You are on page 1of 6

The 20th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, August 27 – September 01, 2017

ONLINE OIL MONITORING ON POWER TRANSFORMERS-


INVESTIGATIONS ON TECHNICAL AND ECONOMICAL REQUIREMENTS -

M. T. Imani1*, P. Werle1, A. Kurz2, J. Schuebel 2


1
Leibniz Universität Hannover, Institute of Electric Power Systems,
Division of High Voltage Engineering and Asset Management, Schering-Institute,
Callinstr. 25A, 30167 Hannover, Germany
2
Messko GmbH, Messko-Platz 1, D-61440 Oberursel, Germany
*Email: <imani@ifes.uni-hannover.de>

Abstract: Today many online oil monitoring systems are available on the market,
covering a huge range from low cost single-parameter detection systems up to costly
multi-parameter analysers. Therefore, it needs to be decided case by case which system
fits best to specific technical and economical requirements, which is often not a
straightforward task, because various economical and technical aspects need to be
considered.
Therefore extensive investigations have been performed on different fluids in order to
verify, which parameters need to be determined in which accuracy by a technical and
economical reasonable online oil monitoring system. For these investigations diverse
common faults have been simulated in a conventional insulating liquid. For each fault
mode, the key gases have been determined, thus based on a key-gas evaluation the
minimum number and accuracy of parameters could be defined, which are needed in
order to identify the failure unambiguously. For the investigations the oil parameters have
been determined using a high precision laboratory measurement equipment, and
simultaneously a 3-parameter-detection online system has been used, in order to verify
the potential of such online monitoring systems to detect malfunction of insulation
systems inside power transformers.
The performed investigations show that online oil monitoring systems have in general the
capability to identify different failures in power transformers, thus measures can be
initiated in time in order to prevent a breakdown. Based on the results described in this
contribution it is possible to decide, which oil online monitoring system should be chosen
under specific technical and economical requirements. Furthermore the results lead to a
recommendation, which oil parameters should be detected and evaluated by an
economically optimized online monitoring system.

1 INTRODUCTION general the gas molecules could be dissolved in


the oil or diffuse into the atmosphere for free
Mineral oil is a blend of complex hydrocarbon breathing transformation or into a gas cushion for
groups like CH, CH2 and CH3. Under thermal, these kind of sealed transformers. Gas generation
electrical and chemical stresses the hydrocarbon in oil is a complex phenomenon and depends on a
chains consists of C-C bonds or C-H bonds are wide spectrum of parameters from oil composition
randomly cleaved and free-radicals can be to fault types. The type and amount of the
generated. As these fragments are very unstable generated gases are governed mainly by fault
chemical products in essence, they tend to couple temperature or energy and fault duration as well.
to one another swiftly. Linkage of long chain As for example acetylene is generated at elevated
compounds results in production of heavy temperatures, this means that the presence of this
hydrocarbons, which are appeared as solid aging gas could be an indicator of a high energy faults.
by-products such as x-wax on the active part of Accordingly, every fault shows to somewhat a
transformers or precipitate as sedimentation on the specified gassing pattern. In this way, the amount,
tank bottom of transformers. Besides, by rate and ratio of gases could be employed to
connection of short-chain free-radicals hydrogen classify the fault mode and severity.
(H-H) or light hydrocarbons gases will be
generated like methane (CH3-H), ethane (CH3- Oil filled power transformers belong to the most
CH3), ethylene (CH2=CH2) and acetylene (CH≡CH). important and expensive components in electrical
Furthermore carbon-oxide gas molecules are energy grids [2-3]. Therefore it is of special interest
formed in addition, because of the decomposition to monitor their condition during operation in order
of cellulose insulation, but CO (C≡O) and CO2 to identify critical conditions before a serious failure
(O=C=O) could also be produced by degradation can occur. Such failures often lead to enormous
of the liquid insulation [1] or could be originated costs not only due to the outage of the transformer
from the atmosphere up to a certain extend. In itself, but also due to consequential costs like loss
of energy supply, loss of production, etc. To Into this set-up the DGA online monitoring system
prevent this worst case scenario, effective online MSense x2.5 was integrated, which can detect
monitoring systems are needed, which are usually hydrogen, carbon-monoxide as well as the
based on the detection of different physico- moisture content of the liquid insulation. A lot of
chemical parameters, mainly dissolved gases often care has been paid for sampling of the liquid
combined with the determination of the moisture sample complying with recommendations provided
content of the insulation liquid. The dissolved gas by [6]. For each experiment, sampling was
analysis (DGA) can indicate an active failure inside performed two times and the mean values were
the transformer according to standards like IEC taken as gas concentration. A full vacuum
60599 or IEEE C57.104, whereas moisture content degassing system is used for analysing the
can indicate a low breakdown voltage of the oil [4 samples.
and 5].
The measured gases are always normalized
This contribution aims at determining the key regarding the gas with the highest concentration in
gases formed by typical faults in power order to have a visual representation, which allows
transformers. Besides, an online monitoring a fast and easy identification of the key or main
system is subject of these investigations in order to gases for each failure type.
study its potential for performing a reliable
condition assessment of the power transformer. 3 EXPERIMENTAL RESULTS

2 EXPRIMENTAL PROCEDURE 3.1 PARTIAL DISCHARGES

The faults in power transformers or generally in oil Partial discharges (PD) are conducting pathways,
filled high voltage components can be categorized which bridges two electrodes partially for a short
to electrical or thermal faults or a combination of duration. They are initiated due to locally
both of them. A fault could be initiated due to an intensified electric field. The source of partial
imperfection inside the insulation system during the discharges can be e.g. voids or impurities in liquid
manufacturing process or as a consequence of an or solid insulations, which can lead to a breakdown
abnormality during operation or as a consequence if the PDs are not detected in time.
of aged insulation. Fault generation and
progression are depending on many factors. Some The PD-fault in oil is generated by placing an
of them extinguish shortly after appearance like aramid pressboard between a needle-plate
some sort of partial discharges, which are initiated electrode configuration. The needle electrode has
by over-voltages and the others could develop a diameter of 1 mm and radius of 3 µm made from
swiftly and metastatically spread up and result in stainless steel. The earth electrode is a brass plate
irreversible degradation of the insulation. In this with diameter of 50 mm. The applied ac voltage is
attempt thermal and electrical faults with different increased to achieve an almost stable partial
temperatures and energies were simulated. discharge value of more than 1 nC and keeping it
for 4 h, thus the gas concentrations shown in Fig. 2
For the investigations, the uninhibited mineral oil have been achieved, with the key gases hydrogen
Shell S2 ZU-I is used. Before each experiment, the and methane. Using the laboratory measurement
insulating fluid is degassed and dehydrated. system 2050 ppm hydrogen and 2 ppm carbon-
monoxide was detected, whereas the MSense x2.5
A closed test set-up, as depicted in Figure 1, .was shows 1995 ppm hydrogen and 4 ppm carbon-
used in order to represent sealed transformers, monoxide dissolved in the mineral oil.
which are typically sold today, thus a loss of gases
by breathing has not to be considered.

Figure 1: Test vessel for simulation of electrical


and/or thermal faults integrated with the Figure 2: Normalized gas concentrations after
3-parameter measurement system partial discharge stress
MSense x2.5
In order to generate high energy discharge faults,
the amplitude of impulse discharges were
3.2 ELECTRICAL DISCHARGES increased to 170 kV and 173.4 W.s and repeated
35 times. The gap distance between high voltage
Sparking occurs due to malfunction of insulation and earth electrode is adjusted by 10 mm. The
system under high electric field. They leave normalized gas concentration is presented in
permanent destruction on cellulose insulation and Fig. 4.
adversely change the insulation oil properties.
Transformer with this incipient fault is in imminent Every discharge is accompanied with considerable
danger of an outage. Arcing discharges having formation of undissolved gases and carbon traces.
plasma core by a temperature about several As could be expected, the key gases for this fault
thousand degrees generate a considerable amount are acetylene and hydrogen and the ratio of
of acetylene and hydrogen. Furthermore, arcing acetylene to hydrogen could estimate the severity
could produce a significant amount of undissolved of the fault.
gases.
3.3 LOCAL OVERHEATING (HOTSPOT)
To determine the emerging gases by electrical
discharges, impulse discharges with a peak of Hotspot (T<300 oC)
60 kV and energy of 21.6 W.s are applied 30 times The over loading of transformers leads to rising
to the treated oil sample. The measured gas temperatures, but hotspots could also stem from
contents and presented in Fig. 3 and show that higher eddy currents within the iron core or
considerable amounts of hydrogen and acetylene transformer tank or be due to bad contact between
have been generates. Besides, small amount of conductors. The type and concentration of gases is
ethylene and methane could also be detected. In governed by the temperature.
laboratory 2 ppm CO and 107 ppm H2 dissolved in
oil could be detected, whereas 5 ppm CO and A resistor, through which a constant current flows,
98 ppm H2 are measured by the MSense. has been employed to generate local overheating
inside the oil. The current is adjusted to have a
constant temperature of 250 oC and keeping it for
3 h. As during this time duration the temperature of
whole sample could increase, the wall of oil
container was cooled down by immersing it into a
thermostatic water bath with regulated temperature
of 20 oC.

Fig. 5 shows the pattern of gassing, which reveals


that methane is the key gas for this mode of fault.
Moreover, a significant amount of propane and
propene is released leading us to the conclusion
that it could be an important marker for local
thermal aging of mineral oil.

Figure 3: Normalized gas concentrations after


electrical discharges

Figure 5: Normalized gas concentrations for a


hotspot with 250 oC
Figure 4: Normalized gas concentrations after
electrical discharges with high energy Using a GC measurement system, gas
concentrations of 7 and 10 ppm for carbon-
monoxide and hydrogen respectively are As the relative percentage of generated gases in
measured, which is comparble with those values Fig. 7 shows, propene is produced more than other
determined by MSense x2.5: 11 ppm carbon- fault gases. It could be hereupon an indicator for
monoxide and 12 ppm hydrogen. thermal fault in insulating fluid. Meanwhile, a high
concentration of ethylene could be measured,
Hotspot (300 oC<T<700 oC) which is usually considered as the key gas for
In order to produce the local thermal fault in oil with hotspot presence in oil.
a temperature between 300 and 700 oC, the
current is increased to have a temperature of 3.4 Combined Thermal/Electrical Fault
approx. 600 oC on the surface of resistor for 5
minutes. As the thermal stress lasts just for few Thermal and electrical faults could occur
minutes no cooling of the oil vessel is necessary. simultaneously in power transformers dependently
During the thermal stress formation of remarkable or independently from each other. To recognize the
amount of bubbles could be observed. pattern of this fault, the dehydrated oil sample is
subjected to thermal stress at an elevated
temperature of 600 oC for 5 minutes. Afterwards,
the oil sample is submitted to 30 impulse
discharges with an amplitude of 60 kV, thus the
gases shown in Fig. 8 have been produced.

As seen in Fig. 8, the main dissolved gas is


propene, which is accompanied by significant
generation of ethylene, methane and hydrogen.
Besides, trace of acetylene could be detected,
which is produced as a consequence of electrical
discharges. It could also be noticed that here
propene and acetylene could be employed as
indicators of thermal and electrical faults,
correspondingly. By dissolved gas measurement
2 ppm CO and 144 ppm hydrogen were detected.
In comparison, the online measurement system
Figure 6: Normalized gas concentrations for a MSense x2.5 could sense 4 ppm CO and 156 ppm
hotspot with 600 oC H2.
As seen in Fig. 6, the pattern of gassing unfolds
this fact that hotspot with this temperature could
result in production of fault gases methane,
propene and ethylene. Compared to the thermal
fault lower than 300 oC, the ratio of concentration
of propene to methane is substantially raised.

Hotspot (T>700 oC)


The current was adjusted to achieve a temperature
of 800 oC on the surface of resistor for 30 seconds,
which was accompanied by releasing of a large
amount of undissolved gases.

Figure 8: Normalized gas concentrations after


combined thermal/electrical stress

Comparing Figures 3, 6 and 8, it becomes obvious


that Figure 8 is a kind of superposition of Figure 3
and 6, thus the chosen representation of failure
gases can be used to simple identify key gases
from single and mixed faults.

Thermal aging of paper

Cellulose insulations undergo an accelerated aging


Figure 7: Normalized gas concentrations for a process at elevated temperatures with the
hotspot with 800 oC presence of moisture and oxygen. In this attempt,
kraft paper samples are impregnated with 3.5 WATER CONTENT
processed uninhibited mineral oils separately.
Afterwards, three groups of samples for each type Water could be found in insulating liquid of power
of oil were prepared: pure oil sample, oil sample transformers as a result of aging of cellulose
with catalysts and an oil sample with paper and insulation or due to the moisture ingress in oil from
catalysts. Usual present metals in power the atmosphere. This chemical compound could
transformer i.e. aluminium, iron, brass and copper adversely accelerate the aging rate of the both
in the form of fine particles each 3 g/l are solid and liquid insulation. Furthermore, this
incorporated in oil to catalyse the aging process. deteriorates breakdown withstand strength of
The usual cellulose/oil weight ratio of 1/10 was insulating liquid. Therefore, it is of prominent
chosen, as a typical value. All samples were put in importance to monitor the moisture content of the
an open stainless steel breakers and submitted to insulating oil. The online monitoring system
thermal stress at 120 oC. MSense x2.5 is equipped with a capacitive sensor
to measure the relative water content of oil.
Dissolved gas analysis was performed after 72 h
and 144 h. The normalized concentration of the In this study another capacitive humidity sensor
produced gases is presented in Fig. 9. It could be Vaisala HM70, which has been formerly calibrated,
noticed that both catalysts and paper have was integrated to the test setup to compare the
significant influence on production of carbon- results measured by MSense x2.5 with those of the
oxides molecules. Vaisala HM70.

The measurement of the relative water content


was performed for oils with three different relative
humidities of 4%, 12% and 33% measured by
Vaisala HM70. Correspondingly those values are
measured by MSense x2.5 5%, 14% and 37%,
which shows a good agreement with those
determined values by the capacitive humidity
sensor Vaisala HM70.

4 DISCUSSION

The investigations show that using an intelligent


representation of dissolved gases a simple
identification of key gases and therefore of the
Figure 9: Normalized gas concentrations after failure type is possible, even if failures are
72 h ageing combined. Furthermore it could have been shown,
that actual available DGA online monitoring
The amount of dissolved gases after 144 h can be systems are quite accurate.
seen in Fig. 10. Paper and metallic particles could
enhance the production of CO and CO2 after 144 h Regarding the gassing behaviour of the
in the same way as shown after 72 h, seen in Fig. investigated insulating oil under different fault
9. modes, the question which key-gases should be
measured could be answered as follows:

For a 2-key gas system hydrogen should be


detected in combination with
 carbon-monoxide, thus a statement about both
active failure and paper ageing
or
 methane, thus a statement about the type of the
failure – electrical or thermal –
becomes possible.

For a 3-key gas system beside the above


mentioned gases acetylene could be measured in
order to differentiate between high and low
intensity faults.
Figure 10: Normalized gas concentrations after
144 h ageing For a 4-key gas system: hydrogen, methane,
acetylene and CO seems to be the best
combination, because it might allow a statement IEEE Elect. Insul. Mag., vol. 21, no. 4, pp. 21–
concerning the type and severity of the failure as 27, Jul./Aug. 2005
well as about the question if paper is involved in
the failure or degraded. [4] IEC 60599, “Mineral oil-impregnated electrical
equipment in service-guide to the interpretation
For a 5-key gas system the measurement of of dissolved and free gases analysis”, 2015
ethylene could be helpful for a better discrimination [5] IEEE C57.104 “Guide for the interpretation of
between thermal faults with different temperature gases generated in oil immersed transformers”,
ranges. 2008

If more gases should be measured more fault [6] IEC 60567, “Oil-filled electrical equipment —
gases and/or CO2 as well as oxygen and nitrogen Sampling of gases and of oil for analysis of
can lead to a more precise statement. However, free and dissolved gases — Guidance”, IEC
certainly this will increase the costs of such a standard, 2005
system and if a monitoring system gives an alarm
[7] P. Werle, D. Bonmann “Monitoring und
– independent if 2 or 9 key gases are monitored –
Diagnose von Leistungstransformatoren zur
usually the same procedure will start, which is to
Optimierung zustandsbasierter Instandhal-
take an oil sample for analysing it in the lab [7].
tungsstrategien“ ETG-Fachtagung, Diagnostik
Therefore, in general a low cost system like a 2
elektrischer Betriebsmittel, Köln, März 2004
key-gas system seems to be preferable. However,
if more information should be achieved at the same
time a 5-key gas sensor maybe in addition with a
moisture sensor might be a good compromise
between costs and technical informative value.

5 CONCLUSIONS

Power transformers are the costliest assets within


the power system grid, thus it is highly demanded
to monitor the condition of power transformers
online, through which incipient faults could be
detected in time. Especially DGA monitoring
systems could convey wealthy information about
the condition of power transformers [6].

The performed investigations show that even


online DGA systems considering less key gases
are quite accurate and reliable, thus a 2-key gas
system is preferable from an economic point of
view, because monitoring more key gases results
in an increased cost-price.

Using normalized gas-concentration-graphs enable


a simple and easy fault identification even in cases
in which more than one failure occur, thus this
representation of failure gases could be helpful
even for untrained staff to get a first impression
about the transformer condition.

REFERENCES
[1] I. Fofana, M. T. Imani M. Farahani, E.
Gockenbach and H. Borsi, “Influence of
Transformer Oil aging by-products on the
dissolved gas analysis”, 18th International
Symposium on High Voltage Engineering,
Seoul Korea, August 2013
[2] M. Duval, "A review of faults detectable by gas-
in-oil analysis in transformers”, Electrical
Insulation Magazine, IEEE, vol. 18, pp. 8-17,
2002
[3] M. Duval and J. Dukarm, “Improving the
reliability of transformer gas-in-oil diagnosis,”

You might also like