gap isolation of switched-open circuits—needed
data, settings, and fault events. It offers automatic
only when work on the feeder is required—is provided by an
sectionalizing and overcurrent fault-detection capabilities
integral, hookstick-operated three-pole disconnect.
and selectable shots-to-lockout settings. All components
Scada-Mate Switching Systems feature a five-time duty-cycle of each device are neatly packaged in a single corrosion-
fault-closing rating of 20,000 amperes, RMS, asymmetrical. resistant enclosure, simplifying installation and minimizing
The ability to close into a fault and remain capable of carrying checkout time.
and interrupting current is a must for any distribution- uu The Communication and Control Unit is a custom-
automation switching device. engineered package that includes a user-specified,
factory-installed and -wired remote terminal unit and
Two S&C current sensors and one S&C current/voltage sensor
communication device; a temperature-compensated,
provide three-phase monitoring of line current and single-
constant-voltage battery charger with rechargeable
phase monitoring of system voltage. The voltage sensor(s)
sealed-lead starved-electrolyte battery packs; and a
also provides 20-VA continuous battery-charging power for
switch control with OPEN/CLOSE pushbuttons, switch-
the control, eliminating the need for a separate distribution
position indicating lamps, a disconnect Closed-and-
transformer. All sensors are of S&C Cypoxy™ Insulator
Latched indicating lamp, a LOCAL/REMOTE switch, and an
construction and serve as support insulators for the switch
operation counter. All components are neatly packaged
live parts—eliminating the cost, clutter, and complexity
in a single 316L stainless steel enclosure, simplifying
associated with separately mounted sensors.
installation and minimizing checkout time.
CONTROLS TO MATCH
The charger is powered by an S&C Voltage Sensor or, in a
YOUR AUTOMATION OBJECTIVES
higher-output version with a unique battery-management
A complete S&C Scada-Mate Switching System includes a
system, from a user-supplied 120-Vac control source. The
Scada-Mate Switch and a control. S&C offers a variety of
charger features integral load-disconnect circuitry to prevent
controls to match your automation objectives:
deep discharge of the batteries on loss of the ac source,
uu The 6801 Automatic Switch Control provides remote plus alarms for loss of the ac source, battery low voltage,
reporting of switch status points, current, voltage, watts, and charger overvoltage. It also includes circuitry to effect
and vars via the DNP 2 Level 3 protocol, and it supports a battery load-test feature when used in conjunction with a
S&C’s IntelliTeam ® SG Automatic Restoration System. suitable remote terminal unit (RTU).
16
AUTOMATION
25 - kV Scada-Mate Switch in the Upright Mounting Configuration
Sealed SF6 interrupters—circuit making Enclosed one-piece Two S&C Current Sensors and one S&C Current/ Interrupter
and circuit breaking are accomplished base—houses drive Voltage Sensor—provide three-phase monitoring OPEN/
internally with no exposed moving parts linkages for interrupters of line current and single-phase monitoring of CLOSED
system voltage (Three-phase voltage sensing indicator
(shown) is optionally available. Voltage sensors
can be provided on both sides of the switch for
designated normally open points on the system.)
SCADA-MATE SWITCHES
60-Hz Ratings—50-Hz Ratings in Parentheses
kV① Amperes, RMS Five-Time Duty-Cycle
Cont. and Mom., Fault Closing, Amperes,
Nom. Max BIL RMS, Asym.
Interr.② Asym.
A variety of options
14.4 17.0 110 600 25 000 20 000 are available—wildlife
(10)◆ (15) (110) (630) (25 000) (20 000)
protection, extension-link
25 29 150 600 25 000 20 000 assemblies, and others
(20)◆ (24) (150) (630) (25 000) (20 000)
34.5 38 200 600 25 000 20 000
(30) (36) (200) (630) (25 000) (20 000)
① System-voltage restrictions apply when the control is powered by S&C Current/
Voltage Sensors.
② Up to 900 amperes continuous in ambient temperatures to 40°C (104°F ) with a
minimum wind velocity of 2 feet (0.6 m) per second.
◆ Minimum voltage rating.
For more information on the Scada-Mate Switching System, see publications 768-30, 768-31, and 768-93 at sandc.com. 17
SCADA-MATE® SWITCHING SYSTEM
Vertical Tiered-outboard
18
18
AUTOMATION
. . . with swing- out panel open
Pole-top Upright
19
For more information on the Scada-Mate CX Switching System, see S&C publications 768-34, 768-711, and 768-712, available on our website sandc.com. 19
SCADA-MATE CX™ SWITCHING SYSTEM
Automation needs change and grow with increased load, Visible-break disconnect. If your system practices require
capacity, and demand for more reliable service. Scada-Mate a visible-break disconnect, Scada-Mate CX Switches can be
CX Switches economically meet these changing needs. furnished with an integral disconnect comprised of three
These three-pole, group-operated interrupter switches are single-phase, hookstick-operated blades, based on S&C’s
specifically designed for automating overhead distribution proven Loadbuster Disconnect® Switch design (see page
systems, either today or in the future. They feature a five- 80). The disconnect is interlocked to prevent opening when
time duty-cycle fault-closing rating of 20,000 amperes, the interrupters are closed and closing the interrupters when
RMS, asymmetrical, plus full live-switching performance the disconnect is open.
under any and all ice conditions. Circuit making and
Controls that meet your requirements. Scada-Mate CX
circuit breaking are accomplished internally, within sealed
Switches are available with a wide range of controls to
interrupters, in a controlled sulfur hexafluoride (SF6)
match your automation objectives.
environment.
For remote supervisory control applications, the 6801
Scada-Mate CX Switches are factory-assembled on a one-
Automatic Switch Control combines sophisticated
piece base and include an integral stored-energy operating
automatic control schemes with remote terminal unit (RTU)
mechanism. Besides electrically operating the interrupters,
functionality, data logging, and advanced communication
the operating mechanism provides nonelectrical mechanical
capabilities in a single package (see page 18). It can manage
opening and closing of the interrupters by means of a
switches and automatically sectionalize a feeder based
manual-operation pull-ring. The switch can be locked open
on factors such as overcurrent, loss of voltage, and phase
to prevent electrical or manual closing.
imbalance. Multiple controls can be programmed to
Scada-Mate CX Switches are also available in a manually communicate with each other using the optional
operated version. On these switches, the stored-energy IntelliTeam® SG Automatic Restoration System (see page 34).
operating mechanism is replaced by a factory-adjusted,
Scada-Mate CX Switches can also be furnished with a
spring-wound hookstick operating mechanism.
custom-engineered communication and control unit that
Sealed interrupters, fully enclosed base. Scada-Mate CX provides the interface between the switch and the master-
Switches feature the same hermetically sealed, low-gas- station computer. It can accommodate a remote terminal
volume interrupters, OPEN/CLOSE indicator, and operating device of any manufacture and can be powered by either a
mechanism as Scada-Mate® Switching Systems. They’re ideal customer-supplied source or S&C Current/Voltage Sensors
for installation in areas prone to icing, polluted and coastal on the Scada-Mate CX Switch.
environments, and remote locales.
For source-transfer applications using two Scada-Mate
Compact. Scada-Mate CX Switches are 40% smaller than CX Switches, a Micro-AT® Source-Transfer Control or 6802
Scada-Mate Switching Systems, and they can be furnished Automatic Switch Control can be furnished. Both controls
without the disconnect to save additional space. provide transfer in as little as 70 cycles.
Upgradable. With Scada-Mate CX Switches, you can Simple installation. Scada-Mate CX Switches are easy to
purchase the features you need today . . . and easily upgrade install. Lifting means are provided for convenient rigging
tomorrow. Switches can be furnished with factory-installed and hoisting. With their integral sensors and disconnect—
S&C Current Sensors or S&C Current/Voltage Sensors. Or, and no vertical operating pipe—Scada-Mate CX Switches
alternately, S&C sensors or sensors of other manufacture can present a clean uncluttered look.
be added later. And an S&C control unit or a control of other
manufacture can be added at any time.
20
14.4-kV Scada-Mate CX Switch in the Upright Mounting Configuration
AUTOMATION
Also Available in Upright—Extra Mounting-Pole Clearance, Upright—Compact, and Tiered-Outboard Mounting Configurations
Enclosed one-piece
base—houses drive
linkages for interrupters
Manual-operation pull-ring
Integral stored-energy
operating mechanism—
with manual opening and
closing capabilities
SCADA-MATE CX SWITCHES
60-Hz Ratings—50-Hz Ratings in Parentheses
kV① Amperes, RMS Five-Time Duty-Cycle
Cont. and Fault Closing, Amperes,
Nom. Max BIL Mom., Asym. RMS, Asym.
Interr.②
14.4 17.0 110 900 25 000 20 000
(10)★ (15) (110) (900) (25 000) (20 000)
25 29 150 900 25 000 20 000
(20)★ (24) (150) (900) (25 000) (20 000)
① System-voltage restrictions apply when the control is powered by S&C
Current/Voltage Sensors.
② Switches furnished with optional visible-break disconnect can carry up to 900 am-
peres continuous in ambient temperatures to 40°C (104°F) with a minimum wind ve-
locity of 2 feet (0.6 m) per second. Maximum allowable conductor temperature is 90°C
(194°F). Without minimum wind velocity of 2 feet (0.6 m) per second, these switches
can carry up to 630 amperes continuous.
★ Minimum voltage rating.
For more information on the Scada-Mate CX Switching System, see publications 768-34, 768-711, and 768-712 at sandc.com. 21
SCADA-MATE® SD SWITCHING SYSTEM
As energy demand and generation capacity continue to Upgradable. Scada-Mate SD Switches can be furnished with
grow, utilities are looking for distribution switching systems factory-installed Current Sensors or S&C Current/Voltage
that are reliable, resilient, and efficient. The Scada-Mate SD Sensors. Or, other manufactures' sensors can be added later.
Switching System is particularly well-suited to meet these Moreover, you can add an S&C control unit or a control from
technical, operational, and economic challenges. It includes another manufacturer at any time.
vacuum interrupting technology, uses no greenhouse gases,
Hookstick-operated versions of the switch also can be
and is totally environmentally friendly.
upgraded with a motor operator, permitting remote
This three-pole, group-operated Scada-Mate SD Switching operation in sectionalizing applications that don’t require
System is designed for overhead distributed automation and sensing and intelligent controls.
to operate in 14.4-kV and 25-kV power-distribution systems.
Visible-break disconnect. For system practices that require
It is rated 900 amperes continuous and interrupting and
a visible-break disconnect, S&C can provide Scada-Mate SD
features peak withstand of 41,600 amperes. This switching
Switches furnished with an integral disconnect comprised
system has a five-time duty-cycle fault-closing rating of
of three single-phase, hookstick-operated blades, based on
12,500 amperes RMS symmetrical.
S&C’s proven Loadbuster Disconnect® Switch design (see
With smart and flexible controls, such as the S&C 6801 page 80). The disconnect is interlocked to prevent opening
Automatic Switch Control, the system can minimize the when the interrupters are closed and closing the interrupters
load under outage conditions and maximize system when the disconnect is open.
uptime. Scada-Mate SD Switches are factory-assembled in
Scada-Mate SD Switching System features:
a controlled environment where the vacuum interrupter
is molded inside solid dielectric S&C Cypoxy™ Insulator uu A stored-energy operating mechanism
material, giving the switching system pole-unit a robust uu Three-phase current sensors and three-phase voltage
construction that protects it from impact, wildlife, dust, sensors on one or both sides of the switch
moisture, and external damage. The Scada-Mate SD is ideal uu A hookstick-operable three-pole disconnect for visible air-
for installation in areas prone to icing, polluted and coastal gap isolation of switched-open circuits
environments, and remote locations.
uu Lockout/tagout
Sealed vacuum interrupters, fully enclosed base. The uu Interlocked disconnects that prevent inadvertent load
Scada-Mate SD switching system uses vacuum interrupters switching
that present no environmental concerns tied to greenhouse
uu Provisions for mounting six surge arresters (three on each
gas emission. They also are not subjugated to the same strict
side of the switch)
regulation governing the production of SF6 switches.
uu Provisions for dead-ending
Models. The Scada-Mate SD Switching system is available in uu Wildlife covers
five mounting configurations, including: compact-crossarm
upright, compact-crossarm upright with extra mounting-pole For remote supervisory control applications, the 6801
clearance, compact-crossarm upright compact (alley arm), Automatic Switch Control combines sophisticated
compact-crossarm tiered outboard, and standard crossarm automatic control schemes with remote terminal unit (RTU)
phase spacing models. Each of these configurations feature functionality, data logging, and advanced communication
an OPEN/CLOSE indicator and an operating mechanism and capabilities in a single package (see page 18). Multiple
can accommodate all switch-option configurations used in controls can be programmed to communicate with
overhead distribution. each other using the optional IntelliTeam® SG Automatic
Restoration System (see page 34).
The Scada-Mate SD Switch is also available in a manually
operated version; the stored-energy operating mechanism Scada-Mate SD Switches can also be furnished with a
is replaced by a factory-adjusted, spring-wound hookstick custom-engineered communication and control unit that
operating mechanism. provides the interface between the switch and the master
station computer.
Sensors: Sensing options for the Scada-Mate SD Switch
include three-phase S&C Current Sensors on the pole-saddle For source-transfer applications using two Scada-Mate
side of the switch, and three-phase S&C Current/Voltage SD Switches, a Micro-AT® Source-Transfer Control or 6802
Sensors on the pole-saddle side or on both the front and Automatic Switch Control can be furnished. Both controls
pole-saddle sides of the switch. provide transfer in as little as 70 cycles.
22
25-kV Scada-Mate SD Switch in the Compact-Crossarm Upright Mounting Configuration
AUTOMATION
Also available in Compact-Crossarm Upright–Extra Mounting-Pole Clearance, Compact-Crossarm Upright–Compact (alley arm),
and Compact-Crossarm Tiered Outboard Configurations
Optional three-
phase S&C Current/
Interrupter OPEN/ Voltage sensors
CLOSED indicator
SCADA-MATE SD SWITCHES
60-Hz Ratings—50-Hz Ratings in Parentheses
kV① Amperes, RMS Five-Time Duty-Cycle
Cont. and Peak With- Fault Closing, Amperes,
Nom. Max BIL RMS, Sym.
Interr.② stand.
14.4 17.0 110 900
41 600 12 500
(10)★ (15) (110) (900)
25 29 125l 900
41 600 12 500
(20)★ (24) (125)l (900)
① System-voltage restrictions apply when the control is powered by S&C
Current/Voltage Sensors.
② Switches furnished with optional visible-break disconnect can carry up to
900 amperes continuous in ambient temperatures to 40°C (104°F) with a minimum
wind velocity of 2 feet (0.6 m) per second. Maximum allowable conductor tempera-
ture is 90°C (194°F). Without minimum wind velocity of 2 feet (0.6 m) per second, these
switches can carry up to 630 amperes continuous.
★ Minimum voltage rating.
l BIL equals 150-kV when there's no optional disconnect and the vacuum interrupter
is closed. BIL equals 150-kV with the optional disconnect and both the vacuum inter-
rupter and the optional disconnect are closed, or both the vacuum interrupter and the
optional disconnect are open.
For more information on the Scada-Mate SD Switching System, see publications 775-31 and 775-450 at sandc.com.
23
REMOTE SUPERVISORY SOURCE-TRANSFER
VISTA® UNDERGROUND DISTRIBUTION SWITCHGEAR
Vista Underground Distribution Switchgear is available in The vacuum bottles of any three-phase fault interrupter
Remote Supervisory and Source-Transfer models. Each offers way can be remotely tripped using external, user-specified
the same features and benefits of manual Vista switchgear, relays. This capability permits advanced applications such as
discussed in detail on pages 56 through 59. protective relay schemes using high-speed communication
for closed-loop and open-loop systems.
REMOTE SUPERVISORY VISTA SWITCHGEAR
Remote Supervisory Vista switchgear provides automated SOURCE-TRANSFER VISTA SWITCHGEAR
switching and fault protection, and it can also perform Source-Transfer Vista switchgear provides fully automatic
auto-sectionalizing without tripping the main breaker. primary-selective service for one, two, or three critical loads.
It includes an S&C Micro-AT® Source-Transfer Control, three-
Up to six load-interrupter switches or fault interrupters can
phase voltage sensing on source ways, and internal power
be motor-operated in a single unit of Vista switchgear. The
provided by voltage transformers. It is available in common-
motor operators may be battery powered or, optionally, self-
bus and split-bus configurations.
powered using internal voltage transformers. The low-voltage
compartment can be furnished with a user-furnished remote
terminal unit or 6800 Series Automatic Switch Control that
supports the IntelliTeam ® SG Automatic Restoration System
and a communication device.
Position-indicating lamps
Operation counter
24
AUTOMATION
REMOTE SUPERVISORY AND SOURCE-TRANSFER
VISTA UNDERGROUND DISTRIBUTION SWITCHGEAR
50/60-Hz ANSI Ratings—IEC Ratings in Parentheses
kV Amperes, RMS
Fault Interrupter Load-Interrupter Switch
Main Bus Short- Ten-Time
System Cont. and Cont. and Mom. and
Max BIL Cont. Circuit, Duty-Cycle
Class Load Load One-
Current① Sym. Fault- Interr.,
Dropping① Dropping① Second, Sym.
Sym.
① Higher ratings are possible. Consult the nearest S&C Sales Office.
Micro-AT®
Source-Transfer Control
Automatic-transfer Source-voltage
Ready indicating lamp indicating lamp
Overcurrent-
lockout indicating
lamp and reset Manual/automatic
key—included with operation selector
optional overcurrent- switch
lockout feature
Menu keys—
Voltage, Current,
Two-line × 24-character Time, Event,
Low-voltage compartment of Source-Transfer
liquid-crystal display Configure, Test, Vista switchgear featuring S&C's Micro-AT ®
and Examine Source-Transfer Control.
No external wiring or control power is required. Just Fault Fiter 200 200 12 500
connect the power cables, configure the remote terminal
unit (RTU), and the gear is ready for service. REMOTE SUPERVISORY AND SOURCE-TRANSFER PME
PAD-MOUNTED GEAR
SOURCE-TRANSFER PMH AND PME MODELS 60-Hz Ratings①
Source-transfer models use power-operated Mini-Rupter
Switches to provide fully automatic three-pole switching kV
Amperes
®
Mini-Rupter Switch, Fuse Short-
Circuit,
of the sources serving critical loads that require a high Load Amperes
Amperes,
Nom. Max BIL Cont. Type RMS, Sym.
degree of service continuity. A field-programmable Dropping Max
S&C Micro-AT ® Source-Transfer Control continuously SME-20 200En 14 000
monitors the status of the two sources and, if voltage 14.4 17.0 95 600 600 SME-4Z 200E 12 500
on the source serving the loads is lost, automatically Fault Fiter 200 14 000
initiates switching to transfer to the alternate source, SME-20 200En 12 500
thus restoring power to the loads. 25 27u 125 600 600 SME-4Z 200E 12 500
Fault Fiter 200 12 500
Source-transfer models are totally self-contained
① Consult the nearest S&C Sales Office for 50-hertz ratings.
switching and protection packages. Each is completely
u 25-kV models equipped with Fault Fiter ® Electronic Power Fuses are rated
factory-assembled and ready for installation. No external 29 kV max.
wiring or control power is required. n SMU-20 Fuse Units are available in ratings through 200K amperes as well as 200E
amperes.
Applicable to solidly grounded-neutral systems only, with fuses connected by a
single-conductor, concentric-neutral type cable to a transformer or transformers.
Rating is 9,400 amperes, RMS, symmetrical for all other applications.
26
AUTOMATION
Remote Supervisory PMH Pad-Mounted Gear Switch Operator
Switch-position target—indicates
whether a Mini-Rupter Switch is open
or closed
Decoupler indicator—shows
whether the switch operator is
coupled to a Mini-Rupter Switch
Decoupler handle—permits
convenient decoupling of the
switch from the switch operator for
functional testing of source-transfer
schemes and exercising of the switch
operator, without disturbing the
power circuit
®
S&C Micro-AT Source-Transfer Control—
microprocessor-based, field-programmable
Bolted covers—provide access to input connectors
and receptacles and terminal blocks
For more information on Remote Supervisory PMH Models, see publication 664-31. For Source-Transfer PMH Models, see publications
663A-30 and 663A-31. For Remote Supervisory PME Models, see publication 666-31. All of these publications are available at sandc.com. 27
HIGH-SPEED FAULT-CLEARING SYSTEM
Industrial and commercial power users are increasingly less The relays communicate with each other through a high-
tolerant to the frequency and duration of outages. Some speed fiber-optic cable network. Relays use the established
utilities have lost such customers to competitors offering transmission-relaying concepts of Permissive Overreaching
more reliable service. Transfer Trip (POTT) and Directional Comparison Blocking
(DCB) to ensure only the fault interrupters on either side of a
S&C’s High-Speed Fault-Clearing System was specifically
faulted backbone cable section open. SCADA isn’t required
developed to address this issue. It can be configured to
but can be readily integrated.
be essentially a no-interruption system for underground
applications. A fault occurring on any segment of the system Any number of switchgear units can be used in the system,
is automatically isolated. But service to the loads is not applied in a closed-loop or an open-loop configuration. In
interrupted (or the interruption is minimal). Communication- either case, a backbone feeder fault is cleared in 6 cycles or
dependent tripping is a key element of the design. less; there’s no need to trip the substation circuit breakers.
The system uses specially configured S&C Remote In a closed-loop application—such as the one shown on
Supervisory Vista® Underground Distribution Switchgear page 29—both ends of the loop must be fed from the same
(see page 24). Each fault-interrupter way of the gear substation. Load will not be lost while a fault is being cleared,
associated with the backbone feeder is equipped with a although some customers may experience a voltage dip.
multifunction, microprocessor-based relay. Each substation
In an open-loop application, feeders from different
circuit breaker feeding the loop of switchgear units is also
substations can be used; an open switching point is
equipped with such a relay.
required in the loop. Some customers may experience a
three- to four-second loss of voltage while the normally
open switch is closed.
28
Typical operation of High-Speed Fault-Clearing System
AUTOMATION
in a closed-loop application
1 3
2 4
Relay 5 detects fault current flowing in the direction of Relays 5 and 6 each recognize the other has sensed fault
its respective arrow, as does Relay 6. Each relay sends a current flowing in the direction of its respective arrow and
“forward fault detected” signal to the other relay. trips its respective fault interrupter. The faulted cable section
is de-energized, but service to the loads served by Vista Units
B and C is uninterrupted.
For more information on the High-Speed Fault-Clearing System, see publication 682-60 at sandc.com. 29
INTELLICAP® 2000 INTELLICAP® AUTOMATIC
CAPACITOR CONTROLS, INTELLINODE™ INTERFACE MODULE
IntelliCap 2000 Automatic Capacitor Control IntelliCap Automatic Capacitor Control
30
AUTOMATION
6801M AUTOMATIC SWITCH OPERATOR
6801M Automatic Switch Operator
6801M AUTOMATIC SWITCH OPERATOR When the associated distribution switches or disconnects
The 6801M Automatic Switch Operator is a fully have been fitted with voltage and current sensing, the
integrated, microprocessor-based operator that combines 6801M operator can be furnished with, or upgraded to,
electromechanical components, a remote terminal unit S&C's IntelliTeam SG Automatic Restoration System. This
(RTU), control circuitry, and communications in a single enables multiple 6801M operators to work together as
package for enhanced installation flexibility and reliability, teams with IntelliRupter® PulseCloser® Fault Interrupters,
and reduced cost. 6800 Series Automatic Switch Controls, and IntelliNode™
Interface Modules.
The 6801M Automatic Switch Operator monitors the entire
switching cycle and can automatically take corrective
action in the event of a problem. It is particularly designed
to operate Omni-Rupter ® Switches and Alduti-Rupter ®
Switches, which are featured on pages 86 to 93. See also the
discussion on S&C’s Smart Grid Services on page 47.
For more information on IntelliCap 2000 Automatic Capacitor Controls, see publications 1024-30 and 1024-31. For more information on IntelliCap
Automatic Capacitor Controls, see publications 1022-30 and 1022-31. For more information on the IntelliNode Interface Module, see publications
31
1043-30 and 1043-31. For the 6801M Automatic Switch Operator, see publication 1045M-30. All of these publications are available at sandc.com.
IPERC GRIDMASTER® MICROGRID CONTROL SYSTEM
The distributed design and construction ensures all electrical ¡¡ IPV6 standard; IPV4 compatible
demand is satisfied while maximizing efficiency and uu Control boot time:
eliminating single points of failure. Ultimately, the GridMaster ¡¡ Typical: 30 seconds; maximum: 120 seconds
system is an economical and effective way to achieve
maximum energy independence by providing: uu Front panel indicators:
¡¡ Green power LED display illuminates when on
uu Reduced energy costs
¡¡ Recessed power switch
uu Reduced fuel consumption and CO2 emissions
uu Optimal integration of renewable energy and energy ¡¡ Base unit: 9.5 lbs. (4.3 kgs)
storage assets ¡¡ Communication modules: 0.21 lbs (0.1 kgs) each
uu Mechanical vibration:
32
AUTOMATION
Intelligent Power Controller (Rack Mount)
19.0
(483)
∅ .30
13.00
(330)
8.25 (210)
3.82
(97)
9.25 (235)
More information about IPERC Gridmaster Microgrid Control System is available at sandc.com. 33
INTELLITEAM® SG AUTOMATIC RESTORATION SYSTEM
Introduced in 1996, the IntelliTeam Automatic Restoration System was the first product of its kind. The system uses peer-to-
peer communication with distributed intelligence to track system conditions and quickly initiate service restoration. It was
way ahead of its time.
In 2003, S&C brought out the IntelliTeam ® II Automatic uu Rapid Self-Healing, which isolates faulted section and
Restoration System—an order of magnitude more powerful restores service to non-faulted sections in seconds (An
than the original. Highly scalable, it supports complex system example is shown on page 35.)
architectures and multiple tie points from multiple sources. uu Communication Enhanced Coordination,
It uses teams of switches to restore service to affected circuit which improves feeder segmentation and reduces
segments when faults or loss-of-source events occur, and it momentary interruptions (In a system where
manages all of this based on allowable line loading. Moreover, IntelliRupter ® PulseCloser ® Fault Interrupters share
each team can have up to eight switches, arranged in radial or the same protection curve, only the IntelliRupter
looped circuits, or a combination of both. fault interrupter closest to a fault will open.)
Now, S&C has advanced IntelliTeam technology with the uu Post-Restoration Load Management, which protects
IntelliTeam SG Automatic Restoration System. It’s even more reconfigured system from loading that exceeds the
robust and easier to use and offers such important features as: capabilities of the system
uu Closed-Loop Operation, which eliminates the need for a
®
uu IntelliTeam Designer, which simplifies system
configuration (Just draw a single-line diagram of your normally open switching point in applications where the
distribution circuits, and the IntelliTeam Designer loop is served from two substations
application will apply all of the IntelliTeam SG settings to uu Site Automation Testing, which lets you emulate
all of the associated team members automatically.) events using actual site parameters and peer-to-peer
communication and—optionally—operate switches
uu Instant Replay, which collects event logs from affected
devices and provides the ability to replay the events on the
systems single-line diagram
IntelliRupter® PulseCloser® Fault Interrupter Remote Supervisory Vista® Underground Distribution Switchgear
34
A TRULY UNIVERSAL SOLUTION 1
The IntelliTeam SG Automatic Restoration System is an Rapid Self-Healing Loss of SRC3,
open platform offering unmatched interoperability. It IntelliTeam® SG Automatic Restoration System
can automate new or existing circuits. It works with
S&C IntelliRupter fault interrupters; Scada-Mate® ,
Scada-Mate CX™ , and Scada-Mate® SD Switching Systems;
Remote Supervisory PMH and PME Pad-Mounted Gear;
and Remote Supervisory Vista ® Underground Distribution
Switchgear.
SOFTWARE
With the IntelliTeam SG Automatic Restoration System,
restoration proceeds without the delays inherent in a
dispatcher-operated or centrally controlled system. The
IntelliTeam SG system monitors real-time current and voltage
2
throughout the system and uses this information to make
smart switching decisions to restore service when outage Rapid Self-Healing Loss of SRC3,
events occur on the system. IntelliTeam® SG Automatic Restoration System
For more information on the IntelliTeam SG Automatic Restoration System, see publication 1044-34 at sandc.com.
For interactive demonstrations of the IntelliTeam SG system derived from real test scenarios
35
using actual switch controls and communication devices, go to sandc.com/it2a.
INTELLITEAM® FMS FEEDER MANAGEMENT SYSTEM
BENEFITS OF DEVICE MANAGEMENT DEVICE DATA & FILE RETRIEVAL
Advanced tools are needed to efficiently manage an uu File Retrieval. Utilities often use traditional methods
entire fleet of automated devices, saving engineers and and tools to access waveform and event files—either
system operators time. This also allows them to work more one device at a time or by rolling a truck. IntelliTeam
effectively, thus further leveraging the smart grid investment FMS facilitates bulk retrieval, both on demand and on
to improve reliability. a scheduled basis.
uu Data Collection. Collecting, organizing, managing, and
To fully realize the benefits of a self-healing smart grid,
displaying relevant data is often done via SCADA and a
S&C offers the IntelliTeam FMS Feeder Management System.
historian, but IntelliTeam FMS does this automatically for
This enterprise software can significantly improve a utility’s
S&C devices and does so while collecting points SCADA
operational efficiency and overall reliability by managing
systems can’t access, such as setpoints.
devices and providing insightful data analytics from an
entire fleet of S&C automated smart grid devices. uu Reporting. Many utilities spend considerable time
defining, generating, and maintaining basic device status
SAVING OPERATIONAL TIME reports. IntelliTeam FMS generates several key reports
By leveraging IntelliTeam FMS software features to automate and custom dashboard displays, which can be exported.
otherwise manual tasks done on a point-by-point, device-
by-device basis, six to eight hours per device can be saved DEVICE CONFIGURATION
annually through improving and automating tasks in three uu Settings Management. Configuring new devices
operational areas: and changing device settings all can be managed by
IntelliTeam FMS. Settings changes also can be applied
DEVICE TRACKING & MAINTENANCE MONITORING across multiple devices, saving many hours when a
uu Device Details. The IntelliTeam FMS displays data related fleet-wide change is required.
to individual devices, enabling a user to diagnose many
uu Change Logs. Without change logs, diagnosing a
issues quickly. Available data include diagnostics, team
problem with a device becomes a matter of detective
status, calibration, settings, and more.
work. IntelliTeam FMS solves the mystery by logging who,
uu Dashboards. Many utilities investigate devices manually when, and what was changed.
or react to SCADA alarms. IntelliTeam FMS offers an
uu Device Filtering. IntelliTeam FMS allows a user to work
automated and proactive approach with both table and
with almost any group of devices based on a wide array
graphical dashboards that automatically track Team
of filtering options. This saves a lot of time when working
Ready statuses and monitor battery health, firmware
with a subset of devices.
versions, and more.
uu Alert Management. Addressing the numerous alerts INCREASING RELIABILITY
devices generate can be a time-consuming task. IntelliTeam FMS’s features help utilities identify issues
IntelliTeam FMS makes it easy to filter down to only before they result in a device not operating as intended.
those devices and alert types that are relevant. Misoperations can cause outages or lost opportunities to
leverage grid automation to restore power. With a fleet of
Dashboards 400 devices, 10 such misoperations can be avoided annually
in three process areas:
36
TEAM STATUS MONITORING Device Filtering/Working Sets
uu Dashboards. Team-Ready statuses and reasons why teams
aren’t in a Ready state are displayed. Communication issues
are a leading cause of teams falling out of a Ready state,
so IntelliTeam FMS offers a dedicated dashboard to track
communication statuses.
uu Alerts. IntelliTeam FMS enables a review of alerts related
to devices falling out of a Ready state, such as being set to
manual operation.
SOFTWARE
DEVICE CONFIGURATION
uu Settings Templates. Utilities can create ideal configurations
for their devices and then replicate those settings to their
entire fleet using saved templates. This avoids manual
settings errors and the use of factory default settings.
uu Device Filtering. Filtering in IntelliTeam FMS is primarily
used to allow working with specific sets of devices, but the
system also can be used to find devices with certain statuses
or settings that must be addressed.
uu Change Logs. Knowing what was changed in a device
can prevent an outage if the change wasn’t intended to
be permanent.
DEVICE COMMUNICATION
IntelliTeam FMS is designed to communicate with S&C devices
via fiber-optic cables and radio, such as S&C SpeedNet ™
Radios or those from third-party vendors. Several technologies
help IntelliTeam FMS adapt to the bandwidth available:
uu User-configurable data-collection intervals.
The frequency at which IntelliTeam FMS contacts a device
for various types of data can be adjusted from seconds to
days based on a utility’s needs and the bandwidth available.
uu Staged Communications. IntelliTeam FMS has the ability
to communicate with only a single device at a time on each
feeder. Communicating with random devices could cause
bottlenecks at the head-end unit if multiple devices on a
feeder are responding to requests concurrently.
uu Adaptive Communications. IntelliTeam FMS communicates
with a set number of devices concurrently for collecting
various types of data, and it adapts to network-response
time. If responses are delayed, then IntelliTeam FMS will not
schedule new data-collection requests until the previous
requests are completed.
For more information on the IntelliTeam FMS Feeder Management System, see S&C publication 1048-31, or visit sandc.com/FMS. 37
INTELLITEAM® CNMS
COMMUNICATION NETWORK MANAGEMENT SYSTEM
As the number of networked grid devices increases, so Benefits include:
does the difficulty of managing network communication. uu Better network awareness and control. Periodic data
Designed to meet the specialized needs of electric utilities, are collected from each radio, with statistics and settings
S&C’s IntelliTeam ® CNMS Communication Network displayed in tables and dashboards. Radio-configuration
Management System simplifies monitoring and management settings for SpeedNet Radios can be changed easily from
of S&C SpeedNet™ Radio and SpeedNet™ SDR Software the CNMS interface.
Defined Radio networks supporting SCADA and distribution
uu Extensive network-visualization capabilities.
automation applications.
Interactive Google Maps interface with color-coded
The IntelliTeam CNMS Communication Network Management link strengths and Google Earth export capabilities for
System provides utilities with a comprehensive view of offline analysis.
network configuration and performance through a browser- uu Easier problem identification. Data filters and visual
based interface. It lets authorized users monitor near real- indicators for alarms and link qualities help administrators
time and archived data on radio networks of all sizes. Users quickly identify problem radios.
can manage each individual radio and effect configuration uu Greater operational efficiency. Network administrators
changes, data backup, and remote firmware upgrades. can perform their duties in a fraction of the time
compared to using the Client Tool.
38
Radio Configuration Settings for SpeedNet Radios Can Be Changed Easily from the Radios Tab
SOFTWARE
Alarms Help Administrators Quickly Identify Problem Radios
For more information on the IntelliTeam CNMS Communication Network Management System, see publications 1073-30 and 1073-31 at sandc.com. 39
SPEEDNET™ RADIOS
SPEEDNET™ CELL EDGE GATEWAY
Reliable communication networks are a critical component As part of the SpeedNet Radio family, the SpeedNet ™ ME
of SCADA and grid-automation systems. When choosing a Mesh End-Point Radio is designed specifically for the
communication solution, a few key parameters to consider communication needs of end-node SCADA devices. It
are resiliency, latency, and security. provides a fast link to its next-hop neighbor(s), which can be
a SpeedNet Repeater Radio that is part of a SpeedNet Radio
Built-in redundant paths and no single point of failure
mesh network or the actual destination. Because it is used as
are inherent features of SpeedNet mesh radio networks,
an end point only, the SpeedNet ME Mesh End-Point Radio
which provide the resiliency required by mission-critical
does not have the ability to perform as a repeater, headend,
grid applications. These radios also support point-to-point
or gateway. It does, however, connect to a SpeedNet Radio
and point-to-multipoint modes of deployment. S&C’s
mesh network that is capable of providing secure, long-range
SpeedNet mesh radios provide the reliable, high-throughput
communication with high message rates.
communications essential to the IntelliTeam® Automatic
Restoration System, and SCADA-only applications.
SpeedNet™ ME Mesh End-Point Radio
SPEEDNET™ RADIOS
SpeedNet Radios deliver low-latency, self-healing
performance. They are equipped for high-volume data
transmission, enabling automation in difficult-to-access
areas. A peer-to-peer mesh network of SpeedNet™ Radios
is easy to set up and maintain. The radios automatically
build routing tables that define message paths. If a node is
lost, the radios quickly establish a new path.
40
By offering the flexible balance of data rates, propagation CONNECTIVITY FOR SCADA AND
range, and interference mitigation, S&C’s SpeedNet SDR radio INTELLITEAM® FMS FEEDER MANAGEMENT SYSTEM
provides a resilient mesh network for grid automation. Utilities without a private wireless network can use the
SpeedNet Cell Edge Gateway as their primary network for
SpeedNet SDR Software Defined Radio SCADA and/or IntelliTeam FMS connectivity.
COMMUNICATIONS
to expand connectivity to remote devices outside the
coverage area of existing utility field area networks. By
SPEEDNET™ CELL EDGE GATEWAY adding communication to devices, you enable monitoring
The SpeedNet Cell Edge Gateway provides a flexible and control functions. The SpeedNet Cell Edge Gateway can
way for devices to securely leverage a cellular network. be deployed in many unique cases to provide connectivity
Data-intensive applications are better managed by an where previously there was none.
alternative network because backhauling large volumes
SpeedNet Cell Edge Gateway
of data over the distribution automation network could
compromise self-healing during an outage. Cellular
networks already in your service area provide a cost-
effective opportunity for utilities to monitor and control
grid devices over a secondary communication network.
COMPARISON MATRIX
SpeedNet 900 Radios SpeedNet™ SDR Software Defined Radios
SpeedNet™ SpeedNet™ ME SpeedNet SDR 4 SpeedNet SDR 4x4 SpeedNet SDR 9 SpeedNet SDR 9x9 SpeedNet™ Cell Edge Gateway
Radio Mesh Radio Radio Radio Radio Radio
3G: 850 MHz, 1900 MHz
Frequency 902-928 MHz 406-430 and 450-470 MHz 928-960 MHz 4G: 700 MHz, 850 MHz, 1700/2100
MHz, 1900 MHz, 2300 MHz
Idle Channel
10 milliseconds 28 milliseconds 14 milliseconds 14 milliseconds 7 milliseconds 100-200 milliseconds①
Latency
Encryption 128-bit AES 256-bit AES 256-bit AES 256-bit AES, ECC
① Many factors affect the speed and performance of cellular devices, including proximity to a cell site, the capacity of the cell site, the surrounding terrain, placement of the
cellular device inside equipment, radio-frequency interference, the number of other devices attempting to use the same spectrum resources, the data plan from wireless
carrier, and weather.
For more information on SpeedNet Radios, see S&C publications 1072-30 and 1072-31. For more information on the SpeedNet ME Mesh End-Point Radio,
see S&C publications 1074-30 and 1074-31. For more information on SpeedNet SDR Software Defined Radios, see S&C publications 1075-30 and 1075-31.
41
For more information on SpeedNet Cell Edge Gateway, see S&C publications 1076-30 and 1076-31. These publications are available at sandc.com.
ANALYSIS DESIGN
S&C’s Power Systems Solutions team of automation-system planning, energy storage, renewable energy, and engineering
experts has vast expertise in the real-world application of technology for improved grid reliability. They’re well-suited to
perform the study, engineering and design, project management, and field services needed to deliver a complete smart grid
solution. These services can be furnished individually or as a complete solution.
42
uu Power-flow studies. S&C determines whether ENGINEERING SERVICES
system voltages remain within specified S&C’s engineering and system design services provide
limits under various contingency conditions, and the best long-term value to your toughest power
whether transformers and conductors system challenges. Our professional engineers dedicate
are overloaded. themselves to being specialists in their fields and applying
uu Reliability studies. Such research helps to that knowledge toward your project vision. S&C engineers
maximize the reliability, efficiency, and safety of hold professional engineering licenses throughout the
a power system. United States. Let us show you how we differentiate
ourselves through S&C’s commitment to quality and in
uu Switching transient studies. S&C will analyze
delighting our customers through world-class services.
the transients associated with the switching
of utility or industrial capacitor banks or shunt Preliminary and Detail Design
reactors, or the performance of transient uu Single-line drawings
mitigation devices during capacitor bank or
uu Civil, electrical, and structural engineering
transmission-line energization.
uu 30%, 60%, and 90% design packages
uu Voltage-stability analysis and model
development. This research is associated with uu Dc and ac schematics
generator interconnection, including renewable uu Grounding drawings
power plants, and is often performed during the uu Lightning protection drawings
generator interconnection application process
uu Wiring diagrams
to evaluate impact of the generator on system
voltage stability. uu Control room design
uu Harmonic studies. Such research assesses the uu Physical layouts, sections, and details
impacts of harmonic-producing loads, such as uu Foundation layouts and details
inverters and other power-electronic equipment, uu Equipment and construction specifications
on the levels of harmonic voltage and current on
uu Bills of material
the utility system.
uu Filter design studies. These are performed Protection and Control Design
to determine passive harmonic filter design uu Bus arrangement and layout drawings
SERVICES
parameters in cases where it is necessary to uu Protection and control logic diagrams
convert shunt capacitor banks to harmonic filters. uu Relay panel layout and settings
uu Insulation coordination studies. These confirm
whether surge arresters applied for equipment SCADA Engineering
transient overvoltage protection caused uu System programming and commissioning
by lightning and switching surges provide uu SCADA points lists
sufficient margins of protection. In renewable uu SCADA screen development and design
power plants, insulation coordination studies
uu Historian design
also include temporary overvoltage analysis to
determine sizing for grounding transformers uu Configuration files
to ensure effective grounding during plant or uu ISO, developer, and utility integration
feeder islanding conditions.
Construction Support
uu On-site engineering support
uu Issued for construction (IFC) drawings
uu System programming and commission
uu Project close-out manuals
uu Indexed As Built Drawing Packages
43
PROJECT EXECUTION
ENGINEERING, PROCUREMENT, FIELD SERVICE
AND CONSTRUCTION S&C’s field-service specialists take our expertise in electrical
S&C’s Power Systems Solutions team takes projects from power systems into the real world with a comprehensive
initial system study and design through to start-up and range of services to support your project needs. From
commissioning in the field. After commissioning, most equipment start-up and personnel training through long-
engineering, procurement, and construction (EPC) work term maintenance, we’re committed to sustaining the life of
for companies is done, but S&C continues to support its your equipment and improving power reliability.
solutions by offering comprehensive asset-management
Installation Support
services, including preventative maintenance and 24x7
remote monitoring. S&C’s technical experts have years of hands-on experience
in the proper installation, testing, and commissioning
S&C offers comprehensive EPC services for a variety of major of S&C’s products. S&C will bring this unique expertise
project settings, including microgrids, substations, and to the customer’s project, ensuring equipment is ready
renewable energy plants. for operation.
S&C offers the following services when executing complex S&C’s experts manage the installation of electric
EPC projects: power equipment, such as circuit-switchers, automatic
source-transfer switchgear, metal-enclosed switchgear,
Engineering & Project Management
overhead distribution equipment, automation systems,
S&C’s engineering and project management success is
power quality and energy storage equipment, and pad-
founded on expert planning, commitment to safety, and
mounted equipment, performing all essential testing and
problem-solving. Engineers produce designs for diverse
commissioning procedures. Installation services can vary in
and complex projects, and our project managers oversee
scope, from providing technical assistance to the customer’s
the scope, schedule, cost, quality, and completion of
crew through complete turnkey support from S&C.
these projects.
Mechanical Checkout, Start-up, and Commissioning
Procurement
For equipment such as automated distribution switching
S&C has the resources and capabilities to procure the
packages, our field-service specialists can provide the testing
equipment, materials, skilled labor, and services needed to
necessary to ensure the system is functioning properly.
get the job done. S&C has established databases of suppliers
Typical commissioning activities include:
and subcontractors with whom we’ve worked around the
uu System and component inspection prior to energization
world and on a variety of projects and project types.
uu Field adjustments
Construction
uu Calibration and programming
S&C’s construction managers oversee on-the-ground
uu Equipment start-up
execution of projects around the world. They are dedicated
to providing expert guidance and solutions for all phases uu System evaluation to ensure conformance to performance
of the construction process and ensure proper equipment specification
installation for every project.
TESTING
44
S&C is the only company in North America able to provide IntelliTeam ® SG Automatic Restoration System Factory
an entire suite of in-house facilities and services to address Acceptance Testing
your testing needs. Most common testing practices include
Factory acceptance testing on devices running S&C’s
material analyses, electrical testing, mechanical testing, and
IntelliTeam SG Automatic Restoration System ensures
forensic testing.
that all information required for a successful IntelliTeam
At the heart of S&C’s state-of-the-art, 43,000-square-foot SG implementation is gathered and understood before
Advanced Technology Center (ATC) is the Nicholas J. Conrad commissioning. Each test is customized to the customer’s
Laboratory, which has two 850-megawatt electrical short- needs. Scenarios can include:
circuit test generators that can test up to 80 kA and up to uu A loss of source for each source
230 kV. The facility also provides a high-speed video system, uu A fault simulation for each line segment
showing real-time data as testing events occur.
uu Contingency events
S&C also offers onsite testing in the field by our experienced
Site Automation Testing
service professionals, including site automation testing,
Site automation testing validates the IntelliTeam SG
operational testing, and radio validation surveys.
implementation in the field. It provides significant insight
S&C Equipment Factory Acceptance Testing into how the IntelliTeam SG system will work on the user’s
S&C routinely provides customer-witnessed factory system using their specific settings. The field engineer
acceptance testing on various pieces of S&C equipment assigned to a site automation test works closely with users to
before shipment to ensure the equipment performs as develop customized and meaningful test scenarios.
required. Factory acceptance testing will vary depending
Operational Testing
on the equipment being tested. Examples include routine
S&C field service technologists can coordinate on-site
tests, such as circuit board and subassembly functionality;
operational testing procedures, including opening energized
mechanical inspection, wiring, insulation resistance, Hi-Pot,
load ways to observe proper system operation. S&C can also
and other tests; or the testing can include customer-
coordinate site-specific test procedures.
specified tests.
Radio Validation Survey
S&C’s field service personnel can perform an on-site radio-
validation survey to properly locate radios for optimum
SERVICES
system startup and performance. The survey determines
individual links that make up the mesh radio network. The
scope of work includes identifying ideal locations for a
mesh radio network and temporarily installing radios while
measurements are made. S&C will evaluate the results of the
survey and provide a written report of recommendations.
45
POST-INSTALLATION SUPPORT
S&C’s regional service centers are located across the nation, uu Cleaning
offering timely support and expertise for necessary repairs uu Lubrication
and restoration services.
uu Adjustment
REMOTE MONITORING & TECHNICAL SUPPORT uu Equipment troubleshooting
Through the Global Support & Monitoring Center (GSMC), uu Repair of non-functional or damaged equipment
S&C provides 24/7 condition-based monitoring of equipment
using pre-installed monitoring hardware. When conditions EQUIPMENT RETROFIT AND UPGRADE
fall outside of normal parameters and a notification is issued, S&C upgrade and retrofit programs can include all parts,
our support staff immediately begin the troubleshooting project coordination, engineering services, and field support
process to resolve issues. necessary to execute the work.
The list below highlights some of the major equipment types Upgrade and/or retrofit programs are available for:
S&C can monitor: uu Circuit-switchers
uu Automation systems:
Circuit breakers
uu Gas pressure and temperature
¡¡ Switching equipment including overhead
and underground distribution switchgear
uu Bushing partial discharge
¡¡ Software
uu Open/Close operations
¡¡ Automatic switch control
PureWave ® DSTATCOM Distributed Static Compensator ¡¡ Communication
and PureWave SMS Storage Management System
uu Real and reactive power EXTENDED WARRANTY
uu System voltages and currents
Besides a standard two-year warranty for new equipment,
S&C offers an extended-warranty program to help extend the
uu System and inverter availability
life of new and existing equipment. S&C provides dedicated
IntelliTeam ® CNMS Communication Network service visits, equipment troubleshooting, and parts repair
Management System and replacement for the duration of the warranty. Contact
uu S&C SpeedNet™ Radios your local S&C representative for more information.
uu Other S&C products with IntelliTeam SG connectivity uu Equipment operation, maintenance, and troubleshooting
46
APPLICATIONS
SUBSTATIONS SMART GRIDS
S&C provides turnkey services for building substations, S&C’s smart grid solutions
including physical design engineering, protection and feature best-in-class
control design engineering, detailed installation drawings, software, switching, and
contractor selection and oversight, on-site testing and communications products to
commissioning, and asset-management services. provide advanced system-
automation capabilities.
RENEWABLE ENERGY PROJECTS
From S&C metal-enclosed
For both wind and solar applications, S&C works with switchgear to service-
you and the local utility to find the most economical and restoration software,
feasible solutions to deliver the best long-term value. S&C is customers get the most out
an industry leader in renewable energy solutions, providing: of S&C smart grid products
uu Medium-voltage protection and control equipment when combined with our engineering, installation,
specifically for renewable energy installations commissioning, monitoring, and asset-management
uu Extensive working experience and strong relationships services.
with local utilities and ISOs
MICROGRIDS
uu Full EPC approaches to reduce system footprints, Microgrids are inherently complex. Integrating a variety
construction costs, and project schedules of distributed generation sources together into one
uu Standard equipment packages to help reduce electrical system is a challenging task, which is further
equipment and installation lead times by up to 60% complicated by achieving microgrid functionality such as
load shedding, islanding, and self-healing. From analysis
and engineering to monitoring and maintenance, S&C
works with customers to design and implement complex
microgrid systems for various applications. In addition
to providing comprehensive EPC services, S&C also
manufactures the core components of a microgrid: the
controller and the switchgear. While competitors package
these components in a variety of ways, S&C is the only
integrator in the industry to provide all key components
SERVICES
necessary for a total microgrid project.
3 4 3 4
V V V V V V
S S S S S S
S S
O O
S S
2 2 2 3 4 3 4 3 4 T
C
T
C
S S
O O
V V V V V V
S S S S S S
2 1 2 1
PMH-6 PMH-9
1 1 1 2 1 2 1 2 1
PMH-3 PMH-4 PMH-5 PMH-6 PMH-7 PMH-8
3 4 3 4
S S
T T
2 1 2 1 2 1 2 1 2 1 2 1 C C
PMH-9 PMH-10 PMH-11 PMH-12 PMH-13 PMH-19 S S S S
O O O O
2 1 2 1
PME-6 PME-9
2 2 3 4 3 4 3 4 3 4 3 4
1 1 2 1 2 1 2 1 2 1 2 1
2 2 3 4 3 4 3 4 3 4 3 4
L L L L
V V V S S V S
C C C O O C O
L L S
S V S V S S S S S S S S S
O O O O O O O O O O O O
C C
MEDIUM VOLTAGE
1 1 2 1 2 1 2 1 2 1 2 1
PMH-3 PMH-5 PMH-6 with 1 or 2 PMH-9 with 1 or 2 PMH-10 with 1 or 2 PMH-10 with 4 PMH-11 with 1, 2, or 3
Switch Operators Switch Operators Switch Operators Switch Operators Switch Operators
2 3 4 3 4 3 4 3 4
L L L L
V V V S V S
C C C O C O
L
V
C
S S S S S S S S S
O O O O O O O O O
1 2 1 2 1 2 1 2 1
PME-5 PME-6 with 1 or 2 PME-9 with 1 or 2 PME-10 with 1, 2, 3, or 4 PME-11 with 1, 2, or 3
Switch Operators Switch Operators Switch Operators Switch Operators
49
PMH PMEPAD-MOUNTED GEAR
®
S&C’s Uni-Rupter Interrupter—provides the
ultimate in single-pole live switching ... just a firm
Insulated roof—“No-drip”
compound on the underside
Dual-purpose front barriers of GPO3-grade,
fiberglass-reinforced polyester—guard against
opening pull on the fuse interrupts the circuit with of the roof guards against inadvertent contact with live parts when in the
a quick-break action; the Uni-Rupter Interrupter formation of condensation that normal vertical position; inserted into the open
self-resets for the next opening operation. could drip onto energized parts gap of a switch or fuse, the barrier provides
Separate current-carrying and fault-closing isolation from bus and upper contacts
contacts are provided
Grappler™ Handling Tool—takes the work
out of fuse handling; it provides sure grip,
Corrosion-resistant non-ferrous perfect balance, and ready control that
door hinges and hinge pins operators appreciate
uu Optional UL Listing
★
®
Fuse compartments illustrate a nonstandard combination of Fault Fiter Electronic Power Fuses (on left) and SML-20 Power Fuses (on right) for comparison only.
50
Viewing window—for visible verification Aluminum bus connections—wire-brushed and
of the switch position is easily removed protected by an oxide-inhibiting abrasive compound—
Penta-Latch
Mechanism—
®
for voltage testing or phasing are bolted at a uniform torque of 50 ft-lbs; two spring
provides
washers per bolt maintain contact pressure
vandal-
Optional mounting provisions for resistant,
automatic,
a fault indicator with a viewing
window in the door—accommodate
®
S&C Mini-Rupter Switch—the field-
tested and proven 600-A three-pole
three-point
one three-phase indicator with door latching for
group-operated interrupter switch
single-phase sensors (fault indicator S&C Pad-Mounted Gear and is fully
shown for illustrative purposes only) coordinated with a provision for
padlocking
Optional terminal Optional distribution-class Interphase and end barriers—GPO3- Optional fuse-
adapters—can be added at surge arresters—available in grade, fiberglass-reinforced polyester storage feature—
all switch and bus terminals to 9-kV through 18-kV ratings for for superior arc and track resistance; accommodates up to
accommodate two connectors application at the source-side switch barriers are easily removed to three spare SML fuse
per terminal switch terminals facilitate terminating cables assemblies, one spare
®
Fault Fiter Electronic
Power Fuse holder, or
PMH PAD-MOUNTED GEAR two spare Fault Fiter
interrupting modules
60-Hz Ratings①
kV
Mini-Rupter
®
Switch, Amperes
Fuse
Short-Circuit,
Amperes Amperes, RMS,
Load Sym.
Nom. Max BIL Cont. Type Load Dropping
Dropping Max
MEDIUM VOLTAGE
with Uni-Rupter
SML-20 200En 200 14 000
SML-4Z 200E 200 12 500
14.4 17.0 95 600 600
Fault Fiter
Electronic
® 200 200 14 000
Power Fuse
SML-20 200En 200 12 500
SML-4Z 200E 200 12 500p
25 27u 125 600 600
Fault Fiter
Electronic
® 200 200 12 500
Power Fuse
① Consult the nearest S&C Sales Office for 50-hertz ratings.
®
u 25-kV models equipped with Fault Fiter Electronic Power Fuses are rated 29 kV max.
®
n SMU-20 Fuse Units are available in ratings through 200K amperes as well as 200E amperes.
p Applicable to solidly grounded-neutral systems only, with fuses connected by single-conductor,
concentric-neutral-type cable to a transformer or transformers. Rating is 9,400 amperes, RMS, symmetrical
for all other applications.
For further information on Manual PMH Models, see publications 662-30 and 662A-31 at sandc.com. 51
PMH PMEPAD-MOUNTED GEAR
Viewing windows—allow easy Generous spacing of bushing wells and parking 200-A Cypoxy™ Insulator bushing
checking of blown-fuse indicators stands—accommodates a full spectrum of elbows, wells—have interfaces in accordance
portable feed-thrus, and accessories with ANSI/IEEE Standard 386
52
Hinged roof—allows
cable to be pulled
up through the roof
opening, making
installation quicker
and easier
Wide-view, unbreakable, 600-A Cypoxy™ Insulator bushings—have
mar-resistant windows— interfaces in accordance with ANSI/IEEE Standard 386
let the operator verify
®
Mini-Rupter Switch position
and check for a visible break Parking stands—accommodate
a variety of accessories
Ground rod—extends
full width of each switch Segregated Deep, spacious termination
compartment; doors may compartment—steel compartments—accommodate
be closed with grounding barriers isolate side-by-side a wide range of elbows and
clamps in place cable compartments accessories with the doors closed
kV
Amperes
®
Mini-Rupter Switch,
Fuse Short-Circuit,
Amperes, RMS,
Load Sym.
Nom. Max BIL Cont. Type Amperes, Max
Dropping
MEDIUM VOLTAGE
SME-20 200En 14 000
SME-4Z 200E 12 500
14.4 17.0 95 600 600
Fault Fiter
Electronic
® 200 14 000
Power Fuse
SME-20 200En 12 500
S&C’s Ultradur™ II Outdoor Finish
SME-4Z 200E 12 500p provides an extremely tough, multistage,
25 27u 125 600 600 baked-on finish with exceptional
Fault Fiter
Electronic
® 200 12 500 performance proven by the most rigorous
Power Fuse battery of tests in the industry. Featured on
both PMH and PME Models.
① Consult the nearest S&C Sales Office for 50-hertz ratings.
®
u 25-kV models equipped with Fault Fiter Electronic Power Fuses are rated 29 kV max.
®
n SMU-20 Fuse Units are available in ratings through 200K amperes as well as 200E amperes.
p Applicable to solidly grounded-neutral systems only, with fuses connected by single-
conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9,400 amperes,
RMS, symmetrical for all other applications.
For more information on Manual PME Models, see S&C publications 665-30 and 665-31 at sandc.com. 53
PMH PMEPAD-MOUNTED GEAR
Brilliant blaze-orange
blown-fuse target—
appears at top of
interrupting module
after Fault Fiter fuse
operates; it’s lucent by
daylight or flashlight
Lustrous-red blown-fuse
target—projects from the top
of the upper-end fitting when
the fuse unit has operated, and Fluorescent fire-red
it automatically resets when blown-fuse target—
Replaceable
a blown fuse unit is replaced; moves to the “BLOWN”
interrupting
fuse condition is easily indicator window in
module
checked with the fuse in the the translucent holder
Closed position when the fuse operates,
permitting a positive visual
check of fuse condition
without removing the fuse
from the mounting; target
fluoresces at night when Electronic
illuminated with a flashlight control
module
SML-20 (shown) and SME-20 Power SML-4Z and SME-4Z (shown) Power
®
Fault Fiter Electronic Power Fuse (shown
Fuses—rated 200E or 200K amperes max
continuous; 60-hertz interrupting ratings
®
Fuses—use S&C’s SM-4 Refill Unit
and are rated 200E amperes max
in fuse holder for mountings with Uni-Rupter
Interrupter)—rated 200 amperes max
®
are 14,000 amperes RMS, symmetrical, at continuous; 60-hertz interrupting continuous at both 14.4 kV and 25 kV in PMH
14.4 kV, 12,500 amperes RMS, symmetrical, rating is 12,500 amperes RMS, Models (In PME Models, the max continuous
at 25 kV (These power fuses feature S&C’s symmetrical at both 14.4 kV and 25 kV rating is 200 amperes at both 14.4 kV and 25 kV.
®
SMU-20 Fuse Unit, designed for universal
use on both your underground and
60-hertz interrupting ratings are 14,000 amperes
RMS, symmetrical, at 14.4 kV, 12,500 amperes
overhead distribution systems.) RMS, symmetrical, at 25 kV.)
®
S&C Power Fuses with the Uni-Rupter Interrupter feature single-pole live switching of single-phase or three-phase load circuits.
TransFuser™ Mountings are furnished with 200-ampere bushing wells for loadbreak or non-loadbreak elbow connections to cable.
54
Fault Fiter ® Electronic Power Fuses combine an
innovative high-tech electronic control module with a
® ®
SMU-20 FUSE UNIT AND SM-4 REFILL UNIT RATINGS
Available Ratings, Amperes
unique interrupting module to solve difficult protection Speed
SMU-20 Fuse Units SM-4 Refill Units
and coordination applications. The control module
S&C “K” 3K—200K —
incorporates a current transformer and circuitry to provide
S&C Standard 1—200E 1—200E
current sensing and the TCC as well as the energy to initiate
S&C Slow 15E—200E 15E—200E
interruption. The Fault Fiter fuse’s unprecedented variety
S&C Very Slow 50E—200E —
of unique electronically derived TCCs provide superior
S&C Coordinating — 210◆
protection and precise coordination for a wide range of
applications. Because the TCC isn’t determined by a fusible ◆ Available in 14.4-kV PMH and PME Models only.
Cooper
McGraw - Edison NX ® 15.5 1.5C —100C
25
23 6C — 40C
MEDIUM VOLTAGE
8.3
3 —50 14.4
15.5
®
RTE ELX 15.5 3 —50
25
23 3 — 40
8.3 12 —140
14.4
15.5 12 —100
Combined Technologies
X Limiter™ 15.5 12 —100
25
23 12 — 40
8.3 3.5C — 40C
14.4
Cutler Hammer CX 15.5 4C — 40C
15.5 4C — 40C 25
Eaton
8.3 60C — 200C
14.4n
Cutler Hammer CXN 15.5 45C — 100C
15.5 45C — 100C 25
For more information on SML and SME Power Fuses, visit sandc.com. 55
VISTA® UNDERGROUND DISTRIBUTION SWITCHGEAR
S&C Vista Underground Distribution Switchgear, available 2. Test the cables using an ungainly clamp-stick-mounted
in ratings through 38 kV, features elbow-connected voltage tester.
components enclosed in a compact, submersible, SF6 - 3. Move the elbows to parking stands, along with grounding
insulated, welded-steel tank, completely protected from bushings or elbows, which also is an unwieldy task.
the environment.
But with Vista switchgear, just one person using a simple
Vista switchgear is offered in five styles—the innovative operating handle merely needs to:
UnderCover™ Style as well as pad-mounted, vault-mounted,
1. Rotate the switch operating shaft to the Open position
manhole, and wind turbine styles. Manual, source-transfer,
and confirm the open gap through the large viewing
and remote supervisory versions are available. All models use
window. Because the hinge end of the switch is
the same basic components, cutting your operator-training
and inventory costs. connected to the bushings, the bushings—and hence
the cables—are isolated from other medium-voltage
Construction details of source-transfer and remote components in the gear.
supervisory models are shown on pages 26 and 27.
2. Test for voltage simply by using the pushbutton voltage
Wind Turbine Style is shown on page 59.
indicator that’s capacitively coupled to the bushings.
HANDLES MORE LOADS PER UNIT 3. Rotate the switch operating shaft to the integral
Vista switchgear is furnished with up to six “ways” per unit, Grounded position and confirm grounding through
each consisting of one of the following: the viewing window.
uu Bus terminals
Vista switchgear is certified arc-resistant per IEC 298,
uu A load-interrupter switch for switching up to Appendix AA, for arcs occurring internal to the gear.
900-ampere main feeders
COMPLETE SYSTEM COORDINATION
uu A microprocessor-controlled, resettable arc-spinner
or vacuum fault interrupter for switching and protecting Vista Switchgear’s unique microprocessor-based
main feeders up to 900 amperes, and 600-ampere or overcurrent control features special, customizable
200-ampere taps, laterals, and subloops “coordinating” speed time-current characteristic curves
(TCCs) that provide complete coordination with upstream
By handling more loads per unit, you need fewer units, relays and downstream fuses. Conventional “E,” “K,” and “T”
saving you money. speed curves are available, too (see page 58).
PLACE GEAR JUST WHERE IT’S NEEDED Separate phase- and ground-overcurrent curves coordinate
Vista switchgear is submersible and considerably smaller with source-side breakers having ground-trip settings. Both
than traditional air-insulated gear, so it can be installed main and tap curves are provided for complete coordination
exactly where needed—even subsurface—without between fault interrupters applied on main feeders and
compromising aesthetics. Your customers are happier, and those applied on subloop taps.
you save money through reduced trenching and shorter
The overcurrent control is programmed with a PC in the
cable runs.
shop or in the field . . . no knobs or dials to compromise
SAFER TO OPERATE security. Simply connect your PC to the USB port covered by
Ordinary elbow gear does isolate operating personnel from a protective cap. All programming software is loaded on the
medium-voltage components—that is, until you need to overcurrent control and is easily accessed via a browser. The
operate it! Consider a routine operation such as isolating a control also features a handy event recorder that captures
downstream cable for repair. With conventional switchgear, information on the last 64 trip events, along with control
two or more specially trained operators need to: status and diagnostic information. External trip provisions are
optionally available, permitting the fault interrupters to be
1. Remove the elbows from their bushings using shotgun
tripped remotely by external controls or relays.
clamp sticks, which is a tedious, awkward task.
56
15-kV UnderCover Style Model 422
Operating panel—located near grade level so UnderCover Style Optional portable motor operator (not shown)—lets you operate any
gear is easily operated from a standing position—away from load-interrupter switch or fault interrupter from a remote location
medium-voltage cables
Switch terminals—equipped
with 600-ampere bushings or
200-ampere bushing wells
®
VISTA UNDERGROUND DISTRIBUTION SWITCHGEAR
50/60-Hz ANSI Ratings—IEC Ratings in Parentheses
kV Amperes, RMS
Fault Interrupter Load-Interrupter Switch
System Main Bus Cont. Short-Circuit,
MEDIUM VOLTAGE
Max BIL Cont. and Ten-Time Duty-Cycle Cont. and Mom. and One-
Class Current① Sym.
Load Dropping① Fault- Interr., Sym. Load Dropping① Second, Sym.
For more information on Vista Underground Distribution Switchgear, see publications 680-30, 681-31, and 681-700 through 681-708 at sandc.com. 57
VISTA® UNDERGROUND DISTRIBUTION SWITCHGEAR
SELECT THE TCC YOU NEED combinations and source-side relays with low time-dial
The Vista switchgear overcurrent control lets you choose settings.)
these time-current characteristic curves: uu Coordinating speed main—with minimum pickup
uu “E” speed—from 25E through 400E amperes settings from 25 through 800 amperes (Ideal for fault
uu “K” speed—from 25K through 200K amperes
interrupters on main feeders. Curves have longer minimum
response times and different shapes to coordinate with
uu “T” speed—from 8T through 200T amperes
tap-interrupter curves.)
uu ANSI/U. S. and IEC—conforms with IEEE C37.112-1996,
“IEEE Standard Inverse-Time Characteristic Equations for Coordinating-speed TCCs can be customized into hundreds
Overcurrent Relays” of different curves using a variety of definite-time delay
(0 through 1,000 seconds) settings.
uu Coordinating speed tap—with minimum pickup settings
from 15 through 400 amperes (Perfect for fault interrupters Negative sequence and sensitive earth fault protection
feeding subloop taps, and it optimizes coordination settings are also included.
with load-side weak link/backup current-limiting fuse
Circuit Configurations①
MANUAL STYLE
MANUAL AND REMOTE SUPERVISORY MODELS
MODELS
110
101
514 523 624 633
Circuit Configurations①
SOURCE-TRANSFER STYLE MODELS
VT VT
VT VT VT VT
VT VT VT VT
VT VT VT VT VT VT VT VT
① Model number indicates the total number of ways as well as the number of load-interrupter switch ways and fault-interrupter ways. For example, Model 431 has
“4” ways—“3” load-interrupter switch ways and “1” fault-interrupter way. Other configurations are available; consult the nearest S&C Sales Office.
58
Vista ® Underground Distribution Switchgear
Optional voltage indicator with liquid-crystal Compact welded-steel tank—protects switching and protection
display—includes test feature components from the environment; stainless steel construction
standard in UnderCover™ Style
Gas-fill port
Operating
mechanisms for
switches and fault Operation selector—prevents Microprocessor-based overcurrent
Pressure gauge (located interrupters— inadvertent operation from control—housed in watertight
under window)—temperature- padlockable in any Closed position directly to enclosure. Current transformers (CTs) (not
and altitude-compensated position Grounded position, and vice versa. visible) provide power and signal inputs
Operating panel of Vista switchgear. Viewing windows, for confirming the open gap and grounded position on load-interrupter
switches and fault interrupters, are located under the hinged covers of the voltage indicators.
Vista Models
MEDIUM VOLTAGE
15-kV Manhole
Style Model 110
38-kV Pad-Mounted Style Model 321 38-kV Wind Turbine-Style Model 101
15-kV Vault-Mounted
Style Model 422
59
VISTA® SD UNDERGROUND DISTRIBUTION SWITCHGEAR
S&C’s Vista SD Underground Distribution Switchgear is solid- available. The operators can be easily decoupled without
dielectric switchgear that reduces the time and complexity of removing any hardware to permit testing of the motor and
routine switching procedures. It was designed with the user controls.
in mind. Key features include:
Vista SD switchgear is completely submersible and suitable
uu Easy-to-achieve visible break. No moving cables or
for application in subsurface vaults subject to flooding. It is
using other accessories are needed to achieve a visible
also available for above-grade application in pad-mounted
break. The isolating disconnect, readily visible through a
style enclosures.
large 3×5-inch window, provides a true visible break in
the circuit. Vista SD switchgear is considerably smaller than traditional
uu Simple operation. The manual handle is easy to operate air-insulated gear, so it can be installed exactly where it’s
and can be operated by hand, rope, or universal pole with needed without compromising aesthetics. Consumers are
the appropriate fitting. Portable motor operators and happier, and you save money through reduced trenching and
accessory pendants are also available. shorter cable runs.
60
Vista ® SD Underground Distribution Switchgear
All terminals are equipped with 600-ampere bushings with threaded studs. Bushings without studs are optional. Fault interrupters can be
optionally furnished with 200-ampere bushing wells. Interfaces conform to ANSI/IEEE 386 and accept all standard insulated connectors and inserts.
®
VISTA SD UNDERGROUND DISTRIBUTION SWITCHGEAR
50/60-Hz ANSI Ratings—IEC Ratings in Parentheses
kV Amperes, RMS
MEDIUM VOLTAGE
Load-Interrupter Switch Fault Interrupter
Main Bus
System Short-Circuit, Continuous, Load Momentary and Three-Time Duty- Continuous, Load
Max BIL Continuous Short-Circuit
Class RMS, Sym. Dropping, and Three- Cycle Fault Closing, Dropping, and Load
Current Interrupting
Load Splitting① Second, Sym. Sym.② Splitting①
15 (12) 17.5 (12) 95 (75) 600 (630) 16 000 600 (630) 16 000 16 000 600 (630)u 16 000l
27 (24) 29 (24) 125 (125) 600 (630) 12 500 600 (630) 12 500 12 500 600 (630)u 12 500
① Parallel or loop switching. Load-interrupter switches and fault interrupters can switch the magnetizing current of transformers associated with this rating. Unloaded
cable switching capability: 10 amperes at 17.5 kV; 20 amperes at 29 kV. Load-interrupter switches and fault interrupters can also switch single capacitor banks through
1800 kvar.
② Applicable to fault closing into closed position.
u 200 amperes if fault interrupters are furnished with optional 200-ampere bushing wells.
l 12 500 amperes if fault interrupters are furnished with optional 200-ampere bushing wells.
61
VISTA® SD UNDERGROUND DISTRIBUTION SWITCHGEAR
CIRCUIT CONFIGURATIONS
514 523
624 633
Model number indicates the total number of ways as well as the number of load-interrupter switch ways and fault-interrupter ways.
For example, Model 431 has “4” ways—“3” load-interrupter switch ways and “1” fault-interrupter way. Other configurations are
available at sandc.com.
62
Operating
mechanism with
mimic bus and
semaphore status Closed Open
indicators—show
the positions of the
load-interrupter
switch or fault
interrupter and
isolating disconnect Viewing window—lets you readily confirm
the position of the isolating disconnect
Optional motor operator—facilitates remote operation of the load-interrupter switch or fault interrupter; can be
decoupled from the operating mechanism to permit testing without changing the switch or fault-interrupter position
Coupled Decoupled
Motor operator includes receptacles for a wired portable remote control pendant plus an auxiliary switch that tracks the
MEDIUM VOLTAGE
position of the isolating disconnect.
For more information on Vista SD Underground Distribution Switchgear, see S&C publications 695-30 and 695-31 at sandc.com. 63
SYSTEM VI™ SWITCHGEAR
System VI Switchgear lineup featuring two four-way Vista Underground Distribution System units, with provisions for future
expansion. Transition bays house air-insulated bushings.
64
System VI Switchgear with Vista Underground Distribution Switchgear Incoming and Outgoing Sections and Air-Insulated Metering Bay
Single-line diagram
SYSTEM VI SWITCHGEAR
kV Amperes, RMS
MEDIUM VOLTAGE
Fault Interrupter Load-Interrupter Switch
System Main Bus Cont. Short-Circuit,
Max BIL Cont. and Ten-Time Duty-Cycle Cont. and Mom. and One-
Class Current① Sym.
Load Dropping① Fault-Interr., Sym. Load Dropping① Second, Sym.
① Higher ratings are possible. Consult the nearest S&C Sales Office.
For more information on System VI Switchgear, see S&C publications 691-700 and 691-701 at sandc.com. 65
CUSTOM METAL-ENCLOSED SWITCHGEAR
Custom Metal-Enclosed Switchgear, rated 4.16 kV through Single-phase protection for single-phase loads.
34.5 kV, features reliable, time-tested fuses and manual or Fuses—unlike circuit breakers—selectively isolate only
power-operated interrupter switches in rugged 11-gauge faulted phases of feeders serving single-phase loads.
steel enclosures. These enclosures are configured into
THREE-FOLD ECONOMY
integrated packages that provide application flexibility,
operating simplicity, and superior dependability in Low purchase cost. Economies inherent in the interrupter
switching and protecting medium-voltage power switch and fuse-protection concept translate into significant
circuits in commercial, institutional, industrial, and high- first-cost savings.
rise installations. S&C’s expertise in this field has been Low installation cost. Metal-enclosed switchgear, light
established through nearly 75 years of metal-enclosed in weight in comparison with breaker gear, is easy to
switchgear design and manufacture. UL and arc-resistent handle and needs no foundation or support channels,
designs are available. only a level floor or pad. Multibay lineups assemble with a
POWER SYSTEM-MATCHED minimum of interbay bolting, and inter-unit bus connections
SWITCHING AND PROTECTION need no taping. Simple field assembly—with no relays to
set and test—means less time, equipment, and manpower.
Full-load switching, plus S&C’s unique one-time and
Future additions are readily accommodated as your
two-time duty-cycle fault closing. S&C interrupter
system expands.
switches carry and interrupt rated load currents, even after
being inadvertently closed into available fault currents Low maintenance cost. S&C fuses are nondamageable and
corresponding to their fault-closing ratings. You can restore do not require any maintenance or calibration to perpetuate
power quickly without first having to repair the switches. the accuracy of their time-current characteristics. S&C
interrupter switches are maintenance-free, requiring only
One-cycle total clearing with S&C SM Power Fuses.
an occasional exercising. S&C gear just needs a check of the
Compare this to the 5 cycles or more required by circuit
insulators and, if necessary, a simple cleaning.
breakers. This simplifies upstream coordination, minimizes
short-circuit stresses on the system. SIMPLIFIED POWER-SYSTEM PLANNING
Choice of unique response curves with maintenance- Simple, reliable, economical—Custom Metal-Enclosed
free S&C Electronic Power Fuses. They provide protection Switchgear is readily configured into basic circuit
unavailable with any other device—even circuit breakers, arrangements that make power-system planning and design
with their relays and batteries. easy, and implementation is logical and straightforward.
The basic arrangements shown on page 69 are often
Three-phase protection for three-phase loads. combined to handle even the most complex distribution
S&C open-phase detectors and overcurrent relays isolate system needs, ensuring maximum service continuity for
three-phase loads from single-phasing and other open- extremely critical loads.
phase conditions.
66
ENTRANCE METERING BAY
BAY FEEDER BAYS
A radial system is the simplest system and is economical—permits
extensive use of dedicated radial circuits (The direct circuitry facilitates quick
E
F location and repair of faulted circuits. Segmentation of a distribution system
SERVICE-ENTRANCE
SWITCHING CENTER with multiple radial circuits limits the extent of service interruption caused
by faults. In this example, the service-entrance bay of the S&C Custom Metal-
Enclosed Switchgear is provided with electronic power fuses to achieve full
UTILITY coordination with the upstream protective device.)
SOURCE
UTILITY SOURCE 1
UTILITY SOURCE 2 Split-bus primary-selective S&C Custom
BUS-TIE Metal-Enclosed Switchgear—allows large
METERING BAY SWITCH in-plant systems to be supplied power through
SPLIT-BUS one switching center because both utility sources
PRIMARY-SELECTIVE
SERVICE-ENTRANCE are fully used under normal operation, with the
E S S S
E SWITCHING CENTER two source interrupter switches closed and the
O
O
N.O. O
F V
S
V
S
F bus-tie switch open; each source, in effect, is
S
T
C the preferred source for its bus section and the
alternate source for the other bus section
MEDIUM VOLTAGE
For more information on Custom Metal-Enclosed Switchgear, see S&C publications 620-55, 620-700, and 621-30 at sandc.com. 67
CUSTOM METAL-ENCLOSED SWITCHGEAR
Inner screen doors. Bolted closed, these doors are a second Bus connections. Protected by an oxide-inhibiting
barrier against inadvertent entry. compound, these connectors are bolted to a uniform torque.
Special-purpose washers and bolts maintain
Category A enclosures. With the simple addition of optimum contact pressure.
padlockable covers over windows and meters, S&C
gear provides the industry’s highest security for this
class of equipment.
Hinged pressure-relief
flaps—open instantly to
relieve overpressure from an
internal arc
Specially strengthened
door hinges and double
door gaskets—maintain the
integrity of the enclosure and
provide extraordinary sealing
Front-facing vents—located
at least 6½ feet (198.1 cm)
above ground, provide
additional means for relieving
arcing by-products
68
Interrupter Switches—handle Type MS Switch Operators—
all live-switching duties and provide high-speed automatic
feature duty-cycle fault-closing trip-open operation of Mini-
ratings, a requisite for automatic Rupter Switches . . . interrupting
control schemes time is 4 cycles; these operators
are available in a choice of
manual or automatic trip-
®
The Mini-Rupter Switches
(pictured)—rated through
closed operation
SM Power Fuses—offered in a
wide variety of ampere ratings
and time-current characteristics,
permitting close fusing ratios ®
Micro-AT Source-Transfer
Controls—minimize
for optimal coordination and
maximum protection; their time- interruptions resulting from
current characteristics are precise loss of one source . . . transfer is
and permanently accurate achieved in as little
as 20-25 cycles
®
Fault Fiter Electronic Power
Fuses—with their exceptional
Electronic Relays—applied on
individual load feeders, protect
TCC versatility and higher three-phase loads from single-
continuous current ratings, phasing resulting from blown
provide features and performance fuses and other open-phase
previously unavailable in any conditions
MEDIUM VOLTAGE
protective device
The Type ZSD Overcurrent
The Fault Fiter Fuse (pictured)— Relays (pictured)—superior to
rated 600 amperes max ordinary overcurrent relays; they
continuous. Paralleled Fault Fiter can distinguish between fault
Fuses provide 1200-ampere current and transformer inrush
protection current
A wide choice of S&C components—exhaustively tested, field-proven, and of unequaled performance and operational
dependability—all expressly designed to solve your power distribution problems
69
FAULT TAMER® FUSE LIMITER
THE NEW GENERATION OF from lightning strikes. The Fault Tamer Fuse Limiter’s high
PROTECTION FOR POLE-TOP TRANSFORMERS inrush-withstand capability eliminates this problem because
S&C’s Fault Tamer Fuse Limiter combines a series fuse and arresters can be tank-mounted without concern for nuisance
backup limiter in one powerful package that can be easily fuse operations.
incorporated into new or existing installations of 14.4-kV,
IMPOSSIBLE TO MISMATCH SERIES FUSE AND LIMITER
25-kV, and 34.5-kV overhead pole-top transformers. Fault
In cutouts with bolt-on backup current-limiting fuses, it’s
Tamer Fuse Limiters provide short-circuit protection to the
possible to inadvertently apply the wrong size fuse link, thus
system, limit let-through current to a level that will minimize
jeopardizing the integrity of your coordination plan. But
catastrophic transformer failures caused by high-magnitude
the clearing characteristics of the Fault Tamer fuse cartridge
internal faults, and minimize damage from high-magnitude
are matched to that of the backup limiter so coordination is
external faults such as bushing flashovers. Fault Tamer Fuse
ensured.
Limiters offer major benefits over conventional fuse cutouts,
including cutouts appendaged with bolt-on backup current- SIMPLER HANDLING
limiting fuses. Re-fusing a bolted-in backup current-limiting fuse means
IMPROVED SERVICE CONTINUITY climbing the pole, or using a bucket truck, to remove the fuse
with a wrench—a time-consuming procedure that requires
Conventional fuse cutouts have limitations that can
wearing gloves and other safety garb.
compromise service continuity. For example, close to
substations—where fault currents can be high—complete But re-fusing Fault Tamer Fuse Limiters is quick and easy.
coordination frequently is not possible between the fuse Because the device’s combination fuse tube and backup
link protecting a pole-top transformer and the upstream limiter drops open after a fault-clearing operation, it can
lateral fuse link. As a result, a large-magnitude fault, such as be removed from the mounting from the ground using an
a wildlife-induced flashover of a transformer bushing, cannot extendostick. The process is made even easier by use of S&C’s
only cause the transformer fuse link to operate but the lateral Talon™ Handling Tool.
fuse link as well, exposing all customers on the lateral to an
extended outage. Fault Tamer Fuse Limiters eliminate this RETROFIT EXISTING INSTALLATIONS
problem because they coordinate with lateral fuse links over Fault Tamer Fuse Limiters are designed to fit into all vintages
the full range of fault currents. of S&C and MacLean Power Systems Type XS Fuse Cutout
Mountings. You can upgrade to the Fault Tamer Fuse Limiter’s
And, unlike conventional cutouts, a Fault Tamer Fuse Limiter’s superior current-limiting protection at minimal cost.
current-limiting action provides clearing characteristics that
coordinate with the instantaneous setting of the substation HEIGHTENED SAFETY
circuit breaker, thus eliminating unnecessary momentary The Fault Tamer device’s backup limiter features internal
interruptions for transformer faults exceeding the breaker’s exhaust control, which prevents fuse-cartridge parts from
instantaneous setting. being expelled during a fault-clearing operation. In contrast,
conventional fuse cutouts—even fuse cutouts with bolted-on
ENHANCED POWER QUALITY
backup current-limiting fuses—can violently expel fuse-link
High-magnitude faults near a substation can suppress the parts during operation, creating a potential exhaust hazard
voltage on the substation bus and on feeders emanating to operating personnel.
from the substation. The Fault Tamer Fuse Limiter’s current-
limiting action clears high-magnitude transformer faults As such, the Fault Tamer Fuse Limiter provides an extremely
before voltage dips can damage or shut down sensitive significant reduction in fire hazard when compared with
electronic equipment served by adjacent feeders. conventional fuse cutouts. The device complies with Spark
Production Class A in Australian Standard AS 1033.1-1990,
MAXIMUM SURGE PROTECTION which requires that no sparks may be produced during a fault-
Voltage surges are a major cause of overhead transformer clearing operation.
failure. Maximum protection from overvoltages can be
achieved by mounting the surge arrester on the transformer MATES PERFECTLY WITH LOADBUSTER ® —
tank, thus shortening the lead from the arrester to the THE S&C LOADBREAK TOOL
transformer winding and to ground. But with the surge Using S&C’s portable loadbreak tool, live switching can be
arrester connected to the load side of a conventional cutout, done at the point that minimizes the length of planned
the fuse link is more susceptible to nuisance operation outages and the number of customers affected.
70
Parallel-groove connector—
other styles are available Attachment hooks for Loadbuster—
The S&C Loadbreak Tool—also guide
tube during closing
Fuse cartridge—replaced
after a fault-clearing operation
Backup limiter—replaced
after a high-magnitude fault-
clearing operation
MEDIUM VOLTAGE
System Maximum
System Class, 60 Hz 50 Hz Interr.,
BIL Cont.
Time in Seconds
For more information on the Fault Tamer Fuse Limiter, see publications 451-30 and 451-31 at sandc.com. 71
TYPE XS FUSE CUTOUTS
SUPERB CURRENT TRANSFER The XS Fuse Cutout’s Loadbuster attachment hooks keep
Upper and lower contacts feature heavily silver-clad, spring- the portable tool positively anchored throughout its entire
loaded, embossed surfaces for built-in wiping action, opening stroke, yet allow for easy removal of the Loadbuster
resulting in minimum electrical resistance. tool. Attaching the Loadbuster tool to the XS Fuse Cutout
cannot cause the fuse tube to drop open prematurely.
72
Parallel-groove connector—tin-plated-
cast red brass. For ease of connection,
accommodates two conductors, even of unlike
size; other connector styles are also available
Trunnion—high-strength
cast bronze, silver plated; Toggle joint ensures reliable
surfaces around the trunnion dropout after interruption
bear on broad hinge surfaces
to keep the tube in alignment Sturdy ferrules—cast red brass; pinned to top
during closing and bottom of tube for permanent alignment
Trunnion
pocket—secures
TYPE XS FUSE CUTOUTS
tube in hinge
during closing 50/60-Hz Ratings Leakage
Distance to
kV Amperes, RMS Ground,
Minimum
Flipper—gives high-speed
terminal separation, quick cable Interr., Asym.
Nom. Max BIL Cont. Inches mm
flip-out, and (in conjunction 60 Hz 50 Hz
with the toggle joint) reduces
10 000 8 000 8½ 216
transmission of forces to fuse link 100
during closing 16 000 12 800 8½ 216
14.4 15 110
MEDIUM VOLTAGE
200 12 000 9 600 8½ 216
Optional features include NEMA Type B and extended Disconnect 300 — — 8½ 216
mounting brackets and a sea-coast design featuring stainless 8 000 6 400 11 279
100
steel components and hardware. 12 000 9 600 11 279
125
200 10 000 8 000 11 279
Disconnect 300 — — 11 279
25 27 8 000 6 400 17 432
100 12 000 9 600 17 432
150 12 000 9 600 26◆ 660◆
200 10 000 8 000 17 432
Disconnect 300 — — 26◆ 660◆
For more information on Type XS Fuse Cutouts, see publications 351-30, 351-31, and 351-705 at sandc.com. 73
POSITROL® FUSE LINKS
Positrol Fuse Links, with their precise time-current carefully checked purity and conductivity are drawn through
characteristics (TCC), nondamageable fusible elements, precision dies to exact cross sections confirmed by laser
and superior fault-interrupting ability, give you the ultimate micrometer. And painstaking assembly ensures no nicks,
in fuse-link performance. They eliminate “sneakouts” no kinks, and no necking down that might compromise
(uncoordinated blowings caused by TCC shifts) and the need TCC accuracy. Elements are swaged to their terminals for
to call on upstream protective devices to do the fuse link’s permanent, nondamageable connections.
work, thereby saving operating dollars and improving service
SUPERIOR FAULT-INTERRUPTING PERFORMANCE
reliability—two factors that are crucial in today’s competitive
environment. The exceptional features of Positrol Fuse Links The fuse link—not the cutout fuse tube—determines
make all of these benefits possible. the ability of a cutout to interrupt low-magnitude fault
currents, particularly transformer secondary-side faults with
NONDAMAGEABLE AND PERMANENTLY ACCURATE their severe transient recovery voltages (TRVs). Extensive
Positrol Fuse Links aren’t affected by aging, vibration, or testing through the full spectrum of secondary faults—
surges that heat the element nearly to the severing point. with realistically severe TRVs—has proved the matchless
They’re nondamageable, so they operate only when they performance of Positrol Fuse Links, whether applied in single-
should—not when they shouldn’t. They won’t sneak out. vented or double-vented cutouts. These links, with their
To a utility, the savings are significant. Positrol Fuse Links controlled-burst-strength extruded thermoplastic sheaths,
eliminate those costly excursions to find and replace reliably interrupt all levels of secondary-fault currents on
needlessly blown fuse links. systems through 27 kV and in single-phase-to-neutral
applications on systems through 38 kV.
And because Positrol Fuse Links are nondamageable, there’s
no need for “safety zones” or “setback allowances.” Close BROAD SELECTION OF SPEEDS
fusing is achievable without fear that changes in time- Positrol Fuse Links are available in six speeds: T, K, QR
current characteristics will occur—causing troublesome (interchangeable with “QA” speed offerings), N, Standard,
departures from your carefully orchestrated protection and and Coordinating.
coordination plans. The enduring permanency of Positrol
TCCs has been repeatedly demonstrated by exhaustive All these speeds, plus a selection of current ratings from
full-scale laboratory testing. 1 through 200 amperes, make optimal coordination and
maximum protection a practical reality at every sectionalizing
TIGHT TOLERANCES point, riser pole, distribution transformer, and capacitor bank.
Positrol Fuse Links have exceptionally tight tolerances—
EASY TO APPLY
typically half those of other fuse links—which means they
can be counted on to clear faults faster. Tight tolerances Easy-to-use application information, developed with the
and nondamageability combine to allow you to choose a same attention to detail as the Positrol Fuse Links themselves,
minimum-size link for each application, ensuring maximum is available to facilitate selection of S&C Fuse Links. Request
protection and enhanced coordination. With Positrol Fuse S&C Data Bulletin 350-110 for transformer protection,
Links, you can even coordinate adjacent ampere ratings. S&C Data Bulletin 350-130 for capacitor protection, or
S&C Information Bulletin 352-170 for series coordination.
These superb performance characteristics of Positrol Fuse These comprehensive application guides take the work
Links are the result of uncompromising design, plus diligent out of selecting the fuse link best suited to each protection
attention to manufacturing details. The fusible elements of requirement.
silver, silver-copper eutectic, and nickel-chrome (depending
on rating) are inherently nondamageable. Wire materials of
Positrol Fuse Links are Rural Utilities Service accepted.
74
Removable buttonhead—permits
use of Positrol Fuse Links in cutouts
with or without arc-shortening rod Speed Comparison Example
1000
100
Time in Seconds
Strain wire—restrains static
force of the cutout flipper spring 10T
10 Std.
1
10K
Terminals are swaged—not soldered,
providing nondamageable element
connections plus a permanent grip of 10QR
the strain wire and cable
10N
0.1
Swaged cable section—prevents
splaying of strands and wadding of
cable during the interrupting process,
ensuring positive withdrawal of the
cable from the sheath
0.01
10 100 1000
Current in amperes
Controlled-burst-strength
sheath—for unmatched full-fault-
spectrum interrupting performance
MEDIUM VOLTAGE
POSITROL FUSE LINK RATINGS
Speed Available Ratings, Amperes
Standard 1 – 200
K 6K – 200K
T 6T – 200T
N 5N – 200N
Tinned copper stranded
cable—resists corrosion and is of QR 1QR – 200QR
a diameter sized to resist corona Coordinating 101 – 103
For more information on Positrol Fuse Links, see S&C publications 352-30 and 352-31 at sandc.com. 75
SMD-20 POWER FUSES SMD-40 POWER FUSES
SMD Outdoor Distribution Fuses are internationally SMD-40 Power Fuses use the same time-proven low-arc-
recognized for their superb protection of transformers, lines, energy fault-interrupting technique as SMD-20 Power Fuses.
cables, and capacitor banks in distribution substations and A stainless steel outdoor silencer virtually eliminates the
on overhead feeders. SMD-20 and SMD-40 Power Fuses, with noise and reaction forces ordinarily associated with outdoor
their SMU Fuse Units, provide full-fault-spectrum protection. power fuses. These lightweight fuses are easily handled using
They detect and interrupt all faults—large, medium, and a universal pole equipped with an S&C Large Clamp.
small (even down to minimum melting current)—with line-
SMU FUSE UNITS … PRECISE PERFORMANCE
to-line or line-to-ground voltage across the fuse, whether the
fault is on the primary or secondary side of the transformer SMU-20® and SMU-40 Fuse Units have silver or pretensioned
and regardless of the transformer-winding connection. nickel-chrome fusible elements that are drawn through
precision dies to very accurate diameters and are of
SMD-20 Power Fuses are designed expressly for today’s
solderless construction, brazed into their terminals. Melting
distribution systems, where higher fault currents, higher
time-current characteristics are precise, with only 10% total
voltages, and higher loads commonly push cutouts beyond
tolerance in melting current, compared to the 20% tolerance
their capabilities. SMD-40 Power Fuses are specially suited
of most fuses.
to the high continuous-current and fault-interrupting
requirements of distribution substations. … NONDAMAGEABLE CONSTRUCTION
SMD-20 Power Fuses are offered in the pole-top style Helical coiling of the fusible elements and the absence of
for overhead use as well in four different station styles, in constraining filler materials result in elements that are free
voltages through 38 kV and a continuous-current rating of from mechanical and thermal stresses. SMU Fuse Units
200 amperes. Interrupting ratings are as follows: conform to their time-current characteristics—not only
initially, but on a sustained basis. Neither age, corrosion, or
SMD-20 POWER FUSES
vibration, nor surges that heat the element nearly to the
Interrupting Rating,
Voltage Rating, kV severing point, will affect the characteristics of these fuse
Amperes, RMS, Sym.
units. With nondamageable construction, there is no need
Nom. Max 60 Hz 50 Hz
to adjust the minimum melting curves for “safety zones” or
14.4 17.0 14 000 11 200
“setback allowances” as required for other fuses.
25 27 12 500 10 000
34.5 38 10 000 8 000 … SUPERIOR LOADING CAPABILITY
SMD-20 Power Fuses use a unique solid-material, low-arc- SMU Fuse Units are designed to accommodate, not
energy technique of fault interruption that produces a mild interrupt, all anticipated loading levels, including daily and
exhaust, with only 20% the arc energy of a cutout. Clearances repetitive peak loads as well as hot- and cold-load inrush
can be keyed to fuse-handling requirements, not fuse- currents. Unlike current-limiting fuses, SMU Fuse Units have
exhaust behavior, allowing structures to shrink to minimum peak-load capabilities in excess of their normal ampere
phase spacings. rating. This generous loading capability, combined with
precise conformance to time-current characteristic (TCC),
SMD-40 Power Fuses are offered in vertical and cluster
nondamageability, and a broad selection of fuse-unit ampere
styles for substation use, in voltages through 29 kV and
ratings and speeds, permits the ultimate in close fusing for
a continuous-current rating of 400 amperes. Interrupting
maximum protection and optimal coordination.
ratings are as follows:
… OUTSTANDING PROTECTION FOR TRANSFORMERS
SMD-40 POWER FUSES
Interrupting Rating, The exceptional peak-load capabilities of SMU Fuse Units
Voltage Rating, kV
Amperes, RMS, Sym. permit the use of low fusing ratios while accommodating
Nom. Max 60 Hz 50 Hz the high loading and inrush currents of distribution
4.8 5.5 25 000 20 000 transformers. These low fusing ratios mean fast clearing
14.4 17.0 25 000 20 000 of faults. Transformer mechanical and thermal stresses
25 29 20 000 16 000 are minimized, extending transformer life, and the faulted
76
SMU-20 Fuse Unit (SMU-40 Fuse Unit is similar)
MEDIUM VOLTAGE
S&C DR 3DR—20DR —
Filament-wound glass-epoxy
SMD-20 and SMD-40 Power Fuses are Rural Utilities Service tube—with exceptionally durable,
ultraviolet-resistant finish
accepted.
For more information on SMD-20 and SMD-40 Power Fuses, see publications 242-31, 242-32, 242-700, and 242-704 at sandc.com. 77
SMD-20 POWER FUSES SMD-40 POWER FUSES
Silver-clad contacts
throughout—backed by
prestressed loading springs,
feature built-in wiping action OVERHEAD—POLE-TOP STYLE SMD-20 MOUNTINGS
50/60-Hz Ratings Leakage Distance
Hinge-and-lower-contact to Ground, Minimum
kV Amperes, RMS
assembly—guides fuse unit
during closing for on-center Polymer Porcelain
Interr., Sym.
approach, even when operated Nom. Max BIL Max Insulator Insulator
from an adverse angle 60 Hz 50 Hz Inches mm Inches mm
200E or
125 14 000 11 200 — — 11 279
200K
14.4 17.0
Station-Style SMD-20 Mountings 150
200E or
14 000 11 200 19 483 17 432
200K
200E or — — 17 432
Available with Cypoxy™ or porcelain station-post insulators. 25 27 150 12 500 10 000
200K 35½ 902 26 660
200E or
34.5 38 200 10 000 8 000 — — 25½ 648
200K
78
Station—Vertical-Style SMD-40 Mountings
Silver-to-silver
contacts throughout—
backed by pre-stressed
loading springs
Guide horns—provide
self-guiding action for the
fuse unit during closing
Interrupting, Sym.
Nom. Max BIL Max Inches mm
60 Hz 50 Hz
10½ 267
4.8 5.5 95 400E 25 000 20 000
15½ 394
14.4 17.0 110 400E 25 000 20 000 15½ 394
25 29 150 400E 20 000 16 000 24 610
79
LOADBUSTER DISCONNECT ® SWITCH
Loadbuster Disconnect Switches are double-duty devices. Loadbuster tool switching helps keep service interruptions
They’re unexcelled as straight disconnects and, when used to a minimum. There’s no need for complex dead-switching
®
with Loadbuster —The S&C Loadbreak Tool, are the ultimate procedures. Loadbuster Disconnect Switches make every
devices for low-cost, universal live switching. Loadbuster disconnect a sectionalizing point, minimizing the length of
Disconnect Switches are available in voltage ratings from planned outages and the number of customers involved.
14.4 through 34.5 kV, with continuous current ratings of 630 And Loadbuster Disconnect Switch operation is simple and
and 900 amperes and a momentary rating of 40,000 amperes. positive—there’s no external arc and no contact burning.
All models, except those in the overhead pole-top style, are
available with a choice of Cypoxy™ or porcelain insulators. LOADBUSTER DISCONNECT SWITCHES—
Branch Feeder, Main Feeder, Crossarm, and Station Styles
Overhead pole top-style models are available with a porcelain
50/60-Hz Ratings Disconnect
or polymer insulator.
kV Amperes, RMS Gap
distribution systems. With their rugged station-type 14.4 15.5 110 10 254
and construction, Loadbuster Disconnect Switches have 630 65,000 10⅞ 276
25 27 125
stepped up the standard for hookstick-operated 900 65,000 10½ 267
distribution-type disconnects. 630 65,000 10 254
25/34.5 38 150
900 65,000 14 356
The high momentary ratings of Loadbuster Disconnect
150 900 65,000 14 356
Switches are made possible by the silver-to-silver contacts 34.5 38
200 900 65,000 14 356
at the attachment-hook end. Contacts won’t weld, burn,
or pit on overcurrents. Loadbuster Disconnect Switches LOADBUSTER DISCONNECT SWITCHES—
will carry rated load, opening and closing without Overhead Pole -Top Style
difficulty, even after long exposure of contacts to 50/60-Hz Ratings Disconnect
atmospheric contamination. kV Amperes, RMS Gap
Peak
Loadbuster Disconnect Switches feature double-member, Nom. Max BIL Cont. Inches mm
Withstand
hard-drawn, round-edged copper blades, formed for extra 14.4 15.5 110 630/900 ■ 65,000 8 203
rigidity to ensure positive engagement with the stationary 25 27 150 630/900 ■ 65,000 11 279
tongue contact when closing, even when closed from
34.5 38 170p 630/900 ■ 65,000 11 279
the side.
p S&C’s tested value for a disconnect with a porcelain insulator. The IEEE rating for a
AS A LOW-COST LOAD SWITCHING DEVICE disconnect with a porcelain insulator is 150 kV. The IEEE rating and S&C tested value for a
disconnect with a polymer insulator is 150 kV.
Loadbuster Disconnect Switches, when used with the ■ S&C rating for ambient temperature through 40°C (104°F), with a minimum
Loadbuster tool, provide the ultimate in distribution live- wind velocity of 1.4 mph. The IEEE rating for this disconnect switch is 630 amperes
switching versatility, economy, and universality. Loadbuster continuous.
80
Optional backup member—
suitable for single- or double-
crossarm mounting; furnished
with either two or four
mounting bolts, flat washers,
lockwashers, and nuts
Superior insulation
characteristics with Cypoxy™ Attachment hooks for Tinned terminal pads—accommodate
Insulators—Cypoxy is S&C’s Loadbuster—The S&C a wide selection of connectors workable
nontracking, self-scouring, Loadbreak Tool—also with hot-line tools
nonweathering cycloaliphatic serve as blade guide
epoxy resin system; there’s
never a compromise of Two-bolt insulator mounting—ensures against
insulation integrity with slipping or turning of live parts, particularly when
these field-proven insulators closing the blade from the side
(Porcelain distribution-type Positive latch and
insulators are also offered.) pryout operate freely
from all angles Silver-to-silver contacts throughout—
backed up by stainless steel loading springs
Blade stop pin—factory-set
for 160-degree opening, can
be readily field-repositioned Double-member, hard-drawn,
to provide 90-degree round-edged copper blades— Overhead Pole Top-Style
opening formed for extra rigidity. Loadbuster Disconnect
Switches—ideal for pole-
dip applications; available
Loadbuster Disconnect Switches are available in two-insulator with a birdproof-design
branch-feeder (pictured above), main-feeder, crossarm, and porcelain insulator or—
station styles, 630 and 900 amperes continuous, to 34.5 kV in ratings through
MEDIUM VOLTAGE
nominal. 25 kV—a lighter,
more-rugged
composite-silicone
polymer insulator,
as shown
For more information on Loadbuster Disconnect Switches, see publications 821-30 and 821-31 at sandc.com. 81
LOADBUSTER®—THE S C LOADBREAK TOOL
82
Switching with the Loadbuster tool is quickly learned. Its one-two-three simplicity is illustrated here with a Type XS Cutout
® ®
and a Loadbuster Disconnect Switch. The same procedure applies with Fault Tamer Fuse Limiters, TripSaver II Cutout-
Mounted Reclosers, and power fuses.
®
1
ATTACH the Loadbuster tool’s anchor to the
attachment hook on the far side of the cutout or
disconnect. Then, engage the pull-ring with the tool’s
pull-ring hook. The Loadbuster tool’s pull-ring latch
prevents inadvertent disengagement.
MEDIUM VOLTAGE
3 REMOVE the Loadbuster tool’s anchor from
the attachment hook and use a “roll-off” movement
to disengage from the pull-ring of the switching
device. The Loadbuster tool is easily reset for the next
opening operation.
For more information on Loadbuster—The S&C Loadbreak Tool, see publications 811-30 and 811-31 at sandc.com. 83
REGULATOR BYPASS SWITCHES
RECLOSER BYPASS DISCONNECTS
Regulator Bypass Switches are used to bypass and isolate Special attention has been given to the operation and
voltage regulators for maintenance. Recloser Bypass alignment of the disconnect blade through the use of
Disconnects are used in combination with separately stainless steel hardware and rigid anchoring of the disconnect
mounted Loadbuster Disconnect ® Switches to bypass and blade to the interrupter blade. Ease of operation is ensured
isolate automatic circuit reclosers for maintenance. Both by floating contact alignment and a carefully positioned and
station-type devices are suitable for other applications, such proportioned pull ring.
as bypassing and isolating current transformers.
Type NL Regulator Bypass Switches perform the same
Regulator Bypass Switches and Recloser Bypass Disconnects
functions as Type XL switches, but the sequence of operation
offer the exceptionally sturdy construction features needed
is done by the operator. Type NL switches are used in
to ensure years of reliable, easy operation:
applications where a 1200-ampere rating is needed or where
uu All blades are of double-member, hard-drawn it is desired to bypass the voltage regulator with its shunt
copper construction. winding energized (bypass blade closed, disconnect blade
uu Silver-to-silver contacts are used at all current- open) so mechanical and electrical testing can be carried out.
transfer points. The surface structure of the stationary
To isolate the regulator, the operator first closes the bypass
contacts differs from that of the blade contacts,
blade to prevent interruption of service. Then, the disconnect
preventing sticking, galling, or seizing. Contacts won’t
blade is opened to open the regulator series-winding circuit.
weld, burn, or pit on overcurrents.
Finally, the interrupter blade is opened; shunt-winding
uu Stainless steel or beryllium-copper loading springs magnetizing current is interrupted within the interrupter,
behind the contact areas of the blades. These springs and the regulator is isolated from the line. The procedure is
keep the contacts under constant pressure and provide reversed to place the regulator back into service.
smooth, positive wiping action during opening and
closing. This feature is especially important for Regulator Recloser Bypass Disconnects, rated up through
Bypass Switches because the bypass blade is normally in 900 amperes, consist of a fuse—a Type SMD-20, Type
the Open position. The bypass blade must carry full load SMD-40, or Type SM-5 Power Fuse, or a Type XS Fuse
current after the contacts have endured long periods of Cutout (depending on the available fault and continuous
exposure to the elements. current levels of the application)—in series with an integral
Loadbuster Disconnect Switches. The fuse is inserted into
Regulator Bypass Switches and Recloser Bypass Disconnects the device to protect the circuit while the recloser is out of
are offered with a choice of Cypoxy™ Insulators or porcelain service. The readily accessible trunnion pocket of the rugged
station-post insulators. Cypoxy station-post insulators are cast bronze hinge makes inserting the fuse easy. Guiding
nontracking, self-scouring, and nonweathering, and they surfaces on the inner surface of the hinge ensure “on-center”
meet or exceed the electrical and mechanical-strength approach of the fuse to the upper live parts during closing.
requirements established in ANSI Standard C29.9 (1983) for And a carefully positioned and proportioned brass
porcelain station-post insulators. pull-ring makes opening with a conventional hookstick
a simple operation.
Type XL Regulator Bypass Switches, rated 600 amperes,
provide built-in mechanical interlocking, sequencing, Recloser Bypass Disconnects are alternately available with a
and synchronization. Only a single pull of a hookstick is second Loadbuster Disconnect Switch (in place of the fuse) for
required to isolate the regulator. The bypass blade closes applications where devices other than protective equipment
first, bypassing the regulator to prevent interruption of are being bypassed for maintenance or inspection.
service. Then, the disconnect blade opens the regulator
series-winding circuit. Finally, the interrupter blade opens; Type XL Regulator Bypass Switches and Recloser Bypass Disconnects
interruption of shunt-winding magnetizing current takes are Rural Utilities Service accepted.
place within the no-external-arc interrupter, and the regulator
is isolated from the line. This switching sequence is reversed
automatically during the closing stroke, putting the voltage
regulator back into operation without interrupting service.
84
Type XL Regulator Bypass Switch Type NL Regulator Bypass Switch
Load terminal
Source terminal
Source terminal
Bypass blade
Interrupter
Interrupter
Interrupter blade
Disconnect
blade Interrupter blade
Disconnect blade
Voltage-regulator terminal
l 600 amperes for Type XL, 1200 amperes for Type NL.
n 30,000 amperes for Type XL, 61,00 amperes for Type NL.
MEDIUM VOLTAGE
— — — l
900 40 000n — — — l
Disconnect — — — l
blade 200E or
34.5 38 200 900 40 000 10 000 8 000 SMD-20
200K
l Furnished with a second S&C Loadbuster Disconnect Switch in place of the fuse.
n Three-second rating is 25,000 amperes, RMS, symmetrical.
Recloser terminal
When furnished with Cypoxy™ Insulators, meets requirements for 150-kV
BIL ratings.
For more information on Regulator Bypass Switches, see publications 841-30 and 841-31.
For more information on Recloser Bypass Disconnects, see publications 842-30, 842-31, and 842-700. All of these publications are available at sandc.com.
85
OMNI-RUPTER ® SWITCHES
ALDUTI-RUPTER ® SWITCHES
S&C Omni-Rupter and Alduti-Rupter Switches provide Power operation is possible with the addition of an S&C
no-external-arc circuit interruption for overhead distribution 6801M Automatic Switch Operator (see page 87). Hookstick-
feeders and outdoor distribution substations. They’re operated models are available, too, in upright, vertical, tiered-
specially designed for these live-switching duties: outboard, and inverted mounting configurations, providing
uu Line switching—Load splitting (parallel or loop the ultimate solution for simple, quick, and cost-effective
switching), load dropping, and associated installation.
charging currents
Integer-style Alduti-Rupter Switches are also available for
uu Transformer switching—Load currents and
switching overhead distribution feeders at system voltages
associated magnetizing currents
through 46 kV and 1200 amperes continuous. They can be
uu Cable switching—Load splitting (parallel or loop power operated through the addition of an S&C Type AS-1A,
switching), load dropping, and associated AS-10, LS-2, or 6801M switch operator, as appropriate.
charging currents
OUTDOOR DISTRIBUTION SUBSTATIONS
OVERHEAD DISTRIBUTION FEEDERS The economics of power distribution have forced heavier
S&C’s switches provide the utmost flexibility in distribution loading of substation transformers through the addition of
system switching. Lines may be readily extended and new feeders and increased loading of existing ones. S&C’s
additional load accommodated because Omni-Rupter and Alduti-Rupter Switch is the ideal switching device for these
Alduti-Rupter Switches can handle heavier-duty loads— heavier duties; it can split load and drop lines or cables,
typically up through the emergency overload rating of the or even the entire load. Its no-external-arc interrupting
line conductor. performance is essential in substations, where close phase
spacings rule out the use of arc-producing disconnects.
S&C switches can drop or split the entire connected load
without complicated breaker-and-switch sequencing. There’s S&C Alduti-Rupter Switches are available in voltage ratings
no need to drop individual loads as a preliminary operation. through 69 kV, in six rugged three-pole group-operated
styles. They’re offered in ratings of 600 amperes and 1200
Increasingly greater load densities have resulted in more
amperes, continuous and interrupting. For applications where
load per mile of line, and more interconnections, laterals, and
simultaneous three-phase switching isn’t needed, single-pole
branches. Interrupter switches provide more sectionalizing
Alduti-Rupter Switches are an excellent alternative; they’re
points to simplify switching procedures, curtail the scope of
conveniently operated with a conventional hookstick.
outages, and facilitate post-outage cold-load pickup.
NO-EXTERNAL-ARC INTERRUPTION
Omni-Rupter Switches are tailored for overhead-line
Every S&C Alduti-Rupter and Omni-Rupter Switch
switching through 29 kV. These 900-ampere switches are
incorporates built-in interrupters; there’s no need to rig
offered in the integer style, with all three switch poles
S&C switches with “add-ons.” Operation is simple and
preassembled on a one-piece steel or insulated base, factory-
straightforward. Interrupter contacts separate at high speed.
assembled and factory-adjusted, and all necessary clearances
The contacts and blade are synchronized to coordinate
are built in. A variety of mounting configurations are
dynamic internal dielectric strength with the interrupter’s
available, tailored to the most popular overhead-distribution
external striking distance, eliminating any chance of
line designs.
flashover. Arc-extinguishing deionizing gases are quietly
Omni-Rupter Switches bring unsurpassed live-switching vented through a labyrinthine muffler. There’s no oil, no
performance to overhead distribution feeders. They vacuum, and no maintenance.
offer a two-time duty-cycle fault-closing capability of 42,000
EXHAUSTIVELY TESTED, UTILITY PROVEN
amperes, peak, and a 10-time duty-cycle fault-closing
Every S&C switch rating is based on full-scale testing: load
capability of 21,000 amperes, peak—plus ice-breaking
splitting, load dropping, line and cable switching—all
capability on opening and closing and substantial emergency
at maximum voltages and rated currents, and with test
overload capabilities. Omni-Rupter Switches are shipped as a
circuits tuned to duplicate the most severe transient
single package. They are easy to hoist using the single-point
recovery voltages likely to be encountered in service. Rated
lifting bracket, and they mount quickly and easily using two
performance is ensured for all live-switching duties. The
through-bolts—no pole bands are required. With the simple
validity of S&C’s testing has been confirmed by more than
addition of the vertical operating mechanism and handle,
60 years of reliable operation of S&C switches on utility
installation is complete.
systems worldwide.
86
6801M Automatic Switch Operator Omni-Rupter Switch—Inverted Mounting Configuration
MEDIUM VOLTAGE
no central processing or SCADA supervision is required. The
IntelliTeam SG system works with other reclosers equipped
with an IntelliNode module, too; each team can include
multiple types of control platforms.
For more information on Omni-Rupter Switches, see publications 765-30, 765-31, and 765-80.
For more information on Alduti-Rupter Switches, see publications 761-30, 761-31, and 761-80.
87
For more information on 6801M Switch Operators, see Descriptive Bulletin 1045M-30. All of these publications are available at sandc.com.
OMNI-RUPTER ® SWITCHES
ALDUTI-RUPTER ® SWITCHES
Omni- Rupter Switch Construction
No-external-arc interrupter—
interrupter contacts and blade are
synchronized to coordinate dynamic
internal dielectric strength with the
interrupter’s external striking distance,
eliminating any chance for flashover
Single-member, square-section,
heavy-gauge, galvanized-steel
base—supports switch poles in
permanent perfect alignment Factory-adjusted hookstick operating handle— One-piece interphase
(Fiberglass-reinforced insulated features large U-shaped pull-rings for smooth operation drive—factory-adjusted
base offers the same performance; through the full opening or closing stroke; it's easy to for close three-phase
it’s finished with two-component operate from under the switch, at an angle, or even from switching simultaneity; it’s
polyurethane enamel for superior behind the pole (Lockout tab is front and center on the nonconducting on insulated-
resistance to weathering.) operating handle.) base models
A 14.4-kV Three-Pole Side-Break Integer Style Omni-Rupter Switch, with steel base, in an upright hookstick-operated mounting
configuration. Other configurations include vertical, triangular, tiered-outboard, and inverted. All are factory-assembled and factory-
adjusted to ensure reliable operation. The Omni-Rupter Switch features a compact, lightweight design with built-in lifting means—
unsurpassed for ease and speed of installation.
S&C Cypoxy™ Insulators provide nontracking, self-scouring, nonweathering performance, so there’s never a
compromise of insulation integrity. Porcelain station-post insulators and silicone insulators are also available.
88
Jaw contact assembly—features
Articulating hinge-end terminal floating jaw contact buttons that provide
pad—pivots to minimize loading on even contact forces between upper and
the blade; provides greater flexibility for lower jaw contacts, reducing friction
jumper connection during operation
Single-point lifting
bracket—provides a
permanent means of
lifting for convenient
rigging and hoisting
MEDIUM VOLTAGE
A variety of options are available, including an insulating section in the vertical shaft, dead-ending extension-link assemblies,
provisions for mounting surge arresters, wildlife protection, and greaseless graphite-impregnated contacts.
89
OMNI-RUPTER ® SWITCHES
ALDUTI-RUPTER ® SWITCHES
Alduti-Rupter Switch Construction
Spring-backed silver-nickel
multifinger blade contacts—
provide four independent
points of contact for optimum
performance and contact pressure
No-external-arc interrupter—interrupter
contacts and blade are synchronized to
coordinate dynamic internal dielectric strength
with the interrupter’s external striking distance,
eliminating any chance for flashover
Corrosion-resistant zinc-nickel-chromate
plated bearing—provides smooth,
maintenance-free performance; bearing
elements are packed in special MIL-spec grease
One pole-unit of 14.4-kV Three-Pole Side-Break Heavy-Duty Style Alduti-Rupter Switch, 600 amperes continuous.
This group-operated design is offered in a variety of standard mounting arrangements, including vertical and upright,
making it ideal for substation applications.
90
Double-member, hard-drawn copper Circuit interruption takes place within S&C’s
Four silver-nickel contact rivets on switch
blades—formed and trussed for extra Cypoxylated™ Assembly-molded interrupter,
blade, plus silver-clad blade support—
rigidity; they’re permanently aligned without external arc or flame—interrupter
ensure efficient current transfer and velvet-
for trouble-free switching contacts and blade are synchronized to
smooth action at the blade hinge; hinge
coordinate dynamic internal dielectric strength
loading springs, truss members, spacer, and
with interrupter’s external striking distance,
equalizer bar—all of stainless steel—are
eliminating any chance for flashover
engineered for optimal contact pressure,
operating ease, and blade stability
Fault-closing contacts—
feature copper-tungsten
disks silver-brazed to
copper blade-tongue, and
carbon-block (600-ampere
switch) or copper-tungsten-
block (1200-ampere switch)
jaw (Current-carrying
contacts consist of four
silver-nickel contact rivets
on a copper blade-tongue;
and a self-aligning, four-
finger, spring-loaded,
silver-clad copper jaw.)
A corrosion-resistant brass
guide bearing—provides smooth,
MEDIUM VOLTAGE
maintenance-free performance
Hex-crimped, galvanized-
steel-pipe operating shaft
Rectangular-section, heavy-
gauge, galvanized steel base
One pole-unit of 34.5-kV Three-Pole Vertical-Break Style Alduti-Rupter Switch, 1200 amperes continuous. Group-operated
vertical-break style switches are available in voltage ratings of 14.4 kV through 34.5 kV, and continuous current ratings of
600 amperes and 1200 amperes. They’re offered in vertical and upright standard mounting arrangements.
91
OMNI-RUPTER ® SWITCHES
ALDUTI-RUPTER ® SWITCHES
OMNI-RUPTER SWITCHES
50/60-Hz Ratings
Available Mounting
Style kV Amperes, RMS
Configurations
Nom. Max BIL Cont. Peak Withstand
Three-Pole Group-Operated—Factory-Assembled and Adjusted
14.4 17.0 110 900 65 000 Vertical, upright, inverted, tiered-outboard,
Side-break integer
25 29 150 900 65 000 triangular
ALDUTI-RUPTER SWITCHES
50/60-Hz Ratings
Available Mounting
Style kV Amperes, RMS
Configurations
Nom. Max BIL Cont. Mom., Asym
Three-Pole Group-Operated—Factory-Assembled and Adjusted
14.4 17.0 110 1200 40 000
25 27 150 1200 40 000
Side-break integer 25 /34.5 38 150 600 40 000 Vertical, upright, tiered outboard
34.5 38 200 600 40 000
34.5 38 200 1200 40 000
25 /34.5 38 150 600 40 000
25 /34.5 38 150 1200 40 000 Vertical, upright, tiered outboard, triangular,
Vertical-break integer
34.5 38 200 600 40 000 pedestal, pole-top
n 1600 amperes, RMS, load interrupting. This model is specifically designed for switching the secondary of single- or double-transformer substations.
600 amperes, RMS, load interrupting. This model is specifically designed for load splitting (parallel or loop switching).
92
Side-Break Integer Omni-Rupter Switch, Side-Break Integer Omni-Rupter Switch,
Inverted Mounting Upright Mounting
93
SMD-1A, -2B, -2C, -3 -50 POWER FUSES
S&C’s SMD ® Power Fuses provide reliable and economical such as station batteries and protective relays. Further
protection for transformers and capacitor banks in outdoor benefits of a compact fuse-protection package
substations. They are offered in these ratings: are low installation costs and a space-saving design that
will fit on almost any structure. The dropout action of these
SMD POWER FUSES
power fuses provides the additional benefit of visible air-
50/60-Hz Ratings
gap isolation for the transformer after fuse operation.
kV Amperes, RMS
Nom. Max BIL Max Interr., Sym SMD Power Fuses are designed to accommodate—
100E 6 700 not interrupt—all anticipated transformer-loading levels.
34.5 38 200 200E 17 500 This loadability, combined with fuse element
300E 33 500
nondamageability, permits close fusing for fast clearing
100E 5 000
46 48.3 250 200E 13 100 of all faults. Moreover, mechanical and thermal stresses
300E 31 500
on the transformer from secondary-side faults are
100E 3 350
200E 8 750 minimized so transformer life is extended.
69 72.5 350
300E 17 500
300E 25 000 S&C’s power fuses provide prompt, reliable operation
115 121 550 250E 10 500 without disrupting service to source-side loads. Other
138 145 650 or 750 250E 8 750 protection alternatives involving transfer-trip relaying,
As with all S&C fuse designs, SMD Power Fuses have automatic grounding switches, or sacrificial switches result
undergone exhaustive full-scale testing to establish their in extensive interruption of service to other loads in the event
ratings and to confirm their full fault-spectrum protection of a fault at the transformer. In addition, grounding-switch
capability. These fuses detect all faults—large, medium, and and sacrificial-switching schemes result in severe bolted-fault
small, even down to the minimum melting current—and they stress to the system and source transformers, plus undue
provide reliable circuit interruption under the most severe fault testing of line-terminal circuit breakers for all faults—
transient recovery voltages that may be encountered. even low-magnitude secondary-side faults.
At the heart of every SMD ® Fuse Unit is S&C’s specially CAPACITOR BANK PROTECTION
designed current-responsive fusible element. It’s When applied for fusing of station capacitor banks, the
exceptionally precise, with a total tolerance in melting substantial loading capability of SMD Power Fuses permits
current of only 10 percent. This precision, plus a wide the use of smaller ampere ratings than may be possible
selection of ampere ratings in three different speeds— with other makes of power fuses—without risking
S&C Standard, Slow, and Very Slow—lets you achieve nuisance fuse operations caused by capacitor-bank inrush
optimal coordination and maximum protection for both or outrush currents. Close fusing ensures rapid isolation of
the source-side system and the downstream equipment. faulted capacitor banks.
The superior element design also ensures the permanence of OTHER APPLICATION CONSIDERATIONS
response characteristics. SMD Fuse Units are unaffected by The exhaust of SMD Power Fuses is nonconducting, unlike
aging, corrosion, vibration, or surges that heat the element the highly ionized blast of expulsion-type fuses that use
nearly to the severing point. They’re nondamageable, fiber-lined fuse tubes. Consequently, it is possible to use
ensuring continued integrity of carefully engineered system standard phase spacings and clearances to ground.
protection and coordination plans. The operation of S&C fuses—from the sensing of current
to the interruption of faults—is the essence of simplicity.
TRANSFORMER PROTECTION
Minimal physical maintenance is required, such as
SMD Power Fuses provide a reliable, economical means to periodic checking of the condition of the fuse-unit
protect small to medium-sized load transformers installed in bore and occasional refinishing of fuse tubes exposed to
utility and industrial substations. The considerable economies severe weathering. There is no possibility of introducing
inherent to power fuse protection are possible because the the protection vagaries commonly associated with
fuse itself is much less costly than other types of protective maintenance of breakers, relays, and control-power
equipment, and there is no need for auxiliary equipment batteries. S&C fuse TCCs are maintenance-free.
94
Vertical Style Mounting How It Works …
Compression-loaded silver-
clad contacts—provide superb
current transfer
Release tube—
weather-sealed
Latch and
upper-contact
assembly—
features a
“floating” roller-
latch mechanism Solid arc-extinguishing
that prevents materials. Fault is quickly and
accidental fuse positively interrupted by high-
dropout yet speed elongation of the arc
releases without and by efficient deionizing and
resistance cooling of the arc path with
when operated turbulent nonconducting gases
intentionally released
®
SMD FUSE UNIT RATINGS
Available Ratings,
Amperes for Fuse Unit Types
Speed SMD-2B,
SMD-1A SMD-2C, SMD-50
SMD-3
S&C
1–200E 1–300E 5E–100E
Standard
S&C Slow 15E–200E 15E–300E 15E–100E
HIGH-VOLTAGE
For more information on SMD Power Fuses, see publications 212-30 and 212-31 at sandc.com. 95
CIRCUIT-SWITCHERS
138-kV Series 2000 Circuit-Switcher Model 2010 with horizontal 138-kV Mark VI Circuit-Switcher applied for capacitor-bank
interrupters and a vertical-break power-operated disconnect switching and protection. Optional pre-insertion inductors
applied for switching and protection of an oil-insulated shunt dramatically reduce inrush current and tame damaging
reactor at a substation belonging to a large southeastern utility. overvoltages that can shut down sensitive adjustable-speed
drives.
96
S&C Circuit-Switchers are offered in several versions: Series 2000 Circuit-Switchers feature interrupters designed
to close the circuit, interrupt the circuit, and maintain rated
Mark V Circuit-Switchers use in-series circuit-breaking
dielectric strength when open. They’re available in mounting
interrupters and a high-speed circuit-making and isolating
configurations suiting the broad spectrum of substation
disconnect. They can be custom tailored to fit any structure,
layouts and profiles, with or without an integral power-
phase spacing, or bus height. And they can be furnished with
operated disconnect.
pre-insertion inductors for unsurpassed capacitor switching.
All Circuit-Switcher interrupters use no-maintenance single-
Mark VI Circuit-Switchers combine the Trans-Rupter II®
pressure SF6 puffer technology for restrike-free, noncurrent-
Transformer Protector’s innovative interrupter technology
chopping, minimum-voltage surge performance. They’re
(see pages 98 and 99) with the Mark V’s high-speed circuit-
field-proven through 50 years of superior service. Isolating
making and isolating disconnect. Mark VI Circuit-Switchers
disconnect blades feature current-carrying contacts with
can also be furnished with pre-insertion inductors—the
built-in wiping action, ensuring a clean, low-resistance
industry standard for reducing inrush current and transient
path. Operators are designed to ensure the full inherent
overvoltages when switching capacitor banks.
mechanical and electrical performance characteristics of
Circuit-Switchers.
A 138-kV Series 2000 Circuit-Switcher Model 2020 with vertical This 138-kV Series 2000 Circuit-Switcher Model 2030 with vertical
HIGH-VOLTAGE
interrupters and a side-break power-operated disconnect applied interrupters and without a disconnect supplanted an existing
for transformer switching and protection. “flash-bus” sacrificial-switching scheme in this transformer
switching and protection application at a large southwestern
utility.
For more information on Mark V Circuit-Switchers, see publications 719-30 and 711-757. For more information on Mark VI Circuit-Switchers,
see S&C publications 712-30 and 712-700. For more information on Series 2000 Circuit-Switchers, see publications 716-30 and 716-31.
All of these publications are available at sandc.com. 97
TRANS-RUPTER II® TRANSFORMER PROTECTOR
SHATTERPROOF COMPOSITE-POLYMER
Stored-energy operating
SILICONE INSULATION
mechanism—sealed for
The Trans-Rupter II Transformer Protector’s interrupter life; no heater needed
and insulating support column stand up to the most severe
environment. The unique patented skirt arrangement on
115-kV and 138-kV pole-units provides enhanced dielectric
performance.
Pole units are fully assembled and factory-tested . . . just
hoist them into position. Installation is quick and easy.
98
Temperature-compensated gas-pressure gauge—
indicates gas pressure; provides two alarm levels
Operating
shaft for
charging tool
Closed-and-
charged indicator
Optional
motor
operator
For more information on Trans-Rupter II Transformer Protector, see publications 731-30, 731-31, and 731-700 through 731-705 at sandc.com. 99
100
101
NOTES
102
103
CONNECT WITH US:
sandc.com
100-G102 © S&C Electric Company 1985-2019, all rights reserved.