Dear Shivashankar/Lakshya

Further to below mail , following are the points to be noted on SCADA communication issue .

SMB communication at SCADA panel End


1. We have checked all the SMB communication at SCADA panel End at before SPD ,after SPD
and after Gateway
2. All SMB are communicating without any interruption at before SPD without any
communication interference
3. All SMB are communicating without any interruption at after SPD without any
communication interference except 3.1 with some interference which is negligible
4. After Gateway SMB 3.2 , 2.2 is not communicating after Gateway ,rest all are communicating
5. At all SMB’s DC switch is ON = 0(register No 31 ) , SPD is healthy = 1 (register No 32)

SMB communication at Local SCADA screen


Inverter 3 SMB
1. SMB 3.1,3.4,3.5,3.7 is communicating ,total current is ok and SPD ,DC switch status ok
2. SMB 3.2 is communicating ,total current is not ok and SPD ,DC switch status is not OK
3. SMB 3.3,3.6 is communicating ,total current is not ok and SPD ,DC switch status is OK
4. SMB 3.8 is communicating ,total current is ok and SPD ,DC switch status is not OK

Inverter 4 SMB
1. SMB 4.1, is communicating ,total current is not ok and SPD ,DC switch status ok
2. SMB 4.2 is communicating ,total current is not ok and SPD ,DC switch status is not OK
3. SMB 4.3,is not communicating ,total current is not ok and SPD ,DC switch status is not OK
4. SMB 4.4,4.5,4.6,4.7,4.8 is communicating ,total current is not ok and SPD ,DC switch status is
OK

Inverter 1 SMB
1. SMB 1.1,1. is communicating ,total current is ok and SPD ,DC switch status is not ok
2. SMB 1.3,1.4 is communicating ,total current is not ok and SPD ,DC switch status is OK
3. SMB 3.3,3.6 is communicating ,total current is not ok and SPD ,DC switch status is OK
4. SMB 3.8 is communicating ,total current is ok and SPD ,DC switch status is not OK