You are on page 1of 8

Metasys Network Sales Resource Manual 635

Application Specific Controllers


Product Bulletin
Issue Date 0294

Variable Air Volume Controller

The Variable Air Volume (VAV) Controller is an The VAV Controller can also function as a
electronic device for digital control of single duct, standalone controller. Figure 1 illustrates the
dual duct, fan powered, and supply/exhaust VAV VAV Controller.
box configurations. Along with the capability of
standalone control of the VAV box, the controller
can also integrate the control of the room or
zone baseboard heat and lighting logic. You
may use the VAV as a standalone controller, or
connected to the Metasys Network through a
Network Control Module (NCM) or Companion.

When connected to the Metasys Network, the


VAV provides all point and control information to
the rest of the network. The devices
communicate through an N2 Bus.
Figure 1: Enclosed Variable Air Volume
Controller

Features and Benefits


❑ Standalone Control System reliability
❑ Network Communications over Facility-wide control efficiencies and cost effective
N2 Bus sensor sharing
❑ Multiple Modes of Operation for Comfort with economy
Various Occupancy Conditions
❑ Built-in Control Program Library No programming
❑ Multiple Packaging Options for Installation flexibility
Both Field and Factory
Installations
❑ Isolated N2 Circuitry Single earth ground connection allowed

❑ Expanded Memory Space Larger download and application capability


❑ Removable N2 and 24 VAC Power Allows disconnection of an individual controller
Plugs without disrupting other controller connections
❑ LED Indicator for Power/Zone Bus Visual indication of proper system function
❑ Screw Terminals for I/O “Quick Connect” lugs and crimping tool not required
Connections Available in Some
Models
Shaded areas above denote new features and benefits.

© 1994 Johnson Controls, Inc. 1


Order No. 635-060
Table 1: Variable Air Volume Controller Types
Point Type AS-VAV110-1 AS-VAV140-1 AS-VAV111-1 AS-VAV141-1

Ambient 32°F to 140°F 32°F to 140°F 32°F to 140°F 32°F to 140°F


Temperature (0°C to 50°C) (0°C to 50°C) (0°C to 50°C) (0°C to 50°C)
Rating
Analog Inputs 6 6 6 6
RTD temperature RTD temperature RTD temperature RTD temperature
elements (1000 ohm elements (1000 ohm elements (1000 ohm elements (1000 ohm
nickel, platinum, or nickel, platinum, or nickel, platinum, or nickel, platinum, or
silicon) silicon) silicon) silicon)
2K ohm setpoint 2K ohm setpoint 2K ohm setpoint 2K ohm setpoint
potentiometers potentiometers potentiometers potentiometers
0 to 10 VDC 0 to 10 VDC 0 to 10 VDC 0 to 10 VDC
transmitters transmitters transmitters transmitters
Binary Inputs 4 4 4 4
(4) Dry contacts (4) Dry contacts (4) Dry contacts (4) Dry contacts
(1) Momentary push (1) Momentary push (1) Momentary push (1) Momentary push
button from zone button from zone button from zone button from zone
sensor for sensor for sensor for sensor for
temporary temporary temporary temporary
occupancy mode occupancy mode occupancy mode occupancy mode
Analog Outputs 0 0 2 2
0 to 10 VDC 0 to 10 VDC
@ 10 mA @ 10 mA
Binary Outputs 8 8 6 6
24 VAC Triacs 24 VAC Triacs 24 VAC Triacs 24 VAC Triacs
@ 0.5 amps (or @ 0.5 amps (or @ 0.5 amps (or @ 0.5 amps (or
0.8 amps if total 0.8 amps if total 0.8 amps if total 0.8 amps if total
power is limited as power is limited as power is limited as power is limited as
stipulated in the stipulated in the stipulated in the stipulated in the
Variable Air Volume Variable Air Volume Variable Air Volume Variable Air Volume
Controller Technical Controller Technical Controller Technical Controller Technical
Bulletin) Bulletin) Bulletin) Bulletin)
I/O Terminations “quick connects” fixed screw terminal “quick connects” fixed screw terminal
(AI, BI, AO, BO) (spade lugs) block (spade lugs) block
Zone Bus spade connectors at screw connections at spade connectors at screw connections at
controller controller controller controller
8 pin phone jack on 8 pin phone jack on 8 pin phone jack on 8 pin phone jack on
controller controller controller controller
6 pin phone jack at 6 pin phone jack at 6 pin phone jack at 6 pin phone jack at
zone sensor zone sensor zone sensor zone sensor
LED indication additional 6 pin phone LED indication additional 6 pin phone
jack on controller jack on controller
LED indication LED indication
24 VAC Power In removable screw removable screw removable screw removable screw
Terminations terminal block terminal block terminal block terminal block
N2 Bus removable screw removable screw removable screw removable screw
Terminations terminal block terminal block terminal block terminal block

2 Application Specific Controllers—Variable Air Volume Controller


Flexible Hardware Packaging Convenient Configuration Setup
The Variable Air Volume Controller can be The VAV Controller doesn’t need to be
configured to match most applications found in programmed in the traditional sense. Instead,
today’s fast evolving VAV marketplace. The the control algorithms and input/output point
VAV is available in two different versions, assignments are configured with the use of the
differing in their output point configuration. Each HVAC PRO software tool.
of these two versions are available in models
The HVAC PRO runs on a laptop computer
with “Quick Connects” (spade lugs) or screw
plugged directly into the VAV Controller or into a
terminations for input/output points. This allows
jack at the room sensor. The jack is connected
you to economically select a controller to match
back to the VAV Controller over a simple twisted
the VAV box application. In addition, cable kits
pair cable called a Zone Bus. Programs loaded
are available to make connections between the
into the VAV Controller are saved in nonvolatile
controller and the damper actuator and velocity
E2PROM memory, so there is no need to reload
pressure transducer easy.
software after a loss of power.
A second option allows you to load the
Controller Enclosure configuration from the laptop via the N2 Bus.
This option speeds up the initial loading and
The controller mounts easily to any surface commissioning process prior to performing the
using either direct mount or a controller final balancing procedures.
enclosure. The common packaging for the VAV
Controller is in the AS-ENC100-0 or in an Programming a VAV Controller is a simple
enclosure provided by the VAV box matter of responding to a series of “yes-no” and
manufacturer. multiple choice questions, and specifying
setpoints and other parameters. No previous
software programming experience is required.

Easy Monitoring and Diagnostics The VAV Controller has a library of proven
control sequences and proportional-integral
with the Zone Terminal (AS-ZTU100-1) algorithms that are automatically configured into
The Zone Terminal (ZT) is a person/controller a total system sequence-of-operation in
interface developed as an easy-to-use controller response to your answers to the questions.
adjustment and indication device. The ZT is Once configured, the VAV Controller’s operating
designed for the user who needs a parameters, such as setpoints, gains, alarm
straightforward method to monitor and adjust limits, and so forth, may be changed from any
points in an HVAC zone. The ZT plugs into the Metasys operator device.
TE-6410 Metastat or TE-6100 Zone Sensor to
communicate with or perform balancing of a VAV
box system. Factory Mounting Relationships
The original equipment manufacturers set up the
VAV control system for factory mounting. This
benefits you by lowering the overall cost of the
installation.

Application Specific Controllers—Variable Air Volume Controller 3


Metasys Network Configuration
As powerful as the VAV Controller is by itself, The Metasys Dynamic Data Access
your facility will benefit even more when VAV networking software, available from the Network
Controllers are part of a larger Metasys Network. Control Unit, makes all information from each
Each VAV Controller can connect to the Metasys VAV Controller available throughout the facility,
N2 Bus (Figure 2). Either a Network Control Unit so that it is possible, for example, to reset chiller
or Companion system can be programmed to or boiler temperatures based on the load
provide added energy management and demands of the VAV Controllers. Dynamic Data
supervisory control capabilities, including optimal Access also makes sensor values, operating
start, demand limiting, load rolling, runtime status, and any other parameter in the VAV
totalization, and more. Controller available to operators anywhere in
your facility.

N1 LAN

NCU NCU

Operator Workstation
ILC
VAV
Controller

ZONSTATOTE ZONE
TO
STAT Z BUS
LCP
DSI
Controller

VAV
Controller

ZONSTATOET ZONE
TO
STAT Z BUS

DSI

AHU
N2 N2
Controller

Metastat
Zone
Terminal VAVMTSYS

Figure 2: VAV Controller in Metasys Network

4 Application Specific Controllers—Variable Air Volume Controller


Metasys Companion Configuration
The Metasys Companion connects to the VAV Companion, which implements built-in energy
Controller over an independent N2 Bus management programs throughout the devices
(Figure 3). User access is through the on the bus.

Operator
Terminal

AHU
Controller

LCP
Controller

ENC100
Enclosure VAV
Controller

N2

Metastat
Zone
Terminal VAVCOMP

Figure 3: VAV Controller in Companion System

Application Specific Controllers—Variable Air Volume Controller 5


Application Flexibility
The VAV Controller can be configured to match An option provides the occupants in the zone the
most applications found in today’s rapidly ability to adjust the setpoint to their preference,
evolving VAV marketplace. The VAV-11n series within a restricted range established by you.
is packaged for factory mounting by original The user setpoint can be overridden by you at
equipment manufacturers in their panels. The any time using the operator interface devices or
VAV-14n series is packaged to accommodate application programs in the Network Control
field installations using screw terminations. The Unit. This allows maximum energy savings
ENC100 enclosure is used when an enclosure is while still allowing occupants some control over
not provided by the original equipment their environment.
manufacturer. In addition, points unused in the
A second option uses an occupancy sensor to
control scheme can be used in supervisory
automatically or manually setback or setup zone
monitoring and control applications by the
temperatures when no one is around. This can
Metasys Network.
further increase energy savings in individual
The VAV Controller offers a variety of zone offices or conference rooms.
sensor connection options that let you select the
Other options provide for control of room lighting
features you--and your occupants--need. The
as well as temperature, turning lights on or off
simplest and most economical option is a solid-
based on the occupancy sensor or scheduled
state sensing element wired directly to the
commands issued from the network. A “Boost”
controller. When this option is chosen, all
mode switch allows an occupant to temporarily
setpoint adjustments and programming changes
provide extra cooling or heating, which is useful
are made using the Operator Workstation or
for conference rooms that experience large heat
Network Terminal on the Metasys Network, or
load fluctuations.
from the Operator Terminal on a Companion
system.

6 Application Specific Controllers—Variable Air Volume Controller


Table 2: Applications and Options
Application Classifications Software Options
Primary Equipment Types VAV Box Single Duct
Dual Duct
Fan Powered or Assisted
Supply/Exhaust
Primary Control Strategies Pressure Dependent
Pressure Independent
Constant Volume
Box Heat Configuration Incremental Valve Actuator
Proportional
Normally Open Valve
Normally Closed Valve
Up to 3 Stages Electric
Baseboard Heat Configuration Incremental Valve Actuator
Normally Open Valve
Normally Closed Valve
Cooling Configuration Incremental Damper Actuator
Proportional Damper Actuator
Fan Configurations Parallel, Temperature Setpoint
Parallel, CFM Setpoint
Series, On-Off Control
Series, Proportional Control
Lighting Control On and off outputs to lighting relay in conjunction with Occ/Unocc
mode
Mode Selections Occupied/Unoccupied, Standby, Shutdown, Boost Control, Morning
Warm-Up, and Cooldown, Temporary Occupied for Time Delay

More Software Capabilities


The VAV Controller has additional capabilities to You can assign high and low alarm limits to all
help manage your facility. For example, the analog inputs to alert an operator at the Metasys
velocity sensor input to a pressure independent Operator Workstation or Companion terminal
system can be automatically calibrated to its when a problem occurs, such as a zone or
zero flow point once per day to ensure the VAV mixed air temperature exceeding comfort or
Controller maintains accuracy at low flows. You safety values.
can also set up this feature to be implemented
The VAV Controller also maintains a software
on a time schedule through the N2 network so
time-of-day clock and can store backup on/off
that a critically controlled zone’s airflow is not
schedules. These schedules will keep your local
interrupted during occupied conditions.
zones in the proper operating mode even if there
is a communication failure with the Network
Control Unit or Companion controller.

Conclusion
As either a member of the fully integrated The VAV Controller combines the best of ease-
system, or as a standalone controller, the VAV of-setup and operation, flexibility of application,
Controller represents the best way to optimize and precise control for comfort and energy
the operation of your HVAC equipment. management.

Application Specific Controllers—Variable Air Volume Controller 7


Specifications
Product AS-VAV110-1 / AS-VAV111-1
AS-VAV140-1 / AS-VAV141-1
Ambient Operating 32° to 140°F (0° to 50°C)
Conditions 10 to 90% RH
Dimensions 6.5 in. x 6.4 in. x 2.2 in. (165 x 163 x 56 mm) without enclosure
(H x W x D) 6.8 in. x 7.3 in. x 4.7 in. (173 x 185 x 119 mm) with enclosure
Ambient Storage -40° to 158°F (-40° to 70°C)
Conditions 10 to 90% RH
Power Requirements 24 VAC, 50/60 Hz at 40 VA (per typical system)
Shipping Weight 1.4 lbs (0.64 kg)
Standards Compliance IEEE 472 IEEE 518 IEEE 587 Category A
FCC Part 15, Subpart J, Class A
UL 916 UL864 VDE 0871 Class B
Agency Listings UL Listed and CSA Certified as part of the Metasys Network
Accessories
(Order Separately)
Power Supply (AS-XFR100) or (EN-EWC15-0)

Zone Terminal (AS-ZTU100-1)

Enclosure Kit (AS-ENC100-0) or (EN-EWC10-0)

HVAC PRO Cable (AS-CBLPRO-2)

N2 Plugs/Power Plugs (AS-TBKIT-0)


Replacement Kit (Kit consists of 5 of each plug type)

Zone Sensors (TE-6410 Series)

Damper Actuator/Velocity (ATP-2040 Series)


Sensor Package
Controller/Velocity (AS-VAVDPT Series)
Sensor Package

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.

Controls Group FAN 635


507 E. Michigan Street Metasys Network Sales Resource Manual
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201

8 Application Specific Controllers—Variable Air Volume Controller

You might also like