Professional Documents
Culture Documents
Abstract: Today many online oil monitoring systems are available on the market,
covering a huge range from low cost single-parameter detection systems up to costly
multi-parameter analysers. Therefore, it needs to be decided case by case which system
fits best to specific technical and economical requirements, which is often not a
straightforward task, because various economical and technical aspects need to be
considered.
Therefore extensive investigations have been performed on different fluids in order to
verify, which parameters need to be determined in which accuracy by a technical and
economical reasonable online oil monitoring system. For these investigations diverse
common faults have been simulated in a conventional insulating liquid. For each fault
mode, the key gases have been determined, thus based on a key-gas evaluation the
minimum number and accuracy of parameters could be defined, which are needed in
order to identify the failure unambiguously. For the investigations the oil parameters have
been determined using a high precision laboratory measurement equipment, and
simultaneously a 3-parameter-detection online system has been used, in order to verify
the potential of such online monitoring systems to detect malfunction of insulation
systems inside power transformers.
The performed investigations show that online oil monitoring systems have in general the
capability to identify different failures in power transformers, thus measures can be
initiated in time in order to prevent a breakdown. Based on the results described in this
contribution it is possible to decide, which oil online monitoring system should be chosen
under specific technical and economical requirements. Furthermore the results lead to a
recommendation, which oil parameters should be detected and evaluated by an
economically optimized online monitoring system.
The faults in power transformers or generally in oil Partial discharges (PD) are conducting pathways,
filled high voltage components can be categorized which bridges two electrodes partially for a short
to electrical or thermal faults or a combination of duration. They are initiated due to locally
both of them. A fault could be initiated due to an intensified electric field. The source of partial
imperfection inside the insulation system during the discharges can be e.g. voids or impurities in liquid
manufacturing process or as a consequence of an or solid insulations, which can lead to a breakdown
abnormality during operation or as a consequence if the PDs are not detected in time.
of aged insulation. Fault generation and
progression are depending on many factors. Some The PD-fault in oil is generated by placing an
of them extinguish shortly after appearance like aramid pressboard between a needle-plate
some sort of partial discharges, which are initiated electrode configuration. The needle electrode has
by over-voltages and the others could develop a diameter of 1 mm and radius of 3 µm made from
swiftly and metastatically spread up and result in stainless steel. The earth electrode is a brass plate
irreversible degradation of the insulation. In this with diameter of 50 mm. The applied ac voltage is
attempt thermal and electrical faults with different increased to achieve an almost stable partial
temperatures and energies were simulated. discharge value of more than 1 nC and keeping it
for 4 h, thus the gas concentrations shown in Fig. 2
For the investigations, the uninhibited mineral oil have been achieved, with the key gases hydrogen
Shell S2 ZU-I is used. Before each experiment, the and methane. Using the laboratory measurement
insulating fluid is degassed and dehydrated. system 2050 ppm hydrogen and 2 ppm carbon-
monoxide was detected, whereas the MSense x2.5
A closed test set-up, as depicted in Figure 1, .was shows 1995 ppm hydrogen and 4 ppm carbon-
used in order to represent sealed transformers, monoxide dissolved in the mineral oil.
which are typically sold today, thus a loss of gases
by breathing has not to be considered.
4 DISCUSSION
If more gases should be measured more fault [6] IEC 60567, “Oil-filled electrical equipment —
gases and/or CO2 as well as oxygen and nitrogen Sampling of gases and of oil for analysis of
can lead to a more precise statement. However, free and dissolved gases — Guidance”, IEC
certainly this will increase the costs of such a standard, 2005
system and if a monitoring system gives an alarm
[7] P. Werle, D. Bonmann “Monitoring und
– independent if 2 or 9 key gases are monitored –
Diagnose von Leistungstransformatoren zur
usually the same procedure will start, which is to
Optimierung zustandsbasierter Instandhal-
take an oil sample for analysing it in the lab [7].
tungsstrategien“ ETG-Fachtagung, Diagnostik
Therefore, in general a low cost system like a 2
elektrischer Betriebsmittel, Köln, März 2004
key-gas system seems to be preferable. However,
if more information should be achieved at the same
time a 5-key gas sensor maybe in addition with a
moisture sensor might be a good compromise
between costs and technical informative value.
5 CONCLUSIONS
REFERENCES
[1] I. Fofana, M. T. Imani M. Farahani, E.
Gockenbach and H. Borsi, “Influence of
Transformer Oil aging by-products on the
dissolved gas analysis”, 18th International
Symposium on High Voltage Engineering,
Seoul Korea, August 2013
[2] M. Duval, "A review of faults detectable by gas-
in-oil analysis in transformers”, Electrical
Insulation Magazine, IEEE, vol. 18, pp. 8-17,
2002
[3] M. Duval and J. Dukarm, “Improving the
reliability of transformer gas-in-oil diagnosis,”