You are on page 1of 10

3440 Screen 7 : Reactive Energy(Export) Screen 8 : Apparent Energy Screen 13 : kVA Demand,

Max kVA Demand


Screen 14 : Import kW Demand /
Max Import kW Demand
V x1000 V x1000
Max Angle Max Angle V x1000 V x1000
KVAr KVArh KVAr KVArh Max Angle Max Angle
KVAr KVArh KVAr KVArh

TABLE 1:
3440 - Single Phase (1 Ph) Units of measurement
A
Min
KVA
x1000
Hz
D
A
Min
KVA
x1000
Hz
D
A
Min
x1000
Hz
A
Min
x1000
Hz
Measured Parameters %THD %THD KVA D KVA D
Single Phase Multi-function Digital Meter System Voltage Volts
%THD %THD

KW x1000 KW x1000

Installation & Operating Instructions System Current Amps kAh


kVAh
P.F.
kWh
kAh
kVAh
P.F.
kWh
KW
kAh
x1000
P.F.
KW
kAh
x1000
P.F.
Max D Max D kVAh kWh
Frequency Hz Max D
kVAh kWh
Max D
Section Contents System Active Power Kwatts
1. Introduction System Reactive Power KVAr
2. Measurement Reading Screens System Apparent Power KVA
3. Programming System Power Factor Screen 10: Min System Voltage
3.1 Password Protection Phase Angle Degree Screen 9 : Ampere Hour & Current Screen 15 :Export kW Demand /
Max Export kW Demand Screen 16 :Run Hour
3.2 Menu selection Active Import Energy (8 Digit resolution) kWh
3.2.1 System Parameter selection screen Active Export Energy (8 Digit resolution) kWh V
Max
x1000
Angle
V
Max
x1000
Angle V x1000
KVAr KVArh V x1000
3.2.1.1 Potential transformer Primary value Reactive Import Energy (8 Digit resolution) kVArh KVAr KVArh
Max Angle
Max
KVAr
Angle
KVArh
KVAr KVArh
3.2.1.2 Potential transformer Secondary value Reactive Export Energy (8 Digit resolution) kVArh
A x1000 A x1000
3.2.1.3 Current transformer Primary value Apparent Energy (8 Digit resolution) kVAh Min Hz
Min
KVA
Hz
D A x1000
A x1000
KVA D Min Hz
3.2.1.4 Current transformer Secondary value Ampere Hour (8 Digit resolution) KAh %THD %THD Min
KVA
Hz
D
KVA D
%THD
3.2.1.5 Demand integration time Current Demand Amps x1000 KW x1000
%THD

KW
3.2.1.6 Auto Scrolling KVA Demand KVA kAh
kVAh
P.F.
kWh
kAh
kVAh
P.F.
kWh KW x1000
KW
kAh
x1000
P.F.
Max D kAh P.F.
3.2.1.7 Low current noise cutoff KW Import Demand
Max D
kWh
kVAh kWh
KW kVAh
Max D
Max D

3.2.2 Communication Parameter selection screen


KW Export Demand KW
3.2.2.1 Address Setting
Max Current Demand Amps
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection Max kVA Demand KVA
Max KW Import Demand KW Screen 11 : Max System Voltage Screen 12 : Current Demand,
3.2.3 Reset Parameter selection screen Max Current Demand Screen 18 :Number of Interruptions
Max KW Export Demand & Current Screen 17 :On Hour
3.2.3.1 Resetting Parameter
Run Hour V x1000 Hours
3.2.4 Output Option selection screen (menu) Max Angle V x1000
V x1000 V x1000
On Hour KVAr KVArh
Max Angle Counts Max Angle Max Angle
3.2.4.1 Configuration of Output KVAr KVArh
KVAr KVArh KVAr KVArh

Number of Interruptions
3.2.4.1.1 Relay 1 output selection menu V1 THD % A
Min
x1000
Hz A x1000 A x1000
A x1000 Min Min Hz
3.2.4.1.1.1 Pulse output I1 THD
KVA D Min Hz
Hz
KVA
% %THD KVA D
KVA
%THD
D
%THD
D

3.2.4.1.1.1.1 Assignment of Energy to Pulse (Relay 1) %THD

3.2.4.1.1.1.2 Pulse Duration Selection KW


kAh
x1000
P.F.
KW x1000
KW x1000 KW x1000
kWh kAh P.F. kAh P.F.
3.2.4.1.1.1.3 Pulse Rate kVAh
Max D kAh
kVAh
P.F.
kWh kVAh kWh kVAh kWh
Max D
Max D
Max D
3.2.4.1.1.2 Limit output
3.2.4.1.1.2.1 Assignment of Limit Output1 to Parameter 2. Measurement Reading Screens
3.2.4.1.1.2.2 Limit Configuration
3.2.4.1.1.2.3 Trip point selection In normal operation the user is presented with one of the measurement reading
3.2.4.1.1.2.4 Hysteresis selection screens out of several screens. These screens may be scrolled through one at a
3.2.4.1.1.2.5 Energizing delay time time in incremental order by pressing the “ Up key” and in decremental order
3.2.4.1.1.2.6 De-energizing delay time by pressing “ Down key”.
3440 Setup Parameter Screen
3.2.4.1.2 Relay 2 output selection menu
3.2.4.1.3 Analog output CODE (PassWord) Exit from setup Parameter to Main Display
3.2.4.1.3.1 Parameter setting for Analog Output-1 Screen 1 : System screen Screen 2 : Phase Angle , Frequency,
3.2.4.1.3.2 Parameter setting for Analog Output-2 (System Voltage, System Current, Sys. Power Factor SEL (Select)
System Active Power)
3.2.5 Quit screen
4. Run - Hour.
5. On - Hour. V
Max
x1000
Angle
V
Max
x1000
Angle
SYS PArA Ser PArA rSEt Out PArA
6. Number of Interruption KVAr KVArh KVAr KVArh
A quit
(System Parameter) (Serial Comm.Parameter) (Reset Parameter) (Output Parameter) A
7. Analog Output (Sec 3.2.2) (Sec 3.2.3) (Sec 3.2.4)
(Exit Menu)
(Sec 3.2.5)
(Sec 3.2.1)
8. Relay Output A
Min
x1000
Hz
A
Min
x1000
Hz
KVA D KVA D
8.1 Pulse output %THD %THD

8.2 Limit Switch none (No Parameter),


KW x1000 x1000 UP
Addr
9. RS 485 ( ModBus ) kAh P.F.
KW
kAh P.F. (Modbus Address) ALL (All Parameter),
kVAh kWh kVAh kWh (PT Primary)
9.1 User Assignable Modbus Register Max D Max D
(Sec 3.2.1.1)
(Sec 3.2.2.1) d (Demand), B rL1 & rL2 AnL Out quit
10. E (Energy), (Relay 1 & 2) (Analog Output) (Exit Menu)
Phaser Diagram hi (Max values), (Sec 3.2.4.1.1) (Sec 3.2.4)
(Sec 3.2.4.1.3)
11. Installation Lo (Min values),
US hr (Run Hour & On Hour),
11.1 EMC Installation Requirements br
(PT Secondary) (Baud Rate) Intr (No. of Interrupts)
11.2 Case Dimensions and Panel Cut-out (Sec 3.2.1.2) (Sec 3.2.2.2) Select any one option using
11.3 Wiring “Down” key . B
Screen 3 : System Power PUL Lt AnL1
11.4 Auxiliary Supply ( Reactive, Apparent, Active) Screen 4 : Active Energy(Import) (Pulse Output) (Limit Output) (Analog1 parameter
11.5 Fusing AP (Sec 3.2.4.1.1.1) (Sec 3.2.4.1.1.2) selection)
(CT Primary) Pr (Acc. To Table)
11.6 Earth / Ground Connections (Sec 3.2.1.3) (Parity Bits) (Sec 3.2.4.1.3.1)
12. V x1000 V x1000 (Sec 3.2.2.3)
Connection Diagrams Max Angle Max Angle
KVAr KVArh KVAr KVArh Para. Selection Para. Selection
13. Specification (i-E, E-E, i-rE, E-rE, (Acc. To Table)
AS A-E, A-H) (Sec 3.2.4.1.1.2.1)
14. Connection for Optional Pulse output / RS 485 /Analog Ouput A x1000 A x1000 (CT Secondary) (Sec 3.2.4.1.1.1.1)
AnL2
Min Hz Min Hz
KVA D KVA D
(Sec 3.2.1.4) (Analog 2 parameter
15030734 Rev.C/12/11 %THD %THD selection)
(Acc. To Table )
Limit Config.
KW x1000 KW x1000 dur (Sec 3.2.4.2.3.2)
Selection
1. Introduction kAh
kVAh
P.F.
kWh
kAh
kVAh
P.F.
kWh
dit (Pulse Duration) (Hi-E, Hi-d,
Max D Max D (Demand Integ.Time ) 60,100,200 Lo-E, Lo-d)
(Sec 3.2.1.5)
The 3440 is a panel mounted 96 x 96mm DIN Quadratic Digital metering (Sec 3.2.4.1.1.1.2) (Sec 3.2.4.1.1.2.2)

system for the measurement important electrical parameters like AC Voltage,


AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) . Auto rAt trip (Trip Point)
The instrument integrates accurate measurement technology ( Voltage & Current (Auto Scrolling)
(Pulse Divisor Rate) 10% to 100%
(Sec 3.2.1.6)
measurements are True RMS upto 15th Harmonic) with 3 line 4 digits ultra high 1, 10, 100, 1000 (Sec 3.2.4.1.1.2.3)
(Sec 3.2.4.1.1.1.3)
Brightness LED display. Screen 5 : Active Energy (Export) Screen 6 : Reactive Energy(Import)
nC
(Noise Current Cut-off) HYS (Hysterisy s)
0.5% to 50%
V x1000 V x1000 V x1000
(Sec 3.2.1.7) B (Sec 3.2.4.1.1.2.4)
Max Angle Max Angle Max Angle
KVAr KVArh KVAr KVArh KVAr KVArh

The front panel has two push buttons through


A
Min
x1000
Hz
which the user may scroll through the A
Min
x1000
Hz
A
Min
x1000
Hz
A En-d : UP KEY
KVA
%THD
D available measurement readings, reset the KVA
%THD
D KVA
%THD
D (Energizing Delay time)
1s to 10s
energy (Import/Export) Min/Max (System Voltage (Sec 3.2.4.1.1.2.5)
KW x1000 and System Current) and configure the product. KW x1000 KW x1000
: DOWN KEY
kAh P.F. kAh P.F. kAh P.F.
kVAh kWh kVAh kWh kWh
kVAh
Max D Max D Max D

dE-d
B (De-energizing Delay time) 1s
to 10s
(Sec 3.2.4.1.1.2.6)

Down Up
2
1
Screen 19 : Voltage & Current %THD Password confirmed. 3.2.1 System parameters Selection
V
Max
x1000
Angle New Password confirmed.
KVAr KVArh V x1000
V x1000
Max Angle
Max Angle
KVAr KVArh
KVAr KVArh
A x1000
Pressing “ Down” key will advance to the “New / Pressing the “ Down” key will return to the 3.2.1.1 Potential Transformer Primary Value
Min
KVA
Hz
D A x1000 change Password” entry stage. A x1000
“New/Change Password”.
%THD Min Hz
Min
KVA
%THD
D
KVA
Hz
D The nominal full scale voltage which will be displayed as Line to Line voltage
%THD
KW x1000
kAh P.F. This screen allows user to set the primary voltage in kilovolts (note the x1000 enunciator).
kVAh kWh
Max D
KW
KAh
x1000
P.F. Pressing the “ Up” key will advance to the Menu selection KW x1000 Pressing the “ Up” key will advances to the
P.F.
KVAh KWh
Max D screen. (See section 3.2).
KAh
KVAh KWh Menu selection screen.(see section 3.2). Pressing the “ Up” key accepts the present value
Max D
and advances to the “potential Transformer secondary
Value edit” menu. (See Section 3.2.1.2).
V x1000
Max
KVAr
Angle
KVArh Pressing the “ Down” key will enter the “Potential
3. Programming Transformer Primary Value Edit” mode.
The following sections comprise step by step procedures for configuring the A
Min
x1000
Hz

3440 for individual user requirements. KVA D Initially the “multiplier must be selected, pressing the
%THD
“ Down” key will move the decimal point position to the
To access the set-up screens press and hold the “ Down” and “ Up” Password Incorrect.
3.2 Menu selection. KW x1000
right until it reaches # # # .# after which it will return to
Key simultaneously for 5 seconds. This will take the User into the Password V x1000
KAh P.F.

Protection Entry Stage (Section 3.1). Max


KVAr
Angle
KVArh The unit has not accepted the 3.2.1 System Parameter selection screen. KVAh KWh
Max D
#. # # #.
Password entered. Pressing the “ Up” key accepts the present
3.1. Password Protection A x1000
Min Hz
This screen is used to select the different system Multiplier (decimal point position) and advances to the
Password protection can be enabled to prevent unauthorised access to set-up KVA D
Pressing the " Down" key will return to V x1000

screens, by default password protection is not enabled.


%THD
Max Angle Parameter like “system type,””CT Ratio”,”PT Ratio”, “potential Transformer primary Digit Edit” mode.
the Enter Password stage. KVAr KVArh
KW x1000
Password protection is enabled by selecting a four digit number other than 0000, KAh P.F.
Pressing the “ Up” key allows the user to set
KWh
setting a password of 0000 disables the password protection. KVAh
Pressing the “ Up” key exits the
A x1000
Max D Min
KVA
Hz
D
Different system parameters. Potential Transformer primary Digit Edit
Password menu and returns operation %THD
(see section 3.2.1.1 to 3.2.1.7) V x1000 Pressing the “ Down” key will scroll the value of
to the measurement reading mode. x1000
Max Angle
KW
KAh P.F.
KVAr KVArh
the most significant digit from 0 through to 9 unless
V x1000 KVAh KWh
Max Angle Max D Pressing the “ down” key will advance to the presently displayed Potential Transformer Primary
KVAr KVArh A x1000
Min Hz Value together with the Current Transformer Primary
Communication selection screen (see section 3.2.2) KVA D

A x1000
%THD Value, previously set, would result in a maximum power
Min
KVA
Hz
D KW x1000
of greater than 666.6 MVA in which case the digit range
%THD KAh
KVAh
P.F.
KWh
will be restricted.
New / Change Password
Max D
KW x1000
KAh P.F.
3.2.2 Communication Parameter selection screen. Pressing the “ Up” key accepts the present value
KVAh KWh V x1000
Max D Max Angle at the cursor position and advances the cursor to the
KVAr KVArh
(*Decimal point indicates that this will be flashing). next less significant digit.
This screen is used to select the different communication
A
Min
x1000
Hz
V x1000 parameters like “Address selection”,”RS485 Parity selection”, The PT Primary value can be set from 100V L-L to 692.8KV L-L.
KVA D Pressing the “ Down” key will scroll the value of the Max Angle
Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present
%THD
first digit from 0 through to 9, the value will wrap from 9
KVAr KVArh
”RS485 baud rate”
to identify the scaling of the number until the cursor position coincides with the steady decimal point
KW x1000 round to 0. A x1000
KAh P.F. Min Hz Pressing the “ Up” key allows the user to set different position. At this stage the decimal point will flash.
KVAh KWh KVA D
V x1000
Max D
Pressing the “ Up” key to advance the operation to
%THD
Communication parameters When the least significant digit has been set pressing the “ Up” key will advance to the
Max Angle
KVAr KVArh
the next digit and sets the first digit, in this case to “2” x1000 (see section 3.2.2.1 to 3.2.2.3)
KW
KAh P.F. “Potential Transformer Primary Value Confirmation” stage.
KVAh KWh
A x1000 Max D
Min
KVA
Hz Pressing the “ down key will advance to Reset parameter Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor
D
%THD
Screen. (see section 3.2.3) flashing at the “hundreds of volts” position.
KW x1000
KAh
KVAh
P.F.
KWh
Potential Transformer Primary Value Confirmation
Max D
V x1000
VRY Angle
This screen will only appear following an edit of the
New / Change Password, first digit entered, prompting for KVArh
V
Max
x1000
Angle second digit. (*Decimal point indicates that this will be 3.2.3 Reset Parameter selection screen. KVAr
Potential Transformer Primary Value.
KVAr KVArh
flashing). A x1000
Min Hz If the scaling is not correct, pressing the “ Down”
A x1000 This screen is used to Reset the different parameters . KVA D
Min Hz V x1000
%THD key will return to the “Potential Transformer Primary
Enter Password, second digit entered, prompt for third
KVA
%THD
D Pressing the “ Down” key will scroll the value of the Max
KVAr
Angle
KVArh Value Edit” stage.
KW x1000
V x1000 digit. (* Denotes that decimal point will be flashing). second digit from 0 through to 9, the value will wrap from KAh P.F.
Max
KVAr
Angle
KVArh
KW
KAh
x1000
P.F.
9 round to 0. A x1000
Pressing the “ Up” key allows the user to Reset different KVAh KWh
Max D
KVAh KWh Min Hz
Max D KVA D system parameters (see section 3.2.3.1)
%THD
A x1000
Min Hz Use the “ Down” key to scroll the value of the third Pressing the “ Up” key to advance the operation to the Pressing the “ Up” key sets the displayed value
KVA D x1000
%THD digit from 0 through to 9, the value will wrap from 9 next digit and sets the second digit, in this case to “1” KW
KAh P.F. and will advance to the Potential Transformer secondary
round to 0. KVAh KWh 0.120kV i.e 120V L-L
Max D Value (See Section 3.2.1.2)
KW
KAh
x1000
P.F. Pressing the “ down key ” will advance to Output
KVAh KWh
Max D Option selection screen (see section 3.2.4).
3.2.1.2 Potential Transformer secondary Value
Press the “ Up” key to advance to next digit.

The value must be set to the nominal full scale secondary voltage which will be obtained from the
New / Change Password, second digit entered, 3.2.4 Output Option selection screen. Transformer when the potential transformer(PT)primary is supplied with the voltage defined in 3.2.1.1
V
Max
x1000
Angle
prompting for third digit. (*decimal point indicates that potential transformer primary voltage.The ratio of full scale primary to full scale secondary is defined
Enter Password, third digit entered, prompt for fourth KVAr KVArh this will be flashing).
This screen will allow the user to select different as the transformer ratio.
V
Max
x1000 digit.
KVAr
Angle
KVArh (* Denotes that decimal point will be flashing). A x1000
V
Max
x1000
Output options Like “Relay1”,”Relay2”,”Analog” Output.
Min
KVA
Hz Pressing the “ Down” key will scroll the value of the KVAr
Angle
KVArh Pressing the “ Up” key accepts the present value
D

A x1000
%THD third digit from 0 through to 9, the value will wrap from 9 V
Max
x1000
Angle
and advances to the “Current Transformer Primary
Min
KVA
Hz Use the “ Down” key to scroll the value of the fourth x1000
round to 0. A x1000
Pressing the “ Up” key allows the user to select &
KVAr KVArh
Value edit” menu. (See Section 3.2.1.3)
D KW Min Hz
%THD digit from 0 through to 9, the value will wrap from 9 KAh P.F. KVA D

round to 0. KVAh KWh


Max D
Configuare the output option (see section 3.2.4.1) A x1000 Note that the range of instrument is from 240 to 480V for
x1000 Min Hz
KW
KAh P.F. Pressing the “ Up” key to advance the operation to KW x1000
KVA
%THD
D 415 V L-L. Please refer the table below for different ranges.
KVAh KWh KAh P.F.
Max D the next digit and sets the third digit, in this case to “5” KVAh KWh Pressing the “ Down” key will enter the “Potential
Max D
Press the “ Up” key to advance to verification of the Pressing the “ down key will advance to Quit screen.
KW
KAh
x1000
P.F. Transformer Secondary Value Edit” mode.
password. KVAh KWh
Max D “ Down” key will scroll the value of the most significant
(see section 3.2.5)
digit from available range of PT secondary value
Pressing the “ Up” key accepts the present value
at the cursor position and advances the cursor to the
V x1000
Enter Password, fourth digit entered, awaiting
New / Change Password, third digit entered, prompting
3.2.5 Quit screen. next less significant digit.
Max Angle verification of the password. V x1000
KVAr KVArh Max
KVAr
Angle for fourth digit. (* denotes that decimal point will be Potential Transformer secondary ranges for various Input Voltages
KVArh
flashing).
A
Min
x1000
Hz V x1000
110V L-L (63.5V L-N) 100 - 120V L-L (57.73V - 69.28V L-N)
A x1000
KVA
%THD
D Min
KVA
Hz
Pressing the “ Down” key will scroll the value of the
Max
KVAr
Angle
KVArh Pressing the “ Up” key will allow the user to Quit from menu 230V L-L (133.0 V L-N) 121 - 239V L-L (69.86V - 138V L-N)
D
%THD
fourth digit from 0 through to 9, the value will wrap from & return to measurement screen. 415V L-L (239.6V L-N) 240 - 480V L-L (138.56V - 277.12V L-N)
KW x1000
KAh P.F. KW x1000 9 round to 0. A
Min
x1000
Hz
KVAh KWh KAh P.F. KVA D
Max D KVAh KWh
Max D
%THD Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present
Pressing the “ Up” key to advance the operation to KW x1000
to identify the scaling of the number until the cursor position coincides with the steady decimal point
the “New Password Confirmed” and sets the fourth digit, KAh
KVAh
P.F.
KWh
position. At this stage the decimal point will flash.
in this case to “3”. Max D

When the least significant digit has been set pressing the “ Up” key will advance to the
“Potential Transformer secondary Value Confirmation” stage.

3 4
Potential Transformer Secondary Value Confirmation 3.2.1.5 Demand Integration Time 3.2.2 Communication Parameter Selection : RS 485 Baud Rate confirmation :
V x1000
V
Max
x1000
This screen will only appear following an edit of the 3.2.2.1 Address Setting : This screen applies to the RS 485 output only. Max Angle
KVAr
Angle
KVAr KVArh Pressing “ Down” key will be re-enter into the.
KVArh
Potential Transformer Secondary Value. This screen is used to set the period over which
V x1000 This screen allows the user to set RS485 parameter for instruments Baud Rate Edit mode
A x1000
Max
KVAr
Angle
KVArh
current and power readings are to be integrated A x1000
Min Hz If the scaling is not correct, pressing the “ Down” The Unit of displayed Readings is minutes.
Min
KVA
Hz
D
KVA
%THD
D
key will return to the “Potential Transformer Secondary %THD Pressing the “ Up” key will select the value and advances
A x1000
Min Hz The range of allowable address is 1 to 247 . to the Parity Selection (See Section 3.2.2.3).
KW x1000 Value Edit” KVA D P. ressing the “ Down” key will scroll through the V x1000
KW x1000
%THD KAh P.F.
KAh P.F. Max Angle
KVAh KWh following Options 8,15,20,30. KVAr KVArh KVAh KWh
Max D
Max D
Pressing the “ Up” key sets the displayed value KW x1000 Enter Address, prompt for first digit.
KAh P.F.
and will advance to the current Transformer Primary KVAh KWh
Max D
Pressing the “ Up” key will advance to Demand A
Min
x1000
Hz
(* Denotes that decimal point will be flashing).
Value (See Section 3.2.1.3) Integration confirmation screen. KVA
%THD
D

KW
KAh
x1000
P.F.
Press the “ Down” key to scroll the value of the first digit
KVAh KWh
Max D

3.2.1.3 Current Transformer Primary Value Press the “ Up” key to advance to next digit. 3.2.2.3 RS 485 Parity Selection :
This screen allows the user to set Parity & number of stop bits of RS 485 port.
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the Demand Integration Time value confirmation
user to display the Line currents inclusive of any transformer ratios, the values displayed represent V x1000 Pressing “ Up” key accepts the present value and
the Current in Amps. Max
KVAr
Angle
KVArh advance to Menu selection (see section 3.2.2).
V x1000
Max Angle
Pressing the “ Up” key accepts the present value and advances to the Current Transformer A x1000 Pressing “ Up” key sets the displayed value and KVAr KVArh

Secondary Value (See Section 3.2.1.4)


Min
KVA
Hz
D will advance to scroll screen. Enter Address, first digit entered, prompt for second digit Pressing the “ Down” key will enter the “Parity & stop bit
%THD
(See Section 3.2.1.6) V x1000 A
Min
x1000
Hz Edit” mode and scroll the value through
Max
KVAr
Angle
KVArh
(* Denotes that decimal point will be flashing). KVA D
Pressing the “ Down” key will enter the “Current KW x1000 %THD

odd : odd parity with one stop bit


KAh P.F.
Transformer Primary Value Edit” mode. This will scroll KVAh KWh
A x1000 KW x1000
Max D

V x1000
The value of the most significant digit from 0 through to 9, Min
KVA
Hz
D Use the “ Down” key to scroll the value of the second digit
KAh
KVAh
P.F.
KWh no 1 : no parity with one stop bit
no 2 : no parity with two stop bit
Max
KVAr
Angle
KVArh unless the presently displayed Current Transformer %THD Max D

Primary Value together with the Potential Transformer KW x1000


E : even parity with one stop bit
KAh P.F.
A
Min
x1000
Hz
Primary Value results in a maximum power of greater KVAh KWh
Max D
KVA
%THD
D
than 666.6 MVA in which case the digit range will be Press the “ Up” key to advance to next digit.
restricted, the value will wrap. Example: If primary value
KW x1000
KAh P.F. of PT is set as 692.8kVL-L (max value) then primary value of
KVAh KWh
Max D Current is restricted to 1157A.
3.2.1.6 Auto Scrolling :
V x1000
RS 485 Parity confirmation :
Max Angle
Pressing the “ Up” key will advance to the next less This screen allows user to enable screen scrolling.
KVAr KVArh
Pressing “ Down” key will be re-enter into Parity Edit mode .
V x1000
significant digit. (* Denotes that decimal point will be Max Angle

flashing).
KVAr KVArh
Auto scrolling Edit. Enter Address, second digit entered, prompt for third digit A
Min
x1000
Hz
V x1000 KVA D
Max
KVAr
Angle (* Denotes that decimal point will be flashing). %THD Pressing the “ Up” key will set the value.
A x1000 KVArh
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of Min
KVA
Hz Pressing “ Up” key accepts the present status and KW x1000
D
nominal voltage, i.e, 462.96 MVA nominal power. %THD advance to the Low Current noise cutoff. A x1000
KAh P.F.
Pressing the “ Up” key again will jump back to the
Min Hz Use the “ Down” key to scroll the value of the third digit KVAh KWh

KW x1000
(See Section 3.2.1.7). KVA D
Max D
communication parameter selection menu (see section 3.2.2).
%THD
When the least significant digit had been set, pressing the “ Up” key will advance to the KAh
KVAh
P.F.
KWh
“Current Transformer Primary Value Confirmation” stage. Max D KW x1000
P.F.
KAh
KVAh KWh
Max D
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero when the
“ Up” key is pressed.
Current Transformer Primary Value Confirmation. 3.2.3 Reset Parameter Selection :
This screen will only appear following an edit of the Current 3.2.3.1 Resetting Parameter
Transformer Primary Value . The following screens allow the users to reset the all Energy , Lo(Min), hi(Max),Demand,Run hour, .
V x1000
Max Angle
V x1000 Pressing the “ Down” key will enter the “Auto Screen On hour, No.of Interrupts
KVAr KVArh If the scaling is not correct, Pressing the “ Down” key Max Angle
KVAr KVArh Scrolling Edit” and toggle the status ‘Yes’ and ‘No’. Enter Address for third digit .
will return to the “ Current Transformer Primary Value Edit” V x1000 Reset (None)
A x1000
Min Hz stage with the most significant digit highlighted (associated A x1000
Max
KVAr
Angle
KVArh V x1000
KVA D Min
%THD decimal point flashing) and the bottom line of the display Hz Max Angle
Pressing “ Up” key advances to Reset Parameter
KVA
%THD
D
Pressing the “ Up” key will select the status displayed Press the “ Up” key to advance to Address confirmation
KVAr KVArh

KW x1000
will be blanked. and advance to the Low Current noise cutoff.
A
Min
x1000
Hz
selection screen (see section 3.2.3)
KAh P.F. KVA
KVAh KWh
KW
KAh
x1000
P.F. (See Section 3.2.1.7). %THD
D
Screen. A
Min
x1000
Hz
Max D
Pressing the “ Up” key sets the displayed value and KVAh KWh
Max D
KVA
%THD
D
Pressing the “ Down” key will enter the “Reset
KW x1000
will advance to the “Current Transformer Secondary Value KAh P.F. option” mode and scroll through Parameter
KVAh KWh KW x1000
Edit” menu. (See Section 3.2.1.4) Max D KAh P.F. and wrapping back to None.
KVAh KWh
Max D

3.2.1.4 Current Transformer Secondary Value 3.2.1.7 Low Current noise cutoff.
This screen allows the user to set Low noise current cutoff in mA.
V x1000 Address confirmation Screen.
Max Angle
This screen is used to set the secondary value for Low current cutoff Edit. KVAr KVArh

Current Transformer. Secondary value “5” for 5A or This Screen confirms the Address set by user . Reset option select, (Resets ALL resettable parameter)
V V x1000
x1000 A x1000
Max
Max
“1” for 1A can be selected. Pressing “ Up” key Angle
Pressing Press the “ Up” key to advance to next Screen
. “ Up” key accepts the present value and
Angle Min Hz V x1000
KVAr KVAr KVArh
KVArh KVA Max Angle
accepts the present value and advances to the advance to System Parameter Selection. %THD
D
KVAr KVArh The user has scrolled through to the “ALL” .
“Rs485 Baud Rate” (See Section 3.2.2.2)
A x1000 Demand integration Time (See Section 3.2.1.5) A
Min
x1000
Hz
(See section 3.2.1) KW x1000
Min
KVA
Hz
D
KVA D KAh P.F. A
Min
x1000
Hz
Pressing “ Up” key will select the value & advance
%THD
Pressing the “ Down” key will enter the CT
%THD KVAh KWh
Max D
Pressing the “ Down” key will reenter the “Address KVA D to the “Reset ALL Confirmation” Mode & will reset all
%THD

Pressing the “ Down” key will enter the “Low current Edit” mode. resettable parameter.
KW x1000
P.F.
Secondary value edit mode and scroll the value KW
KAh
x1000
P.F.
x1000
KAh KW
KVAh KWh through the values available. KVAh KWh
Max D
noise cutoff Edit” mode and scroll the “Value” through 0 & 30 KAh P.F.
Max D KVAh KWh
and wrapping back to 0. Setting 30 will display measured Max D

Pressing the “ Up” key will advance to the CT currents as 0 below 30 mA.
Secondary value confirmation.
3.2.2.2 RS 485 Baud Rate :
CT Secondary value confirmation Low current noise cutoff Confirmation. This screen allows the user to set Baud Rate of RS 485 port.
Reset ALL Confirmation.
V x1000 V x1000 V x1000
The values displayed on screen are in kbaud. V x1000
Max Angle This screen will only appears following an edit of CT Max Angle Max Angle
Max Angle
KVAr KVArh
secondary value .
KVAr KVArh KVAr KVArh KVAr KVArh
Pressing the “ Down” key will re-enter the reset
pressing the “ Down” key will re-enter the “Low current Pressing “ Up” key accepts the present value and option Select mode.
A x1000 A x1000 Noise cutoff Edit” mode. A x1000
advance to the Parity Selection (See Section 3.2.2.3). A x1000
Min
KVA
Hz
D
If secondary value shown is not correct, pressing the Min
KVA
Hz Min
KVA
Hz
Min
KVA
Hz
D
%THD
Down key will return to CT secondary edit stage by %THD
D
%THD
D
%THD Pressing “ Up” key will jump back to the reset
blanking the bottom line of the display. parameter selection screen (see section 3.2.3).
KW
KAh
x1000
P.F.
KW x1000
P.F.
Pressing “ Up” key set displayed value and KW x1000
P.F.
Pressing the “ Down” key will enter the “Baud Rate KW
KAh
x1000
P.F.
KAh KAh
KVAh KWh
Max D
KVAh KWh will jump back to the system parameter selection KVAh KWh
Edit” mode and scroll the value through 2.4, 4.8, 9.6, 19.2 KVAh KWh
Max D
Pressing “ Up” key sets the displayed value and Max D
(See section 3.2.1)
Max D
and back to 2.4.
will advance to Demand integration Time Edit menu.
(See Section 3.2.1.5)

5 6
Reset Lo Confirmation
Reset option select, (Reset A Demand, KVA Demand V
Max
x1000
Angle
3.2.4.1.1.1.2 Pulse Duration Selection:
KVAr KVArh
V
Max
x1000
Angle Parameters KW demand (Import/Export)) Pressing the “ Down” key will re-enter the This screen applies to the Analog Output Selection.
KVAr KVArh
“Reset option Select mode. V x1000
This screen applies only to the Pulsed output mode of both the relay
A x1000
The user has scrolled through to the “d” . Min Hz
Max
KVAr
Angle
KVArh
This screen allows the user to set Relay energisation time in milliseconds.
KVA
A x1000 D
Pressing “ Up” key will Select the Analog output
Min
KVA
Hz
D
%THD
Pressing “ Up” key will jump back to the
%THD Pressing “ Up” key will select the value and Reset Parameter selection screen (see section 3.2.3). A x1000 selection menu (See section 3.2.4.3)
KW x1000
P.F.
Min Hz Pulse Duration Edit.
KW x1000
resets all Demand parameters. KAh
KVAh KWh
KVA
%THD
D
V x1000
KAh P.F. Max D
KVAh KWh
KW x1000
Max
KVAr
Angle
KVArh
Pressing “ Up” key accepts the present value and
Max D
KAh P.F. Pressing the “ Down” key will advance to Quit screen. advance to pulse rate selection menu
KVAh KWh
Max D A
Min
x1000 (see section 3.2.4.1.1.1.3).
Hz
KVA D
%THD Pressing the “ Down” key will enter the “Pulse Duration
KW x1000
Edit” mode and scroll the value through 60, 100, 200 and
KAh P.F.
wrapping back to 60.
Reset Demand parameters Confirmation. V x1000
Reset option select, hr (ON Hour & Run Hour) KVAh KWh
Max D
Max Angle
V x1000 KVAr KVArh Pressing the “ Up” key will select the value and advances
Max Angle
Pressing the “ Down” key will re-enter the The user has scrolled through to the “hr” to “Pulse Duration Confirmation”.
KVAr KVArh
This screen allows the user to quit the output option
“Reset option Select mode. A
Min
x1000
Hz
A x1000
KVA D Pressing “ Up” key will select the value and V x1000
%THD Max Angle
Min
KVA
Hz
D
advance to the “Reset hr Confirmation” Mode & KVAr KVArh
Pressing “ Up” key will advance to the
%THD Pressing “ Up” key will jump back to the KW x1000 Will reset On hour & Run Hour both.
Reset Parameter selection screen (see section 3.2.3). KAh P.F. Output Parameter selection (See section 3.2.4)
KW x1000 KVAh KWh
A
Min
x1000
Hz V
Pulse Duration Confirmation.
P.F. Max D x1000
KAh KVA D Max Angle
KVAh KWh %THD KVAr KVArh
Max D
This screen will only appear following an edit of the
x1000
KW
KAh P.F. Pressing the “ Down” key will go back to A x1000
Pulse duration.
KVAh KWh Min Hz
Max D Relay1 output option (See section 3.2.4.1). KVA KVA D
%THD pressing the “ Down” key will re-enter the “Pulse
KW x1000
Duration Edit” mode.
Reset hr Confirmation KAh
KVAh
P.F.
KWh
Reset option select, (Resets all Energies) V
Max
x1000
Max D
Pressing “ Up” key set displayed value and
Angle
V x1000
KVAr KVArh Pressing the “ Down” key will re-enter the Will advance to pulse rate selection menu
Max
KVAr
Angle
KVArh The user has scrolled through to the “E” Energy “Reset option Select mode. (See section 3.2.4.1.1.1.3)
value. A
Min
x1000
Hz
A
Min
x1000
KVA
%THD
D
Pressing “ Up” key will jump back to the 3.2.4.1.1 Relay1 output Selection menu :
Hz
KVA D Pressing “ Up” key will select the value and Reset Parameter selection screen (see section 3.2.3).
%THD
advance to the “Reset Energy Confirmation” Mode KW
KAh
x1000
P.F. 3.2.4.1.1.1 Pulse output : 3.2.4.1.1.1.3 Pulse Rate
KVAh KWh
KW
KAh
x1000
P.F.
& resets all Energies (Import Enegy, Export Energy Max D
KVAh KWh
Max D
Import reactive, Export reactive, Apparent Energy This screen applies to the Relay Output option only. The screen allows user to set the energy
Ampere Hour) pulse rate divisor. Divisor values can be selected through 1,10,100,1000.
This screen is used to assign Relay1 in Pulse
V
Max
x1000
Angle output mode
KVAr KVArh
V x1000
Pressing “ Up” key accepts the presents value
Pressing “ Up” key will advance to the Max Angle and advances to the “Configuration of Output”
Reset option select, (Reset Number of Interrupt) A x1000 KVAr KVArh

V x1000
Min
KVA
Hz Pulse (for Relay1) output configuration (See section 3.2.4.1).
D
Reset Energy Confirmation. Max
KVAr
Angle
KVArh The user has scrolled through to the “intr” %THD (See section 3.2.4.1.1.1.1) A x1000
Min Hz
V
Max
x1000
Angle x1000
KVA D Pressing the “ Down” key will enter the “Pulse rate
KVAr KVArh Pressing the “ Down” key will re-enter the “Reset A x1000
KW
KAh P.F. Pressing “ Down” key will show “Limit”output option %THD
divisor edit” mode and scroll the values through the
option” mode. Min Hz Pressing “ Up” key will select the value and KVAh KWh
values 1,10,100,1000 wrapping back to 1.
Max D
A x1000
KVA
%THD
D
advance to the “reset Interrupt Confirmation” Mode & (See section 3.2.4.1.1.2) KW
KAh
x1000
P.F.
Min Hz
KVA D Will reset number of Auxiliary supply interruption count. KVAh KWh
Max D
%THD Pressing “ Up” key will jump back to the KW
KAh
x1000
P.F.
Pressing the “ Up” key advances to the “Pulse rate
KW x1000
Reset Parameter selection screen (see section 3.2.3). KVAh KWh
Max D
Divisor Confirmation” menu.
KAh P.F.
KVAh KWh
Max D

3.2.4.1.1.2 Limit output :


Pulse Rate Divisor Confirmation.
This screen is used to assign Relay1 in limit output mode. This screen will only appear following an edit of the
V x1000
V x1000 Max
Reset Interrupt Confirmation Max Angle KVAr
Angle
KVArh Pulse rate divisor.
Reset option select, (Reset Hi) V x1000
KVAr KVArh
Pressing “ Up” key will assign
Max Angle
V x1000 KVAr KVArh
Pressing the “ Down” key will re-enter the A x1000
Limit (for Relay1) output mode.(See section 3.2.4.1.1.2.1) A x1000 If the Pulse rate shown is not correct, pressing the
Max Angle Min Hz
KVAr KVArh The user has scrolled through to the “Hi” (Max) “Reset parameter Selection”(see section 3.2.3).
Min
KVA
Hz
D
KVA D “ Down” key will return to the “Pulse rate divisor
%THD
A x1000
Min Hz
%THD
Pressing “ Down” key wil go back to the pulse option Edit” stage by blanking the bottom line of the
A
Min
x1000 Pressing “ Up” key will select the value and KVA
%THD
D
KW x1000
KW x1000
display.
KVA
Hz
D advance to the “Reset Hi Confirmation” Mode & will KAh P.F. (For Relay 1) screen.(See section 3.2.4.1.1.1) KAh
KVAh
P.F.
KWh
%THD
KW x1000
Pressing “ Up” key will jump back to the KVAh KWh
Max D
Reset Maximum (Hi) values of Voltage & Current KAh P.F.
Reset Parameter selection screen (see section 3.2.3).
Max D
Pressing “ Up” key sets the displayed value and
KW x1000 KVAh KWh
KAh P.F. Avg. Appeared at input. Max D will advance to the “Configuration of output”.
KVAh KWh
Max D (See section 3.2.4.1)

3.2.4.1.1.1.1 Assignment of Energy to pulse output (Relay 1) : 3.2.4.1.1.2.1 Assignment of Limit output (for Relay1) to parameter.
3.2.4. Output Option selection menu This screen is for Limit output mode selection. It allows the user to set Limit output corresponding
This screen allows the user to assign pulse output to energy (for Relay 1) measured value . Refer Table 2“ Parameter for Analog & Limit output “ for assignment.
3.2.4.1 Configuration of Output
Reset hI (Max) Confirmation.
V x1000 Pressing “ Up” key accepts the present setting
Max Angle This screen applies to the Relay1 Output option Selection . and advance to “Pulse duration selection”
KVAr KVArh
Pressing the “ Down” key will re-enter the V x1000 V
Pressing “ Up” key accepts the present value and
x1000
“Reset option Select mode.
V x1000 Max Angle (see section 3.2.4.1.1.1.2). Max advance to the Limit1 configuration select screen.
Max Angle Pressing “ Up” key will select the KVAr KVArh KVAr
Angle
KVArh
A
Min
x1000
Hz
KVAr KVArh
Pressing the “ Down” key will enter into edit mode (see section 3.2.4.1.1.2.2 ).
KVA
%THD
D
Relay1 output selection menu(See section 3.2.4.1.1) A x1000 and scroll through the energy setting A x1000
A x1000 Min
Pressing “ Up” key will jump back to the Min Hz
Hz Min Hz
Pressing the “ Down” key will enter the “ Limit1 output Edit”
KVA pressing the “ Down” key will advance KVA D KVA D
A - E : Apparent Energy
KW x1000 D
KAh P.F. Reset Parameter selection screen (see section 3.2.3). %THD
%THD %THD
mode and scroll the values, as per Table 2,
KVAh KWh
Max D
KW x1000
Relay2 output option below. KW x1000 I - E : Import Energy ( Active ) KW x1000 “ Parameter for Analog & Limit Output”
E - E : Export Energy ( Active )
KAh P.F. KAh P.F.
KAh P.F.
KVAh KWh KVAh KWh
KVAh KWh
Max D Max D
Max D
I - rE : Import Reactive Energy Pressing the “ Up” key advance to the Limit1 output
E - rE : Export Reactive Energy confirmation screen .
A - H : Ampere Hour

Reset option select, (Reset Lo)


V x1000
Max Angle This screen applies to the Relay2 Output option Selection . Pulse output (for Relay 1) confirmation : Limit1 output Confirmation :
KVAr KVArh The user has scrolled through to the “Lo” (Min)
V x1000 V x1000 V x1000
Max Angle Max Angle Max Angle
KVAr KVArh KVAr KVArh Pressing “ Down” key will be re-enter into edit mode . KVAr KVArh Pressing the “ Down” key will re-enter the “ Limit1
A
Min
x1000
Hz Pressing “ Up” key will select the value and Pressing “ Up” key will advance to the select
KVA output Edit”
%THD
D
advance to the “Reset Lo Confirmation” Mode & will A x1000 A x1000 A x1000
reset minimum values of Voltage & Current Avg. Min Hz Relay 2 output selection menu. (See section 3.2.4.1.2) Min Hz Min Hz
Pressing the “ Up” key sets the displayed value and will
KW x1000
appeared at Input.
KVA D KVA D
Pressing the “ Up” key will set the value and advances KVA D
KAh P.F. %THD %THD %THD
advance to the Limit1 Configuration select screen
KVAh KWh to the “ Pulse duration selection ”(see section 3.2.4.1.1.1.2).
Max D
KW x1000 KW x1000 KW x1000 ( see section 3.2.4.1.1.2.2 )
KAh P.F. KAh P.F. KAh P.F.
KVAh KWh
Max D
pressing the “ Down” key will advance to KVAh KWh
Max D
KVAh KWh
Max D

Analog output option below.

7 8
3.2.4.1.1.2.2 Limit1 Configuration select Analog output 1 Confirmation
This screen is used to set the Limit1 Configuration, four different types of configuration can be selected Value confirmation Screen.
3.2.4.1.1.2.5 Energizing Delay time. V x1000

V x1000
Max
KVAr
Angle
KVArh
This Screen will appear only after edit mode of Analog output 1
H i - E (High Alarm & Energized Relay) Max
KVAr
Angle
KVArh
This screen allows the user to set Energizing Delay time for Relay 1 Limit Assigned Parameters . Parameter.
H i - d (High Alarm & De-Energized Relay) This Screen confirms the value set by user . A x1000
L o - E (Low Alarm & Energized Relay) A x1000
Min
KVA
Hz
V
Max
x1000
Angle L o - d (Low Alarm & De-Energized Relay) Min Hz %THD
D
Pressing the “ Down” key will re-enter the “ Analog
KVA D
KVAr KVArh
(For detail refer to section 9.2) %THD Press the “ Up” key to advance to next Screen V x1000 Pressing “ Up” key accepts the present value and output 1 Edit”
Max Angle KW x1000
KVAr KVArh advance to De-energizing delay screen KAh P.F.
A
Min
x1000
Hz Pressing the “ Up” key accepts the present value and KW
KAh
x1000
P.F.
. KVAh KWh

KVA D
advances to the “Trip point selection”screen KVAh KWh “Hysteresis selection” ( see section 3.2.4.1.1.2.4) A x1000
Max D
Pressing the “ Up” key sets the displayed value and
%THD Max D
(see section 3.2.4.1.1.2.3)
Min
KVA
Hz
D
Pressing the “ Down” key will enter the will advance to the Analog output 2 selection screen
KW x1000 Pressing the “ Down” key will return in edit mode %THD “Energizing Delay” Edit mode and ( see section 3.2.4.1.3.2 )
KAh
KVAh
P.F.
KWh
Pressing the “ Down” key will enter the Limit1 configuration scroll the “Value” through 1 to10
Max D edit mode and scroll through the Modes available . KW
KAh
x1000
P.F.
KVAh KWh
Pressing the “ Up” key advances to the Max D

Limit1 configuration type confirmation menu.


3.2.4.1.3.2 Parameter setting Analog Output 2 ( Optional )
3.2.4.1.1.2.4 Hysteresis selection :
This screen applies to the Hysteresis selection. This screen is for analog output 2 only. It allows the user to set analog output 2 to corresponding
Limit1 Configuration Confirmation measured parameter . Refer table2 “ Parameter for Analog & Limit output “.
Energizing delay time Confirmation.

This screen will only appear following the edit of This screen allows the user to set Hysteresis V x1000 This screen will appear only after edit mode of Pressing “ Up” key accepts the present value and
Max Angle
V
Max
x1000
Angle system type. If system type is to be changed again, V x1000 for relay1 output KVAr KVArh Energizing delay time V x1000
advance to Analog output selection screen
KVAr KVArh Max
KVAr
Angle
KVArh
Max
KVAr
Angle
KVArh
(see section 3.2.4.1 ).
The allowable range is 0.5% to 50 % of Trip point . A x1000 pressing the “ Down” key will re-enter the “Energizing
A x1000 pressing the “ Down” key will return to the Limit1configuration Min Hz Pressing the “ Down” key will enter the “ Analog
Min Hz A x1000
KVA D delay Edit” mode. A x1000
KVA D Type edit stage by blanking the bottom line of the display Min Hz
%THD
Min Hz output 2 Edit” mode and scroll the values, as per
%THD KVA
%THD
D Enter value, prompt for first digit. KVA D
Table 2.“ Parameter for Analog output”
KW x1000
x1000
(* Denotes that decimal point will be flashing). KAh P.F.
KW
KAh P.F. Pressing the “ Up” key sets the displayed value and KW x1000 KVAh KWh
Pressing “ Up” key set displayed value and KW x1000
KVAh KWh
will advance to “Trip point selection” Screen
KAh P.F. Max D
KAh P.F. Pressing the “ Up” key advance to the Analog output 2
Max D KVAh KWh
Max D Press the “ Down” key to scroll the value of the first digit will advance to Assignment of De-energizing delay time. KVAh KWh
Max D confirmation screen .
(See section 3.2.4.1.1.2.3 ) (See section 3.2.4.1.1.2.6 )
Press the “ Up” key to advance to next digit.

3.2.4.1.1.2.3 Trip point selection : 3.2.4.1.1.2.6 De-Energizing Delay time. Analog output 2 Confirmation :
V x1000

This screen applies to the Trip point selection. The first digit entered, prompt for second digit This screen allows the user to set De-Energizing Delay time for Relay 1 Limit Assigned Parameters . Max Angle

V
KVAr KVArh This Screen will appear only after edit mode of Analog output 2
x1000
This screen allows the user to set Trip point for instruments Max
KVAr
Angle (* Denotes that decimal point will be flashing). Parameter.
KVArh A x1000
Pressing
. “ Up” key accepts the present value and
Min
KVA
Hz
D
The allowable range is 10% to 120% for High Alarm . A x1000
V x1000 advance to Configuration of Output. %THD
Max
V x1000
The allowable range is 10% to 100% for Low Alarm .
Min
KVA
Hz
D
Use the “ Down” key to scroll the value of the second digit KVAr
Angle
KVArh (See section 3.2.4.1 ) Pressing the “ Down” key will re-enter the “ Analog
Max Angle KW x1000
KVAr KVArh %THD
KAh P.F. output 2 Edit”
KVAh KWh
KW x1000
A
Min
x1000
Hz
Pressing the “ Down” key will enter the Max D
A
Min
x1000
Hz
Enter value, prompt for first digit. KAh
KVAh
P.F.
KWh
KVA D
“De-Energizing Delay” Edit mode and Pressing the “ Up” key sets the displayed value and
%THD
KVA D (* Denotes that decimal point will be flashing). Max D Press the “ Up” key to advance to next digit. will advance to the Analog output selection screen
%THD scroll the “Value” through 1 to10
KW x1000
P.F.
(see section 3.2.4.1 ).
KW x1000 Press the “ Down” key to scroll the values of the first digit KAh
KVAh KWh
KAh P.F.
Max D
KVAh KWh
Max D

Press the “ Up” key to advance to next digit.


4. Run Hour

V x1000 This Screen shows the total no. of hours the load is connected
V x1000 The second digit entered, prompt for third digit Max Angle
Even if the Auxiliary supply is interrupted count of Run hour
Max Angle De-Energizing delay time Confirmation. KVAr KVArh
V x1000 KVAr KVArh (* Denotes that decimal point will be flashing). will be maintained in internal memory & displayed in
Max Angle The first digit entered, prompt for second digit V x1000
KVAr KVArh
Max Angle This screen will appear only after edit mode of A
Min
x1000
the format “hours. Min”.
(* Denotes that decimal point will be flashing). A
Min
x1000 KVAr KVArh KVA
Hz
D
A x1000 KVA
Hz
D
De-energizing delay time. %THD For example if Displayed count is 105000.10 r-H it indicates
Min Hz %THD
KVA D A x1000 105000 hours & 10 minutes.
%THD Use the “ Down” key to scroll the value of the second digit Use the “ Down” key to scroll the value of the third digit Min Hz KW x1000
KW
KAh
x1000
P.F.
KVA
%THD
D
pressing the “ Down” key will re-enter the KAh
KVAh
P.F.
KWh
After 999999.59 run hours display will restart from zero.
KW
KAh
x1000
P.F.
KVAh KWh
Max D
“De-energizing delay Edit” mode. Max D
To reset run hour manually see section Resetting
x1000
KVAh KWh
Max D Press the “ Up” key to advance to next digit.
KW
KAh P.F. Parameter 3.2.3.1
KVAh KWh
Max D
Pressing “ Up” key set displayed value and
will advance to Configuration of Output.
(See section 3.2.4.1 )
5. On Hour
Entered value for third digit . 3.2.4.1.2 Relay 2 Output Selection :
This Screen shows the total no. of hours the Axillary Supply is
The second digit entered, prompt for third digit V x1000
V x1000
ON. Even if the Auxiliary supply is interrupted count of the
Max Max Angle
V
Max
x1000
Angle (* Denotes that decimal point will be flashing). KVAr
Angle
KVArh Configuration of Relay 2 for Pulse or Limit Output is same as Relay 1. If you Select the Pulse output KVAr KVArh
On hour will be maintained in internal memory & displayed in
KVAr KVArh
Press the “ Up” key to advance to Hysteresis option for Relay 1 same setting will be applicable for Relay 2 except assignment of energy to Pulse the format “hours. min”.
A x1000 output (i.e. Energy assignment of both relay can be different.) A x1000
A
Min
x1000 Min
KVA
Hz confirmation Screen. Min
KVA
Hz
D For example if Displayed count is 005000.10 On-H it indicates
Hz D
KVA %THD %THD
%THD
D
Use the “ Down” key to scroll the value of the third digit 005000 hours & 10 minutes.
KW x1000
P.F.
KW
KAh
x1000
P.F.
After 999999.59 On hours display will restart from zero.
KW x1000 KAh
KAh P.F.
KWh
KVAh KWh
Max D
KVAh KWh
Max D To reset On hour manually see section Resetting
KVAh
Max D Parameter 3.2.3.1
3.2.4.1.3 Analog Output
3.2.4.1.3.1 Parameter setting for Analog Output 1 ( Optional )
This screen is for analog output 1 only. It allows the user to set analog output 1 to corresponding
measured parameter . Refer table2 “ Parameter for Analog & Limit output “. 6. Number of Interruption :
Hysteresis confirmation Screen.
Entered the value for third digit .
V x1000
Pressing “ Up” key accepts the present value and This Screen Displays the total no. of times the Axillary
V x1000 Max Angle
This Screen confirms the percentage value set by user .
Max Angle KVAr KVArh
V
V x1000
Supply was Interrupted. Even if the Auxiliary supply is
KVAr KVArh
& Screen will appear only after edit mode of Hysteresis. Max
x1000
Angle advance to the Analog output 2 selection (see section 3.2.4.1.3.2 ). Max Angle

KVAr KVArh
KVAr KVArh
interrupted count will be maintained in internal memory
A x1000
A x1000 Min Hz To reset No of Interruption manually see section
Min Hz Press the “ Up” key to advance to trip point KVA D
Press the “ Up” key to advance to next Screen A x1000 Pressing the “ Down” key will enter the “ Analog output 1 Edit” A x1000
KVA
%THD
D
confirmation Screen.
%THD
Min Hz
Min
KVA
Hz
Resetting Parameter 3.2.3.1
KVA D mode and scroll the values, as per Table 2 %THD
D

KW x1000 %THD
KW x1000 KAh P.F. “Parameter for Analog & Limit output”
KAh P.F. KVAh KWh “Energizing delay time” ( 3.2.4.1.1.2.5 ) KW x1000
KW x1000
P.F.
KVAh KWh Max D KAh
Max D KAh P.F. KWh
KVAh
KVAh KWh
Max D
Pressing the “ Up” key advance to the Analog output 1 Max D

confirmation screen .

9 10
7. Analog Output ( optional ) : 8.2 Limit Switch :
The each byte in RTU mode has following format:
7. Analog Output ( optional ) : Limit switch can be used to monitor the measured parameter ( Ref.Table:2 )in relation
with to a set limit. 8-bit binary, hexadecimal 0-9, A-F
TABLE 2 : Parameter for Analog & Limit output The limit switch can be configured in one of the four mode given below:-
This module provides two d.c. isolated outputs .There are two output options 2 hexadecimal characters contained in each 8-bit field of
1) Hi alarm & Relay Energized Relay..
the message
2) Hi alarm & De-Energized Relay.
1) Two 0 - 1mA outputs , internally powered . Parameter No. Parameter Range
3) Lo alarm & Energized Relay.
2) Two 4 - 20mA outputs , internally powered .
4) Lo alarm & De-Energized Relay. Format of Data Bytes 4 bytes (32 bits) per parameter.
0 None Floating point format ( to IEEE 754)
The 0 -1mA output module has an 0V return on each end of the 4 way connector Most significant byte first (Alternative least significant byte first)
( Please refer section 14 for connection details ) 1 System Volts 0 - 100 % Hi Alarm:
If Hi-Alarm Energized or Hi Alarm De-Energized option is selected then relay will get energized Error Checking Bytes 2 byte Cyclical Redundancy Check (CRC)
4 System IL 0 - 100 %
On both modules the output signals are present on pins A1(Anolog Output 1) & or De-energized,if selected parameter is greater than or equal to trip point.
A2 (Analog Output 2)
0 - 120 % Byte format 1 start bit,
7 System W Lo Alarm:
8 data bits, least significant bit sent first
These outputs can be individually assigned to represent any one of the measured and displayed If Lo-Alarm Energized or Lo Alarm De-Energized option is selected then relay will get energized 1 bit for even/odd parity
10 System VA 0 - 120 % or De-energized,if selected parameter is less than or equal to trip point.
Parameters. 1 stop bit if parity is used; 1 or 2 bits if no parity
13 System Var 0 - 120 % Trip point:
All settlings are user configurable via the user interface screen. See Analog o/p selection Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600,
( section 3.2.4.1.3 ) for details . 180 / 0 / -180 Trip point can be set in the range of 10% to 120 % of nominal value for Hi-Alarm &
16 * PF 19200 bps.
10% to 100 % of nominal value for Lo-Alarm.
19 * PA 180 / 0 / -180 Function code :
Hysteresis:
36 Freq. 45 to 66 Hz Hysteresis can be set in the range of 0.05% to 50 % of set trip point . 03 Read Holding Registers Read content of read /write location ( 4X )
* Note : Refer diagrams 1 & 2 If Hi-alarm Energized or Hi-alarm De-energized is selected then relay will get
43 Watt Demand Imp. 0 - 120 % De-energized or Energized respectively, if set parameter value is less than Hysteresis 04 Read input Registers Read content of read only location ( 3X )
Similarly if Lo-alarm Energized or Lo-alarm De-Energized. 16 Presets Multiple Registers Set the content of read / write locations ( 4X )
44 Watt Max Demand Imp. 0 - 120 %
Energizing Delay:
45 Watt Demand Exp 0 - 120 % The energizing delay can be set in the range from1 to 10 sec.
46 Watt Demand Max Exp 0 - 120 % De-Energizing Delay: 01 Illegal function The function code is not supported by 3440
The De-energizing delay can be set in the range from1 to 10 sec. Illegal Data Attempt to access an invalid address or an attempt to read
Diagram 1 : ( 4 -20 mA ) 51 VA Demand 0 - 120 % 02
Address or write part of a floating point value
0 0 ( 12 mA) Note : In case of lo alarm if trip point is set at 100% then maximum 20%
52 VA Max Demand. 0 - 120 %
Hysterisis can be set.. 03 Illegal Data Attempt to set a floating point variable to an invalid value
53 Current Demand. 0 - 100 % Value

54 Current Max Demand. 0 - 100 %


Exception Cases : An exception code will be generated when 3440 receives ModBus query with
valid parity & error check but which contains some other error ( e.g. Attempt to set floating point
variable to an invalid value ) The response generated will be “Function code” ORed with HEX (80H).
Example of different configuration. The exception codes are listed below
Parameter No: 4 (Current 1)
270 0 ( 8 mA) 90 0 ( 16 mA) 8. Relay output (Optional) : Trip Point = 50%
3440 is provided with either 1 or 2 relay for pulse output as well as for limit switch Hysteresis = 50% of trip point
Energising Delay: 2s
8.1 Pulse Output : De-energising Delay: 2s

Pulse output is the potential free, very fast acting relay contact which can be used to drive an external 1) Hi alarm & Energised relay 2) Hi alarm & De-energised relay
Accessing 3 X register for reading measured values:
0
mechanical counter for energy measurement.
181 ( 4 mA)
3440 pulse output can be configured to any of the following parameter through setup parameter screen Relay Energise Relay De-energise Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
1) Active Energy (Import) Input Relay De-energise Input Relay Energise of 3X registers (Parameters measured by the instruments).
2) Active Energy (Export) Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
3)Reactive Energy (Import)
4)Reactive Energy (Export) 50% Trip point 50% Trip point Example :
5)Apparent Energy To read parameter ,
180 0 ( 20 mA) 25% Hysterisis point 25% Hysterisis point
6)Ampere hour Volts : Start address= 04 (Hex) Number of registers = 02
Time Time
Note : Number of registers = Number of parameters x 2
TABLE 3 : Energy Pulse Rate Divisor 2s 2s 2s 2s Each Query for reading the data must be restricted to 20 parameters or less. Exceeding
Pulse rate the 20 parameter limit will cause a ModBus exception code to be returned.
Divisor Pulse System Power*
1 1per Whr Up to 3600W 3) Lo alarm & Energised relay 4) Lo alarm & De-energised relay Query :

Diagram 2 : ( 0 - 1 mA ) 1per kWhr Up to 3600kW


Relay De-energise Relay Energise
1per MWhr Above 3600kW 01 (Hex) 04 (Hex) 00 (Hex) 04(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)
0 0 ( 0.5 mA) Input Relay Energise Input Relay De-energise
10 1per 10Whr Up to 3600W
1per 10kWhr Up to 3600kW Device Function Start Address Start Address Number of Number of CRC CRC
75% Hysterisis point 75% Hysterisis point Address Code High Low Registers Hi Registers Lo Low High
1per 10MWhr Above 3600kW
100 1per 100Whr Up to 3600W 50% Trip point 50% Trip point
1per 100kWhr Up to 3600kW
Start Address High : Most significant 8 bits of starting address of the parameter requested.
1per 100MWhr Above 3600kW Time Time
1000 1 per 1000Whr Up to 3600W Start Address low :Least significant 8 bits of starting address of the parameter requested.
1 per 1000kWhr Up to 3600kW 2s 2s 2s 2s Number of register Hi : Most significant 8 bits of Number of registers requested.
270 0 ( 0.25 mA) 90 0 ( 0.75 mA) 1per 1000MWhr Above 3600kW Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Pulse Duration 60 ms,100 ms or 200 ms 9. RS 485 ( ModBus ) Output :
Above options are also applicable for Apparent and Reactive Energy. 3440 supports MODBUS (RS485) RTU protocol( 2-wire ) . Response: Volt (219.25V)
* System power = CT(Primary) x PT(Primary)
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained
181 0 ( 0 mA) together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, 43 (Hex) 5B (Hex)
Ampere Hour: 01 (Hex) 04 (Hex) 04 (Hex) 41 (Hex) 21 (Hex) 6F (Hex) 9B (Hex)
an Earth connection should be made at one point on the network.Loop (ring) topology does not require any
termination load. Line topology may or may not require terminating loads depending on the type and length
Divisor 1(Default) Device Function Byte Data Register1 Data Register1 Data Register2 Data Register2 CRC CRC
of cable used. The impedance of the termination load should match the impedance of the cable and be at both Low Byte
CT secondary = 1A Max pulse rate 3600 pulses per Ah ** Address Code Count High Byte High Byte Low Byte Low High
ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
CT secondary = 5A Max pulse rate 720 pulses per Ah **
180 0 ( 1 mA)
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments
Byte Count : Total number of data bytes received.
Divisors 10 can be connected in RS485 network.The permissible address range for 3440 is between 1 and 247 for
32 instruments. Broadcast Mode (address 0) is not allowed. Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
CT secondary = 1A Max pulse rate 3600 pulses per 10Ah ** Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
CT secondary = 5A Max pulse rate 720 pulses per 10Ah ** The maximum latency time of an 3440 is 200ms i.e. this is the amount of time that can pass before the Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
first response character is output. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
Divisors 100
CT secondary = 1A Max pulse rate 3600 pulses per 100Ah ** After sending any query through software ( of the Master) , it must allow 200ms of time to elapse before (Note : Two consecutive 16 bit register represent one parameter.)
CT secondary = 5A Max pulse rate 720 pulses per 100Ah ** assuming that the 3440 is not going to respond. If slave does not respond within 200 ms,
Master can ignore the previous query and can issue fresh query to the slave.
Divisors 1000
CT secondary = 1A Max pulse rate 3600 pulses per 1000Ah **
CT secondary = 5A Max pulse rate 720 pulses per 1000Ah **

Pulse duration 60 ms, 100 ms or 200 ms


**No. of Pulses per Ampere hour = Maximum Pulses / CT Ratio
Where, CT Ratio = (CT primary/ CT Secondary)

11 12
Table 4 : 3 X register addresses (measured parameters)
Table 5 : 4 X register addresses 40025 Min - Reset This address is used to reset the Min parameters value.
Address Parameter Parameter Modbus Start Address Hex Write Zero value to this register to reset the Min parameters.
(Register) No. High Byte Low Byte Byte Count : Total number of data bytes received. Address Parameter Parameter Read / Write Modbus Start Address Hex Writing any other value will return an error.
30001 1 Volts 00 0 (Register) No. High Byte Low Byte
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested. 40027 Max - Reset This address is used to reset the Max parameters value.
30007 4 Current 00 6 Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested. 40001 1 Demand Time R/Wp 00 00
Write Zero value to this register to reset the Max parameters.
30013 7 W 00 C 40003 2 Demand Period R/Wp 00 02
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Writing any other value will return an error.
30019 10 VA 00 12 40007 4 Sys Voltage R 00 06
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. 40029 Analog Out 1- This address is used to set the parameter for Analog Output 1.
30025 13 VAR 00 18 40009 5 Sys Current R 00 08 Write one of the parameter no. As per the options given in
(Note : Two consecutive 16 bit register represent one parameter.) Para Set
30031 16 PF 00 1E 40013 7 Pulse Width R/Wp 00 0C Table 2 for Analog & Limit Output Parameters.
30037 19 Phase Angle 00 24 40015 8 Energy Reset Wp 00 0E Writing any other value will return an error.
30071 36 Freq 00 46 40017 9 Run/On Hour & Interruption Reset Wp 00 10 This address is used to set the parameter for Analog Output 2..
40031 Analog Out 2-
30073 37 Wh Import 00 48 Example : Writing the CT Secondary to 1 amps 40019 10 RS 485 Set-up Code R/Wp 00 12 Para Set Write one of the parameter no. As per the options given in
30075 38 Wh Export 00 4A 40021 11 Node Address. R/Wp 00 14 Table 2 for Analog & Limit Output Parameters.
30077 39 VARh Import 00 4C System type : Start address= 2A (Hex) Number of registers = 02 40023 12 Pulse Divisor R/Wp 00 16 Writing any other value will return an error.
30079 40 VARh Export 00 4E 40025 13 Min Reset Wp 00 18 40033 PT Primary This address allows the user to set PT Primary value.
30081 41 VAh 00 50 Query: Change the CT Secondary to 1 amps 40027 14 Max Reset Wp 00 1A The maximum settable value is 692.8kV L-L & also depends on the
30083 42 Ah 00 40029 15 Analog Out 1- Para Sel R/Wp 00 1C per phase 666.6MVA Restriction of power combined with CT
52
40031 16 Analog Out 2- Para Sel R/Wp 00 primary.
30085 43 W Demand (Import) 00 54 Device Address 01 (Hex) 1E
30087 44 W Max Demand (Import) 00 56 40033 17 PT Primary R/Wp 00 20 40035 CT Pimary This address allows the user to set CT Primary value.
30089 W Demand (Export) 00 40035 18 CT Primary R/Wp 00 22 The maximum settable value is 9999 & also depends on the
45 58 Function Code 10 (Hex)
40037 19 System Power 00 24 per phase 666.6MVA Restriction of power combined with PT primary
30091 46 W Max Demand (Export) 00 5A R
30101 VA Demand 00 40041 21 Register Order/Word Order R/Wp 00 28 40037 Sys Power System Power (Read Only) is the Nominal system power based on
51 64 Starting Address Hi 00 (Hex)
40043 22 CT Secondary R/Wp 00 2A the values of Nominal system volts and Nominal system current.
30103 52 VA Max Demand 00 66
30105 00 40045 23 PT Secondary R/Wp 00 2C 40041 Word Order Word Order controls the order in which 3440 receives or
53 A Demand 68 Starting Address Lo 2A(Hex)
40047 24 Relay1 output select R/Wp 00 sends floating - point numbers:- normal or reversed register
30107 54 A Max Demand 00 6A 2E
40049 25 R/Wp order . In normal mode, the two registers that make up
30133 67 Volts Ave Max 00 84 Number of Registers Hi 00 (Hex)
Pulse1/Limit1 Parameter select 00 30
a floating point numbers are sent most significant bytes first.
30135 68 Volts Ave Min 00 86 40051 26 Limit1 Trip point R/Wp 00 32 In reversed register mode , the two registers that make up
30141 71 Current Ave Max 00 8C 40053 27 Hysteresis(Limit1) R/Wp 00 34 a floating point numbers are sent least significant bytes first.
Number of Registers Lo 02(Hex)
30143 72 Current Ave Min 00 8E 40055 28 Limit1 delay(On) R/Wp 00 36 To set the mode, write the value ‘2141.0’ into this register-
30207 104 V1 THD( % ) 00 CE 40057 29 Limit1 delay(Off) R/Wp 00 38 the instrument will detect the order used to send this value and
Byte Count 04 (Hex)
30213 107 I1 THD ( % ) 00 D4 40059 30 Relay2 output select R/Wp 00 3A set that order for all ModBus transaction involving floating point
40061 31 Pulse2/Limit2 Parameter select R/Wp 00 3C numbers.
30227 114 Run Hour 00 E2 Data Register-1High Byte 3F (Hex)
30229 00 40063 32 Limit2 Trip point R/Wp 00 3E 40043 CT secondary This address is used to read and write the CT secondary value
115 On Hour E4
40065 33 Hysteresis(Limit2) R/Wp 00 40 write one of the following values to this address.
30231 116 No. Of Interrupts 00 E6 Data Register-1 Low Byte 80(Hex)
40067 34 Limit2 Delay(On) R/Wp 00 42 1=1A CT secondary
5=5A CT secondary
Accessing 4 X register for Reading & Writing : Data Register-2 High Byte 00(Hex)
40069 35 Limit2 Delay(Off) R/Wp 00 44
writing any other value will return an error.
40071 36 Password R/W 00 46
40045 PT secondary This address is used to read and write the PT secondary value.
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting 40073 37 Limit1 Configuration select R/Wp 00 48
Data Register-2 Low Byte 00(Hex) Ref Table for the range of PT secondary settable values in
and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses. 40075 38 Limit2 Configuration select R/Wp 00 4A Section 3.2.1.2
CRC Low 40077 39 Auto scroll R/Wp 00 4C
7C (Hex) 40047 Relay1 output This address is used to select the Relay 1 operation as pulse or
Example : Reading CT Secondary 40079 40 30mA Noise Current Elimination R/Wp 00 4E
System type : Start address= 2A (Hex) Number of registers = 02 select Limit.
CRC High 34 (Hex) write one of the following values to this address.
Note :Number of registers = Number of Parameters x 2 0 = Pulse output on Relay 1
128 (Decimal) = Limit output on Relay 1
Byte Count : Total number of data bytes received. writing any other value will return an error.
Device Address 01 (Hex) Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
40049 Pulse1/Limit1 This address is used to assign the Parameter to Relay1
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested. parameter If Limit option is selected refer table 2 for parameter number
Function Code 03 (Hex)
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Explanation for 4 X register : select & if Pulse option is selected then refer table 7.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. 40051 Limit1 This address is used to set the trip point in %. Any value between
Start Address High 00 (Hex)
(Note : Two consecutive 16 bit register represent one parameter.) Address Parameter Description Trip Point 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
this address. Writing any other value will return an error.
2A (Hex)
Start Address Low 40001 Demand Reset Demand Reset is used to reset the Demand parameter. A value 40053 Hysteresis This address is used to set the hysteresis between
of zero must be Written to this register to reset the Demand (Limit1) 0.5 to 50 . Writting any other value will return an error.
Number of Registers Hi 00 (Hex) period. Writing any other value will return an error.
40055 Limit1 This address is used to set the Energizing delay between
40003 Demand Demand period represents demand time in minutes. The Energizing 1 to 10 . Writting any other value will return an error.
Number of Registers Lo 02 (Hex) Response: Period applicable values are 8,15,20 or 30. Writing any other value will Delay
return an error.
40057 Limit1 This address is used to set the De-Energizing delay between
CRC Low 40007 System This address is read only and displays System Voltage de-energizing 1 to 10 . Writting any other value will return an error.
E5 (Hex)
Device Address 01 (Hex) Voltage Delay
CRC High System 40059 Relay2 This address is used to select the Relay 2 operation as pulse or
C3 (Hex) 40009 This address is read only and displays System Current
Function Code 10 (Hex) Current output select Limit.
write one of the following values to this address.
40013 Pulse Width This address is used to set pulse width of the Pulse output. 0 = Pulse output on Relay 2
Start Address High 00 (Hex) Write one of the following values to this address:
Start Address High : Most significant 8 bits of starting address of the parameter requested. of Relay 128 (decimal) = Limit output on Relay 2
60 : 60 ms writing any other value will return an error.
Start Address low :Least significant 8 bits of starting address of the parameter requested. 2A (Hex) 100 : 100 ms
Number of register Hi : Most significant 8 bits of Number of registers requested. Start Address Low 40061 Pulse2/Limit2 This address is used to assign the Parameter to Relay2
200 : 200 ms
Parameter If Limit option is selected refer table 2 for parameter number
Number of register Lo : Least significant 8 bits of Number of registers requested. Writing any other value will return error .
Number of Registers Hi 00 (Hex) select & if Pulse option is selected then refer table 7.
(Note : Two consecutive 16 bit register represent one parameter.)
40015 Reset Energy This address is used to reset the Energy Counter. 40063 Limit2 This address is used to set the trip point in %. Any value between
02 (Hex) Counter Write zero value to this register to reset the energy counter. 10 to 100 for Lo- alarm & 10 to120 for Hi-alarm can be written to
Response: Number of Registers Lo Trip point
Writing any other value will return an error. this address. Writing any other value will return an error.
40017 Run/On Hour & This address is used to reset the Run/On hour & number Hysteresis
Device Address 01 (Hex) CRC Low 60 (Hex) Interruption of Interruption . Write zero value to this register to reset 40065 This address is used to set the hysteresis between
(Limit2) 0.5 to 50 . Writting any other value will return an error.
reset the Run/On hour & number of Interruption.
Function Code 03 (Hex) CRC High 00 (Hex) Writing any other value will return an error. 40067 Limit2 This address is used to set the Energizing delay between
Energizing 1 to 10 . Writting any other value will return an error.
40019 Rs485 Set-up This address is used to set the baud rate, Parity, Number of delay
Byte Count 04 (Hex)
Code stop bits. Refer to Table 6 for details.
40069 Limit2 This address is used to set the De-Energizing delay between
3F (Hex) Start Address High : Most significant 8 bits of starting address of the parameter requested. De-Energizing 1 to 10 . Writting any other value will return an error.
Data Register1 High Byte delay
Start Address low :Least significant 8 bits of starting address of the parameter requested.
40021 Node This register address is used to set Device address
80 (Hex)
Number of register Hi : Most significant 8 bits of Number of registers requested.
Data Register1Low Byte Address between 1 to 247 .
Number of register Lo : Least significant 8 bits of Number of registers requested.
40023 Pulse Divisor This address is used to set pulse divisor of the Pulse output.
(Note : Two consecutive 16 bit register represent one parameter.) Write one of the following values to this address:
Data Register2 High Byte 00 (Hex)
1: Divisor 1
10 : Divisor 10
Data Register2 Low Byte 00(Hex) 100 : Divisor 100
1000 : Divisor 1000
CRC Low Writing any other value will return an error.
F7 (Hex)

CRC High CF (Hex)

13 14
9.1 User Assignable Modbus Registers: User Assignable mapping Registers User Assignable Data Registers
( 4X Registers Table10 ) ( 3X Registers Table 9 )
Address Parameter Description (Starting Address) (Starting Address)
The 3440 contains the 20 user assignable registers in the address range of 0x200 (30513) to
0x226 (30551) (see Table 9). 0x200 Voltage (0x0000) 0x200 0x200 0x201
40071 Password This address is used to set & reset the password. (16 bit) (16 bit)
Valid Range of Password can be set is 0000 - 9999 . Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the instrument Response :
1) If password lock is present & if this location is read it will can be mapped to these 20 user assignable registers. 0x201 Power Factor (0x001E) 0x202 0x202 0x203
return zero. Parameters (3X registers addresses ) that resides in different locations may be accessed by Device Address 01 (Hex)
(16 bit) (16 bit)

2) If Password lock is absent & if this location is read it will the single request by re-mapping them to adjacent address in the user assignable registers area.
0x202 Wh Import (0x0048) 0x204 0x204 0x205
return One. The actual address of the parameters ( 3X registers addresses) which are to be assessed via (16 bit) (16 bit)
Function Code 10 (Hex)
3) If password lock is present & to disable this lock address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 10).
0x203 0x206 0x206 0x207
first send valid password to this location then write “0000” Frequency (0x0046) (16 bit) (16 bit)
02 (Hex)
to this location Table 9 : User Assignable 3X Data Registers Start Address High
4) If password lock is present & to modify 4X parameter Address Parameter Modbus Start Address (Hex)
Assignable Register High Byte Low Byte 00 (Hex)
first send valid password to this location so that 4X parameter (Register) Number. Start Address Low
will be accessible for modification. 30513 257 Assignable Reg 1 02 00
5) If for in any of the above case invalid password is send then 30515 258 Assignable Reg 2 02 02 00 (Hex)
meter will return exceptional error 2. Number of Registers Hi
30517 259 Assignable Reg 3 02 04
30519 260 Assignable Reg 4 02 06 0x212 Current (0x0006) 0x224 0x224 0x225
40073 Limit1 This address is used to set the Configuration for relay 1 02 (Hex) (16 bit)
Number of Registers Lo (16 bit)
Configuration see table 8 . Writting any other value will return an error. 30521 261 Assignable Reg 5 02 08
Select 30523 262 Assignable Reg 6 02 0A 0x213 VAh (0x0050) 0x226 0x226 0x227
(16 bit) (16 bit)
30525 263 Assignable Reg 7 02 0C CRC Low 40 (Hex)
40075 Limit2 This address is used to set the Configuration for relay 2
Configuration see table 8 . Writting any other value will return an error. 30527 264 Assignable Reg 8 02 0E
Select 30529 265 Assignable Reg 9 02 10 CRC High 70 (Hex) To get the data through User assignable Register use following steps:
Auto scroll This address is used to activate or de-activatethe auto scrolling write 30531 266 Assignable Reg 10 02 12 1) Assign starting addresses(Table3) of parameters of interest to a
40077
0-Deactivate 30533 267 Assignable Reg 11 02 14 “User assignable mapping registers” in a sequence in which they are to be accessed
1-Activate 30535 268 Assignable Reg 12 02 16 (see section “Assigning parameter to user assignable registers”)
Writing any other value will return an error. 30537 269 Assignable Reg 13 02 18 Reading Parameter data through User Assignable Registers:
30mA Noise This address is used to activate or de-activatethe 30 mA noise 30539 270 Assignable Reg 14 02 1A 2) Once the parameters are mapped data can be acquired by using
40079 In assigning query Voltage and Power Factor parameters were assigned to 0x 200 and
current current elimination write 30541 271 Assignable Reg 15 02 1C “User assignable data register “ Starting address . i.e to access data of Voltage,
0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202 (table9). So to read
Elimination 0-Deactivate 30543 272 Assignable Reg 16 02 1E Voltage and PowerFactor data reading query should be as below. Power factor,Wh import, Frequency send query with starting address 0x200
30 (Decimal)-Activate 30545 273 Assignable Reg 17 02 20 with number of register 8 or individually parameters can be accessed
Writing any other value will return an error. 30547 274 Assignable Reg 18 02 22 Query: for example if current1 to be accessed use starting address 0x212.
30549 275 Assignable Reg 19 02 24 (See section Reading Parameter data through User Assignable Registers)
30551 276 Assignable Reg 20 02 26
Device Address 01 (Hex)
10. Phaser Diagram :
Table 10 : User Assignable mapping register ( 4X registers) Function Code 04 (Hex)
Address Parameter Modbus Start Address (Hex)
Table 6 : RS 485 Set-up Code (Register) Number. Mapping Register High Byte Low Byte 02 (Hex)
Start Address High
40513 257 Mapped Add for register #0x0200 02 00
Baud Rate Parity Stop Bit Decimal value 40514 258 Mapped Add for register #0x0202 02 01 00 (Hex) Capacitive Inductive
Start Address Low
40515 259 Mapped Add for register #0x0204 02 02
19200 NONE 01 12 40516 260 Mapped Add for register #0x0206 02 03
Number of Registers Hi 00 (Hex)
19200 NONE 02 13 40517 261 Mapped Add for register #0x0208 02 04
19200 EVEN 01 14 40518 262 Mapped Add for register #0x020A 02 05
19200 ODD 01 15 Number of Registers Lo 04 (Hex) **
40519 263 Mapped Add for register #0x020C 02 06
9600 NONE 01 08 40520 264 Mapped Add for register #0x020E 02 07
9600 NONE 02 09 40521 265 Mapped Add for register #0x0210 02 08 CRC Low F0 (Hex)
9600 EVEN 01 10 40522 266 Mapped Add for register #0x0212 02 09
9600 ODD 01 11 40523 267 Mapped Add for register #0x0214 02 0A CRC High 71 (Hex)
4800 NONE 01 04 268
40524 Mapped Add for register #0x0216 02 0B
4800 NONE 02 05 40527 269 Mapped Add for register #0x0218 02 0C Start Address High : Most significant 8 bits of starting address of User assignable register.
4800 EVEN 01 06 40528 270 Mapped Add for register #0x021A 02 0D
4800 ODD 01 07 Start Address low :Least significant 8 bits of starting address of User assignable register.
40529 271 Mapped Add for register #0x021C 02 0E
2400 NONE 01 00 Number of register Hi : Most significant 8 bits of Number of registers requested.
40530 272 Mapped Add for register #0x021E 02 0F
2400 NONE 02 01 Number of register Lo : Least significant 8 bits of Number of registers requested.
40531 273 Mapped Add for register #0x0220 02 10 Capacitive
2400 EVEN 01 02 **Note : Two consecutive 16 bit register represent one parameter. Inductive
40532 274 Mapped Add for register #0x0222 02 11
2400 ODD 01 03 Since two parameters are requested four registers are required Sign of Sign of Sign of Inductive /
40533 275 Mapped Add for register #0x0224 02 12 Connections Quadrant Active Reactive Power Capacitive
40534 276 Mapped Add for register #0x0226 02 13
NOTE : Power ( P ) Power ( Q ) Factor ( PF )
Codes not listed in the table above may give rise to unpredictable results including loss of Example : Response : (Voltage = 219.30 / Power Factor = 1.0) Import 1 +P +Q + L
communication. Excise caution when attempting to change mode via direct Modbus writes.
Assigning parameter to user assignable registers Import 4 +P -Q + C
To access the voltage (3X address 0x0000) and Power Factor (3X address 0x001E) through user Device Address 01 (Hex)
Export 2 -P +Q - C
assignable register assign these addresses to 4x register (Table 10 ) 0x0200 and 0x0201 respectively .
Function Code 04 (Hex) Export 3 -P -Q - L
Assigning Query:
Table 7 : Pulse1 & Pulse2 Configuration select Inductive means Current lags Voltage
Byte count 08 (Hex) Capacitive means Current leads Voltage
Device Address 01 (Hex)
Code Configuration When 3440 displays Active power ( P )with “ + ” ( positive sign ) , the connection

}
Data Register-1High Byte 43 (Hex)
0 Import Active Energy is “ Import ” .
Function Code 10 (Hex)
1 Export Active Energy Data Register-1 Low Byte When 3440 displays Active power ( P )with “ - ” ( negative sign ) , the connection
5B (Hex)
2 Import Reactive Energy is “ Export ” .
Starting Address Hi 02 (Hex) Voltage Data
3 Export Reactive Energy
Data Register-2 High Byte 4E (Hex)
4 Apparent Energy
Starting Address Lo
11. Installation
00 (Hex)
Data Register-2 Low Byte 04 (Hex) Mounting is by four side clamps, slide the side clamps through side slot till
side clamp gets firmly locked in a groove (Refer fig.) Consideration
Number of Registers Hi 00 (Hex)*
should be given to the space required behind the instrument to allow

}
Data Register-3 High Byte 3F (Hex) for bends in the connection cables.
Table 8 :Limit1 & Limit2 Configuration select Number of Registers Lo 02(Hex)*
Data Register-3 Low Byte 80 (Hex) PANEL
SLIDE IN THIS DIRECTION AND LOCK
Code Configuration Byte Count 04 (Hex) Power Factor Data
0 Hi- alarm & Enegised relay Data Register-4 High Byte 00 (Hex)
1
2
3
Hi- alarm & Denegised relay
Lo- alarm & Enegised relay
Lo- alarm & Denegised relay
Data Register-1High Byte

Data Register-1 Low Byte


00 (Hex)

00 (Hex)
} Voltage*
(3X Address 0x0000)
Data Register-4 Low Byte

CRC Low
00 (Hex)

79 (Hex)
3440

Data Register-2 High Byte

Data Register-2 Low Byte


00 (Hex)

1E (Hex) } Power Factor*


(3X Address 0x001E)
CRC High 3F (Hex)

CRC Low 6A (Hex)

CRC High C7 (Hex)

* Note : Parameters should be assigned in Multiple of two i.e. 2,4,6,8.......20.

15 16
As the front of the enclosure conforms to IP54 it is protected from water spray
from all directions, additional protection to the panel may be obtained by the
12. Connection Diagram :
use of an optional panel gasket. The terminals at the rear of the product Accuracy 0.5:
should be protected from liquids.
Voltage + 0.5 % of range
The 3440 should be mounted in a reasonably stable ambient temperature SINGLE PHASE
0
and where the operating temperature is within the range -10 to 55 C DIGITAL METERING SYSTEM Current + 0.5 % of range Display
Vibration should be kept to a minimum and the product should not be 2 3
Frequency 0.15% of mid frequency
mounted where it will be subjected to excessive direct sunlight. LED 3 line 4 digits . Digit height 11mm
Active Power + 0.5 % of range Update Approx. 1 seconds
Re- Active Power + 0.5 % of range
Apparent Power + 0.5 % of range Controls
L N
Caution AUX
Active Energy User Interface Two push buttons
SUPPLY + 0.5 % of range
1. In the interest of safety and functionality this product must be installed by
P1 S1 L
a qualified engineer, abiding by any local regulations. L Re - Active Energy + 0.5 % of range.
O
A Standards
2. Voltages dangerous to human life are present at some of the terminal N D Apparant Energy + 0.5 % of range
connections of this unit. Ensure that all supplies are de-energised before
Power Factor + 1 % of Unity EMC Immunity IEC 61326
attempting any connection or disconnection.
13. Specification : Angle + 1 % of range 10V/m min-Level 3 industrial low level
3. These products do not have internal fuses therefore external fuses must electromagnetic radiation environment
be used to ensure safety under fault conditions. Inputs Analog Output + 1 % of Output end value IEC 61000-4-3.
Nominal input voltage 57.7 VL-N to 277V L-N Total harmonic Distortion +1%
Safety IEC 61010-1 , Year 2001
11.1 EMC Installation Requirements
IP for water & dust IEC 60529
This product has been designed to meet the certification of the EU directives Accuracy 0.2:
when installed to a good code of practice for EMC in industrial environments, Max continuous input 120% of Rated Value
e.g. voltage Voltage + 0.2 % of range
Isolation 2.2 kV RMS 50 Hz for 1 minute
Max short duration input 2 x Rated Value Current + 0.2 % of range
1. Screened output and low signal input leads or have provision for fitting Dielectric voltage withstand according to DINEN61010-1 between
voltage (1s application repeated 10 times
RF suppression components, such as ferrite absorbers, line filters etc., in Frequency 0.15% of mid frequency test between circuits and 1)Input circuit(voltage/current) & AUX & Analog
at 10s intervals)
the event that RF fields cause problems. accessible surfaces output & pulse output Versus Case
Active Power + 0.2 % of range
Nominal input voltage burden 0.2VA Approx. 2)Voltage input circuit & AUX Versus Current
Note: It is good practice to install sensitive electronic instruments that are Re- Active Power + 0.2 % of range input circuit
performing critical functions, in EMC enclosures that protect against electrical 3)Voltage input circuit Versus AUX
interference which could cause a disturbance in function. Nominal input current 1A / 5A AC rms programmable at site Apparent Power + 0.2 % of range
4)Input circuit(voltage/current) Versus Analog
Max continuous input current 120% of Rated Value Active Energy + 0.2 % of range
2. Avoid routing leads alongside cables and products that are, or could be, a output & RS485 & Pulse output
source of interference. Re - Active Energy + 0.2 % of range. NOTE: Analog output and RS485 are not isolated.
Nominal input current burden 0.6VA Approx.
Apparant Energy + 0.2 % of range
3. To protect the product against permanent damage, surge transients must Max short duration current input 20 x Rated Value (1s application repeated
be limited to 2kV pk. It is good EMC practice to suppress differential 5 times at 5 min. intervals) Power Factor + 1 % of Unity
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme Angle + 1 % of range Environmental
circumstances it may be necessary to temporarily disconnect the System CT primary values Std. Values from 1 to 9999A (1 or 5 Amp secondaries)
auxiliary supply for a period of greater than 5 seconds to restore correct Analog Output + 1 % of Output end value Operating temperature -10 to 55 0 C
operation. Total harmonic Distortion +1% 0
Auxiliary Storage temperature -20 to +65 C
The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded. Relative humidity 0 .. 90 % RH
Standard nominal Auxillary 110V AC/50 Hz , 230V AC/50 Hz ,380V AC/50 Hz ,
4. ESD precautions must be taken at all times when handling this product. supply voltages & Frequency 100 - 250V AC- DC, 12 - 48V DC Reference conditions for Accuracy :
Warm up time 3 minute (minimum)
0 0
Reference temperature 23 C + 2 C Shock 15g in 3 planes
a.c. supply voltage tolerance +20 % / -15 % of Rated Value
11.2 Case Dimension and Panel Cut Out a.c. supply frequency range 45 to 66 Hz Input frequency 50 or 60Hz + 2% Vibration 10 .. 55 Hz, 0.15mm amplitude

a.c. supply burden 4.5V A Input waveform Sinusoidal (distortion factor 0.005) Enclosure ( front only ) IP 54 as per IEC 60529

3.78” 3.15” 3.62” d.c. supply burden 3W Auxiliary supply voltage Rated Value + 1 %
96mm 80mm 92mm
Auxiliary supply frequency Rated Value + 1 %
Operating Measuring Ranges Voltage Range 50...100% of Nominal Value.
3.78” 3.62” 60...100% of Nominal Value for THD.
96mm FRONT DISPLAY PANEL CUTOUT 92mm Voltage 5 .. 120 % of Rated Value Enclosure
AREA Current Range 10...100 % of Nominal Value.
20...100% of Nominal Value for THD. Style 96mm x 96mm DIN Quadratic
Current 5 .. 120 % of Rated Value
Power Cos phi / Sin phi = 1 Material Polycarbonate Housing ,
Frequency 40 .. 70 Hz For Active / Reactive Power & Energy Self extinguish & non dripping as per
10... 100% of Nominal Current & UL 94 V-0
MAX PANEL THICKNESS 0.18”,5mm Power Factor 0.5 Lag ... 1 ... 0.8 Lead
50... 100% of Nominal Voltage
Terminals Screw-type terminals
Accuracy Power Factor / Phase Angle 40... 100% of Nominal Current &
Depth < 80 mm
Accuracy 1.0: 50... 100% of Nominal Voltage
11.3 Wiring
Voltage Weight 0.620 kg Approx.
Input connections are made directly to screw-type terminals with indirect + 0.5 % of range
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of Current Nominal range of use of influence quantities for measurands
+ 0.5 % of range
cable should meet local regulations. Terminal for both Current and Voltage
2
inputs will accept upto 3mm x 2 diameter cables. Frequency 0.15% of mid frequency Voltage 50 .. 120 % of Rated Value
Note : It is recommended to use wire with lug for Active Power + 0.5 % of range
Current 10 .. 120 % of Rated Value
connection with meter. Re- Active Power + 0.5 % of range
Rated Value + 10 %
Input frequency
Apparent Power + 0.5 % of range 0
11.4 Auxiliary Supply Temperature 0 to 50 C
Active Energy + 1 % of range
3440 should ideally be powered from a dedicated supply, however it may be Auxiliary supply voltage Rated Value + 10 %
Re - Active Energy + 1 % of range.
powered from the signal source, provided the source remains within the limits
of the chosen auxiliary voltage. Apparant Energy + 1 % of range Auxiliary supply frequency Rated Value + 10 %
0
Power Factor + 1 % of Unity Temperature Coefficient 0.025% / C for Voltage (50..120% of Rated Value)
0
11.5 Fusing Angle + 1 % of range
(For Rated
0
value range of use 0.05% / C for Current (10..120% of Rated Value )
It is recommended that all voltage lines are fitted with 1 amp HRC fuses. 0... 50 C )
Analog Output + 1 % of Output end value Error change due to variation of an 2 * Error allowed for the reference
influence quantity condition applied in the test.
Total harmonic Distortion +1%
11.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in
accordance with local regulations.

17 18
14. Connection for Optional Pulse Output / RS 485
/ Analog Output (rear view of 3440): 7. RS 485 + Two Analog Output

1. One Pulse Output (One Limit Output)


Pulse output Option ( 1 or 2 Relay ) :

Relay 1NO + 1NC B A Gnd


Gnd A1 A2 GND
4 -20 mA RS 485
Switching Voltage & Current 240VDC , 5Amp.

Default Pulse rate Divisor 1 per Wh (up to 3600W), N/O N/C COM
1 per kWh (up to 3600kW), Relay 1
1 per MWh (above 3600 kW)

Pulse rate Divisors Programmable on site

10 1 per 10Wh (up to 3600W),


1 per 10kWh (up to 3600kW), 8. RS 485 Output + One Pulse (One Limit) + Two Analog Output
1 per 10MWh (above 3600 kW) 2. Two Pulse Output ( Two Limit Output)
100 1 per 100Wh (up to 3600W),
1 per 100kWh (up to 3600kW),
1 per 100MWh (above 3600 kW)

1000 1 per 1000Wh (up to 3600W),


1 per 1000kWh (up to 3600kW),
N/O N/C COM N/O N/C COM N/O N/C COM B A Gnd
1 per 1000MWh (above 3600 kW) Gnd A1 A2 Gnd
Relay 1 Relay 2 Relay 2 RS 485
0 - 1mA

Pulse Duration 60ms , 100ms or 200ms

Note : Above conditions are also applicable for Reactive & Apparent Energy .

3. RS 485 Output
ModBus ( RS 485 ) Option :
9. Two Pulse (Two Limit) + RS 485 Output
Protocol ModBus ( RS 485 )

Baud Rate 19200 , 9600 , 4800 or 2400


( Programmable ) B A Gnd
Parity Odd or Even, with 1 stop bit, RS 485
or None with 1 or 2 stop bits

N/O N/C COM N/O N/C COM B A Gnd


Analog Output Option : Relay 1 Relay 2 RS 485

Linear 0 ... 1mA dc into 0 - 2 kohm


Uni-directional, internally powered . 4. Two Analog Output
4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.

Gnd A1 A2 GND
4 -20 mA

5. One Pulse (One Limit) + RS 485 Output

N/O N/C COM B A Gnd


Relay 2 RS 485

6. One Pulse (One Limit) + Two Analog Output

Gnd A1 A2 Gnd N/O N/C COM The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and
is intended to describe the correct method of installation for this product.
0 - 1mA Relay 2 It is the user's responsibility to determine the suitability of the installation method in the user's field conditions.

19

You might also like