Comparision of HT & LT Generator ( Typical - 8x2000 KVA )
LT (415 V ) HT (11000 Volts )
1 Exhaust System Same Same
2 Fuel System Same Same 3 Cooling System Same Same 4 Fault Level More Less 5 Fault Current ( Approx ) - KA 210 11 6 No of DG sets in parallel on Limited Nos of More no of Dg sets Common Bus DG set ( Max can work on Common 2 to 3 ) Bus
7 System Reliability / Power Less More
Stability 8 Current Handling More Current Less amount of is to be Current to be Handled Handled
9 I2R Loss More Less
10 Voltage Drop More Less 11 Capital Cost of DG Less More . Approx ( 25 % Higher ) 12 Cabling Cost More ( approx Less 4 to 5 times more )